INTRODUCTION TO SINGLE STACK
The Single Stack system is an engineered single-stack drainage concept for multi-story buildings typically three
stories and taller. Two primary fittings, the Aerator and De-aerator, in conjunction with standard DWV pipe and
fittings make the Single Stack concept unique by accomplishing the function of drainage, waste and venting within
one vertical pipe instead of two. This along with the elimination of individual fixture vents results in reduced costs,
reduced labor, and reduced space requirements.
HISTORY
The Single Stack system was developed in Switzerland in the 1950’s and represented the first time a scientific
approach was taken to the protection of trap seals in sanitary systems. The hydraulic and pneumatics characteristics
of intermittent flows were studied using a 10-story testing tower complete with measuring instruments. It was found
that controlled flow velocities reduced the excessive pressure excursions that can occur in traditional systems. The
unique interior geometry of the Single Stack fitting provides this control and maintains these pressures within
acceptable limits. Once fully perfected, the Single Stack system was marketed to other industrialized counties
around the world. Developed initially in cast iron, Single Stack was introduced to the United States marketplace in
the mid-1960s in the form of a copper DWV system. In 1977, Single Stack became available in hubless cast iron,
which offered superior noise suppression characteristics and ease of assembly.
APPROVALS
Single Stack Aerator and De-Aerator fittings are manufactured to conform to ASTM A1109.
Code approval procedures for Single Stack systems continue to change as model codes are revised and updated to
reflect new and different approaches to plumbing. Most model codes, including various city and state versions, do
not specifically address Single Stack systems and the approval process will differ slightly in each jurisdiction. Single
Stack approvals are often granted under Alternate Material & Methods or Alternate Engineered Design sections of
the prevailing code. In some cases, the approval must be sought for each individual project in a particular
jurisdiction.
Many areas require the manufacturers review and approval of the design and usually must bear the seal of a
Registered Professional Engineer having a license in that jurisdiction.
DESIGN
Wade Specification Drainage Products can assist with the approval process with respect to technical data and plan
review services. While traditional DWV plumbing systems certainly work well, the inventor and subsequent
developers of Single Stack have provided the industry with design criteria and techniques to engineer DWV systems.
This results in performance and savings that are attractive to the professionals of the plumbing industry is evidenced
by the fact that they continue to specify, install, and promote the use of Single Stack. The savings realized with the
use of this proven technological advancement in plumbing helps to maintain a healthy construction industry. Single
Stack is safe, economical, and functional. The performance record is excellent. Contact our office for ways Cast Iron
Single Stack can help you with your next multi-story project.
Single Stack Aerators and De-aerators may be used with stacks, branches, and run-outs made from any acceptable
DWV material providing proper transition couplings are used. Penetrations of floor/ceiling assemblies, shafts, and
fire rated assemblies must be incorporated in accordance with the Building Code requirements. The definition of
sweeps and bends shall be based on cast iron hubless fittings. The written rules shall prevail. Illustration drawings
are included for interpretation and clarity only. Designs and conditions not outlined in this manual shall be submitted
for approval. In accordance with our policy of continual product improvement, we reserve the right to amend
specifications without prior notification. Although every effort is made to ensure accuracy, Wade Specification
Drainage Products cannot be held responsible for errors and omissions in the printing of this manual. All Single
Stack technical data provided by Wade, including but not limited to drawings, catalogs, and consultations remain the
exclusive property of Wade. Use of this information for purposes other than Single Stack products made by Laperle
is strictly prohibited.
1
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
The Single Stack system controls the flow within the pipe to keep pressure excursions from exceeding +/- one-inch of water
column which is the standard for sanitary drainage systems. The system consists of a vertical stack open to the atmosphere,
horizontal branches to each fixture, Aerator fittings, and De-aerator fittings.
The Single Stack conveys waste from the upper levels of the building to the base of each stack. Flow through a vertical stack will
cling to the interior wall surface and proceed downward in a swirling motion leaving the center portion as an open airway. As long
as this airway exists, pressures are balanced within the stack. Left uncontrolled, the flow will increase in speed to a point known
as terminal velocity and can form a complete cross-sectional blockage of the tube. This will result in positive and negative
pressures ahead and behind the flow that may cause trap seal failures through induced siphonage and/or blowback. The Single
Stack system eliminates the formation of the "hydraulic plug" and maintains a core of air throughout the vertical stack.
The horizontal branches connect to the plumbing fixture and direct wastes to the Single Stack. Single Stack branch sizing criteria
allocates approximately 75% of the cross-sectional area for venting purposes. Single Stack branch design remains the key to
flexibility and the developed length limitations that exclude additional re-vent piping far exceed those of "traditional" systems. The
branch size may telescope allowing a possible run-out of fifty-seven feet without a return vent pipe. Developed length is
determined by measuring along the centerline of all horizontal piping located in the ceiling and/or wall space. The vertical drop
distance is not included in the calculation. A Single Stack system does not use the traditional "S-trap" configuration rather it
employs a sizing criteria designed to eliminate self-siphonage and provide proper venting. A typical Single Stack branch
connection to a lavatory would consist of a 1-1/4" tailpiece, a 1-1/2" trap-arm, and a 2" vertical drop making it impossible to
completely fill the 1-1/2" trap-arm with a 1-1/4" tailpiece – much less the 2" vertical drop.
The third component of a Single Stack system is the Aerator fitting. Aerators are placed in the vertical stack usually at each
typical floor level and must remain in a full upright position. They contain no moving parts and require no special tools for
maintenance. Their ability to balance the pressure excursions stem from the geometry of the full size waterways through the body
of the fitting. Two distinct chambers are found in the body of the Aerator fitting. One is called an offset chamber where flows from
the upper floors enter the fitting and actually "offset" around the horizontal branch inlets. This offset is designed to reduce the flow
velocity and also break up any "hydraulic plug" formation associated with terminal velocity. Once leaving the offset chamber it will
again cling to the interior surface of the pipe leaving the center area open for air. This occurs as the flow reaches Aerator fittings
at each floor and also eliminates the need for the "yoke-vents" required in "conventional" systems. Vertical distance between
Aerators must not exceed twenty feet. Interior baffles are situated to control the effects of flow through the Aerator. To guard
against blocking the cross-sectional area of the stack with a horizontal discharge, a second chamber is provided adjacent to the
offset chamber. This mixing chamber is completely separated from the vertical stack flow through the use of a separation baffle.
