220kV Transmission System
220 kV Switchyard EquipmentUnit Required Offered
Performance and Design Criteria
Circuit Breakers for 220 kV System
Circuit breaker type - SF6
Manufacturer
Nominal voltage kV 220
Rated voltage kV 245
Rated frequency Hz 50
Rated phase to ground lightning impulsewithstand voltage (peak) kV 1050
Rated power frequency short withstand voltage kV 460
Rated short-circuit breaking current kA 50
Rated short-circuit making current (peak) kA 125
Rated nominal current A 2000
Rated short-circuit duration s 1
Minimum creepage distance mm 6125
First pole-to-clear factor - 1.3
Rated operating sequence(three-phase auto reclosing) -
0-0.3s – C0-1 min – C0 or C0-15s-
C0
Maximum breaking time ms 60
Maximum making time ms 100
Number of tripping coils 2
Number of closing coils 1
Protection class - IP 55
Auto reclosing single and three phase
Drive - 1 pole
Type of drive - Spring type
Power supply for drive V 110 DC
Power supply for auxiliary contacts V 110 DC
Power supply for heater V 220/380 AC
Auto reclosure, single and three phase yes/no yes
7518P01/FICHT-8825852-v12 Section VI-3
220kV Transmission System
220 kV Switchyard EquipmentUnit Required Offered
Performance and Design Criteria
Isolator with Two Grounding Switch, 220 kV
Manufacturer
Type outdoor
Type of operation center break
Earthing on both sides yes/no yes
Nominal voltage kV 220
Rated voltage kV 245
Rated nominal current A 2000
Rated short time current Ith (1s) kA 50
Rated short-circuit making current Idyn (peak) kA 125
Rated phase-to-ground lightning impulsewithstand voltage (peak) kV 1050
Rated power frequency short withstand voltage kV 460
Rated frequency Hz 50
Minimum creepage distance mm 6125
Protection class - IP 55
Drive - 1 or 3 pole
Type of drive - Electric motor
Power supply for drive V 110 DC
Power supply for auxiliary contacts V 110 DC
Power supply for heater V 220/380 AC
Manual operating facility yes/no yes
Isolator with one or two Grounding Switches, 220 kVManufacturer
Type outdoor
Type of operation center break
Earthing on one side yes/no yes
Nominal voltage kV 220
Rated voltage kV 245
Rated nominal current A 2000
7518P01/FICHT-8825852-v12 Section VI-4
220kV Transmission System
220 kV Switchyard EquipmentUnit Required Offered
Performance and Design Criteria
Rated short time current Ith (1s) kA 50
Rated short-circuit making current Idyn (peak) kA 125
Rated phase-to-ground lightning impulsewithstand voltage (peak) kV 1050
Rated power frequency shortwithstand voltage kV 460
Rated frequency Hz 50
Minimum creepage distance mm 6125
Protection class - IP 55
Drive - 1 or 3 pole
Type of drive - Electric motor
Power supply for drive V 110 DC
Power supply for auxiliary contacts V 110 DC
Power supply for heater V 220/380 AC
Manual operating facility yes/no yes
Current Transformers, 220 kV
Manufacturer
Type outdoor
Nominal voltage kV 220
Rated voltage kV 245
Rated secondary currents A 1
Class accuracy for metering - 0.2
Class accuracy for measurement - 0.5
Class accuracy for protection system - 5 P 20
7518P01/FICHT-8825852-v12 Section VI-5
220kV Transmission System
220 kV Switchyard EquipmentUnit Required Offered
Performance and Design Criteria
Number of cores -
metering 1
measuring 1
protection 4
Rated burden VA 50
Minimum creepage distance mm 6,125
Transformation ratio -
a)200 - 400 b)50c)100d)200e)1000-20001/1/1/1/1/1 A
Rating of protective cores VA 50
Rating of measuring cores VA 30
Rated phase to ground power frequencywithstand voltage (peak) kV 1050
Rated power frequencywithstand voltage (peak) kV 460
Rated short time current Ith (1s) kA 50
Voltage Transformers, 220 kV (capacitive)
Manufacturer
Type
Nominal voltage kV 220
Rated voltage kV 245
Transformation ratio -
220/0.1/0.1/0,1
kV3 / 3 / 3 /
3
Capacity of main winding VA 100
Capacity of secondary winding VA 100
Accuracy class for metering - 0.2
Accuracy class for measuring - 0.5
Accuracy class for protection - 3 P
Minimum creepage distance mm 6125
Rated phase-to-ground lightning impulsewithstand voltage (peak) kV 1050
7518P01/FICHT-8825852-v12 Section VI-6
220kV Transmission System
220 kV Switchyard EquipmentUnit Required Offered
Performance and Design Criteria
Rated power withstand voltage (peak) kV 460
Lightning Arresters, 220 kV System
Manufacturer
Type
Nominal voltage kV 220
Rated voltage kV 198
Rated continuous voltage kV 20
Rated discharge current kA 10
220 kV Lighting Arrester Discharge Counter
Manufacturer
Type outdoor
Counter indication digital
Protection class IP 55
Number per three arresters 1
Post Insulator, 220 kV
Manufacturer
Type
Rated voltage kV 245
Rated phase to ground lightning impulsewithstand voltage (peak)
kV 1050
Rated power frequencywithstand voltage (peak) kV 460
Minimum creepage distance mm 6125
Conductor at 220 kV Switchyard
Manufacturers -
Type - Aluminum conductor acc.
