Distribution Maintenance &

Repair Techniques to Avoid

System Shutdown

Line Tapping ● Line Stopping ●Valve

Insertion

Presented by: Fred Haines

Page 2: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

• Fire hydrants without auxiliary valves

• Broken valves that need to be replaced

• Sections of your system that can not be isolated

• Old water main that needs to be replaced

• Repairs that require system shutdown

to complete

System O&M Challenges…

Page 3: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

• A shut-off valve is

broken or, worse

yet, does not

exist?

The Problem…

• A hydrant repair

becomes hydrant

replacement?

Page 4: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Turn off the water supply and suffer the consequences later!!!

Old Technique…

Page 5: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

• System pressure drops

• Large portion of the community without water

• Possibility of boil orders due to contamination

• Loss of fire protection

• Loss of water revenue

• Possible EPA involvement

Eliminate Health & Safety Risk with a Line Stop or Valve Insertion

Impacts & Challenges of Shut Down…

Community Impact

Page 6: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

– Difficulty locating underground or under-

pavement valves

– Determining whether all valves work

– Unsafe working environment

– Purge Air and Flushing

– Overtime / Comp time issues

– Cleaning plugged meters

Eliminate Health & Safety Risk with a Line Stop or Valve Insertion

Impacts & Challenges of Shut Down…

Work Challenges

Page 7: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

• Larger pipe sizes, greater water

pressure and greater volume of water

• More demands on your time, smaller

staffing

• Age of pipe, valves, and hydrants

• Attitudes of society have changed –

impatient. Social media “blitz”.

Why Change Now?

Page 8: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

• New regulations – more stringent

water quality standards

• Regulation enforcement

• Water conservation

• Operator safety

• Budget Considerations

Why Change Now?

Page 9: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Project Constants:

➢ Excavation

➢ Material (valve, hydrant,

etc.) labor,

Inherent to any process, no

matter how you handle

your shutdown problem.

The True Cost to Shut Down…

Page 10: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

➢ Time to read the maps…if

they are correct

➢ Locate and turn valves

➢Break a valve

➢ Advertise the shutdown

➢ Overtime

➢ Loss of fire protection

➢ Increased liability

➢ Backflow problems

The True Cost to Shut Down…

Page 11: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

➢ Compliance with rules and regulations

➢Issuing of boil orders

➢Sampling

➢Lab costs

➢Additional notification

➢Media fallout

➢Re-chlorinization and de-chlorinization

➢ Loss of treated water

➢Gallons lost draining

➢Gallons lost purging➢ Loss of water revenue

The True Cost to Shut Down…

Page 12: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Line Stopping

Never shutdown…

Page 13: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Use a line-stop/insert valve system…instead of

shutting down

Page 14: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Required – Line tapping machine (typical below)

Page 15: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Side Tapping (illustrated)

Page 16: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

• Establishes a connection

to an existing pipeline

• Utilizes a valve, fitting,

and sealed tapping

machine to cut a hole

into pipeline without loss

of pressure or contents

• Available sizes: 4″

through 20″

• Also known as hot

tapping

Line Tapping Explained…

Page 17: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Traditional Tapping Methods

Traditional tapping methods provides a means for

coupon retention which allows for inspection,

evaluation and verification.

Page 18: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Line Stopping Machine (illustrated)

Page 19: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

• Developed over 50 years

ago; introduced to water

industry in 1980

• Utilizes the line tapping

process with the addition

of flow stopping

• Temporarily stops flow to

allow repairs or

maintenance without

disrupting service

Line Stopping Process Overview

Page 20: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Line Stopping Animation

Page 21: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

• Effectively used in:

– Rural water systems

– Public and private utilities

– Gas distribution systems

– Industrial systems

• Used by 1000’s of

municipalities: Domestic and

International

Line Stopping

Page 22: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

➢ Commonly used when:

➢ Inserting, changing or

repairing valves

➢ Adding, changing or

repairing hydrants

➢ Tying in new lines or

services

➢ Performing repairs

➢ Changing large meters or

backflow preventers

➢ Abandoning, cutting or

capping lines

Line Stopping

Page 23: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Example: Hydrant Valve Installation

Page 24: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Example: Hydrant Valve Installation

Page 25: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Example: 6” Tuberculated Pipe 80psi

Page 26: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Line Stopping with Bypass

Page 27: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Example of Line Stopping Heads

