DEHUMIDIFICATION: Natatorium Application & Product Guide

Design, Construct, and Operate toControl Indoor Humidity

Page 2: Design, Construct, and Operate to Control Indoor  · PDF fileDEHUMIDIFICATION: Natatorium Application & Product Guide Design, Construct, and Operate to Control Indoor Humidity
Page 3: Design, Construct, and Operate to Control Indoor  · PDF fileDEHUMIDIFICATION: Natatorium Application & Product Guide Design, Construct, and Operate to Control Indoor Humidity

Natatoriums have historically posed a difficultenvironment for the conventional HVAC system.The continuous moisture load swimming pools

generate challenges the mechanical system and createsmultiple opportunities for structural damage. The combination of humidity and chlorine not only attack the building, but also provide a breeding ground for moldand bacteria which can jeopardize occupant health andcomfort.

Munters offers a variety of systems in several differentsizes, configurations, and thermodynamic process optionsto meet the customer’s needs.

Munters is the largest manufacturer of dehumidifiers in the world. Since developing the first desiccant

dehumidifier in the late 1930’s, Munters has continued to innovate in the fields of dehumidification and

energy recovery. Our long history and extensive expertise in dehumidification makes us the premier

choice for your dehumidification needs.

Munters is the world leader in dehumidification

Munters, The Humidity Expert

Our extensive knowledge and experience makes us the premierchoice for your dehumidification needs.

1

Page 4: Design, Construct, and Operate to Control Indoor  · PDF fileDEHUMIDIFICATION: Natatorium Application & Product Guide Design, Construct, and Operate to Control Indoor Humidity

Prevent Condensation

High humidity and condensation on the buildingstructure can cause significant damage. A detailed dewpoint analysis of the building is required to eliminatecondensation both during initial design and through theend of construction. Thermal bridges in the walls andwindows should be analyzed and reviewed carefully toavoid building damage.

Protect the building and its occupants

Introduce Outside Air into the BuildingOutside air must be brought into the space to dilute

the chlorine that has evaporated from the pool and toprovide fresh air for the occupants.

In order to make room for this outside air, mechanicalexhaust is required. This exhaust should exceed the outdoor air quantity to maintain negative air pressure inthe pool area. Pay special attention that the airflow movesin the correct direction. This ensures that humidity andodors will not transfer into adjacent spaces, and alsokeeps high humidity out of the wall cavities to minimizethe potential for condensation.

Building DesignIt is important to start with the correct

envelope construction to avoid significant problemsduring the life of the building. A proper vapor barrier is needed to keep moisture from being trappedin the buildings walls and roof assembly. Additionallycare should be taken with regard to the window quantity, design and installation, as well as the wallconstruction detail and its insulation. Condensation onbuilding elements during low outdoor air temperaturesshould be carefully guarded against. Please refer to theASHRAE handbooks and The Humidity ControlDesign Guide published by ASHRAE for more information on this subject.

Vapor Retarder Layer

64˚ F (18˚ C)The surface of the interior insulation becomes cold enough to allow condensation to form. The vapor barrier must be installed on the interior side of theinstallation to prevent water from reaching thecold insulation, where condensation will form.

Outdoors0˚ F (-17.8˚ C)

Concrete Block

Face Brick

Rigid Polystyrene Insulation

Inside the Natatorium82˚ F (28˚ C) 60%rhDew Point = 67˚ F (19.4˚ C)

Standard 62.1 – 2004 calls for:0.48 CFM PER SQUARE FOOT OF POOL AND DECK AREA &7.5 CFM PER PERSON IN THE SPECTATOR AREA

FROM ASHRAE

An efficient HVAC system must function properlyduring all seasons and be capable of handling all possibleindoor and outdoor air conditions—even those abnormalswings. The system should provide precise humidity control because the evaporating water from the pool iscontinuously released into the air. and must be constantlyremoved. Space air condition and water temperature mustalso be balanced for occupant comfort based on the typeof pool. (See chart at right).

The recommended conditions for pools as indicatedin the ASHRAE Applications Handbook and HumidityControl Design Guide:

FROM ASHRAE

Air Temp ºF75 to 85

80 to 85

78 to 85

80 to 85

80 to 85

Type of PoolRecreational Therapeutic Competition DivingWhirlpool/Spa

RH%50 to 60

50 to 60

50 to 60

50 to 60

50 to 60

Water Temp ºF75 to 85

85 to 95

76 to 82

80 to 90

97 to 104

2

Page 5: Design, Construct, and Operate to Control Indoor  · PDF fileDEHUMIDIFICATION: Natatorium Application & Product Guide Design, Construct, and Operate to Control Indoor Humidity

Temperature ºF

78 80 82 84 86 88 90 92 94 96 98 100 102 104

Pool Evaporation Rate

Evaporation Rate Equation:

POOL LOAD = 0.1 X POOL AREA X �ΔVAPOR PRESSURE X USE FACTOR

Use Factor

0.5

0.65

0.65

0.8

0.8

1.0

1.0

Type of Pool

Residential

Fitness Club / Condo

Therapy / Elderly Swim

Hotel

Institutional / School

Public Pools

Spas and Whirlpools

Where:Load = the evaporation rate of the pool (lbs/hr)Pool Area = the surface area of the water (sq. ft.)ΔVapor Pressure = the difference in vapor pressure of the air and water (in of Hg)Use factor = the occupancy factor from ASHRAE.