Total cross-section mm2
Aluminum cross-section mm2 2 x 400
7518P01/FICHT-8825852-v12 Section VI-7
220kV Transmission System
220 kV Switchyard EquipmentUnit Required Offered
Performance and Design Criteria
Conductor design: number of strands x diameter
Aluminum mm 400
Conductor diameter mm
Conductor weight kg/m
Theoretical breaking force kN
Ohmic resistance at 20°C WW/km
Insulator String at 220 kV
Manufacturers -
Type -
Insulating body material -
Rated electromechanical or mechanical strength kN
Max. shed diameter mm
Installation height mm
Nominal creepage distance mm
Rated short-time withstand current kA
Weight kg
Dead-end and suspension strings
Number of cap insulators per string
Single string Pcs.
Double string Pcs.
Clamps/Dead-End Joints, 220 kV
Manufacturers
Type
Cross-section
7518P01/FICHT-8825852-v12 Section VI-8
132 kV Transmission System
132 kV Switchyard EquipmentUnit Required Offered
Performance and Design Criteria
Circuit Breakers for 132 kV System
Circuit breaker type - SF6
Manufacturer
Nominal voltage kV 132
Rated voltage kV 145
Rated frequency Hz 50
Rated phase to ground lightning impulsewithstand voltage (peak) kV 650
Rated power frequency short withstand voltage kV 275
Rated short-circuit breaking current kA 40
Rated short-circuit making current (peak) kA 100
Rated nominal current A 1000
Rated short-circuit duration s 1
Minimum creepage distance mm 4000
First pole-to-clear factor - 1.3
Rated operating sequence(three-phase auto reclosing) -
0-0.3s – C0-1 min – C0 or C0-15s-
C0
Maximum breaking time ms 60
Maximum making time ms 100
Number of tripping coils 2
Number of closing coils 1
Protection class - IP 55
Auto reclosing single and three phase
Drive - 1 pole
Type of drive - Spring type
Power supply for drive V 110 DC
Power supply for auxiliary contacts V 110 DC
Power supply for heater V 220/380 AC
Auto reclosure, single and three phase yes/no yes
7518P01/FICHT-8825852-v12 Section VI-9
132 kV Transmission System
132 kV Switchyard EquipmentUnit Required Offered
Performance and Design Criteria
Isolator with Two Grounding Switch, 132 kV
Manufacturer
Type outdoor
Type of operation center break
Earthing on both sides yes/no yes
Nominal voltage kV 132
Rated voltage kV 145
Rated nominal current A 1250
Rated short time current Ith (1s) kA 40
Rated short-circuit making current Idyn (peak) kA 100
Rated phase-to-ground lightning impulsewithstand voltage (peak) kV 650
Rated power frequency short withstand voltage kV 275
Rated frequency Hz 50
Minimum creepage distance mm 4000
Protection class - IP 55
Drive - 1 or 3 pole
Type of drive - Electric motor
Power supply for drive V 110 DC
Power supply for auxiliary contacts V 110 DC
Power supply for heater V 220/380 AC
Manual operating facility yes/no yes
Isolator with one or two Grounding Switches, 132kVManufacturer
Type outdoor
Type of operation center break
Earthing on one side yes/no yes
Nominal voltage kV 132
Rated voltage kV 145
Rated nominal current A 1250
7518P01/FICHT-8825852-v12 Section VI-10
132 kV Transmission System
132 kV Switchyard EquipmentUnit Required Offered
Performance and Design Criteria
Rated short time current Ith (1s) kA 40