As horizontal flow enters the Aerator fitting, it must transition to a vertical flow before smoothly uniting with any stack flow. These
actions take place on an intermittent basis as both stack and branch flows may not be present simultaneously. At the top of the
separation baffle, a vent aperture or opening can be found. This provides the venting action between the branches and stack,
which balances any pressure fluctuations. A second baffle is located perpendicular to the separation baffle in the mixing chamber
to prevent cross-flow from opposing branch inlets.
The final component of the Single Stack system is the De-aerator fitting. It is located at the base of each stack and at any
horizontal stack offset. It is designed to effectively deal with the pressure fluctuations that occur when vertical flow transitions to
horizontal flow. This phenomenon is referred to as hydraulic jump and in some cases, can cause a complete cross-sectional
blockage of the horizontal pipe. The De-aerator fitting has two features designed to overcome these adverse effects. The first
feature is an internal nosepiece, which reduces the flow velocity prior to the horizontal transition. It also allows the air and waste
to separate thus balancing the internal pressures. The second feature of the De-aerator fitting is the Pressure Relief Line (P.R.L.).
The P.R.L. outlet is located on top of the De-aerator and is routed from the De-aerator to the horizontal drain. It connects to the
horizontal drain above the centerline at a minimum of distance of ten pipe diameters downstream from the stack. The ten pipe
diameters are based on the stack size (i.e. 4" stack = 40" minimum) and this places the P.R.L. connection beyond the hydraulic
jump zone. Note that all connections into the horizontal drain must meet this minimum distance requirement. The Single Stack
system terminates at the P.R.L. connection point to the horizontal drain
How Single Stack Works
2
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
3
Table A
Fixture Type Trap Size Fixture Unit
Bar Sink 1-1/2 2.0
Bath Group (Full) * 6.0
Bathtub 1-1/2 2.0
Bidet 1-1/2 2.0
Clothes Washer 2 4.0
Dishwasher 1-1/2 2.0
Disposer 1-1/2 3.0
Drinking Fountain 1-1/4 1.0
Floor Drain (2") 2 2.0
Floor Drain (3") 3 5.0
Kitchen Group *** 5.0
Lavatory 1-1/4 1.0
Table A-1 (Fixture Units for Water Saving Fixtures)
Fixture Type Trap Size Apartments &
Condominiums
Office Buildings &
Commercial Spaces Hotels & Motels
Bar Sink 1-1/4 0.5 0.5 0.5
Bath Group (Full) * 3.0 4.0
Bath Group (Half) ** 2.0 3.0
Bathtub 1-1/2 3.0 3.0
Bidet 1-1/2 1.0 1.0
Clothes Washer 2 4.0
Dishwasher 1-1/2 2.0 2.0
Disposer 1-1/2 0.5
Drinking Fountain 1-1/4 0.5
Floor Drain (Emergency) 2 thru 4 0.0 0.0 0.0
Kitchen Group *** 3.0
Lavatory 1-1/4 1.0 1.0 0.5
Service Sink 3 3.0 3.0 3.0
Shower 2 2.0 2.5
Sink 1-1/2 2.0 2.0 2.0
Urinal 2 3.0
Water Closet 3 3.0 3.0
Water Closet (Public) 3 4.0
Table A (continued)
Fixture Type Trap Size Fixture Unit
Lavatory 1-1/4 1.0
Service Sink 3 5.0
Shower 2 2.0
Sink 1-1/2 2.0
Urinal 2 4.0
Water Closet 3 6.0
All Other Fixtures
1-1/4 1.0
1-1/2 2.0
2 3.0
2-1/2 4.0
3 5.0
4 6.0
* Bath Group (Full) consists of (1) Water Closet (1) Lavatory and (1) Tub/Shower.
** Bath Group (Half) consists of (1) Water Closet and (1) Lavatory.
*** Kitchen Group consists of (1) Sink Trap with Dishwasher and Disposer.
Drainage Fixture Unit Values
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
4
Table B (Single Stack Loading)
Stack Size
(Inches)
Maximum Drainage
Fixture Units
3" * 64
3" (Over 7
Floors) * 102
4" 504
5" 1,010
6" 2,200
8" 3,900
* No more than 12 water closets are
permitted on 3" stacks. The 3" stack
will use a 4" De-Aerator at the base of
the stack.
Single Stack fittings are manufactured in accordance with ASTM A1109-18
Standard Specification for Special Fittings for Single-Stack Hubless Cast Iron
Soil Pipe Fittings for Sanitary, Waste and Vent Piping Applications
Table D (Branch Loading)
Maximum Drainage Fixture Units
Branch Size
(Inches)
Horizontal Piping
1/4" Per. Ft.
Slope
1/8" Per. Ft.
Slope
2" 6 ** 5 **
3" 16 13
4" 90 72
** No water closets are permitted on 2"
branch lines. Clothes washing machine
branch lines (2") shall not exceed five feet
(5’-0") in developed length.
Drainage Fixture Unit Values
Fixture Load Tables
Table B (Single Stack Stack Loading)
Stack Size (Inches) Maximum Drainage
Fixture Units
3" * 64
3" (Over 7 Floors) * 102
4" 504
5" 1,010
6" 2,200
8" 3,900
* No more than 12 water closets are permitted
on 3" stacks. The 3" stack will use a
4" De-Aerator at the base of the stack.
Table C (Building Drain Loading)
Maximum Drainage Fixture Units
Drain Size
(Inches)
Horizontal Piping
1/4" Per. Ft.
Slope
1/8" Per. Ft.
Slope
4" 216 175
5" 350 280
6" 850 680
8" 2,700 2,160
10" 3,900 3,120
12" 5,800 4,640
Note: This Table is also used for sizing
horizontal stack offsets.
Table C (Building Drain Loading)
Maximum Drainage Fixture Units
Drain Size
(Inches)
Horizontal Piping
1/4” Per. Ft.
Slope
1/8” Per. Ft.