Vapor Pressure (Inches of Mercury)

Water

Air

0.9670.4840.581

1.0330.5170.620

1.1030.5510.662

1.1760.5880.706

1.2540.6270.753

1.3360.6680.802

1.423------

1.515------

1.612------

1.714------

1.821------

1.935------

2.054------

2.180------

100%50%60%

Relative HumidityFluid Type

btu/hr

105

158

210

252

546

630

872

966

1092

Activity per hour

Seated at Rest

Seated Very Light Work

Seated, Light Work

Walking, Standing

Moderate Dancing

Walking Briskly w/Loads

Light Exercise

Medium Athletic Activity

Athletics

lbs/hr

0.10

0.15

0.20

0.24

0.52

0.60

0.83

0.92

1.04

Outside Air Humidity Load

OA Humidity Load Equation: use ASHRAE design dew point conditions:

OA LOAD (LBS/HR) = 0.000643 X OACFM X �ΔHUMIDITY RATIO

Where:OA Load = the humidity load of the outside air (lbs/hr)OACFM = Ventilation Air Quantity (cfm)ΔHUMIDITY RATIO = the difference in absolute humidity of the outside air and the space

FROM ASHRAE APPLICATIONS HANDBOOK

Calculate the Loads

Properly calculating the internal and external loads of the facility is a

critical step in designing a natatorium. The HVAC equipment is sized

based on load calculations and the type of facility being constructed.

An indoor swimming pool has a remarkable chance of experiencing

moisture problems, but with accurate load calculations of the pool

evaporation rate, peak outside air loads, and the internal load in the

space you can successfully design a healthy and enjoyable natatorium.

FROM ASHRAE APPLICATIONS HANDBOOK

Internal Humidity Load

People are an internal load to thespace and their activity should beconsidered in the calculation. Use the chart below to determinethe activity load per hour.

TOTAL HUMIDITY LOAD = OA HUMIDITY LOAD + INTERNAL HUMIDITY LOAD + POOL LOAD

3

Page 6: Design, Construct, and Operate to Control Indoor  · PDF fileDEHUMIDIFICATION: Natatorium Application & Product Guide Design, Construct, and Operate to Control Indoor Humidity

Weather is a critical component of the building load. When climate is hot and dry, it presents different challenges for a HVAC system than when it is hot and humid. Differing outdoor conditions require specific performances from dehumidification and air conditioning systems. The same type of system throughout the country will not efficiently meetthe needs of different area and different climate requirements.

Energy recovery and mechanical dehumidifierrequirements are significantly different basedon outdoor conditions.

In the west, the outdoor condition is gener-ally much lower than the space condition.Outdoor air can naturally be used for indoordehumidification, and if provided with an effi-cient energy recovery device, it can be done atsignificantly reduced operating costs.

In the east, outdoor air can be used parttime for dehumidification and the mechanicaldehumidification cycle is only needed for thehigher ambient humidity. With colder tempera-tures in the north, energy recovery for winteroperation is easily justified. Depending on thepriorities of the user, a significantly differentsystem may be appropriate to maximize energyefficiency.

CA

NV

ID

MT

WY

UT

AZ

TX

NM

COKS

OK

NE

SD

ND

MN

IA

MO

AR

LA

MSAL

FL

GA

IL

WI

IN

MI

OH

KY

TN

SC

VA

NC

PA

NY

WV

HI

MEWA

CAKY

VA

NC

V T

OR

MD

NJ

NH

R I

CT

MA

DE

DC

QC

NL

ONMBSK

ABBC QCABBC CANADA

NVUT

CCCOOOKKSS MO

IIILLL IIINN

WVCCAA

KKYYVVAA

NJ

DEUNITED STATES

DRY

Dew Point Temperature

Duct DesignThe air distribution system should

be designed in such a way as to minimize stagnation in the buildingenvelope. While keeping velocity overthe pool surface low, air movement isdesirable to control chloramines.

Supply air should be washed overwindows and other surfaces that mayexperience low temperatures in coldweather that might lead to condensation. Exhaust and return airinlets should be located high to capture hot and humid air. Whirlpoolsshould have an exhaust air connectiondirectly above.