Rated short-circuit making current Idyn (peak) kA 100
Rated phase-to-ground lightning impulsewithstand voltage (peak) kV 650
Rated power frequency shortwithstand voltage kV 275
Rated frequency Hz 50
Minimum creepage distance mm 4000
Protection class - IP 55
Drive - 1 or 3 pole
Type of drive - Electric motor
Power supply for drive V 110 DC
Power supply for auxiliary contacts V 110 DC
Power supply for heater V 220/380 AC
Manual operating facility yes/no yes
Current Transformers, 132 kV
Manufacturer
Type outdoor
Nominal voltage kV 132
Rated voltage kV 145
Rated secondary currents A 1
Class accuracy for metering - 0.2
Class accuracy for measurement - 0.5
Class accuracy for protection system - 5 P 20
7518P01/FICHT-8825852-v12 Section VI-11
132 kV Transmission System
132 kV Switchyard EquipmentUnit Required Offered
Performance and Design Criteria
Number of cores -
Metering 1
measuring 1
protection 4
Rated burden VA 50
Minimum creepage distance mm 4000
Transformation ratio - 300 100-200 1/1/1/1/1/1 A
Rating of protective cores VA 50
Rating of measuring cores VA 30
Rated phase to ground power frequencywithstand voltage (peak) kV 650
Rated power frequencywithstand voltage (peak) kV 275
Rated short time current Ith (1s) kA 40
Voltage Transformers, 132 kV (capacitive)
Manufacturer
Type
Nominal voltage kV 110
Rated voltage kV 245
Transformation ratio -
132/0.1/0.1/0,1 kV3 / 3 / 3 /
3
Capacity of main winding VA 100
Capacity of secondary winding VA 100
Accuracy class for metering - 0.2
Accuracy class for measuring - 0.5
Accuracy class for protection - 3 P
Minimum creepage distance mm 4000
Rated phase-to-ground lightning impulsewithstand voltage (peak) kV 650
Rated power withstand voltage (peak) kV 275
7518P01/FICHT-8825852-v12 Section VI-12
132 kV Transmission System
132 kV Switchyard EquipmentUnit Required Offered
Performance and Design Criteria
Lightning Arresters, 132 kV System
Manufacturer
Type
Nominal voltage kV 132
Rated voltage kV 118
Rated continuous voltage kV 20
Rated discharge current kA 10
132 kV Lighting Arrester Discharge Counter
Manufacturer
Type outdoor
Counter indication digital
Protection class IP 55
Number per three arresters 1
Post Insulator, 132 kV
Manufacturer
Type
Rated voltage kV 145
Rated phase to ground lightning impulsewithstand voltage (peak)
kV 650
Rated power frequencywithstand voltage (peak) kV 275
Minimum creepage distance mm 4000
Conductor at 132 kV Switchyard
Manufacturers -
Type - Aluminum conductor acc.
Total cross-section mm2
Aluminum cross-section mm2 1 x 400
Conductor design: number of strands x diameter
Aluminum mm 400
7518P01/FICHT-8825852-v12 Section VI-13
132 kV Transmission System
132 kV Switchyard EquipmentUnit Required Offered
Performance and Design Criteria
Conductor diameter mm
Conductor weight kg/m
Theoretical breaking force kN
Ohmic resistance at 20°C WW/km
Insulator String at 132 kV
Manufacturers -
Type -
Insulating body material -
Rated electromechanical or mechanical strength kN
Max. shed diameter mm
Installation height mm
Nominal creepage distance mm
Rated short-time withstand current kA
Weight kg
Dead-end and suspension strings
Number of cap insulators per string
Single string Pcs.
Double string Pcs.