A Line-Stop Head

– Flexible rubber stopper easily handles moderate pressures, tuberculated lines

– Provides 95-100% flow stoppage at the point of repair

– Available from 4″ to 12″

– Good for pressures up to 100 PSI (7 bar)

Page 28: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Example of Line Stopping Heads

Bullet Head

– Ideal for use with higher pressure systems, bypass lines

– Available from 4″ to 20″

– Good for pressures up to 250 PSI (17 bar)

Page 29: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Line Stopping Heads

Pivoting Head

– Used for larger size mains, higher pressures

– Used primarily to 12” line size

Page 30: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Example of Line Stopping Heads

Folding Head

– Ideal for large diameter cast iron, ductile iron, steel, and concrete pipes with average pressure (under 150 PSI)

– Enables smaller diameter tap to be performed

– Diameters to 60” are readily available through specialized line stop contractors

Page 31: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

An Example of Line Stop Fittings

Page 32: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Line Stop Fittings – typical Bill of Material

Line Stop Fitting

Test and Working Pressures: 375 psi test

pressure max. 250 psi working pressure.

Stainless Steel Construction: Offers improved

corrosion resistance and durability.

Made in the USA – May be required to comply

with AIS and Buy American Project Requirements

NSF 61 and NSF 372 Classified - NSF/ANSI

Standard 61 and NSF/ANSI Standard 372 to meet

the regulatory requirements for the U.S. and

Canada assuring safe use in drinking water

systems.

Factory Pressure Test – Recommended

pressure tested and serialized for traceability

before leaving manufacturing facility.

Line Stop Fitting

Page 33: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

• Designed to achieve workable shutdown.

• Provides 95-100% stop at point of repair

• No service interruptions

• No loss of fire protection

• Reduced labor costs – less overtime, fewer man-hours

to complete

• Contamination and backflow eliminated

• Reduced loss of treated water and associated water

revenue

• Safer working conditions

Benefits of Line Stopping

Page 34: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Insertion Valve (illustrated)

Page 35: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Insertion Valve Installation Animation

Page 36: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Insertion Valve Bill of Materials

Page 37: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street
Page 38: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Operating Nut:

Steel, Cast

Standard Black

indicates open left

Page 39: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Operating Nut:

Steel, Cast

Optional Red indicates

open right

Page 40: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Bonnet Hardware:

304 Stainless SteelDomestic 304 Stainless Steel

Option available

Body Mounting Hardware:

304 Stainless SteelDomestic 304 Stainless Steel

Option available

Page 41: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Valve Bonnet:

Standard Epoxy

Coated Carbon Steel

Page 42: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Valve Bonnet:

Optional 304 Stainless Steel

Page 43: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Valve Body:

304 Stainless Steel

Page 44: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Completion Plug Pins:SAE GRADE 8 STEEL, ZINC COATED Completion Pin Plugs:

SAE GRADE 8 STEEL, ZINC COATED

Page 45: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Upper and Lower Body

Sealing Gaskets:

BUNA-N Rubber

Body Armor Shields:

16 gauge

304 Stainless Steel

Page 46: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Completion Plug O-ring:

BUNA-N RubberFlange O-Ring:

BUNA-N Rubber

Not Pictured:

Valve Stem O-Ring

BUNA-N Rubber

Quad O-ring

Seals

Valve Bonnet O-Ring:

BUNA-N Rubber

Page 47: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Cartridge Wipe Seal:

EDPM

Page 48: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Valve Cartridge

Wipe Seal

Page 49: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

6” IV 250 Patriot

Resilient Wedge

Page 50: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Exploded 6” Resilient Wedge Seat

Rubber

Layers

Mesh

Layers

Page 51: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Resilient Wedge

Front View

Page 52: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Cross section of resilient wedge.

Rubber

Mesh

Page 53: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Resilient Wedge BEFORE compression

Page 54: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Resilient Wedge DURING

compression

Page 55: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Resilient Wedge AFTER compression

Page 56: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Completion Plug:

Reinforced

Composite Polymer

Stem Collar:

No Lead Brass

Conforms to NSF 372

Page 57: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Heavy Duty Valve Stem:

304 Stainless Steel

4”-8” valves - 1.5” Diameter

10” & 12” valves – 2”

Diameter

Valve Stem O-ring:

BUNA-N Rubber

Page 58: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Insertion Valve Basic Specifications

Insertion Valve

Cut-away

Test and Working Pressures: 375 psi test

pressure max. 250 psi working pressure.