Ductwork should be aluminum, painted galvanized, 300 series stainless steel or lightweight corrosion resistant fabric.Munters offers DryFlo Ducting. DryFlo ducting is cylindrical tubes constructed of a durable fabric that uniformly dis-perses air into the space. (See Munters Distribution System illustration above.)

Temperature & humidity controlled room

Return air vent mounted as

high as possiblein room

Weather-proofMunters dehumidifier

sits outside natatorium

Exhaust outsideair intake to flush

out chlorine-laden odors

Dry air keeps glass freeof condensation and

water damage

Dry ductwork resistant to mold and mildew growth

Dry pool environment helps preservepool structure from moisture damage

Dryer floors

Exhaustfan

COOLER & HUMID

HOT & HUMID

Choose pool technology best suited for that region

4

Page 7: Design, Construct, and Operate to Control Indoor  · PDF fileDEHUMIDIFICATION: Natatorium Application & Product Guide Design, Construct, and Operate to Control Indoor Humidity

Wringer Pool

Southeast, Northeast, Southwest, Northwest

Reduced compressor runtime for enhanced

reliability, Low operating cost, Increased ventilation

Small, Medium, Large

Ventilation Pool

Southwest, Northwest

Eliminated compressor runtime for enhanced

reliability, Low operating cost,Increased ventilation

Small, Medium, Large

Pool Desiccant

Southeast, Northeast

Reduced compressor runtime for enhanced reliability

Medium, Large

DryCool Pool

Southeast, Northeast

Low first cost

Small, Medium

Climate

Priority

SystemSize

Where is the building locatedand what is the local climate?

Hot and Humid: Southeast U.S.Humid, but with cold winter climate: Northeast U.S.Hot and Dry: Southwest U.S.Dry, but with cold winter climate:Northwest U.S.

What are the priorities of thesystem required?

1. Reliability2. First Cost3. Operating Cost4. Increased Ventilation during most of

the year

What is the system size requirement?

Small - < 150 lbs/hrMedium - > 150 lbs/hr, < 300 lbs/hrLarge - > 300 lbs/hr

System Types and Features

Selecting the Right System

1 2 3

The system features listed do not outline the extent of the product line availability, rather they outline the features of the systems in competitive environments.See the specificsystem description on the following pages to see the available capacities of each product.

Munters Offers Different SolutionsFour different types of systems are available to meet both the difficult requirements of the natatorium and the

diverse climates these buildings may experience. These different solutions can be optimized to provide the best solutionfrom a first cost, life cycle cost, and sustainability perspective. They allow for the optimization of energy savings and performance.

Heat Pump OptionWringer Pool and Ventilation Pool systems are availablewith the heat pump option to heat the pool water. Thisoptions adds an evaporator coil to the exhaust airstream as it leaves the unit to recover the last amount ofheat from the building exhaust. This allows the heatpump system to efficiently heat the pool water all yearlong. The dehumidification cycle is not required tooperate and the system is sized based on the energyavailable in the exhaust air stream. The heat pump isalso configurable to provide air heating in the winter whenever sufficient heat is available from the exhaustair stream, and providing very efficient heating of theoutside air after it has been preheated by the sensibleheat exchanger.

MIX OF O/A, PREHEATED BY AIR-TO-AIR HX, AND

RECIRCULATION AIR

EXHAUST AIR(AFTER HX)

POOL WATER OUT 90ºF (32.2ºC)

POOL WATER IN 80ºF (26.7ºC)

HEATED S/A TO SPACE

SCROLLCOMPRESSOR

POOL WATER HEATER(CONDENSER 2)

SUPPLY AIR HEATER(CONDENSER 1)

5

Page 8: Design, Construct, and Operate to Control Indoor  · PDF fileDEHUMIDIFICATION: Natatorium Application & Product Guide Design, Construct, and Operate to Control Indoor Humidity

Product Features

• 2” double wall casing

• Sensible counter-flow, cross-flow, and heat pipe heat

exchangers with up to 88% efficiency

• Simple dehumidification and energy recovery modes for easy

maintenance and control

• Outside air dehumidification mode for reduced compressor

run hours

• Increased ventilation throughout many operating hours

• Built in building exhaust fan to maintain negative pressure

• Packaged DX, split system DX, water cooled DX & chilled

water options

• DDC microprocessor controls option

• Option for 100% outside air during purge mode

• Stainless steel drain pans

• Heat pump air and water heating available as option

• ETL listed

Wringer Pool Products DescriptionThe Wringer Pool dehumidifier utilizes energy recovery toprovide heat recovery in the winter and pre-cool/reheatduring the summer. The combination of mechanical dehu-midification and outside air dehumidification provides anextremely efficient and reliable dehumidification system.The energy derived from the cooling coils is used to reheatthe supply air through a refrigerant reheat coil. During highoutdoor humidity the cooling coil acts as the dehumidifier,using the heat exchanger to minimize energy. When thehumidity outside is lower than the desired space condition,the unit brings in more outside air to meet the dehumidifi-cation load without the need for the cooling coil or com-pressor run hours, while the heat exchanger recovers theheat from the exhaust air stream to minimize the heatingrequirement. The unit modulates the outside air to theminimum position during very cold conditions to minimizeenergy requirements. In addition, a heat pump option canbe added to the exhaust air stream to provide pool waterand/or supply air heating to increase overall unit efficiency.