Clamps/Dead-End Joints, 132 kV
Manufacturers
Type
Cross-section
7518P01/FICHT-8825852-v12 Section VI-14
220kV Transmission System
Power Transformers/ReactorsUnit Required
Data Bid DataPerformance and Design Criteria
220/132/33kV Auto Transformer
Maximum continuous rating (MCR) for the 3 phase units ONAN/ ONAF
MVA 90/110
Number of Phases 3
Number of windingsAuto plus stabilising
Normal ratio of transformation at no load and at principle tap - HV/LV/TV kV 220/132/33
Corresponding highest system voltages kV 245/145/36
Corresponding lowest system frequency Hz 48
Minimum withstand voltages:
Full wave impulse withstand
of windings
of line terminal bushings
Induced over voltage
Power frequency withstand of neutral
kVp
kVp
kV rms
kV rms
1050/650/170
1050/650/170
460/275/70
38
Type of coolingONAN/ONAF
Minimum continuous rating MVA 90/110
Rating of tertiary windings MVA 30
Service conditions:
External cooling medium
Altitude not exceeding
Air temperature not exceeding
Average air temperature in any one year not exceeding:
In any one day
Average in one year
-
m
°C
°C
°C
Air
2000
42
35
25
Maximum temperature:
Top oil rise normal
Average ONAN winding rise
Average ONAF winding rise
°C
°C
°C
50
55
55
7518P01/FICHT-8825852-v12 Section VI-15
220kV Transmission System
Power Transformers/ReactorsUnit Required
Data Bid DataPerformance and Design CriteriaMaximum hot spot temperature at maximum continuous rating at yearly average ambient temperature
°C 98
Winding hot spot temperature on emergency overload not exceeding
°C 140
Phase connections:
(a) HV winding
(b) LV winding
(c) TV winding
(d) Vector group - HV/LV/TV
Star
Star
Delta
YNa0d1
Short circuit withstand fault level at terminals of:
220 kV busbars
132 kV busbars
33 kV busbars
kA
kA
kA
50
40
25
Impedance voltage at 75 °C and at normal tap and MCR between windings (% on HV Base):
HV & LV % on HV base % 13
Delta connected tertiary winding
(a) Nominal voltage
(b) External load
kV
- initially
- future
33
200 kVA
up to 400 kVA
Total range of variation of on load
transformation ratio (on HV side) as sl. no. 4:
ratio .....
ratio .....
Size of steps
plus %
minus %
10
10
1.25
Type of control
On load local,
remote and supervisory
electrical and hand operation
Line drop compensation Yes
Whether automatic control required and referenced voltage
Yes, 110V, 50Hz
7518P01/FICHT-8825852-v12 Section VI-16
220kV Transmission System
Power Transformers/ReactorsUnit Required
Data Bid DataPerformance and Design CriteriaWhether separate remote control panel required Yes
Estimated distance between remote control point and transformer
mSee
drawings
DC supply:
Nominal
Maximum float voltage,
V
V
110
125
Whether provision for supervisory control required, including AVR setting
Yes
Whether marshalling kiosk requiredTankside Cubicle
Number of transformers for which automatic control is to be suitable
1 (and provision for future 2nd)
Terminations
Bushing insulators or cable boxes on line and neutral terminals:
i) HV line
ii) Neutral
iii) LV line
iv) Tertiary winding
Bushings
Bushings
Bushings
Bushings
BCT Particulars
i) HV (220kV) Side:
Core 1 & Core 2:Core 3 :
400-200/1A, 60VA, 5P20.
Ratio, burden and accuracy
class shall be matched
with WTI meter.
ii) LV (132kV) Side:
Core 1, Core 2 &Core 3:
400-200/1A, 60VA, 5P20.
