0' 4' 8' 16' SCALE: SKETCH TITLE Plot Date: DISCLAIMER: ROOM TEMPLATES ARE GRAPHICAL REPRESENTATIONS OF SELECTED ROOM TYPES THAT ILLUSTRATE VA PLANNING REQUIREMENTS FOR SPACE, ROOM CONTENTS, AND ROOM SPECIFIC ENGINEERING SYSTEMS. THEY PROVIDE TYPICAL CONFIGURATIONS, PLANNING CRITERIA, AND GENERAL TECHNICAL GUIDANCE, AND ARE NOT INTENDED TO BE PROJECT SPECIFIC REQUIREMENTS. 6/27/2018 11:40:00 PM PHARMACY (PHOD5) DISCLAIMER DISCLAIMER: ROOM TEMPLATES ARE A CRITICAL COMPONENT TO VA TECHNICAL INFORMATION LIBRARY (TIL) WHICH PROVIDES STANDARDS FOR ALL VA PLANNING, DESIGN, AND CONSTRUCTION PROJECTS. ROOM TEMPLATES ARE DEPARTMENT AND ROOM ALIGNED CRITERIA DESCRIBING SPACE, ROOM CONTENTS, AND OTHER TECHNICAL REQUIREMENTS FOR THE DEVELOPMENT OF VA PROJECTS. ROOM TEMPLATES COMMUNICATE THE BASIS OF DESIGN (BOD) AND ARE REQUIRED TO BE UTILIZED BY PROJECT TEAMS WORKING ON NEW CONSTRUCTION AND RENOVATIONS OF EXISTING FACILITIES. THE MATERIAL CONTAINED IN THE ROOM TEMPLATE CONSTITUTES A STANDARD FOR VA PLANNING, DESIGN, AND CONSTRUCTION. ANY SUBSTANTIAL VARIANCE FROM STANDARDS SHALL BE CONSIDERED ONLY AS REQUIRED TO ACCOMMODATE SPECIFIC SITE, FUNCTIONAL, AND OPERATIONAL CONDITIONS. EACH SUBSTANTIAL VARIANCE SHALL HAVE A BASIS OF RATIONALE AND BE DOCUMENTED IN THE PROJECT RECORD. CLINICIANS, PROVIDERS, PRIMARY USERS, AND OTHER STAKEHOLDERS SHALL BE INVOLVED IN PROJECT SPECIFIC DEVELOPMENT OF ROOM TEMPLATES AND BIM TEST-FITS TO BEST ADAPT STANDARDS FOR SPECIFIC FUNCTIONAL, OPERATIONAL , AND SITE CONDITIONS AND TO PROVIDE OPTIMUM SERVICES ENVIRONMENTS FOR VETERANS. STAKEHOLDER INVOLVEMENT AND REQUIREMENTS SHALL BE DOCUMENTED IN THE PROJECT RECORD. ROOM TEMPLATES ARE NOT PROJECT-SPECIFIC. SITE SPECIFIC ISSUES MUST BE ADDRESSED WITH THE CONTEXT OF VA STANDARDS AND APPLIED TO EACH INDIVIDUAL PROJECT. USE OF THIS ROOM TEMPLATE DOES NOT PRECLUDE THE NEED FOR , NOR ABSOLVE PLANNERS, DESIGNERS, AND CONSTRUCTORS OF THEIR RESPONSIBILITY TO PROVIDE COMPLETE, FUNCTIONAL, SAFE, AND SECURE DESIGNS SUITED TO THE UNIQUE REQUIREMENTS OF EACH PROJECT. EQUIPMENT AND SYSTEMS ARE SHOWN IN AN ILLUSTRATIVE, PERFORMANCE-BASED FORMAT AND ARE NOT INTENDED TO DEPICT, SUGGEST, OR OTHERWISE CONSTITUTE ENDORSEMENT OF ANY SPECIFIC PRODUCT OR MANUFACTURER. MANUFACTURERS SHOULD BE CONSULTED FOR ACTUAL DIMENSIONS, CONFIGURATIONS, AND UTILITY REQUIREMENTS. LEASING

DISCLAIMER LEASING PHARMACY (PHOD5)

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

0' 4' 8' 16'

SCALE:

SKETCH TITLE

Plot Date:

DISCLAIMER: ROOM TEMPLATES ARE GRAPHICAL REPRESENTATIONS OF SELECTED ROOM TYPES THAT ILLUSTRATE VA PLANNING REQUIREMENTS FOR SPACE, ROOM

CONTENTS, AND ROOM SPECIFIC ENGINEERING SYSTEMS. THEY PROVIDE TYPICAL CONFIGURATIONS, PLANNING CRITERIA, AND GENERAL TECHNICAL GUIDANCE, AND

ARE NOT INTENDED TO BE PROJECT SPECIFIC REQUIREMENTS.