OUTSIDE AIR

EXHAUST AIR

RETURN AIR

SUPPLY AIR

COOLING COIL

SENSIBLEHEAT

EXCHANGER

A

D CB E

Wringer Airflow & Schematic

Wringer Capacity Chart

WR 04WR 06WR 08WR 12WR 18WR 24WR 30WR 40WR 50

Unit

4,0006,0008,00012,00018,00024,00030,00040,00050,000

4,7007,4009,000

12,70022,00027,00032,00039,00044,000

1,000 - 1,5001,500 - 2,2502,000 - 3,0003,000 - 4,5004,500 - 6,7506,000 - 9,0007,500 - 11,00010,000 - 15,00012,000 - 18,000

Pool Size (sq. ft.)

CFM Weight (lbs.)Dimensions (in.)

L x W x H

84 x 66 x 19284 x 66 x 19284 x 66 x 192

100 x 74 x 216132 x 78 x 234144 x 98 x 252

144 x 114 x 276144 x 146 x 312144 x 156 x 396

State Summer Winter

Point

ABCDE

Return

Outside Air

Post Heat Exchanger

Post Cooling Coil

Supply Air

CFM

10,0009,0009,0009,0009,000

ºF

8493897070

gr/hr

10465656565

CFM

10,0002,0002,0002,0009,000

ºF

84-135555

105

gr/hr

77244

61

6

Page 9: Design, Construct, and Operate to Control Indoor  · PDF fileDEHUMIDIFICATION: Natatorium Application & Product Guide Design, Construct, and Operate to Control Indoor Humidity

Product Features

• Foam injected 2” double wall casing

• Desiccant enhanced process for lower connected tonnage

and lower operating cost

• Packaged DX, split system DX, water cooled DX and chilled

water options

• Coated cooling coils and other critical components

• DDC microprocessor controls

• Option for 100% outside air during purge mode

• Stainless steel drain pans

• ETL listed

Point

ABCDE

State Summer Winter

Return

Post Cooling Coil

Post Desiccant Wheel

Outside Air

Supply Air

CFM

6,0006,0006,0004,000

10,000

ºF

8251699579

gr/hr

1005634

12068

CFM

6,0006,0006,0004,000

10,000

ºF

8282822090

gr/hr

1001001001064

DryCool Pool

OUTSIDE AIR

EXHAUST AIR

RETURN AIR

SUPPLY AIR

COOLING COIL

DESICCANTWHEEL

MOIST AIR TO ATMOSPHERE

AIR COOLEDCONDENSER

HEATED TO

115°F

AC

D

B E

DryCool Pool Capacity

HCU-N 1005HCUc-2410HCUc-3412HCUc-3415HCUc-4015HCUc-4020HCUc-6020HCUc-6030HCUc-8030HCUc-8040

Unit

1,0001,3502,2502,7002,7002,7003,6005,4005,4007,200

1,2002,4003,4003,4004,0004,0006,0006,0008,0008,000

2,2003,7504,0004,0004,5004,500

10,00010,00014,00014,000

250500833

1,0001,0001,3331,3332,0002,0002,667

1,2001,5002,5003,0003,0004,0004,0006,0006,0008,000

5101215152020303040

40 lbs/hr70 lbs/hr90 lbs/hr105 lbs/hr115 lbs/hr145 lbs/hr160 lbs/hr225 lbs/hr240 lbs/hr315 lbs/hr

58 x 43 x 61178 x 65 x 57178 x 65 x 57178 x 65 x 57193 x 65 x 72193 x 65 x 72226 x 86 x 70226 x 86 x 70249 x 96 x 86249 x 96 x 86

9003,5003,5003,5004,2504,2505,2505,2507,8507.850

Maximum CFMOA Return Total

MinimumExhaust

MaximumExhaust

Tons Dehumid lbs/hrDimensionsL x W x H

WeightPounds

Capacity based on 82F 60% RH space condition

DryCool Airflow & Schematic

Product DescriptionThe DryCool Pool dehumidifier provides energy effi-cient dehumidification in a small packaged product atlow cost. Condenser heat is recovered from thedirect expansion refrigeration system to provide thereactivation energy for the desiccant dehumidificationprocess. The cooling energy of the refrigeration sys-tem is used to cool and dehumidify the air prior toentering the desiccant wheel. The hybrid refrigerant-desiccant system provides an efficient dehumidifier byeliminating the overcooling required with a refrigera-tion only based dehumidifier. The system uses thereactivation fan as the exhaust air fan to maintainnegative pressure in the space while further enhanc-ing efficiency and minimizing the unit footprint andcost.