Slope
3” 42 36
4” 120 96
5” 350 280
6” 850 680
8” 2,700 2,160
10” 3,900 3,120
12” 5,800 4,640
Note: This Table is also used for sizing horizon-
tal stack offsets.
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
5
Drawing 1
Sizing Requirements
Aerator and Stack Rules
See Table ‘B’ for
vertical stack
Extend stack full size thru roof
See to Table ‘C’ for
horizontal drain sizing
Refer to Table ‘D’ for horizontal
branch sizing
(A) The stack size shall be in accordance with Table B based on the total fixture unit load determined by Table A or
A-1.
(B) The stack shall not telescope or decrease in size and must be continued full size through the roof. (Drawing 1)
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
6
Drawing 2
Required Aerator Connections
Aerator and Stack Rules
Aerator Fitting
De-Aerator Fitting
Extend stack full size thru roof
(C.) An Aerator fitting is required at each level where the following horizontal branches enter the stack:
(Drawing 2) (1) Any soil branch (2) A waste branch the same size as the stack size (3) A waste branch one
pipe size smaller than the stack size.
(D.) The Aerator fitting must be placed in a vertical plane. Tilting the Aerator to offset the Single Stack stack is not
permitted.
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
7
Drawing 3
In-Line Offset Requirements
In-Line offsets are made using (1) quarter bend
and (2) eighth bends.
Maximum of (2) In-Line Offsets are permitted.
Aerator and Stack Rules
(E.) At any level where an Aerator is not required, an "in-line" offset consisting of two one-eighth bends and one
quarter bend may be used. The vertical distance between Aerators or "in-line" offsets shall not exceed twenty
feet (20’-0").
NO MORE THAN TWO CONSECUTIVE "IN-LINE" OFFSETS ARE PREMITTED. (Drawing 3)
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
8
(F.) Waste branches two pipe sizes smaller than the stack size may connect directly to the stack through a sani-
tary fitting. (Drawing 4)
Clear Waste water branches only. No soil branches from water closets are permitted.
Table F (Single Stack Waste
Branch Sizing) *
Stack Size
(Inches)
‘A’
Maximum Waste
Size
‘B’
3" 2"
4" 2 1/2"
5" 3"
6" 4"
* Clear Waste water branches only. No
soil branches from water closets are
permitted
Aerator and Stack Rules
Drawing 4
Direct Stack Connections
Stack Size ‘A’
Stack from upper floors
Stack Size ‘A’
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
9
(G) Horizontal stack offsets exceeding sixty degrees (60°) from vertical require a De-aerator fitting and Pressure
Relief Line (PRL). The Pressure Relief Line connects to the vertical portion of the stack downstream of the
offset. Soil and waste branches may connect to the horizontal portion of the offset. These connections should be
made between the two vertical portions of the stack at a minimum distance of ten pipe diameters (based on
stack size) downstream of the higher vertical stack. Branch connections to a horizontal stack offset less than ten
pipe diameters in length should be made as far downstream on the horizontal as possible. Soil and waste
branches must not connect where the offset makes a horizontal change of direction. Waste branches may
connect to the horizontal portion of the Pressure Relief Line (PRL), except on buildings with battery type water
closet installations. Waste branches shall be at least one pipe size smaller than the PRL. Waste branch
connections must not be made into any vertical portion of the PRL. Clothes washers must not connect to the
PRL. Horizontal stack offsets should be sized per Table ‘C’ based on the total fixture unit load of all fixtures
connecting to the offset and fixtures upstream. The entire stack size must not be smaller than the largest
horizontal offset size. (Drawing 5)
Aerator and Stack Rules
Drawing 5
Stack Offset Requirements
Stack from
upper floors
Installer is responsible for
proper support of piping
per local code authority.
PRL is not required to be directly above soil line. It is required to be at a higher elevation than the soil line prior to connection
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
10
Aerator and Stack Rules
Drawing 6
Combining Stacks
The PRL connection to the
horizontal drain terminates
the Single Stack system
Stack from upper floors
Stack from upper floors
Installer is responsible for
proper support of piping
per local code authority.
(H) Single Stack stacks may be combined before entry into the main sewer connection. The stacks should combine
downstream of each Pressure Relief Line (PRL) termination point. The total fixture unit load of the combined
stacks determines collection main line sizing. (Drawing 6)
PRL is not required to be directly above soil line.
It is required to be at a higher elevation than the
soil line prior to connection
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
11
Waste & Soil Branch Rules
Drawing 40
Multiple Single Stack Connections
(I) An additional Single Stack may be connected to another Single Stack if a De-Aerator fitting is incorporated
below the stack Aerator fitting and a pressure relief line connects below the branch. The connection must be
made with a wye type fitting. Sizing of the branch is established by the drainage fixture units upstream of the
connection. Sizing for the main Single Stack is the total drainage fixture units of the combined stacks.
(Drawing 40)
PRL is not required to be directly above soil
line. It is required to be at a higher eleva-
tion than the soil line prior to connection
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
12
Drawing 7
Vent Offset Requirements
Aerator and Stack Rules
4" Stack
4" Stack
(J) Stack vent headers above the highest fixture may offset prior to the vent thru roof penetration (VTR). The
horizontal vent header and VTR should be increased one pipe size when exceeding twenty feet (20’-0") in
horizontal length. (Drawing 7)
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
13
Drawing 8
Vent Offset Requirements
Aerator and Stack Rules
4" Stack
4" Stack 4" Stack
4" Stack
(K) Stack vent headers above the highest fixture may be combined prior to the vent thru roof penetration (VTR)
with one vertical stack extending through the roof. The one combined vertical stack must be one pipe size
larger than the largest of the combined stacks. If the distance between any stack and the VTR exceeds twenty
feet (20’-0"), the horizontal offset shall be increased one (1) pipe size larger than the downstream stack.
(Drawing 8)
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
14
De-Aerator and Building Drain Rules
(A) A De-aerator fitting is required at the base of each stack. The De-aerator fitting shall be installed in the vertical
portion of the stack. The distance between the De-aerator fitting and the Single Stack building drain shall not
exceed five feet (5’-0"). (Drawing 9)
De-Aerator and Building Drain Rules
Drawing 9
Base of Stack Requirements
Stack from upper floors
Installer is responsible for
proper support of piping
per local code authority.