6/27/2018 11:40:00 PM

PHARMACY (PHOD5)DISCLAIMER

DISCLAIMER:

ROOM TEMPLATES ARE A CRITICAL COMPONENT TO VA TECHNICAL INFORMATION LIBRARY (TIL) WHICH PROVIDES STANDARDS FOR ALL VA PLANNING, DESIGN, AND CONSTRUCTION PROJECTS. ROOM TEMPLATES ARE DEPARTMENT AND ROOM ALIGNED CRITERIA DESCRIBING SPACE, ROOM CONTENTS, AND OTHER TECHNICAL REQUIREMENTS FOR THE DEVELOPMENT OF VA PROJECTS. ROOM TEMPLATES COMMUNICATE THE BASIS OF DESIGN (BOD) AND ARE REQUIRED TO BE UTILIZED BY PROJECT TEAMS WORKING ON NEW CONSTRUCTION AND RENOVATIONS OF EXISTING FACILITIES. THE MATERIAL CONTAINED IN THE ROOM TEMPLATE CONSTITUTES A STANDARD FOR VA PLANNING, DESIGN, AND CONSTRUCTION. ANY SUBSTANTIAL VARIANCE FROM STANDARDS SHALL BE CONSIDERED ONLY AS REQUIRED TO ACCOMMODATE SPECIFIC SITE, FUNCTIONAL, AND OPERATIONAL CONDITIONS. EACH SUBSTANTIAL VARIANCE SHALL HAVE A BASIS OF RATIONALE AND BE DOCUMENTED IN THE PROJECT RECORD.

CLINICIANS, PROVIDERS, PRIMARY USERS, AND OTHER STAKEHOLDERS SHALL BE INVOLVED IN PROJECT SPECIFIC DEVELOPMENT OF ROOM TEMPLATES AND BIM TEST-FITS TO BEST ADAPT STANDARDS FOR SPECIFIC FUNCTIONAL, OPERATIONAL , AND SITE CONDITIONS AND TO PROVIDE OPTIMUM SERVICES ENVIRONMENTS FOR VETERANS. STAKEHOLDER INVOLVEMENT AND REQUIREMENTS SHALL BE DOCUMENTED IN THE PROJECT RECORD.

ROOM TEMPLATES ARE NOT PROJECT-SPECIFIC. SITE SPECIFIC ISSUES MUST BE ADDRESSED WITH THE CONTEXT OF VA STANDARDS AND APPLIED TO EACH INDIVIDUAL PROJECT. USE OF THIS ROOM TEMPLATE DOES NOT PRECLUDE THE NEED FOR , NOR ABSOLVE PLANNERS, DESIGNERS, AND CONSTRUCTORS OF THEIR RESPONSIBILITY TO PROVIDE COMPLETE, FUNCTIONAL, SAFE, AND SECURE DESIGNS SUITED TO THE UNIQUE REQUIREMENTS OF EACH PROJECT.

EQUIPMENT AND SYSTEMS ARE SHOWN IN AN ILLUSTRATIVE, PERFORMANCE-BASED FORMAT AND ARE NOT INTENDED TO DEPICT, SUGGEST, OR OTHERWISE CONSTITUTE ENDORSEMENT OF ANY SPECIFIC PRODUCT OR MANUFACTURER. MANUFACTURERS SHOULD BE CONSULTED FOR ACTUAL DIMENSIONS, CONFIGURATIONS, AND UTILITY REQUIREMENTS.

LEASING

BA C

D2

1

1

1

1

CENTERLINE

EQUIPMENT JSN

NUMBER & NAMEELEVATION

REFERENCE

2X2 TROFFER LIGHT

FIXTURE

2X4 TROFFER LIGHT

FIXTURE

EXHAUST REGISTER RETURN REGISTER SUPPLY DIFFUSER

2X2 ACOUSTIC CEILING

SYSTEM

RECESSED CAN

LIGHT FIXTURE

CLEARANCE LINESOVERHEAD LINES

COMPOUND CEILING,

GYPSUM BOARD ON

METAL STUD

ROOM TAG

SINGLE SWITCH DIMMER SWITCH

WALL-MOUNTED

QUADRAPLEX OUTLET

FLOOR-MOUNTED

DUPLEX OUTLET

WALL-MOUNTED

DUPLEX OUTLET

FLOOR-MOUNTED

DATA OUTLET

WALL-MOUNTED

DATA OUTLET

Type CommentsJSN#

SPRINKLER HEAD

MULTIPLE SWITCH

(SUBSCRIPT INDICATES

QUANTITY)

