Design and Analysis of Output Filter for 3-Phase UPS Inverter

Embed Size (px)

Citation preview

  • 8/10/2019 Design and Analysis of Output Filter for 3-Phase UPS Inverter

    1/6

    Design and Analysis of Output Filter for 3 phase

    UPS

    Inverter

    Byoungwoo Ryu*, Jaesik

    Kim**,

    Jaeho Choi , and Changho Choi

    Chungbuk National University*

    48 Gaesindong, Cheongju, Chungbuk

    Phone: +82-43-261-2425, Fax: +82-43-276-7217

    E-Mail: choi@,power.chunPbuk.ac.kr

    POSCON Ltd., Seoul, S. KORE A**

    361-763

    S.

    KOREA

    Abstract

    This paper proposes a design method of the

    L-C

    output filter for three-phase

    UPS

    inverter: The

    harmonic components

    of

    the output voltages are

    dependent

    on

    the

    L-C

    value and the system time

    constant defined by the switching frequency, the

    speed o f control processo< the controller gain, and

    etc., but their characteristics are complicate and

    entangled each othel: In this paper: the relation

    between the

    L-C

    value and the system time constant

    are described with the closed form and the filter

    values can be calculated to meet the limit of voltage

    THD considering the system time constant. The

    schematic design procedure is given by a single f l ow

    chart and the proposed filter design algorithm is

    verified through the simulation an d experiments.

    Key words: output filter design, UPS, zero-output

    impedance

    1 Introduction

    There are two kinds of harmonic sources that make

    the UPS output voltage waveform be distorted: One

    is caused by the PWM switching of inverter and the

    other is caused by the nonlinear characteristics of the

    load. If any linear loads are connected to the inverter

    output side, then the output voltage harmonics due to

    the PWM switching can be eliminated by inserting

    the L-C filter between the inverter and the loads, and

    it

    is well known how to design the optimal values of

    the filter components [ l , 21. But the configuration of

    the power circuit with L-C filter cannot meet the zero

    output impedance at all. Therefore, the capacitor

    voltage is usually collapsed in case of the sudden

    load change or under the nonlinear load.

    By using the fast feedback controller for the output

    capacitor voltage, the harmonic distortion due to the

    nonlinear load characteristics, such as the capacitor

    input type rectifier load or transient load change, can

    be complemented [3]. But the performance of the

    feedback controller is dependent on the system time

    constant defined by the switching frequency, the

    speed of control processor, and the controller gain.

    And the harmonics suppression characteristics of the

    L-C filter and the feedback controller are entangled

    each other and complicate to analyze. Therefore, it is

    difficult to design the L-C filter considering the

    system time constant with the conventional methods.

    In this paper, the harmonics characteristics due to

    the L-C filter value and the system time constant are

    described with the closed form and L-C filter values

    can be calculated to meet the given specification of

    voltage THD, considering the system time constant.

    It means that the harmonic components due to the

    PWM switching of inverter and the nonlinear load

    characteristics are decoupled separately, and the L-C

    filter value and the performance of the feedback

    controller are determined to meet each allotted ratio

    of THD, for the harmonics suppression [4, 51.

    The design procedure of the L-C filter for three-

    phase UPS inverter is described. The transfer

    function of the filter output voltage to the load

    current is given as the closed form and it is possible

    to get the L-C values by solving this closed form.

    The capacitor value can be calculated with the given

    system time constant defined by the performance of

    the system controller. This procedure is more

    practical to design the power circuit and control

    circuit of inverter for UPS than the conventional one.

    And also, the effect of the load current to the voltage

    distortion can be calculated from the closed form, so

    it is possible to analyzed the system how much the

    voltage waveform is distorted under the nonlinear

    load.

    Finally, the schematic design procedure is given by

    a single flow chart and the proposed filter design

    algorithm is verified through the simulation.

    2

    Three phase PWM VSI system

    The three-phase voltage and curren t equations of

    0-7803-7156-9/02/ 10.000 2002 IEEE 941

    PCC-Osaka 2002

  • 8/10/2019 Design and Analysis of Output Filter for 3-Phase UPS Inverter

    2/6

    P WM INVERTER

    LC

    FILTER LOAD

    I

    I

    Fig.

    1

    Configuration of three-phase PWM-VSI power

    circuit.

    I

    I

    Fig.

    2

    Single-phase equivalent block diagram.

    the input and output sides of the filters are transferred

    to , he dq-values under the stationary reference frame

    as (1) and ( 2 ) .

