CUSTOMER:

ABU DHABI OIL REFINING COMPANY (TAKREER)

PROJECT NO.: 5640

PROJECT:

NORM HANDLING, TREATMENT & DISPOSAL PROJECT AT

BeAAT

Doc. No.:

5640-DS-6200-FU-004

DOCUMENT TITLE: DATA SHEET FOR

WET ALARM CHECK VALVE Sh 2 of 2 Rev. C

WET ALARM CHECK VALVE

1 ITEM No. * 2 QUANTITY 8 EA (7 EA of Ø4” &, 1 EA of Ø6”) 3 MANUFACTURER VIKING / TYCO / VICTAULIC / OR SIMILAR 4 MODEL * 5 CODE REQUIREMENT NFPA / DGS 6 APPROVAL UL LISTED & FM APPROVED

7 FLUID HANDLED FIRE WATER 8 PAINTING COLOR FIRE RED 9

PROCESS AND OPERATING CONDITIONS10 LOCATION OUTDOOR INDOOR 11 OPERATING TEMPERATURE (ºC) 58 12 MINIMUM WORKING PRESSURE (barg) 1.4(20 PSI) 12 MAXIMUM WORKING PRESSURE (barg) 20 (300 PSI)

13 ACTUATION TYPE OPERATED AUTOMATICALLY

TECHNICAL DATA 14 INLET BASE CONNECTION ANSI 150# RF FLANGED GROOVED

15 OUTLET CONNECTION ANSI 150# RF FLANGED GROOVED

16 VALVE BODY TYPE HORIZONTAL VERTICAL ANGLE 90º DIAPHRAM

17

MATERIALS

BODY DUCTILE IRON 18 CLAPPER DUCTILE IRON WITH EPDM CLAPER FACING 19 SEAT RING BRONZE 20 SPRING STAINLESS STEEL 21 ALL TRIM PIPING & FITTINGS C.S. GALVANIZED

22 ACCESSORIES

NAME PLATE MANUAL RELEASE STATION SOLENOID VALVE

HIGH PRESSURE SWITCH LOW PRESSURE SWITCH PRESSURE GAUGES ELECTRICAL ELEMENTS FOR CLASSIFIED AREA TYPE:__________________________________

HYDRAULIC ALARM GONG DRAIN VALVE DRAIN CUP

TEST & INSPECTION

23

WORKSHOP TEST DIMENSION CHECK

PERFORMANCE TEST UL and/or FM APPROVED

SPARE PARTS

24 YES NO BY VENDOR

NOTES

25

C

C

C

C

C