FLOOR-MOUNTED

QUADRAPLEX OUTLET

ROOM NAME

(ROOM CODE)AREA NSF

0' 4' 8' 16'

SCALE:

SKETCH TITLE

Plot Date:

DISCLAIMER: ROOM TEMPLATES ARE GRAPHICAL REPRESENTATIONS OF SELECTED ROOM TYPES THAT ILLUSTRATE VA PLANNING REQUIREMENTS FOR SPACE, ROOM

CONTENTS, AND ROOM SPECIFIC ENGINEERING SYSTEMS. THEY PROVIDE TYPICAL CONFIGURATIONS, PLANNING CRITERIA, AND GENERAL TECHNICAL GUIDANCE, AND

ARE NOT INTENDED TO BE PROJECT SPECIFIC REQUIREMENTS.

1/4" = 1'-0"

6/27/2018 11:40:00 PM

PHARMACY (PHOD5)LEGEND

LEASING

0' 4' 8' 16'

SCALE:

SKETCH TITLE

Plot Date:

DISCLAIMER: ROOM TEMPLATES ARE GRAPHICAL REPRESENTATIONS OF SELECTED ROOM TYPES THAT ILLUSTRATE VA PLANNING REQUIREMENTS FOR SPACE, ROOM

CONTENTS, AND ROOM SPECIFIC ENGINEERING SYSTEMS. THEY PROVIDE TYPICAL CONFIGURATIONS, PLANNING CRITERIA, AND GENERAL TECHNICAL GUIDANCE, AND

ARE NOT INTENDED TO BE PROJECT SPECIFIC REQUIREMENTS.

6/27/2018 11:38:59 PM

PHARMACY (PHOD5)AXONOMETRIC

LEASING

+48"

+48

"+

48"

+48"

PHARMACIST

STATION

TECH STATION TECH STATION TECH STATION MAILOUT

STATION

(7

.72m

)

25

'-4

"

DIS

PE

NS

ING

/ C

ON

SU

LT

(12.8m)

42'-0"

4

1

2

3

ROBOT DISPENSERM7280

WORKSPACE, W/

OVERHEAD CAB, WALL

MNTD

E0210

REFRIGERATOR,

BIOLOGICAL

R6060

CHAIR, DRAFTING,

ROTARY

F0230

COMPUTER WITH FLAT

PANEL MONITOR

M1801

COUNTER, WORK, W/

STORAGE CAB, PHARM,

WALL-MNTD

E0636

READER, BAR CODE,

HAND HELD

F2700

PRINTER, LABEL,

PHARMACY

M1830COUNTER, PILL-TABLET,

AUTOMATED, COUNTER

MNTD

M7265

1,055 NSF

PHARMACY

(PHOD5)

5'-6

"

5'-6

"

SHELVING, STORAGEM2050

BASKET, WASTEPAPERF2000

CAN, TRASH, 44 GALF2020

CLOCK, BATTERY, 12"F3200

PURIFIERL2000

DISPENSER, SOAPA5075

LAVATORY, VITREOUS

CHINA

P3100

EYEWASH, HANDS-FREEP1965

REFRIGERATORR7050

BOOKCASE, OPEN, 5

SHELF

F0115

DISTRIBUTION SYSTEM,

MEDICATION, AUTOMATIC

M3150

DISPENSER, PAPER

TOWEL, SENSOR, HANDS

FREE

A5082

CAROUSELU0002

LAVATORY, VITREOUS

CHINA

P3100

EYEWASH, HANDS-FREEP1965

COMPUTER WITH FLAT

PANEL MONITOR

M1801

0' 4' 8' 16'

SCALE:

SKETCH TITLE

Plot Date:

DISCLAIMER: ROOM TEMPLATES ARE GRAPHICAL REPRESENTATIONS OF SELECTED ROOM TYPES THAT ILLUSTRATE VA PLANNING REQUIREMENTS FOR SPACE, ROOM

CONTENTS, AND ROOM SPECIFIC ENGINEERING SYSTEMS. THEY PROVIDE TYPICAL CONFIGURATIONS, PLANNING CRITERIA, AND GENERAL TECHNICAL GUIDANCE, AND

ARE NOT INTENDED TO BE PROJECT SPECIFIC REQUIREMENTS.