    A

    1

    vc i

    o

    c / s

    The three-phase system can be described by the

    two single-phase systems of 'd' and 'q' as shown in

    Fig. 2 without the coupling terms. The dq single-

    phase equivalent blocks are shown as the M I S 0

    system with two inputs of the inverter output voltage

    and the load current in Fig. 2 . We will deal with the

    equivalent system of 'd' axis only in the equations

    below and it can be applied to

    q

    axis equally.

    From Fig. 2 , the transfer function of the capacitor

    output voltage to the inverter output voltage and the

    load current can be described in (3) neglecting the

    resistance of inductor [ 5 ]

    In conventional method of the filter design, the

    second term is treated as the disturbance and only the

    first term is considered to determine the L-C values.

    Once the product of L,Cj is calculated from the

    expecting cut-off frequency of the L-C filter, the

    exact values of Lf nd Cf are determined at values that

    minimize the cost function defined by the summation

    of the reactive powers. This design procedure can be

    applied to a linear load well. But under the nonlinear

    load or transient load change, we cannot neglect the

    harmonics components due to the second term.

    If

    the inductor value is minimized at almost zero in

    (3),

    the capacitor voltage can be independent on the

    load current characteristics and it means that the UPS

    system works as an ideal voltage source. To minimize

    the inductor value, the capacitor value should be

    maximized. But as the increase of the capacitor value,

    the power rating of an inverter will be increased due

    to the increase of the reactive power.

    So

    it is

    permitted to increase the inductor value for the

    decrease of the capacitor value as far as the harmonic

    components of the capacitor voltage is controlled

    with the help of fast feedback voltage controller. It is

    clear from the above that the filter design value

    should be compromised as the performance of the

    system controller. But they are coupled each other

    and the filter values are adjusted as the performance

    of the controller by the try-and-error method in the

    conventional methods.

    3 Proposed filter design method

    3.1

    Transfer function of system controller

    Figure 3 shows the system block diagram with

    controller. The control system is designed based on

    double regulation loops: the main feature is the inner

    control loop of the current flowing through the filter

    capacitor can be limited within a given range and a

    second feedback has been performed using an outer

    voltage loop which makes it possible to improve the

    dynamics of the entire control system. The transfer

    function is driven as

    (4).

    I 1

    Fig. 3 System block diagram with controller

    In (4), let's consider the input-output transfer

    characteristics responding to the voltage command

    942

  • 8/10/2019 Design and Analysis of Output Filter for 3-Phase UPS Inverter

    3/6

    and the load current separately. For the analysis of

    the effect due to the capacitor com mand voltage, the

    effect due to the load current can be neglected by

    putting zero, I,,=O. Then th e controller gains, Kp, Ki,

    and

    K ,

    can be designed to m eet-the ideal controller.

    For this, the gain of the transfer function satisfies unit

    to make all the values of the nominator and the

    denominator are same within the passing bandwidth.

    From the above, (4) is simplified as (5).

    If the inverter output L-C filter is designed well to

    eliminate the harmonics included in the inverter

    output voltage, then the command voltage of

    5),

    Vcd*

    is substituted by the fundamental component of the

    inverter output voltage, Vadl s in (6).

    For the analysis of the effect due to the change of

    load current only, the first term o f the right side of (6)

    can be neglected and the transfer characteristics of

    the capacitor voltage to the load current is given as

    7).

    7 )

    c d ( j n o o ) L P ~ W , ~

    IOd ( i n ) K , K ,

    3.2

    Design of con troller gain

    For the design of controller gain, CDM(Coefficient

    Diagram Method) controller with observer canonical

    form is used [6]. The characteristic equation of (4) is

    defined in

    CDM

    controller by (8) to meet the

    robustness.

    a

    r 2

    3 5 s 3 0 s

    ao no

    Y2YI

    YI

    With the comparison of the coefficients of two

    equations, the transfer function of the capacitor

    voltage to the load current given by (7) is described

    as

    (9).

    ( 9 )

    If the specification of the capacitor voltage

    harmonics caused by the nonlinear load current is

    given arbitrary, then the relation between the system

    time constant and the capacitor value

    C

    is given

    as the closed form of (9). In this equation, the

    stability factors of are used here as y , =2.5 and

    y 2

    2

    which satisfy the Manabes recommendation

    [5,61.

    And also, from the same methods of comparison,

    all the values of controller gains,

    Kp,

    Ki,nd

    K ,

    are

    given as like the following equations.