400/1A, 10VA, Cl 3.0
iii) Neutral Core 1:200-100-400/1A,
60VA, 5P20
7518P01/FICHT-8825852-v12 Section VI-17
220kV Transmission System
Power Transformers/ReactorsUnit Required
Data Bid DataPerformance and Design CriteriaAccommodation on tank for
outdoor weatherproof HV
neutral current transformers
Yes
Pollution category of outdoor
bushing insulators
25 mm/kV
of system rated
(highest)
voltage
Cooling
Number of cooler banks required per transformerTo suit
transformer design
Rating of each cooler bank as percentage of total loss at CMR %
50
Standby cooling requirementOne fan in each group
General
Type of oil preservation system Air Cell
Maximum acceptable noise level 78 dBA
Dimensions
length
wide
weight
mm
mm
mm
Weight
total
transport
Oil
kg
kg
kg
7518P01/FICHT-8825852-v12 Section VI-18
220kV Transmission System
Power Transformers/ReactorsUnit Required
Data Bid DataPerformance and Design Criteria
Power transformer 220 /33kV
/Type - 3-phase oil immersed
Manufacturer
Country of origin
Applicable standards - IEC 60076, 60354
Rated power ONAN MVA 23 MVA
Rated voltage kV/kV 220/33
Highest system voltage kV/kV 245 / 36
Rated frequency Hz 50
Vector group - YN0yn0
Impedance voltage (at rated power) % 13
Insulation - Uniform
Type of cooling -ONAN/ONAF
Temperature rise at rated power over 40°C maximum ambient temperature:
-
oil (upper level) °C 50
Winding °C 60
Rated power frequency withstand voltage HV/LV kV460 /
275
Rated lightning impulse withstand voltage HV/LV kVpeak1050 / 650 /
200
Max. noise level (Lp) dB (A) 66
Max. no-load current % In 0.2
losses no loud kW
losses at ONAN kW
losses at ONAF kW
Short circuit withstand 3s kA 50
Impedance homopolar WW/ph
7518P01/FICHT-8825852-v12 Section VI-19
220kV Transmission System
Power Transformers/ReactorsUnit Required
Data Bid DataPerformance and Design Criteria*external
connection
primary air
secondary cables
Dimensions
lenght mm
wide mm
height mm
Weight
Total kg
transport kg
oil kg
On-load tap changer
Type - Resistor
Rated current A
Rated short-time current
Maximum kA 50
3 seconds kA 10
On-load tap changer - + 10x1,5%
Installation mode - HV side
Rated operations duty (min.) Oper. 200.000
7518P01/FICHT-8825852-v12 Section VI-20
220kV Transmission System
Power Transformers/ReactorsUnit Required
Data Bid DataPerformance and Design Criteria
220kV Transmission System
Power Transformers/ReactorsUnit Required
Data Bid DataPerformance and Design Criteria
Power transformer 132 /33kV
/Type - 3-phase oil immersed
Manufacturer
Country of origin
Applicable standards - IEC 60076, 60354
Rated power ONAN MVA 23 MVA
Rated voltage kV/kV 132/33
Highest system voltage kV/kV 145 / 36
Rated frequency Hz 50
Vector group - YN0yn0
Impedance voltage (at rated power) % 13
Insulation - Uniform
Type of cooling - ONAN
Temperature rise at rated power over 40°C maximum ambient temperature:
-
oil (upper level) °C 50
Winding °C 60
Rated power frequency withstand voltage HV/LV kV 275 / 80
Rated lightning impulse withstand voltage HV/LV kVpeak 650 / 200
Max. noise level (Lp) dB (A) 66
Max. no-load current % In 0.2
7518P01/FICHT-8825852-v12 Section VI-21
220kV Transmission System
Power Transformers/ReactorsUnit Required
Data Bid DataPerformance and Design Criterialosses no loud kW
losses at ONAN kW
losses at ONAF kW
Short circuit withstand 3s kA 40
Impedance homopolar WW/ph
connection
primary air
secondary cables
Dimensions
lenght mm
wide mm
height mm
Weight
Total kg
transport kg
oil kg
On-load tap changer
Type - Resistor
Rated current A
Rated short-time current
Maximum kA 40
3 seconds kA 10
On-load tap changer - + 10x1,5%
Installation mode - HV side
Rated operations duty (min.) Oper. 200.000
7518P01/FICHT-8825852-v12 Section VI-22
220kV Transmission System
Power Transformers/ReactorsUnit Required
Data Bid DataPerformance and Design Criteria
General
Relays: - Digital
standard - IEC 60255
maximum ambient temperature for rated accuracy
oC 55
maximum temperature by storage oC 60
maximum humidity % 80
electromagnetic compatibility tests
- EN 50081
EN 50082-1
IEC 60255-6
insulation tests
- IEC 60255-5
IEC 60870-2-1
mechanical tests (vibration and shock stress)
- IEC 60255-2-1
IEC 60068-2