1/4" = 1'-0"

6/27/2018 11:38:59 PM

PHARMACY (PHOD5)FLOOR PLAN (1,055 NSF / 98.01 NSM)

LEASING

AA

A

A A

A

A

A AA A

A

A

A AA A

A

1,055 NSF

PHARMACY

(PHOD5)

(12.8m)

42'-0"

(7

.72m

)

25

'-4

"

CAROUSELU0002

0' 4' 8' 16'

SCALE:

SKETCH TITLE

Plot Date:

DISCLAIMER: ROOM TEMPLATES ARE GRAPHICAL REPRESENTATIONS OF SELECTED ROOM TYPES THAT ILLUSTRATE VA PLANNING REQUIREMENTS FOR SPACE, ROOM

CONTENTS, AND ROOM SPECIFIC ENGINEERING SYSTEMS. THEY PROVIDE TYPICAL CONFIGURATIONS, PLANNING CRITERIA, AND GENERAL TECHNICAL GUIDANCE, AND

ARE NOT INTENDED TO BE PROJECT SPECIFIC REQUIREMENTS.

1/4" = 1'-0"

6/27/2018 11:39:00 PM

PHARMACY (PHOD5)REFLECTED CEILING PLAN

LEASING

CLOCK, BATTERY, 12"F3200

EYEWASH, HANDS-FREEP1965

BASKET, WASTEPAPERF2000

LAVATORY, VITREOUS

CHINA

P3100DISPENSER, SOAP

A5075

REFRIGERATOR,

BIOLOGICAL

R6060DISPENSER, PAPER

TOWEL, SENSOR, HANDS

FREE

A5082

DISTRIBUTION SYSTEM,

MEDICATION, AUTOMATIC

M3150

CAN, TRASH, 44 GALF2020

CAROUSELU0002

PURIFIERL2000

CAN, TRASH, 44 GALF2020

SHELVING, STORAGEM2050

0' 4' 8' 16'

SCALE:

SKETCH TITLE

Plot Date:

DISCLAIMER: ROOM TEMPLATES ARE GRAPHICAL REPRESENTATIONS OF SELECTED ROOM TYPES THAT ILLUSTRATE VA PLANNING REQUIREMENTS FOR SPACE, ROOM

CONTENTS, AND ROOM SPECIFIC ENGINEERING SYSTEMS. THEY PROVIDE TYPICAL CONFIGURATIONS, PLANNING CRITERIA, AND GENERAL TECHNICAL GUIDANCE, AND

ARE NOT INTENDED TO BE PROJECT SPECIFIC REQUIREMENTS.

1/4" = 1'-0"

6/27/2018 11:39:00 PM

PHARMACY (PHOD5)ELEVATIONS

ELEVATION 1

ELEVATION 2

LEASING

SHELVING, STORAGEM2050

CHAIR, DRAFTING,

ROTARY

F0230

COUNTER, WORK, W/

STORAGE CAB, PHARM,

WALL-MNTD

E0636

COMPUTER WITH FLAT

PANEL MONITOR

M1801

PRINTER, LABEL,

PHARMACY

M1830

COUNTER, PILL-TABLET,

AUTOMATED, COUNTER

MNTD

M7265

ROBOT DISPENSERM7280

SHELVING, STORAGEM2050

0' 4' 8' 16'

SCALE:

SKETCH TITLE

Plot Date:

DISCLAIMER: ROOM TEMPLATES ARE GRAPHICAL REPRESENTATIONS OF SELECTED ROOM TYPES THAT ILLUSTRATE VA PLANNING REQUIREMENTS FOR SPACE, ROOM

CONTENTS, AND ROOM SPECIFIC ENGINEERING SYSTEMS. THEY PROVIDE TYPICAL CONFIGURATIONS, PLANNING CRITERIA, AND GENERAL TECHNICAL GUIDANCE, AND

ARE NOT INTENDED TO BE PROJECT SPECIFIC REQUIREMENTS.

1/4" = 1'-0"

6/27/2018 11:39:01 PM

PHARMACY (PHOD5)ELEVATIONS

ELEVATION 4

ELEVATION 3

LEASING

0' 4' 8' 16'

SCALE:

SKETCH TITLE

Plot Date:

DISCLAIMER: ROOM TEMPLATES ARE GRAPHICAL REPRESENTATIONS OF SELECTED ROOM TYPES THAT ILLUSTRATE VA PLANNING REQUIREMENTS FOR SPACE, ROOM

CONTENTS, AND ROOM SPECIFIC ENGINEERING SYSTEMS. THEY PROVIDE TYPICAL CONFIGURATIONS, PLANNING CRITERIA, AND GENERAL TECHNICAL GUIDANCE, AND

ARE NOT INTENDED TO BE PROJECT SPECIFIC REQUIREMENTS.