PRL is not required to be directly
above soil line. It is required to be
at a higher elevation than the soil
line prior to connection
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
15
(B) The Single Stack building drain size shall be in accordance with Table ‘C’ based on the total fixture unit load
determined by Table A or A-1. The transition to a larger Single Stack building drain size shall be made in the
vertical stack below the Deaerator fitting, except as noted in paragraph "L". (Drawing No. 10)
Drawing 10
Base of Stack Requirements
De-Aerator and Building Drain Rules
Table C (Building Drain Loading)
Maximum Drainage Fixture Units
Drain Size
(Inches)
Horizontal Piping
1/4” Per. Ft.
Slope
1/8” Per. Ft.
Slope
3” 42 36
4” 120 96
5” 350 280
6” 850 680
8” 2,700 2,160
10” 3,900 3,120
12” 5,800 4,640
Note: This Table is also used for sizing horizon-
tal stack offsets.
Piping downstream of the Pressure Relief Line (PRL) is considered conventional
plumbing and shall be sized by the prevailing Plumbing Code or Table C, whichever is
applicable. Fixture unit values shall be based on data from Table A or Table A-1.
Stack from upper floors
The Pressure Relief Line connection
to the horizontal drain terminates the
Single Stack system
Installer is responsible for
proper support of piping
per local code authority.
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
16
(C) The De-Aerator fitting requires a Pressure Relief Line (PRL). The Pressure Relief Line (PRL) connects to the
Single Stack building drain a MINIMUM distance of ten pipe diameters (based on stack size) downstream from
the centerline of the stack. The PRL connects to the Single Stack building drain above the centerline of the
drain. The PRL may be rolled to the side providing the bottom of the PRL is above the centerline of the Single
Stack building drain. (Drawing 11)
Drawing 11
Pressure Relief Line Requirements
Minimum Pressure Relief
Line Elevation Requirements
De-Aerator and Building Drain Rules
Stack Size
Installer is responsible for
proper support of piping
per local code authority.
PRL is not required to be directly above soil line.
It is required to be at a higher elevation than the
soil line prior to connection
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
17
(D) The installed slope for the Single Stack building drain and PRL is recommended to be one-quarter inch per
foot (2%). Installed slopes of one-eighth inch per foot (1%) are permitted, however pipe capacity is reduced by
a factor of 0.8 as shown in Table C. Installed slopes less than one-eighth inch per foot (1%) are strictly
prohibited. (Drawing 12)
Drawing 12
Installed Slope Requirements
De-Aerator and Building Drain Rules
Stack from upper floors
Building Drain Line
Table C (Building Drain Loading)
Maximum Drainage Fixture Units
Drain Size
(Inches)
Horizontal Piping
1/4” Per. Ft.
Slope
1/8” Per. Ft.
Slope
3” 42 36
4” 120 96
5” 350 280
6” 850 680
8” 2,700 2,160
10” 3,900 3,120
12” 5,800 4,640
Note: This Table is also used for sizing horizontal
stack offsets.
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
18
De-Aerator and Building Drain Rules
(E) Soil and waste branches may connect to the Single Stack building drain BETWEEN the centerline of the stack
and the termination point of the Pressure Relief Line (PRL). All connections shall be made a MINIMUM distance
of ten pipe diameters (based on stack size) downstream from the centerline of the stack. (Drawing No. 13)
See Table ‘C’ for Horizontal
Single Stack Drain Sizing
Note: Minimum distance requirements apply to any connection into the horizontal drain.
Drawing 13
Base of Stack Connections
Note: Recommended Lavatory waste is 1-1/4’ tailpiece with 1-1/2" trap arm.
Min. 10 Pipe Diameters
(Based on Stack Size)
Stack Size
Table C (Building Drain Loading)
Maximum Drainage Fixture Units
Drain Size
(Inches)
Horizontal Piping
1/4” Per. Ft.
Slope
1/8” Per. Ft.
Slope
3” 42 36
4” 120 96
5” 350 280
6” 850 680
8” 2,700 2,160
10” 3,900 3,120
12” 5,800 4,640
Note: This Table is also used for sizing hori-
zontal stack offsets.
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
19
De-Aerator and Building Drain Rules
Drawing 14
Base of Stack Connections
(F) Soil and waste branches cannot connect where the Single Stack building drain makes a horizontal change of
direction. (Drawing 14)
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
20
De-Aerator and Building Drain Rules
Drawing 15
Branch Connections to P.R.L.
(G) Waste branches may connect to the horizontal portion of the Pressure Relief Line (PRL), except on battery type
installations. Waste branches shall be at least one pipe size smaller than the PRL. Waste branch connections
shall not be made into any vertical portion of the PRL. Clothes washers must not connect to the PRL.
(Drawing No. 15)
Note: Recommended Lavatory waste is 1-1/4" tailpiece with 1-1/2" trap arm.
Soil branches are not allowed to connect to PRL.
Minimum 10 Pipe Diameters
(Based on Stack Size)
Stack from upper floors
Installer is responsible for
proper support of piping
per local code authority.
Table H (Maximum Branch Size)
Maximum Drainage Fixture Units
PRL Size
(Inches)
Max. Branch
Size
PRL Max.
DFU’s
3” 2 1/2” 16
4” 3” 90
6” 3” 90
Note: Minimum distance requirements
apply to any connection into a horizontal
drain line. Connections to PRL are for
clear water waste only—No soil waste
allowed; No clothes washers; No
connections allowed on any vertical
portion of the PRL.
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
21
De-Aerator and Building Drain Rules
(H) Soil and waste branches may connect downstream of the Pressure Relief Line (PRL) termination point
providing conventional plumbing rules are applied. The vent header from these fixtures may connect to the
vertical portion of a Single Stack stack below an Aerator fitting through a sanitary tee installed with the flow
radius down. The vent load of these fixtures shall be added to the fixture unit load on the Single Stack stack.
(Drawing No. 16)
Drawing 16
Conventional Remote Venting
Remote "conventional" plumbing.
Size waste and vents per local code.
Remote "conventional" plumbing.