    4 Filter design procedure

    Before proceeding of the filter design, the UPS

    specification and the system parameters are given as

    followings:

    1) Total harmonic distortion factor of voltage,

    THD,

    is below 5% in case of both

    0.8

    linear

    lagging load and nonlinear rectifier load with the

    crest factor,

    CF=1.

    2 ) Modulation index,

    my

    is given as

    0.7

    considering

    the variation range of DC link voltage and load.

    The flowchart of filter design procedure is shown

    in Fig.

    4.

    In the design process, if the calculated total

    harmonic distortion factor of the output voltage THD,

    doesnt meet the specification, then it repeats the

    routine after decreasing the rate of voltage harmonics

    due to the dominant load current harmon ics [4,5].

    4.1

    Define the harmonics

    of SPWM VSI

    voltage

    and

    load

    current

    The voltage harmonics of

    SPWM-VSI

    is defined

    ideally as (13) and the fundamental component and

    dominant harmonics of inverter output voltage

    normalized by DC input voltage

    is

    given as Table

    I.

    Under the assumption of ideal voltage waveform,

    the nonlinear load current harmonics of capacitor

    input type rectifier with the crest factor, CF=3 is

    analyzed using the computer simulation. Table I

    shows the Fourier coefficients of load current

    normalized by the fundamental component.

    43

  • 8/10/2019 Design and Analysis of Output Filter for 3-Phase UPS Inverter

    4/6

    Table I. Normalized inverter voltage harmonics,

    v a d ~ v d ~s the change of mo dulation index, mp

    mf

    Order

    1

    F S W

    f7 2

    1 0.9 0.8 0.7 0.6 0.5

    1.00 0.90 0.80

    0.70

    0.60

    0.50

    0.60 0.71 0.82 0.92 1.01 1.08

    0.32 0.27 0.22 0.17 0.13

    0.09

    n

    Mag.

    4.2 Determine the impedance ratio of inductor

    and capacitor

    The impedance ratio

    of

    inductor and capacitor is

    determined to satisfy the condition that the ratio of

    output voltage to input voltage at the specific

    harmonic order shown

    in (14)

    can be smaller than

    3[ ]

    of the fundamental component of the output

    voltage as shown in (15). The specific harmonic

    order will be given as the same value of switching

    frequency.

    1 3

    5

    7 9 11 13

    1.00 0.73

    0.35

    0.07 0.04

    0.02 0.01

    (14)

    4.3 Determine the capacitance value based on the

    cost function

    The upper limit of the capacitance is determined

    at the value that minimizes the cost function defined

    by the total kVA

    of

    the filter L-C components as

    shown in (16).

    In (16),

    W

    is the w eighting coefficient determined

    due to the relative cost of inductor to the capacitor.

    4.4 Determine the system time constant and

    capacitance value

    The system time constant zi s selected 3 times

    longer than the switching time considering the

    system stability and the dynamics empirically. Then

    the capacitance value is calculated using the given

    values of system time constant and the rate of

    permitting voltage harmonics due to the load current

    from (8). The permission level of the harmonics due

    to the nonlinear load current is initially selected 1 A]

    considering the remaining harmonics after

    eliminating with

    L-C

    filter. If the THD, canno t meet

    the specification finally, then the calculation of the

    capacitance value should be repeated after decreasing

    this level.

    0.01 y2y,2 1

    xc

    ~

    n 2 w i I o n

    5

    4.5

    Determine the gains of controller

    Using

    1

    0) to (1 2), all values of controller gains

    K,,,

    Ki,

    nd K, are determined with the given value of

    the stability factor and the determined values of the

    system time constant and capacitance.

    4.6

    Calculation of the output voltage harmonics

    The total harmonic distortion factor of the output

    voltage THD,is calculated from (4) as described in

    (1 8). The determined values of controller gains and

    the L-C parameters are used for this calculation.

    After the calculation of THD,, if it does not meet

    the specification, then the above process should be

    repeated from the top after modifying the condition

    as followings: 1 ) In case o f linear load, repeat the

    calculation process after decreasing the impedance

    ratio

    of

    inductance and conductance from

    3[ ].

    2 ) In

    case of nonlinear load, repeat it after decreasing the

    harmonics ratio caused by the load current from

    1

    ?I.