Other: all other Norms as specied on technical document
- IEC
switching capacity of output contacts W 1000
manufacturer references year 2
Panels:
standard - IEC 60529
protection class - IP 52
pre-wired - Yes
floor-mounted - Yes
steel sheet thickness mm > 2
7518P01/FICHT-8825852-v12 Section VI-23
220kV Transmission System
Power Transformers/ReactorsUnit Required
Data Bid DataPerformance and Design Criteria
maximum height mm 2000
maximum width mm 800
maximum depth mm 600
front-door material - Glass
coloring - RAL 7035
HV line protections
Differential protection (ANSI: 87L):
Type -
Manufacturer -
Place of manufacture -
Rated values:
frequency Hz 50
phase current A 1
auxiliary voltage V DC 110
Settings:
ranges of values of restrained protection I/InO 0.05 – 2.00
ranges of values of unrestrained protection I/InO 0.5 – 35.00
ranges of times sec 0.00 – 30.00
Distance protection (ANSI: 21):
Type -
Manufacturer -
Place of manufacture -
Rated values:
frequency Hz 50
phase current A 1
phase to phase voltage V 110
7518P01/FICHT-8825852-v12 Section VI-24
220kV Transmission System
Power Transformers/ReactorsUnit Required
Data Bid DataPerformance and Design Criteria
aux. voltage V DC 110
Settings:
ranges of values Ohm 0.050 – 600
ranges of times sec 0.00 – 30.00
minimum number of independent impedance zones
- 4
type of characteristic of teleprotection - PUTT, POTT
trip mode - 1-/3 pole
minimum number of autoreclose cycles (AR-cycles)
- 3
fault locator and event (disturbance) recorder - Yes
Remote communication:
protocol - IEC 60870-5-
103transmission rate Baud 9600
Back-up overcurrent protection (ANSI: 50/51 &50N/51N):
Type -
Manufacturer -
Place of manufacture -
Rated values
frequency Hz 50
phase current A 1
phase to phase voltage V 110
aux. voltage V DC 110
Settings
ranges of values A 0.10 – 35.00
ranges of times sec 0.00 – 30.00
7518P01/FICHT-8825852-v12 Section VI-25
220kV Transmission System
Power Transformers/ReactorsUnit Required
Data Bid DataPerformance and Design Criteria
minimum number of DTL stages for 50/51 - 2
minimum number of IDMT stages for 50/51 - 1
minimum number of DTL stages for 50N/51N - 2
minimum number of IDMT stages for 50N/51N - 1
Transformer Differential Protection
Manufacturer
Type
Ratings
Secondary current A
Rated frequency Hz
DC supply V
Main Characteristics
Range of operating coil settings % of C.T. rating
Range of bias coil settings
Recommended operating coil setting
Recommended bias coil setting
Number of bias coils
Minimum sensitivity
earth faults % of C.T. rating
phase faults % of C.T. rating
Maximum trough fault at which the protective equipment is stable with recommended settings:
earth faults % of C.T. rating
phase faults % of C.T. rating
7518P01/FICHT-8825852-v12 Section VI-26
220kV Transmission System
Power Transformers/ReactorsUnit Required
Data Bid DataPerformance and Design CriteriaMaximum time delay between initiation of fault and energizing of breaker trip circuit
3 x IN
10xIN
(ms)
Communication Interfaces
Protection functions
Transformer Restricted Earth Fault Protection
Manufacturer
Relay type
Tripping current range from – to X IN
Tripping time range from – to ms
Transformer Overcurrent and earth fault Protection
Manufacturer
Relay type
Tripping current range from - to x IN
ms
Tripping time range from - to x IN
ms
Tertiary winding protection
Manufacturer
Relay type
Phase balance protection
Manufacturer
Relay type
Reactor
Differential protection (ANSI: 87T):
Type -
7518P01/FICHT-8825852-v12 Section VI-27
220kV Transmission System
Power Transformers/ReactorsUnit Required
Data Bid DataPerformance and Design CriteriaManufacturer -
Place of manufacture -
Rated values
frequency Hz 50
phase current A 1
aux. voltage V DC 110
Settings
ranges of values of restrained protection I/InO 0.05 – 2.00
ranges of values of unrestrained protection I/InO 0.5 – 35.00
ranges of times sec 0.00 – 30.00
Settings
CT supervision
Operating time ms
Scheme burdens
DC burden W
AC burden Ohm
Contact rating
Make and carry for 0.2 s VA
Break
Operation indicator
Insulation
AC inputs (for 1 minute to all circuits and to case earth)
kV
High voltage impulse withstand voltage kV peak
Back-up overcurrent protection (ANSI: 50/51 & 49):