Size waste and vents per local code.
Note 1: the Pressure Relief Line
(PRL) connection to the horizontal
drain terminates the Single Stack
System.
Stack from upper floors
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
22
De-Aerator and Building Drain Rules
(I) Soil and waste branches may connect to the vertical stack below the De-aerator fitting. These connections shall
be made through a wye-type fitting or through an Aerator fitting. (Drawing No. 17)
Drawing 17 De-Aerator Transition Details
PRL = Pressure Relief Line
W.C. = Water Closet
PRL = Pressure Relief Line
F.M.B.O. = Floor Mount Back Outlet
W.C. = Water Closet
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
23
De-Aerator and Building Drain Rules
(J) Entry to the Single Stack building drain from the stack shall be made using a short sweep (where allowed by
code), long sweep, two one-eighth bends, or a combination wye & one-eighth bend with blind plug upstream.
Drawing 18 De-Aerator Transition Details
Short Sweep (where allowed by local code)
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
24
De-Aerator and Building Drain Rules
(K) Fixtures considered too remote from the Single Stack may be plumbed by conventional methods. This waste
and vent area shall be sized in accordance with local prevailing ordinances. (Drawings 16 & 19)
Drawing 19
Remote Plumbing Connections
Remote "conventional" plumbing.
Size waste and vents per local code.
Note: Recommended Lavatory waste is 1-1/4" tailpiece with 1-1/2" trap arm.
Stack continues to lower floors
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
25
De-Aerator and Building Drain Rules
(L) Commercial building battery type installations and Single Stack stacks serving clothes washers shall use a De-
Aerator fitting equal in size to the Single Stack building drain serving that stack. A four-inch (4") De-aerator fitting
will be required on three-inch (3") Single Stack. (Drawing 20)
Drawing 20
Battery Installations
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
26
Branch Line Rules
(A) The maximum developed length of a three-inch (3") soil branch shall not exceed twelve feet (12’-0"). (Drawing
21)
Soil Branch Rules
Drawing 21
3" Soil Branch Developed Lengths
(B) The maximum developed length of a four-inch (4") soil branch shall not exceed twenty-seven feet (27’-0").
(Drawing 22)
Drawing 22
4" Soil Branch Developed Lengths
Maximum 12'-0"
Maximum 27'-0"
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
27
Soil Branch Rules
(C) Developed lengths are measured along the centerline of all horizontal branch piping located in ceiling and wall
areas. Vertical drops from trap arms or fixtures are not included in the developed length calculations. Developed
length distances include 45⁰ elevation changes. (Drawing 22)
Drawing 22
3" & 4" Combined Soil Branch Developed Lengths
Maximum 12'-0"
Maximum 27'-0"
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
28
(D) The maximum developed length of a two-inch (2") waste branch shall not exceed fifteen feet (15’-0"). The
maximum developed length of a three-inch (3") waste branch shall not exceed fifteen feet (15’-0"). Developed
lengths are measured along the centerline of all horizontal branch piping located in ceiling and wall areas.
Vertical drops from trap arms or fixtures are not included in the developed length calculations. Waste branches
two pipe sizes smaller than the stack size may connect directly to the stack through a sanitary fitting.
(Drawing 23)
Clear Waste Branch Rules
Drawing 23
Waste Branch Developed Lengths
Maximum 15'-0"
Maximum 15'-0"
Maximum 15'-0"
3" 3" 3"
3"
Developed length distances shall
include 45° elevation changes
Note: Recommended Lavatory waste is 1-1/4" tailpiece
with 1-1/2" trap arm
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
29
(E) Telescoping branches are allowed; each size can accommodate the maximum developed length for that size:
A two-inch (2") waste branch shall not exceed fifteen feet (15'-0"); a three-inch (3") waste branch shall not
exceed fifteen feet (15'-0"); a four-inch (4") waste branch shall not exceed twenty seven feet (27'-0").
Developed lengths are measured along the centerline of all horizontal branch piping located in ceiling and wall
areas. Vertical drops from trap arms or fixtures are not included in the developed length calculations. Waste
branches two pipe sizes smaller than the stack size may connect directly to the stack through a sanitary fitting.
(Drawing 24)
Waste Branch Rules
Drawing 24
Waste Branch Developed Lengths
Maximum 15'-0"
Maximum 15'-0"
Maximum 15' 0"
Maximum 27'-0"
Maximum 15'-0"
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
30
(F) Branch sizing shall be in accordance with Table D based on the total fixture unit load determined by Table A or
A-1. The installed slope for horizontal branches is recommended to be one-quarter inch per foot (2%). Installed
slopes of one-eighth inch per foot (1%) are permitted however pipe capacity is reduced by a factor of 0.8 as
shown in Table D. Installed slopes less than one-eighth inch per foot (1%) are strictly prohibited.
(G) Branches having three ninety degree (90°) horizontal changes of direction shall be increased one pipe size at
the third ninety degree ( 90°) change of direction nearest the stack. (Drawing 25)
Waste Branch Rules
Drawing 25
Change of Direction Branch Detail
(H) This increase is not required if one of the directional changes can be made with two one-eighth bends or a short
sweep radius bend. (Drawing 26)
Drawing 26
Change of Direction Branch Detail
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
31
Waste Branch Rules
(I) The transition from a horizontal or vertical branch to another horizontal branch must be made with a wye-type
fitting. (Drawing 27)
(J) Horizontal branch piping at the base of a vertical drop exceeding forty inches (40") in height shall be increased
one pipe size. This increase is not required when the lower portion of the drop is made at forty-five degrees
(45°) and the upper vertical portion is less than forty inches (40"). (Drawing No. 28)
Drawing 28
Branch Sizing—Vertical Drops
40" or Less
Over 40"
40" or
Less
Over 40"
Drawing 27
Change of Direction Branch Detail
Note: Recommended Lavatory waste is
1-1/4" tailpiece with 1-1/2" trap arm.