7

Page 10: Design, Construct, and Operate to Control Indoor  · PDF fileDEHUMIDIFICATION: Natatorium Application & Product Guide Design, Construct, and Operate to Control Indoor Humidity

Ventilation Pool Products DescriptionThe Ventilation Pool unit is an enhanced energy recovery system.

The core of the unit is an efficient sensible energy recovery heat

exchanger. The chart below shows that outdoor air can be used

to provide dehumidification for natatorium environments effective-

ly up to approximately 60ºF dew point. The outdoor air supply

can be modulated to provide the correct dehumidification capaci-

ty and to not over-dehumidify when possible. In western or simi-

lar climates, the 60ºF dew point condition is rarely exceeded.

This allows the system to maintain the desired space humidity

most of the time with no need for mechanical dehumidification.

On occasion when it is exceeded the resultant increase in space

humidity is small. Temperature and humidity in the space will

exceed the design condition for a short period of time, but the

trade off is a simplified unit design with no refrigeration system.

Cooling can be provided with indirect evaporative cooling,

enhancing the system performance and efficiency. Direct evapo-

rative humidification can be added to the supply air. This will

minimize the evaporation rate of the pool and the chemical

requirements for pool maintenance. Simple, low operating cost,

low maintenance, and improved air quality through increased

ventilation make the Ventilation Pool unit an attractive option for

natatoriums.

Product Features

• 2” double wall casing

• Optional indirect evaporative cooling to provide cooling dur-

ing high ambient temperatures

• Optional direct evaporative cooling to minimize pool evapora-

tion during low dew point conditions

• Sensible counter-flow, cross-flow, and heat pipe heat

exchangers with up to 88% efficiency

• Simple dehumidification and energy recovery modes for easy

maintenance and control

• Outside air dehumidification mode eliminating compressors

• Increased ventilation throughout many operating hours

• DDC microprocessor controls option

• Option for 100% outside air during purge mode

• Heat pump air and water heating available as option

• ETL listed

OUTSIDE AIR

EXHAUST AIR RETURN AIR

HEATING COILSENSIBLE

HEATEXCHANGER

B D E

A

C

Ventilation Airflow & Schematic

State Summer Winter

Point

ABCDE

Return

Outside Air

Post Heating Coil

Post Heat Exchanger

Supply Air

CFM

10,5002,0007,0007,000

10,000

ºF

8495616876

gr/hr

104118

808080

CFM

10,5002,0002,0002,000

10,000

ºF

8400

7198

gr/hr

77444

55

Outdoor Air Dehumidification

05101520253035404550556065

OutsideDew PointTemp. ºF

5,0005,0005,0005,0005,0005,0005,0005,0005,0005,0005,0005,0005,0005,000

3022972902822712582422232021771471116919

10,00010,00010,00010,00010,00010,00010,00010,00010,00010,00010,00010,00010,00010,000

60559558156454351748444740435429322213839

OACFM

lbs of H20

Removed20,00020,00020,00020,00020,00020,00020,00020,00020,00020,00020,00020,00020,00020,000

1,2101,1891,1621,1281,0851,03496889480870758744427678

Note: Based on space condition of 82ºF, 60% RH.

OACFM

lbs of H20

Removed

OACFM

lbs of H20

Removed

8

Page 11: Design, Construct, and Operate to Control Indoor  · PDF fileDEHUMIDIFICATION: Natatorium Application & Product Guide Design, Construct, and Operate to Control Indoor Humidity