7518P01/FICHT-8825852-v12 Section VI-28
220kV Transmission System
Power Transformers/ReactorsUnit Required
Data Bid DataPerformance and Design CriteriaType
Manufacturer -
Place of manufacture -
Rated values
frequency Hz 50
phase current A 1
phase to phase voltage V 110
aux. voltage V DC 110
Settings
ranges of values A 0.10 – 35.00
ranges of times sec 0.00 – 30.00
minimum number of DTL stages of 50/51 - 2
minimum number of IDMT stages of 50/51 - 1
k-factor of 49 0.1 – 4.0
time constant 49 min 1.0 – 999.0
Busbar protection
Differential protection (ANSI: 87L):
Type -
Manufacturer -
Place of manufacture -
Rated values
frequency Hz 50
phase current A 1
aux. voltage V DC 110
ranges of values of restrained protection I/InO 0.05 – 2.00
ranges of values of unrestrained protection I/InO 0.5 – 35.00
7518P01/FICHT-8825852-v12 Section VI-29
220kV Transmission System
Power Transformers/ReactorsUnit Required
Data Bid DataPerformance and Design Criteria
ranges of times sec 0.00 – 30.00
Settings
CT supervision
Operating time ms
Scheme burdens
DC burden W
AC burden Ohm
Contact rating
Make and carry for 0.2 s VA
Break
Operation indicator
Insulation
AC inputs (for 1 minute to all circuits and to case earth)
kV
High voltage impulse withstand voltage kV peak
7518P01/FICHT-8825852-v12 Section VI-30
220kV Transmission System
MV Switchgear Minimum requirements Offered
Performance and Design Criteria Unit Data Data
33kV switchgear
manufacturer
designation
type - metalclad
insulation air
nominal system voltage kV 33
highest value of system operating voltage kV 40,5
range of highest voltage for equipment (IEC 60071-1) -
rated frequency Hz 50
rated short-circuit current (3 s) kArms 31,5
rated lightning impulse withstand voltage kVpeak 170/ (185)*
rated power frequency short duration withstand voltage
kVrms 70/ (85)*
symmetrical breaking current kA 31,5
short circuit making current kApeak 80
rated current
busbar, sectionalizer A 1250
outgoing feeders A 600
incoming feeder from transformer A 1250
protection class (with closed door) - IP 3X
rated operating cycle of circuit breaker -0-0.3 sec.-C0-
3 min.-C0
rated voltage of CB drive V 110 DC
type of circuit breaker - vacuum
type of current transformers -cast-resin insulated
ratings of current transformers
primary winding:
incoming feeder A 600-1250
outgoing feeders A 200-400
accuracy class for measuring / metering 0.5
7518P01/FICHT-8825852-v12 Section VI-31
220kV Transmission System
MV Switchgear Minimum requirements Offered
Performance and Design Criteria Unit Data Data
*external
accuracy class for protection 5P20
type of voltage transformersinductive, cast-resin insulated
ratings kV30/0.1/0.1
3/3/3
accuracy class for protection 3 P
accuracy class for measuring / metering 0.5
7518P01/FICHT-8825852-v12 Section VI-32
Station service transformersUnit Required
Data Bid DataPerformance and Design Criteria
Station service transformers 33/ 0.4 kV
Type
Manufacturer
Country of origin
Type -3-phase
hermetically sealed
Applicable standard - IEC 60076
Rated apparent power kVA 160
Rated voltage HV/LV kV 33/0.4
Rated frequency Hz 50
Vector group - Dyn 11
Impedance voltage % 4
Off-load tap changer regulation - + 2x2,5%
Type of cooling - ONAN
Rated power frequency withstand voltage kV 70/ (85)*
Rated lightning impulse withstand voltage kVpeak 170/ (185)*
*external
7518P01/FICHT-8825852-v12 Section VI-33
Substation Control and monitoring systemUnit Required
Data Bid DataPerformance and Design Criteria
Substation control and monitoring system
System availability % > 99,95
Meantime between failure h > 8750
Automatic time synchronization at all nodes of the network
Yes
Time resolution events msec < 10
Fault indication LEDs on modules Yes
Spare % 20
Station Bus
ProtocolIEC 61850-
8-1
Transmission medium FOC
Transmission rate MBit/s 100
Ethernet Switches
Manufacturer
Type
Power supply from station battery
Clock system
Manufacturer
Type
Synchronization source
Synchronization interval
Station computer
Manufacturer
Type
Power supply from station battery (DC-supply) V 110
7518P01/FICHT-8825852-v12 Section VI-34
Substation Control and monitoring systemUnit Required