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
32
Waste Branch Rules
(K) Branch piping with vertical drops exceeding ten feet (10’-0") shall be increased one pipe size. (Drawing 29)
Drawing 29
Branch Sizing—Vertical Drops
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
33
Waste Branch Rules
Drawing 30
Soil Branch Connection Detail
(L) A three-inch (3") soil branch shall be increased one pipe size at the connection
point of other fixtures. This increase is not required when computing fixture unit
loads from Table A-1. (Drawing 30)
(M) Two fixtures using 1-1/4" tailpiece/trap sizes may combine into a single two-inch (2") vertical drop. (Drawing 31)
Drawing 31
Combining Branches into a Vertical Drop
Note: Recommended Lavatory
waste is 1-1/4" tailpiece with 1-1/2"
trap arm.
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
34
Waste Branch Rules
(N) Fixtures using 1-1/2" tailpiece/trap sizes and larger require separate vertical drops from each trap arm or may
combine into a single vertical drop that is increased one pipe size. This increase is not required if the change in
elevation is made at forty-five degrees (45°). The fixture trap arm shall be one pipe size larger than the fixture
tailpiece and this increase may be made at the wall. (Drawing 32)
Drawing 32
Branch Sizing—Vertical Drops
Note: Recommended Lavatory waste is 1-1/4" tailpiece with 1-1/2" trap arm.
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
35
Waste Branch Rules
Drawing 33
Clothes Washer Branch
Maximum 5'-0"
Maximum 15'-0"
Clothes washer branches shall be three-inch (3") in size. Clothes washer branches with
no vertical drops and developed lengths five feet (5'-0") or less may be two-inch (2") in
size. (Drawing 33)
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
36
Waste & Soil Branch Rules
(O) Soil branch connections to the Single Stack shall be made through the "C" and/or "D" inlet of the Aerator fitting.
Soil branch developed lengths shall not exceed 12'-0" for a three inch branch size or 27'-0" for a four inch
branch size. (Drawing 34)
Maximum 12’-0"
Maximum 27’-0"
Drawing 34
Soil Branch Developed Lengths
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
37
(P) Pressure Equalizing Lines may be used as an alternate to the rules concerning increased branch sizes.
Pressure Equalizing Lines shall rise vertically above the branch and connect to the Single Stack stack above the
flood rim of the fixtures they serve. Pressure Equalizing Lines may be routed directly through the roof.
(Q) Soil branch lengths beyond the limits stated in paragraph (P) will require a conventional vent or a 2" Pressure
Equalizing Line (PEL). The vent header or PEL may connect to the Single Stack stack a minimum of 3'-0"
above the Aerator fitting. (Drawing 35)
Waste Branch Rules
Drawing 35
Clothes Washer Branch
Over 27’-0"
Over 15’-0"
Table I
(Minimum Pressure Equalizing Line)
Branch Size (Inches) Pressure Equalizing
Line Size (Inches)
4" 2"
3" 1-1/2"
2" 1-1/4"
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
38
Waste & Soil Branch Rules
Drawing 36
Waste Branch Developed Lengths
Maximum 15'-0"
Maximum 15'-0"
Maximum 27'-0"
Maximum 15'-0"
(R) Waste branch developed lengths shall not exceed 15'-0" for two or three inch pipe sizes; Waste branch
developed lengths shall not exceed 27'-0" for four inch pipe sizes. Developed lengths beyond these limits
require a convention vent or a Pressure Equalizing Line (PEL). The vent header or PEL may connect to the
Single Stack a minimum of 3'0" above the Aerator fitting. (Drawing 36)
Note: Recommended Lavatory waste is 1-1/4" tailpiece with 1-1/2" trap arm.
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
39
Waste & Soil Branch Rules
Drawing 37
Waste & Soil Branch Connections
(S) Waste branches one pipe smaller than the pressure relief line (PRL) may connect to the PRL. Soil branches
and washing machine connections are not allowed. No connections are permitted into any vertical portion of
the PRL. Note 1: Soil and waste branches may connect to the horizontal drain between the Single Stack stack
and the PRL termination provided the connection is a minimum of 10 pipe diameters downstream of the stack
centerline.
The De-Aerator fitting may be installed above the finished floor providing it is within 5'-0" of the horizontal drain.
(Drawing 37)
Note: Recommended Lavatory waste is 1-1/4" tailpiece with 1-1/2" trap arm.
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
40
Waste & Soil Branch Rules
(T) Horizontal stack offsets shall be sized per Table ‘C’ based on
the drainage fixture unit loading of all upstream fixtures.
Increasing the horizontal drain size at this point will require an
increase of the entire stack size from just above the lowest
level de-aerator fitting and continued to the vent terminal. The
pressure relief line (P.R.L.) shall connect to the vertical portion
of the stack downstream of the offset. The horizontal drain at
the base of the Single Stack shall be sized per Table ‘C’ and
shall not be smaller than the required stack size. (Drawing 38)
Drawing 38
Multiple Offset Stack Requirements
Table C (Building Drain Loading)
Maximum Drainage Fixture Units
Drain Size
(Inches)
Horizontal Piping
1/4” Per. Ft.
Slope
1/8” Per. Ft.
Slope
3” 42 36
4” 120 96
5” 350 280
6” 850 680
8” 2,700 2,160
10” 3,900 3,120
12” 5,800 4,640
Note: This Table is also used for sizing horizontal
stack offsets.
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
41
Waste & Soil Branch Rules
Drawing 39
Multiple Vent Header Sizing Requirements
(U) Multiple Vent Header Sizing Requirements. (Drawing 39)
Note 1: The horizontal portion of each individual vent header that exceeds 20'-0" in length shall be increased
one pipe size larger than the downstream stack size.
Note 2: The vent header from two combined vent headers shall be increased one pipe size larger than the
largest individual vent. This increased sizing does not apply if previously made as noted above.
Note 3: Sizing for three or more combined vent headers is based on the cumulative drainage fixture unit total
from each stack and capacities shown in Table J.
Table J
Vent Header Size
(Inches) Maximum D.F.U. Load
5" 600
6" 1380
8" 3600
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
42
Aerator Rough-In and Block-out
Single Stack is adaptable to most multi-story projects with minimal structural impact and in many instances reduces space
requirements for DWV systems. The available space for dropped ceilings will alter the Aerator fitting location and the resulting
slab penetration. The following illustrations are minimal cored opening or block-out conditions for 4" pipe size Aerator fittings.