    44

  • 8/10/2019 Design and Analysis of Output Filter for 3-Phase UPS Inverter

    5/6

    Harmonics analysis o f

    PWM voltage and no nlinear load current

    Calculating frequency transfer function of

    filter input to filter output vo ltage

    1

    Determine the impedance ratio of

    filter inductor and capacitor

    ,

    output

    Power

    output

    Voltage

    Considered

    Controller

    Making closed form of filter capacitance and system equivalent time

    constant using transfer function with contvoller

    using closed form for load current harmonics

    of the amplitude of dominant

    30[kVA] Switching 9.54[kHz]

    Frequency

    22O[V] Controller 2OO[us]

    time constant

    f

    4o[uH]

    Considered L /

    165[uH]

    Cost function

    c/ =100[uF]

    c 25[uF]

    R/

    0 05f 0.05

    calculated by cost function

    Retune to the system

    1

    the impedance ratio of

    I

    equivalent time constant

    Selecting controller gains

    satisfying the system response

    4

    Analyzing output voltage harmonics under the linear and nonlinear load

    using transfer function considering the system performance

    of

    controller

    Calculating DC link voltage

    I

    Fig. 4 Flowchart o f filter design procedure

    5 Simulation results

    Table I shows the system parameters and the

    design values of

    L-C

    filter and the controller gains

    using the filter design flowchart as show n in Fig.

    4.

    In

    case of the linear R-L load, the THD, of

    capacitor output voltage is

    3.2[ ]

    when the

    L-C

    filter

    is

    designed by the conventional method based

    on

    the

    cost function and 3.7[ ] when it is designed by the

    proposed method, respectively. From the results, it is

    verified that both methods are us ef d under the linear

    load.

    From Fig. 5 to Fig.

    8,

    the output voltage and

    current waveforms and the harmonic spectra of the

    output voltage waveform under the capacitor input

    type three-phase rectifier with

    CF=

    re shown

    Table 111. System parameters for simulation

    945

  • 8/10/2019 Design and Analysis of Output Filter for 3-Phase UPS Inverter

    6/6

    300

    300

    I I

    0.00

    0 01 0 02

    0 03

    T i m sec]

    -300

    0.00 0 01 0.02 0.03

    Tims [sec]

    Fig.

    5

    Output voltage and current waveforms with L-

    C filter designed by the conventional method.

    Fig. 7 Output voltage and current waveforms with L-

    C filter designed by the proposed method.

    .

    2 4 6 8 1 12 14 16

    Order

    ..

    _ _ _ .

    h

    2

    4 6

    8 1 12 14

    16

    Order

    Fig.

    6

    Harmonic spectrum of output voltage in

    conventional method. proposed method.

    Fig.

    8

    Harmonic spectrum of output voltage in

    When the filter is designed by the conventional

    method, the voltage waveform is distorted a little and

    the its

    THD,

    is 8.5[ ] with the given system time

    constant. Therefore, to meet the specification of

    THD,, the inductor value should be reduced and the

    capacitor value should be larger. And the inverter

    power rating will be increased due to the increase of

    the reactive power.

    On the other hand, if the filter is designed by the

    proposed method, then the output voltage waveform

    is almost sinusoidal and the THD, comes within the

    specification with 4.6[%].

    6.

    Conclusion

    References

    [ l ] S .

    Dewan and

    P.

    Ziogas, Optimum filter design for a

    single phase solid-state UPS system,

    IEEE Trans. Ind.

    Appl.,

    vol.

    IA-15, no. 6, pp. 664-669, 1979.

    [2] T. G. Habetler

    and

    D. M. Divan, Rectified Inverter

    reactive component minimization, in Conf. Rec. of

    IEEE PESC87, pp. 648-657, 1987.

    [3] A.

    Kusko, D. Galler, and

    N.

    Medora, Output

    impedance of PWM UPS inverter-feedback vs. filters,

    in Con Rec. of IEEE IAS90, p p .

    1044-1048,

    1990.

    [4]

    . Kim,

    J.

    Choi, and

    F.

    Blaabjerg, Design and analysis

    of

    output filter for UPS, in ConJ: Rec. of EPE2001,

    DS3.1, 2001.

    This paper proposes a filter design procedure for

    three-phase

    UPS

    inverter. By using the proposed

    closed form under the given system time Constant.

    Therefore, the L-C filter value can be determined

    using any try and error method.

    [51

    J Kim, Design of output filter and controller fo r UPS

    inverter, Ph. D thesis in Chungbuk National University,

    2001.

    [6] S. Manabe, C oefficient diagram m ethod, in ConJ Rec.

    o IFAC symposium

    on

    Automatic Control in Aerosp ace,

    method, the filter values can be calculated from the

    quickly through the systematic procedure without

    pp. 199-210, 1998.

    946