Stainless Steel Construction: Offers improved

corrosion resistance and durability.

Made in the USA – May be required to comply

with AIS and Buy American Project Requirements

NSF 61 and NSF 372 Classified - NSF/ANSI

Standard 61 and NSF/ANSI Standard 372 to meet

the regulatory requirements for the U.S. and

Canada assuring safe use in drinking water

systems.

Factory Pressure Test – Recommended

pressure tested and serialized for traceability

before leaving manufacturing facility.

Page 59: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

IV 250 – Sealing Surface

IV 250 valve cartridge

designed to seal on

engineered sealing

surface within the valve

body.

Page 60: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

IV 250 – Resilient Wedge Seal

Resilient wedge

seal

Page 61: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

• Insertion Valves

– Constant flow

– System control

– Immediate results

– In place working

valve

– Value added options

– Safe working

conditions

– Water conservation

• System Shutdown

– Boil orders

– Complicated planning

– Loss of fire protection

– Large street excavation and

street patches (5’x5’)

– Working in unsafe

trenching and knee-high

mud

– Reaming the pipe wall or

completely severing the

pipe

– Need for heavy equipment

on-site

Insertion Valve versus System Shutdown

Page 62: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

16” Insertion Valve An Inside Look

Page 63: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

16” Insertion Valve An Inside Look

Page 64: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Open Position Closed Position

16” Insertion Valve An Inside Look

Page 65: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

16” Insertion Valve An Inside Look

Page 66: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

20” and 24” Insertion Valve

➢ Permanent asset

➢ Ductile iron valve

construction with fusion-

bonded epoxy coating

➢ Resilient wedge valve

cartridge

➢ Stainless-steel hardware

➢ Fast installation

➢ Tried and true installation

process

Integrated temporary gate

valve

Page 67: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

20” and 24” Insertion Valve

Installation Process

Page 68: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

20” and 24” Insertion Valve

Valve Closure

Page 69: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Asbestos cement pipe

Cast/ductile iron pipe

PVC pipe (IPS or C-900)

Steel pipe

Insertion Valves & Line-Stop Pipe Compatibility

Page 70: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

AWWA Standards➢ There are no AWWA standards covering

insertion valves.

➢ AWWA C509-15 (Resilient-Seated Gate Valves

for Water Supply Service) is the closest

standard which applies to insertion valves.

➢ Some material specifications of C509-15 are

met depending on the manufacturer.

➢ The important part of C509-15 are the

performance standards or the “Proof of Design”

tests.

Page 71: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

➢C509-15 Proof of design consists of 4

separate tests.

➢Hydrostatic Gate Test

➢Torque Test

➢Leakage Test

➢Hydrostatic Shell Test

Insert Valve Testing

Page 72: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Insert Valve Testing

Page 73: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Insert Valve Testing

Page 74: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Insert Valve Testing

Page 75: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Insert Valve Testing

Page 76: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Insert Valve Testing

Page 77: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Insert Valve Testing

Page 78: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Insert Valve Testing

Page 79: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Insert Valve Testing

Page 80: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Old 12”

Valve12”

Insert

Valve

Installed

Page 81: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street
Page 82: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street
Page 83: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Applications:

Valve Installation in Pump

Station(s)

Page 84: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Applications: Versatility -

Multiple Lines

Page 85: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Applications: Versatility -

Multiple Lines

Page 86: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Insertion Valve Installation Flexibility

Page 87: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Insertion Valve Service Providers

Page 88: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

• Premier Contract

Services utilizing The

Hydra-Stop System are

offered through Hydra-

Stop’s nationwide

network of Premier

Service Providers.

• Hydra-Stop offers the

largest and most

experienced Service

Provider network in the

industry.

Hydra-Stop Premier Service Providers Contract

Services

Page 89: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

• Product required (line-stop or insertion

valve)

• Type of Pipe (material)

• Pipe O.D.

• Pressure

• Scope of Work

• Location of Work

• Number of Mobilizations

• Number of Days on Line

What you need to know for an insertion valve of line

stop…

Page 90: Distribution Maintenance & Repair Techniques to Avoid ......• System Shutdown –Boil orders –Complicated planning –Loss of fire protection –Large street excavation and street

Contact: Jason Chase or Fred Haines

Telephone: (203) 693-3740

Email: [email protected]

[email protected]

Website: www.Harper-Haines.com

Thank you for attending!