Note: Dimensions of Aerator rough-in can be
altered if a slab relief is provided on the bottom
of the cored opening or a larger diameter core
is utilized.
Slab Block-out
Cored Slab
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
43
De-Aerator Rough-In
The De-Aerator fitting is often located above the finish floor to reduce ceiling space requirements. The following
illustrations show dimensional data for connection methods to the De-Aerator fitting.
4" De-Aerator w/ PRL Fitting 4" De-Aerator w/ Upright Wye & Cap
4" De-Aerator w/ Quarter Bends 4" De-Aerator w/ Quarter Bends & Eighth Bends
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
44
Supplemental Illustrations
The following pages are to be used for interpretation and clarity of the written rules listed on the preceding pages. The
written rules shall take precedence over all illustrations. All possible scenarios are not covered by these illustrations.
Designs and conditions not shown may require approval by the manufacturer.
System Page
Water Closet Connections (Floor Mount Floor Outlet)……………………………………………... 47
Water Closet Connections (Wall Hung Foot Support)……………………………………………….48
Water Closet Connections (Floor Mount Back Outlet)……………………………………………... 49
Bathroom Connections (Water Closet / Lavatory / Tub)…………………………………………… 50
Bathroom Connections (Water Closet / Lavatory / Tub)…………………………………………… 51
Bathroom Connections (Water Closet / Lavatory / Tub)…………………………………………… 52
Bathroom Connections (Water Closet / Lavatory / Tub) Back to Back…………………………… 53
Bathroom Connections (Water Closet / Lavatory / Shower / Bidet)………………………………. 54
Bathroom Connections (Water Closet / Lavatory / Tub / Shower / Sink)………………………… 55
Miscellaneous Connections (Floor Drain / Water Cooler / Shower / Mop Sink / Sink)…………. 56
Commercial Building Connections (Water Closets / Urinals / Floor Drains)…………………….. 57
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
45
Typical Layouts
Water Closet Connections
Typical Floor Mount Floor Outlet
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
46
Typical Layouts
Water Closet Connections
Wall Hung Foot Supported
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
47
Typical Layouts
Water Closet Connections
Typical Floor Mount Back Outlet
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
48
Typical Layouts
Bathroom Connections
Water Closet / Tub / Lavatory (Back to Back)
Note: Recommended Lavatory waste is 1-1/4" tailpiece with 1-1/2" trap arm.
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
49
Typical Layouts
Bathroom Connections
Water Closet / Tub / Lavatory (Back to Back)
Note: Recommended Lavatory waste is 1-1/4" tailpiece with 1-1/2" trap arm.
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
50
Typical Layouts
Bathroom Connections
Water Closet / Tub / Lavatory (Back to Back)
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
51
Typical Layouts
Bathroom Connections
Water Closet / Tub / Lavatory (Back to Back)
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
52
Typical Layouts
Bathroom Connections
Water Closet / Shower / Lavatory / Bidet
Note: Recommended Lavatory waste is 1-1/4" tailpiece with 1-1/2" trap arm.
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
53
Typical Layouts
Bathroom Connections
Water Closet / Tub / Shower / Lavatories / Sink
Note: Recommended Lavatory waste is 1-1/4" tailpiece with 1-1/2" trap arm.
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
54
Typical Layouts
Miscellaneous Fixture Connections
Wash Machine / Shower / Sink / Water Cooler / Mop Sink
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
55
Typical Layouts
Commercial Building Connections
Water Closets / Floor Drains / Urinal
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
56
Terms and Conditions of Sale
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
57
Terms and Conditions of Sale
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
58
Specification and Manufacturer Services
We suggest the following specification.
The Cast Iron Single Stack DWV system shall be installed in accordance with approved construction plans and specifications,
and in compliance with criteria set forth by Design Manual #119 as published by Wade Specification Drainage Products.
The cast iron single stack Aerator and De-aerator fittings shall be manufactured and distributed by Wade. The Aerator and De-
aerator fittings shall be in compliance with ASME Standard A1109 as published by the American Society of Mechanical
Engineers.
Contact Wade Specification Drainage Products by phone at 800-638-9537 or fax at 888-879-9233 for additional information.
MANUFACTURER SERVICES
In addition to normal business services, Wade Specification Drainage Products will:
• Furnish complete technical assistance and information on the latest techniques of design, installation and inspection of the
Cast Iron Single Stack system.
• Provide design/drawing assistance, plans check, and drawing review.
• Provide Value Engineering assistance.
• Provide field inspection service with written reports furnished to all designated parties. Inspections and reports will be
subject to a negotiated, equitable fee.
• Provide assistance in training of designers, installers and inspectors on an as needed, invitational basis. Seminars will be
subject to a negotiated, equitable fee.
These services assume the obvious. Wade Specification Drainage Products shall furnish all Cast Iron Single Stack products and
the design shall comply with all appropriate criteria set forth by Design Manual #119.
DESIGN NOTES
All Cast Iron Single Stack technical data provided by Wade including but not limited to drawings, catalogs, and consultations
remain the exclusive property of Wade Specification Drainage Products. Use of this information for purposes other than Single
Stack products made by Wade is strictly prohibited and may result in the assessment of fees or charges.
The Wade Single Stack system represents a logical advancement in the technology of sanitary drainage systems. This
manual is intended to address basic plumbing rules that apply when designing, installing, or inspecting a Cast Iron
Single Stack system.
The use of Single Stack Design Manual #119 along with good plumbing practices and techniques will assure a safe and modern
plumbing system. Installation requirements such as clean-outs, hydraulic integrity, support systems, slab penetrations and
fireproofing do not differ from traditional DWV practices and continue to be the responsibility of the designers, installers and
inspectional authorities.
Single Stack Aerators and De-aerators may be used with stacks, branches, and run-outs made from any acceptable DWV
material providing proper transition couplings are used. Penetrations of floor/ceiling assemblies, shafts, and fire rated assemblies
must be protected in accordance with the Building Code requirements.
The definition of sweeps and bends shall be based on cast iron hubless fittings manufactured in accordance with ASTM Standard
A888.
In reference to Design Manual #119, the written rules shall prevail. Illustration drawings are included for interpretation and clarity
only.