6/27/2018 11:40:00 PM

PHARMACY (PHOD5)ROOM DATA

ARCHITECTURAL & INTERIOR DESIGN

Ceiling Type:

Ceiling Height:

Wall Finish:

Base:

Floor Finish:

Special Requirement:

Sound Protection:

Ceiling Finish:

Wainscot:

Slab Depression:

Doors:

Notes:

TELECOMMUNICATION / SPECIAL SYSTEMS

Data:

Telephone:

Duress Alarm:

Intercom:

Motion Intrusion Detection (MID):

Security Surveillance Television (SSTV):

Code Blue:

Cable Television:

Electronic Access and Door Control:

Nurse Call:

Public Address:

VA Satellite TV:

Video Teleconferencing (VTEL):

Special Requirement:

Notes:

LIGHTING

Special Requirement:

Luminaire Type:

Notes:

POWER

Electrical system design to comply with the latest NFPA 70 and 99

Design in accordance with project requirements.

Emergency Power:

Normal Power:

Special Requirement:

Notes:

HEATING, VENTILATING, AND AIR CONDITIONING

Refer to HVAC Design Manual.

Design in accordance with project requirements.Refer to the current version of PG-18-10 Chapter 6 Table 5 –"Mechanical Room Data Sheets" for room temperatures, humidity range, room air change requirements, and pressurization

Notes:

PLUMBING AND MEDICAL GASES

Design in accordance with project requirements.

Cold Water:

Drain:

Medical Air:

Medical Vacuum:

Special Requirement:

Hot Water:

Reagent Grade Water:

Oxygen:

Notes:

FIRE PROTECTION AND LIFE SAFETY

Design in accordance with project requirements.

Alarm Detection:

Sprinkler:

Alarm Annunciator:

Notes:

Ref. Door Type Detail #SD080000-01 for door typesRef. Door Sizes Detail #SD080000-02 for door sizes

General Requirement: Lighting system design shall be based on the guidance of applicable Illuminating Engineering Society North America (IESNA) Standards.

9'-0" (2700mm)

AT

--

m: GWB f:P

--

m: RF at h: 4" (100mm)

RF

--

--

m:Metal t:36 s:V

--

Yes

Yes

--

--

--

--

--

--

--

--

--

Yes

--

--

Design in accordance with project requirements.

--

Connect to receptacles and equipment

--

--

Yes

Yes

--

--

--

--

--

--

Visual (15cd), center of tile

--

Recessed pendant, center of tile

LEASING

0' 4' 8' 16'

SCALE:

SKETCH TITLE

Plot Date:

DISCLAIMER: ROOM TEMPLATES ARE GRAPHICAL REPRESENTATIONS OF SELECTED ROOM TYPES THAT ILLUSTRATE VA PLANNING REQUIREMENTS FOR SPACE, ROOM

CONTENTS, AND ROOM SPECIFIC ENGINEERING SYSTEMS. THEY PROVIDE TYPICAL CONFIGURATIONS, PLANNING CRITERIA, AND GENERAL TECHNICAL GUIDANCE, AND

ARE NOT INTENDED TO BE PROJECT SPECIFIC REQUIREMENTS.

6/28/2018 12:15:38 AM

DISPENSE / CONSULT WINDOW (PHOW2)DISCLAIMER

DISCLAIMER:

ROOM TEMPLATES ARE A CRITICAL COMPONENT TO VA TECHNICAL INFORMATION LIBRARY (TIL) WHICH PROVIDES STANDARDS FOR ALL VA PLANNING, DESIGN, AND CONSTRUCTION PROJECTS. ROOM TEMPLATES ARE DEPARTMENT AND ROOM ALIGNED CRITERIA DESCRIBING SPACE, ROOM CONTENTS, AND OTHER TECHNICAL REQUIREMENTS FOR THE DEVELOPMENT OF VA PROJECTS. ROOM TEMPLATES COMMUNICATE THE BASIS OF DESIGN (BOD) AND ARE REQUIRED TO BE UTILIZED BY PROJECT TEAMS WORKING ON NEW CONSTRUCTION AND RENOVATIONS OF EXISTING FACILITIES. THE MATERIAL CONTAINED IN THE ROOM TEMPLATE CONSTITUTES A STANDARD FOR VA PLANNING, DESIGN, AND CONSTRUCTION. ANY SUBSTANTIAL VARIANCE FROM STANDARDS SHALL BE CONSIDERED ONLY AS REQUIRED TO ACCOMMODATE SPECIFIC SITE, FUNCTIONAL, AND OPERATIONAL CONDITIONS. EACH SUBSTANTIAL VARIANCE SHALL HAVE A BASIS OF RATIONALE AND BE DOCUMENTED IN THE PROJECT RECORD.