Product Features

• Foam injected 2” double wall casing

• Desiccant dehumidification process for lower connected

tonnage and lower compressor run hours

• Low relative humidity during dehumidification process for

reduced corrosion

• Packaged DX, split system DX, water cooled DX and chilled

water options

• Coated cooling coils and other critical components

• DDC microprocessor controls option

• Option for 100% outside air during purge mode

• Stainless steel drain pans

• ETL listed

Pool Desiccant

OUTSIDE AIR

OUTSIDE AIR

RETURN AIR

COOLINGCOIL

POOLHEATING

COIL

MOIST AIR TO ATMOSPHERE

DESICCANTWHEEL

GASBURNERHEATED

TO250°F

AD

E

FCB

Pool Desiccant Capacity Chart

DDS 20DDS 30DDS 40

10,00030,00050,000

10,00030,00050,000

12,00030,00050,000

250500

1,000

10,00015,00025,000

100200300

250 lbs/hr350 lbs/hr500 lbs/hr

219 x 80 x 70219 x 96 x 101280 x 134 x 101

6,5008,500

10,500

Maximum CFMOA Return Total

MinimumExhaust

MaximumExhaust

Tons Dehumid lbs/hrDimensionsL x W x H

WeightPounds

DDS Airflow & Schematic

Unit

Point

ABCDEF

State Summer Winter

Return

Post Desiccant Wheel

Post Heating Coil

Post Cooling Coil

Outside Air

Supply Air

CFM

10,00010,00010,00010,000

5,00015,000

ºF

80119119

659575

gr/hr

100545454

12076

CFM

10,00010,00010,00010,000

5,00015,000

ºF

8282

1251252090

gr/hr

1001001001001070

Products DescriptionThe Pool Desiccant unit utilizes a silica gel desiccant dehu-

midification wheel with gas fired reactivation to provide

dehumidification without the need for compressorized

refrigeration. Cooling coil operation is only required to pro-

vide temperature reduction in the space during high ambi-

ent temperatures. The wheel turns at a slow 0.1 rpm mini-

mizing maintenance. The desiccant process heats and

dehumidifies the supply air reducing the heating required in

the heating mode. The effect of this process provides low

relative humidity inside the unit and therefore reduced cor-

rosion. Great flexibility and reliability are provided in a

packaged large capacity unit.

9

Page 12: Design, Construct, and Operate to Control Indoor  · PDF fileDEHUMIDIFICATION: Natatorium Application & Product Guide Design, Construct, and Operate to Control Indoor Humidity

Annual Energy Expense $16,761.40

10297928782777267625752474237322722171272-3

DryBulb

DryBulb

Annual Energy Expense $5,109.04

10297928782777267625752474237322722171272-3

LocationSupply CFMRequired Supply Air Humidity RatioSummer Outside AirReturn Air TemperatureReturn Air Relative Humidity

3119 MBH189 MBH198 #/Hr.50.2 ºF

Temp.MCWB*

Total Hours.*

atCondition

DPOutside

Air

7576747270676461575247433834302521161161-3

63.367.666.465.464.562.059.657.453.748.042.338.732.829.927.021.318.913.37.61.6-4.7-81.9

06581653244876817597006045815655727258695893712311641158993

5,0005,0005,0005,0005,0005,0005,00010,0017,5255,7294,7664,3803,9343,7563,6123,3923,3223,1943,0983,0262,9712,843

DehumidCoil Tons

27.6431.0328.9927.1125.3820.8116.540.000.000.000.000.000.000.000.000.000.000.000.000.000.000.00

DehumidCoil Cost

$0$22$197$524$964

$1,188$1,320

$0$0$0$0$0$0$0$0$0$0$0$0$0$0$0

Condenser Heat

AvailableBTUH

414,652465,418434,864406,969380,774312,183248,038

000000000000000

RequiredSupply

Air Temp.

73.274.375.476.578.379.882.082.683.283.784.384.985.586.186.687.287.888.489.089.590.190.7

No HeatSupply

Air Temp.

74.174.174.174.174.174.174.179.479.479.579.579.379.279.078.878.778.578.478.278.077.877.8

Cost to Heat Supply

Air$0$0$2$11$38$75$147$66$72$70$76$86$97$138$184$136$94$63$48$36$30$33

Condenser AirReheatCredit

$0$0$2$11$38$75$147$0$0$0$0$0$0$0$0$0$0$0$0$0$0$0

CondenserWaterHeat

Credit$0

$1.66$16.06

$45$89.70$114.66$64.29

$0$0$0$0$0$0$0$0$0$0$0$0$0$0$0

DollarsSpentTotal

$0$20.16

$181.01$478.63$874.24

$1,073.22$1,255.49

$66.00$72.06$69.60$76.04$85.61$96.78

$138.10$183.99$135.66$93.54$62.78$47.88$35.94$29.67$32.64

Operating Cost of Munters Ventilation Pool Product

Economic Evaluation and Life Cycle Cost

Munters has software tools to analyze the operating cost of each system. Unit selection andcost data are inputted with design parameters, local weather data, and energy costs. The output isannual energy cost, annual energy savings, and simple payback.