Designs and conditions not outlined in this manual shall be submitted for approval to Wade Specification Drainage Products.
In accordance with our policy of continual product improvement, we reserve the right to amend specifications without prior
notification. Although every effort is made to ensure accuracy, Wade Specification Drainage Products cannot be held responsible
for errors and omissions in the printing of this manual.
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
59
Single Stack Aerator Rules
(A) The stack size shall be in accordance with Table B based on the total fixture unit load determined by Table A or
A-1.
(B) The stack shall not telescope or decrease in size and must be continued full size through the roof.
(C) An Aerator fitting is required at each level where the following horizontal branches enter the stack:
• Any soil branch
• A waste branch the same size as the stack size.
• A waste branch one pipe size smaller than the stack size
• The Aerator fitting shall be placed in a vertical plane. Tilting the Aerator to offset the Sovent® stack is not
permitted.
• At any level where an Aerator is not required, an "in-line" offset consisting of two one-eighth bends and one
quarter bend may be used. The vertical distance between Aerators or "in-line" offsets shall not exceed twenty
feet (20’-0"). No more than two consecutive "in-line" offsets are permitted.
(F) Waste branches two pipe sizes smaller than the stack size may connect directly to the stack through a sanitary
fitting.
(G) Horizontal stack offsets exceeding sixty degrees (60) from vertical require a De-aerator fitting and Pressure
Relief Line (PRL). The Pressure Relief Line (PRL) shall connect to the vertical portion of the stack downstream of
the offset. Soil and waste branches may connect to the horizontal portion of the offset. These connections shall be
made BETWEEN the two vertical portions of the stack at a minimum distance of ten pipe diameters (based on stack
size) downstream of the higher vertical stack. Branch connections to a horizontal stack offset less than ten pipe
diameters in length shall be made as far downstream on the horizontal as possible. Soil and waste branches shall
not connect where the offset makes a horizontal change of direction. Waste branches may connect to the horizontal
portion of the Pressure Relief Line (PRL), except on office building battery type installations. Waste branches shall
be at least one pipe size smaller than the PRL. Waste branch connections shall not be made into any vertical portion
of the PRL. Clothes washers shall not connect to the PRL. Horizontal stack offsets shall be sized per Table C based
on the total fixture unit load of all fixtures connecting to the offset and fixtures upstream. The entire stack size shall
be no smaller than the largest horizontal offset size.
(H) Wade Single Stack may be combined before entry into the main sewer drain. The stacks shall combine
downstream of each Pressure Relief Line (PRL) termination point. The total fixture unit load of the combined stacks
determines collection drain line sizing.
(I) Stack vent headers above the highest fixture may offset prior to the vent thru roof penetration (VTR). The
horizontal vent header and VTR shall be increased one pipe size when exceeding twenty feet (20’-0") in horizontal
length.
(J) Stack vent headers above the highest fixture may be combined prior to the vent thru roof penetration (VTR) with
one vertical stack extending through the roof. The one combined vertical stack shall be one pipe size larger than the
largest of the combined stacks. If the distance between any stack and the VTR exceeds twenty feet (20’-0"), the
horizontal offset shall be increased one (1) pipe size larger than the downstream stack.
Single Stack
Wade Drains • 11910 CR 492, Tyler, TX 75706 • Phone: 800-638-9537 Fax: 888-879-9233 • wadedrains.com
60
Single Stack De-Aerator Rules
(A) A De-aerator fitting is required at the base of each stack. The De-aerator fitting shall be installed in the vertical portion of the
stack. The distance between the De-aerator fitting and the building drain shall not exceed five feet (5’-0").
The building drain size shall be in accordance with Table C based on the total fixture unit load determined by Table A or A-1. The
transition to a larger building drain size shall be made in the vertical stack below the Deaerator fitting, except as noted in
paragraph "I".
(B) The De-aerator fitting uses a Pressure Relief Line (PRL). The Pressure Relief Line (PRL) connects to the Single Stack system
building drain a MINIMUM distance of ten pipe diameters (based on stack size) downstream from the centerline of the stack. The
PRL connects to the Single Stack building drain above the centerline of the drain. The PRL may be rolled to the side providing the
bottom of the PRL is above the centerline of the Single Stack system building drain.
(C) The installed slope for the Single Stack system building drain and PRL is recommended to be one-quarter inch per foot (2%).
Installed slopes of one-eighth inch per foot (1%) are permitted however pipe capacity is reduced by a factor of 0.8 as shown in
Table C. Installed slopes less than one-eighth inch per foot (1%) are strictly prohibited.
(D) Soil and waste branches may connect to the building drain BETWEEN the centerline of the stack and the termination point of
the Pressure Relief Line (PRL). All connections shall be made a MINIMUM distance of ten pipe diameters (based on stack size)
downstream from the centerline of the stack. Soil and waste branches shall not connect where the building drain makes a
horizontal change of direction.
(E) Waste branches may connect to the horizontal portion of the Pressure Relief Line (PRL), except on battery type installations.
Waste branches shall be at least one pipe size smaller than the PRL. Waste branch connections shall not be made into any
vertical portion of the PRL. Clothes washers shall not connect to the PRL.
(F) Soil and waste branches may connect downstream of the PRL termination point providing conventional plumbing rules are
applied. The vent header from these fixtures may connect to the vertical portion of a stack below an Aerator fitting through a
sanitary tee installed with the flow radius down. The vent load of these fixtures shall be added to the fixture unit load on the Single
Stack system.
(G) Soil and waste branches may connect to the vertical stack below the De-aerator fitting. These connections shall be made
through a wye-type fitting or through an Aerator fitting. Entry to the building drain from the stack shall be made using a short
sweep, long sweep, two one-eighth bends, or a combination wye & one-eighth bend fitting.
(H) Fixtures considered too remote from the Single Stack system may be plumbed by conventional methods. This waste and vent
area shall be sized in accordance with local prevailing ordinances.
(I) Office building battery type installations and Single Stack systems serving clothes washers shall use a De-aerator fitting equal
in size to the building drain serving that stack. A four-inch (4") De-aerator fitting will be required on three-inch (3") Single Stack
system.