CLINICIANS, PROVIDERS, PRIMARY USERS, AND OTHER STAKEHOLDERS SHALL BE INVOLVED IN PROJECT SPECIFIC DEVELOPMENT OF ROOM TEMPLATES AND BIM TEST-FITS TO BEST ADAPT STANDARDS FOR SPECIFIC FUNCTIONAL, OPERATIONAL , AND SITE CONDITIONS AND TO PROVIDE OPTIMUM SERVICES ENVIRONMENTS FOR VETERANS. STAKEHOLDER INVOLVEMENT AND REQUIREMENTS SHALL BE DOCUMENTED IN THE PROJECT RECORD.

ROOM TEMPLATES ARE NOT PROJECT-SPECIFIC. SITE SPECIFIC ISSUES MUST BE ADDRESSED WITH THE CONTEXT OF VA STANDARDS AND APPLIED TO EACH INDIVIDUAL PROJECT. USE OF THIS ROOM TEMPLATE DOES NOT PRECLUDE THE NEED FOR , NOR ABSOLVE PLANNERS, DESIGNERS, AND CONSTRUCTORS OF THEIR RESPONSIBILITY TO PROVIDE COMPLETE, FUNCTIONAL, SAFE, AND SECURE DESIGNS SUITED TO THE UNIQUE REQUIREMENTS OF EACH PROJECT.

EQUIPMENT AND SYSTEMS ARE SHOWN IN AN ILLUSTRATIVE, PERFORMANCE-BASED FORMAT AND ARE NOT INTENDED TO DEPICT, SUGGEST, OR OTHERWISE CONSTITUTE ENDORSEMENT OF ANY SPECIFIC PRODUCT OR MANUFACTURER. MANUFACTURERS SHOULD BE CONSULTED FOR ACTUAL DIMENSIONS, CONFIGURATIONS, AND UTILITY REQUIREMENTS.

LEASING

BA C

D2

1

1

1

1

CENTERLINE

EQUIPMENT JSN

NUMBER & NAMEELEVATION

REFERENCE

2X2 TROFFER LIGHT

FIXTURE

2X4 TROFFER LIGHT

FIXTURE

EXHAUST REGISTER RETURN REGISTER SUPPLY DIFFUSER

2X2 ACOUSTIC CEILING

SYSTEM

RECESSED CAN

LIGHT FIXTURE

CLEARANCE LINESOVERHEAD LINES

COMPOUND CEILING,

GYPSUM BOARD ON

METAL STUD

ROOM TAG

SINGLE SWITCH DIMMER SWITCH

WALL-MOUNTED

QUADRAPLEX OUTLET

FLOOR-MOUNTED

DUPLEX OUTLET

WALL-MOUNTED

DUPLEX OUTLET

FLOOR-MOUNTED

DATA OUTLET

WALL-MOUNTED

DATA OUTLET

Type CommentsJSN#

SPRINKLER HEAD

MULTIPLE SWITCH

(SUBSCRIPT INDICATES

QUANTITY)

FLOOR-MOUNTED

QUADRAPLEX OUTLET

ROOM NAME

(ROOM CODE)AREA NSF

0' 4' 8' 16'

SCALE:

SKETCH TITLE

Plot Date:

DISCLAIMER: ROOM TEMPLATES ARE GRAPHICAL REPRESENTATIONS OF SELECTED ROOM TYPES THAT ILLUSTRATE VA PLANNING REQUIREMENTS FOR SPACE, ROOM

CONTENTS, AND ROOM SPECIFIC ENGINEERING SYSTEMS. THEY PROVIDE TYPICAL CONFIGURATIONS, PLANNING CRITERIA, AND GENERAL TECHNICAL GUIDANCE, AND

ARE NOT INTENDED TO BE PROJECT SPECIFIC REQUIREMENTS.