Chicago, IL.20,0000.01215,0008260

Cooling Equipment C.O.PSummer Building LoadWinter Building LoadMax Evaporation RateDX LAT

Change Over Dew PointHeat Recovery EffectivenessCooling Fuel CostCost of Heating FuelEfficiency of Fuel Conversion (Heating)Outside Air CFM at Change Over

58.365.0$0.100/kwh=$9.77/Million BTU of Cooling Input$1.00/1,000,000 BTU8012,000

LocationSupply CFMRequired Supply Air Humidity RatioMin Outside AirReturn Air Temperature

3180 MBH300 MBH198 #/Hr.

Temp.MCWB*

Total Hours.*

atCondition

DPOutside

Air

7576747270676461575247433834302521161161-3

63.367.666.465.464.562.059.657.453.748.042.338.732.829.927.021.318.913.37.61.6-4.7-81.9

06581653244876817597006045815655727258695893712311641158993

5,0005,0005,0005,0005,0005,0005,0005,0005,0005,0005,0005,0005,0005,0005,0005,0005,0005,0005,0005,0005,0005,000

DehumidCoil

LAT/Tons

62.1/40.560.5/46.960.9/45

61.3/43.561.7/42.162.5/38.763.3/35.763.9/33.264.8/29.266/24.1

82/082/082/082/082/082/082/082/082/082/082/082/0

DehumidCoil Cost

$0$33$307$842

$1,602$2,211$2,853$2,955$2,397$1,711

$0$0$0$0$0$0$0$0$0$0$0$0

Condenser Heat

AvailableBTUH

608,142703,896676,459652,889632,694580,941536,244498,342438,289362,567

000000000000

RequiredSupply

Air Temp.

73.774.875.876.977.979.080.081.182.183.284.285.386.387.488.589.590.691.692.793.794.895.8

No HeatSupply

Air Temp.

72.169.668.767.866.866.265.564.764.263.874.573.372.070.869.568.367.065.864.563.362.060.8

Cost to Heat Supply

Air$0$1$11$41$98$169$268$337$341$318$153$185$223$327$447$340$237$162$125$95$79$88

Condenser AirReheatCredit

$0$1$11$41$98$169$268$337$341$374$0$0$0$0$0$0$0$0$0$0$0$0

CondenserWaterHeat

Credit$0

$1.66$16.06$45.68$89.70$134.82$135.71$42.41

$0$0$0$0$0$0$0$0$0$0$0$0$0$0

DollarsSpentTotal

$0$31.34

$290.50$796.50

$1,511.98$2,075.71$2,665.17$2,819.62$2,354.74$1,754.98$153.47$184.55$222.57$327.40$446.72$339.58$237.08$162.05$125.29$95.04$79.11$88.48

Operating Cost of Conventional Refrigeration-Based Pool Dehumidifier as ComparisonChicago, IL.20,0000.01215,00082

Cooling Equipment C.O.PSummer Building LoadWinter Building LoadMax Evaporation Rate

Heat Recovery EffectivenessCooling Fuel CostCost of Heating FuelEfficiency of Fuel Conversion (Heating)Return Air Relative Humidity

0$0.100/kwh=$9.77/Million BTU of Cooling Input$1.00/1,000,000 BTU8060

*Weather data used for Chicago, IL. Heat exchanger effectiveness is based on dry sensible heat transfer. Condensing within the heat exchanger will increase performance.

$5,000 vs. $16,000

10

Page 13: Design, Construct, and Operate to Control Indoor  · PDF fileDEHUMIDIFICATION: Natatorium Application & Product Guide Design, Construct, and Operate to Control Indoor Humidity

$0$29.46

$324.01$998.35

$1,598.11$2,130.02$2,805.21

$77.48$75.73$79.01$87.98

$100.24$123.42$133.20$129.15$81.80$51.82$26.77$14.49$3.97$0.32

$0

DryBulb

LocationSupply CFMRequired Supply Air Humidity RatioSummer Outside AirReturn Air TemperatureReturn Air Relative Humidity

360 MBH200 MBH198 #/Hr.58.3 ºF

Annual Energy Expense $8,870.54

10297928782777267625752474237322722171272-3

DryBulb

Temp.MCWB*

Total Hours.*

atCondition

DPOutside

Air

7776747270686661565147423733292419151061-4

67.167.666.465.464.563.763.057.451.846.040.036.330.327.324.117.811.08.92.01.6-4.7-81.9

0672243428631925858755688671665734708621362212101511310

5,0005,0005,0005,0005,0005,0005,00010,0016,7795,3254,5084,1753,7813,6253,4923,2953,1523,1173,0303,0262,9712,843

DehumidCoil Tons

43.6641.8938.4035.0531.8628.8025.880.000.000.000.000.000.000.000.000.000.000.000.000.000.000.00

DehumidCoil Cost

$0$29$324$998

$1,598$2,130$2,805

$0$0$0$0$0$0$0$0$0$0$0$0$0$0$0

Condenser Heat

AvailableBTUH

327,485327,485327,485327,485327,485327,485327,485

000000000000000

RequiredSupply

Air Temp.