1/4" = 1'-0"

6/28/2018 12:15:38 AM

DISPENSE / CONSULT WINDOW (PHOW2)LEGEND

LEASING

0' 4' 8' 16'

SCALE:

SKETCH TITLE

Plot Date:

DISCLAIMER: ROOM TEMPLATES ARE GRAPHICAL REPRESENTATIONS OF SELECTED ROOM TYPES THAT ILLUSTRATE VA PLANNING REQUIREMENTS FOR SPACE, ROOM

CONTENTS, AND ROOM SPECIFIC ENGINEERING SYSTEMS. THEY PROVIDE TYPICAL CONFIGURATIONS, PLANNING CRITERIA, AND GENERAL TECHNICAL GUIDANCE, AND

ARE NOT INTENDED TO BE PROJECT SPECIFIC REQUIREMENTS.

6/28/2018 12:11:03 AM

DISPENSE / CONSULT WINDOW (PHOW2)AXONOMETRIC

LEASING

1

2

3

4

(2.64m)

8'-8"

(1.83m)

6'-0"

(1.83m)

6'-0"

500 NSF

DISPENSE / CONSULT,

WINDOW(PHOW2)125 NSF

CONSULT ROOM(OFDC2)

PRINTER, COMPUTERM1825

CHAIR, DRAFTING,

ROTARY

F0230

BASKET, WASTEPAPERF2000

COMPUTER WITH FLAT

PANEL MONITOR

M1801

(1

.98

m)

6'-6

"

(1

.52

m)

5'-0

"

(3

.05

m)

10

'-0

"

BOARD, BULLETINF3025

TELEPHONE, DESK,

MULTI-LINE

A1015

READER, BAR CODE,

HAND HELD

F2700

CLOCK, BATTERY, 12"F3200

(7.32m)

24'-0"

(7.32m)

24'-0"

PASS-THROUGH

TO FILLING

QUEUING AREA

BOARD, BULLETINF3025

ADA COUNTER

0' 4' 8' 16'

SCALE:

SKETCH TITLE

Plot Date:

DISCLAIMER: ROOM TEMPLATES ARE GRAPHICAL REPRESENTATIONS OF SELECTED ROOM TYPES THAT ILLUSTRATE VA PLANNING REQUIREMENTS FOR SPACE, ROOM

CONTENTS, AND ROOM SPECIFIC ENGINEERING SYSTEMS. THEY PROVIDE TYPICAL CONFIGURATIONS, PLANNING CRITERIA, AND GENERAL TECHNICAL GUIDANCE, AND

ARE NOT INTENDED TO BE PROJECT SPECIFIC REQUIREMENTS.

1/4" = 1'-0"

6/28/2018 12:11:03 AM

DISPENSE / CONSULT WINDOW (PHOW2)FLOOR PLAN

LEASING

B

B

B

B

B

B

B

B

C

C C

C

500 NSF

DISPENSE / CONSULT,

WINDOW(PHOW2)125 NSF

CONSULT ROOM(OFDC2)

(3.81m)

12'-6"

(7.32m)

24'-0"

(3

.05m

)

10

'-0

"

0' 4' 8' 16'

SCALE:

SKETCH TITLE

Plot Date:

DISCLAIMER: ROOM TEMPLATES ARE GRAPHICAL REPRESENTATIONS OF SELECTED ROOM TYPES THAT ILLUSTRATE VA PLANNING REQUIREMENTS FOR SPACE, ROOM

CONTENTS, AND ROOM SPECIFIC ENGINEERING SYSTEMS. THEY PROVIDE TYPICAL CONFIGURATIONS, PLANNING CRITERIA, AND GENERAL TECHNICAL GUIDANCE, AND

ARE NOT INTENDED TO BE PROJECT SPECIFIC REQUIREMENTS.

1/4" = 1'-0"

6/28/2018 12:11:03 AM

DISPENSE / CONSULT WINDOW (PHOW2)REFLECTED CEILING PLAN

LEASING

PRINTER, COMPUTERM1825

COUNTERCT020

BOARD, BULLETINF3025

CAMERA, SURVEILLANCEF2245

CLOCK, BATTERY, 12"F3200

CABINET, FILING,

LATERAL, HALF HEIGHT

F0420

BOARD, BULLETINF3025

PRINTER, COMPUTERM1825

COMPUTER WITH FLAT

PANEL MONITOR

M1801

CHAIR, DRAFTING,

ROTARY

F0230

BASKET, WASTEPAPERF2000

CAMERA, SURVEILLANCEF2245

CABINET, FILING,

LATERAL, HALF HEIGHT

F0420

BOARD, BULLETINF3025

CABINET, FILING,

LATERAL, HALF HEIGHT

F0420

COMPUTER WITH FLAT

PANEL MONITOR

M1801

CHAIR, DRAFTING,

ROTARY

F0230

BASKET, WASTEPAPERF2000

CABINET, FILING,

LATERAL, HALF HEIGHT

F0420

TELEPHONE, DESK,

MULTI-LINE

A1015 COMPUTER WITH FLAT

PANEL MONITOR

M1801

CHAIR, DRAFTING,

ROTARY

F0230

CLOCK, BATTERY, 12"F3200

0' 4' 8' 16'

SCALE:

SKETCH TITLE

Plot Date:

DISCLAIMER: ROOM TEMPLATES ARE GRAPHICAL REPRESENTATIONS OF SELECTED ROOM TYPES THAT ILLUSTRATE VA PLANNING REQUIREMENTS FOR SPACE, ROOM

CONTENTS, AND ROOM SPECIFIC ENGINEERING SYSTEMS. THEY PROVIDE TYPICAL CONFIGURATIONS, PLANNING CRITERIA, AND GENERAL TECHNICAL GUIDANCE, AND

ARE NOT INTENDED TO BE PROJECT SPECIFIC REQUIREMENTS.

1/4" = 1'-0"

6/28/2018 12:11:04 AM

DISPENSE / CONSULT WINDOW (PHOW2)ELEVATIONS

ELEVATION 1 ELEVATION 2

ELEVATION 3 ELEVATION 4

LEASING

0' 4' 8' 16'

SCALE:

SKETCH TITLE

Plot Date:

DISCLAIMER: ROOM TEMPLATES ARE GRAPHICAL REPRESENTATIONS OF SELECTED ROOM TYPES THAT ILLUSTRATE VA PLANNING REQUIREMENTS FOR SPACE, ROOM

CONTENTS, AND ROOM SPECIFIC ENGINEERING SYSTEMS. THEY PROVIDE TYPICAL CONFIGURATIONS, PLANNING CRITERIA, AND GENERAL TECHNICAL GUIDANCE, AND

ARE NOT INTENDED TO BE PROJECT SPECIFIC REQUIREMENTS.

6/28/2018 12:15:38 AM

DISPENSE / CONSULT WINDOW (PHOW2)ROOM DATA

ARCHITECTURAL & INTERIOR DESIGN

Ceiling Type:

Ceiling Height:

Wall Finish:

Base:

Floor Finish:

Special Requirement:

Sound Protection:

Ceiling Finish:

Wainscot:

Slab Depression:

Doors:

Notes:

TELECOMMUNICATION / SPECIAL SYSTEMS

Data:

Telephone:

Duress Alarm:

Intercom:

Motion Intrusion Detection (MID):

Security Surveillance Television (SSTV):

Code Blue:

Cable Television:

Electronic Access and Door Control:

Nurse Call:

Public Address:

VA Satellite TV:

Video Teleconferencing (VTEL):

Special Requirement:

Notes:

LIGHTING

Special Requirement:

Luminaire Type:

Notes:

POWER

Electrical system design to comply with the latest NFPA 70 and 99

Design in accordance with project requirements.

Emergency Power:

Normal Power:

Special Requirement:

Notes:

HEATING, VENTILATING, AND AIR CONDITIONING

Refer to HVAC Design Manual.

Design in accordance with project requirements.Refer to the current version of PG-18-10 Chapter 6 Table 5 –"Mechanical Room Data Sheets" for room temperatures, humidity range, room air change requirements, and pressurization

Notes:

PLUMBING AND MEDICAL GASES

Design in accordance with project requirements.

Cold Water:

Drain:

Medical Air:

Medical Vacuum:

Special Requirement:

Hot Water:

Reagent Grade Water:

Oxygen:

Notes:

FIRE PROTECTION AND LIFE SAFETY

Design in accordance with project requirements.

Alarm Detection:

Sprinkler:

Alarm Annunciator:

Notes:

Ref. Door Type Detail #SD080000-01 for door typesRef. Door Sizes Detail #SD080000-02 for door sizes

General Requirement: Lighting system design shall be based on the guidance of applicable Illuminating Engineering Society North America (IESNA) Standards.

9'-0" (2700mm)

AT

--

m: GWB f:P

--

m: RF at h: 4" (100mm)

RF

--

--

OPEN

--

Yes

Yes

--

--

--

--

Yes

--

--

--

Yes

--

--

--

Design in accordance with project requirements.

--

Connect to receptacles and equipment

--

--

--

--

--

--

--

--

--

--

Visual (15cd), center of tile

--

Recessed pendant, center of tile

LEASING