79.279.280.480.981.582.182.783.283.884.484.985.586.186.787.287.888.488.989.590.190.691.2

No HeatSupply

Air Temp. F°

76.476.476.476.476.476.476.479.980.180.180.180.079.979.779.679.579.479.279.078.878.778.6

Cost to Heat Supply

Air$0$1$8$30$59$97$157$77$76$79$88$100$123$133$129$82$52$27$14$4$0$0

Condenser AirReheatCredit

CondenserWaterHeat

Credit$0$0$0$0$0$0$0$0$0$0$0$0$0$0$0$0$0$0$0$0$0$0

Operating Cost of Wringer Pool ProductWashington DC20,0000.01215,0008260

Cooling Equipment C.O.PSummer Building LoadWinter Building LoadMax Evaporation RateDX LAT

Change Over Dew PointHeat Recovery EffectivenessCooling Fuel CostCost of Heating FuelEfficiency of Fuel Conversion (Heating)Outside Air CFM at Change Over

58.365.0$0.100/kwh=$9.77/Million BTU of Cooling Output$1.00/1,000,000 BTU8012,000

LocationSupply CFMRequired Supply Air Humidity RatioMin Outside AirReturn Air Temperature

3180 MBH300 MBH198 #/Hr.

Annual Energy Expense $19,770.76

10297928782777267625752474237322722171272-3

7576747270686661565146423733292419151061-4

63.367.666.465.464.563.763.057.451.846.040.036.330.327.324.117.811.08.92.01.6-4.7-81.9

0672243428631925858755688671665734708621362212101511310

5,0005,0005,0005,0005,0005,0005,0005,0005,0005,0005,0005,0005,0005,0005,0005,0005,0005,0005,0005,0005,0005,000

62.1/40.560.5/46.960.9/45

61.3/43.561.7/42.1

62/4162.2/40.163.9/33.265.3/27.466.4/22.5

82/082/082/082/082/082/082/082/082/082/082/082/0

$0$33$381

$1,240$2,116$3,034$4,347$3,341$2,426$1,822

$0$0$0$0$0$0$0$0$0$0$0$0

608,142703,896676,459652,889632,694615,350601,517498,342411,333338,867

000000000000

73.774.875.876.977.979.080.081.182.183.284.285.386.387.488.589.590.691.692.793.794.895.8

72.169.667.866.865.864.764.764.564.163.874.573.372.070.869.568.367.065.864.563.362.060.8

$0$1$14$60$129$226$385$381$361$357$177$217$289$320$319$209$135$71$39$11$1$0

$0$1$14$60$129$226$385$381$361$291$0$0$0$0$0$0$0$0$0$0$0$0

$0$1.66$19.93$67.25$118.49$174.69$256.08$153.41$26.75

$0$0$0$0$0$0$0$0$0$0$0$0$0

$0$31.34

$360.62$1,172.33$1,997.31$2,859.12$4,091.29$3,187.39$2,399.73$1,887.00$177.25$217.21$285.60$319.72$319.23$208.71$135.47$70.85$38.96$10.74$0.89

$0

Operating Cost of Conventional Refrigeration-Based Pool Dehumidifier as ComparisonWashington DC20,0000.01215,00082

Cooling Equipment C.O.PSummer Building LoadWinter Building LoadMax Evaporation Rate

Heat Recovery EffectivenessCooling Fuel CostCost of Heating FuelEfficiency of Fuel Conversion (Heating)Return Air Relative Humidity

0$0.100/kwh=$9.77/Million BTU of Cooling Input$1.00/1,000,000 BTU8060

*Weather data used for Washington, DC. Heat exchanger effectiveness is based on dry sensible heat transfer. Condensing within the heat exchanger will increase performance.

DollarsSpentTotal

Temp.MCWB*

Total Hours.*

atCondition

DPOutside

Air

DehumidCoil Tons

DehumidCoil Cost

Condenser Heat

AvailableBTUH

RequiredSupply

Air Temp.

No HeatSupply

Air Temp. F°

Cost to Heat Supply

Air

Condenser AirReheatCredit

CondenserWaterHeat

Credit

DollarsSpentTotal

This two-page comparison allows the designer and end user to make intelligent decisionsregarding system configuration and payback criteria. Together, Munters can assist in selecting thecorrect systems and options to meet the customers needs and desires.$8,000 vs. $19,000

$0$1$8$30$59$97$157$0$0$0$0$0$0$0$0$0$0$0$0$0$0$0

11

Page 14: Design, Construct, and Operate to Control Indoor  · PDF fileDEHUMIDIFICATION: Natatorium Application & Product Guide Design, Construct, and Operate to Control Indoor Humidity

Munters Flexibility

Natatoriums vary in size, shape,

and location. Some are low, small

rooms, others are atriums of

hotels with vast deck areas and

high ceilings. Some are totally

interior with no transmission load,

while others are completely

enclosed in glass with large

transmission loads. Munters

provides a standard or

customized product for precise

application for any amount and

proportion of sensible and latent

capacity to meet the load.

Munters provides systems with

increased outside air throughout

the year to improve indoor air

quality, while reducing the air to

minimum required airflows during

extreme temperatures to

minimize operating cost.