Data Bid DataPerformance and Design Criteria
Common bay unit
Manufacturer
Type
Power supply from station battery (DC-supply) V 110
Interfaces to remote control centers
Serial Interface IEC 60870-5-101
Transmission medium
Data transmission rate Bit/s 9600
Serial Interface IEC 60870-5-104
Transmission medium FOC
Data transmission rate MBit/s 10
Other serial Interface
Transmission medium FOC
Data transmission rate
Operator workstations (HMI)
Hardware
Manufacturer
Type
Power supply from station battery via converter V AC 230
CPU
Working memory
Hard disk
RAID-System
External memory DVD or Disk array
Operating system
Screens 2 TFT
Screen size inch 20
Pixels 1280 x 1024
7518P01/FICHT-8825852-v12 Section VI-35
Substation Control and monitoring systemUnit Required
Data Bid DataPerformance and Design Criteria
MMI-Software
Manufacturer
Type
System Performance
Exchange of display (first reaction) sec. < 1
Presentation of a binary change in the process display
sec. < 0.5
Presentation of an analogue change in the process display
sec. < 1
From order to process output sec. < 0.5
From order to updating the display sec. < 1.5
Hardcopy printer
Number of printers 1
Power supply from station battery via converter V AC 230
Format DIN A3
Color Yes
Pages / min. > 12
Presentation of an analogue change in the process display
sec. < 1
From order to process output sec. < 0.5
From order to updating the display sec. < 1.5
Event printer
Number of printers 1
Power supply from station battery via converter V AC 230
Format DIN A4
Color No
Pages / min.
Service and Analysis System
Hardware
7518P01/FICHT-8825852-v12 Section VI-36
Substation Control and monitoring systemUnit Required
Data Bid DataPerformance and Design Criteria
Manufacturer
Type
Power supply from station battery via converter V AC 230
CPU
Working memory
Hard disk
External memory DVD
Operating system
Screens 1 TFT
Screen size inch 20
Pixels 1280 x 1024
Service and Analysis Software
Manufacturer
Type
Service unit
Hardware Laptop
Manufacturer
Type
Power supply V AC 230
CPU
Working memory
Hard disk
Operating system
External memory DVD
Screen size inch 14
Pixels 1280 x 1024
Service Software
Manufacturer
Type
7518P01/FICHT-8825852-v12 Section VI-37
Substation Control and monitoring systemUnit Required
Data Bid DataPerformance and Design Criteria
Panels
Pre-wired Yes
Floor-mounted Yes
Steel sheet thickness mm > 2
Protection class IP 52
Maximum height mm 2000
Maximum width mm 800
Maximum depth mm 600
Front-door material glass
Coloring RAL 7035
Bay control units (IEDs)for high voltage application
Manufacturer
Type
Power supply from station battery (DC-supply) V 110
Protocol IEC 61850
Other protocols
Bay control units (IEDs)for middle voltage application
Manufacturer
Type
Power supply from station battery (DC-supply) V 110
Protocol IEC 61850
Other protocols
7518P01/FICHT-8825852-v12 Section VI-38
Optical Telecommunication Equipment Unit Required Data
Bid Data
Performance and Design Criteria
ODF
Manufacturer -
Type -
Number of fiber interconnections - 96
Connector loss dB/connector < 0.5
Screw on type connectors - yes
designed for 19” cubicles - yes
SDH Multiplexer and Access Multiplexer
General
Manufacturer of
n x 2 MBit multiplexer equipment -
terminal equipment -
Type(s) of
n x 2 MBit multiplexer -
terminal equipment -
Maximum extension of transmission capacity of individual terminal by adding plug in cards. -
Ditto. for multiplexer based on 2 MBit-hierarchy. -
Maximum extension for multiplexer and terminal equipment racks. -
Protection class(es) of terminal equipment racks. -
Construction RequirementsOperating principle of amplifiers:optical - optical (bit rate insensitive) - Yes
Operating range of fibre optic terminals.
STM - 1 MBit/s 155
STM - 4 MBit/s 622
Operating principle of optical transmitter.
7518P01/FICHT-8825852-v12 Section VI-39
Optical Telecommunication Equipment Unit Required Data
Bid Data
Performance and Design Criteria
Optical Parameters
Nominal operating wavelength.
Remaining overall system margin at start of life/end of life.Receiver sensitivity (at BER of 10-10) at start of life/end of life.
Transmission Parameters
Bit error rate (path including terminals) at
n x 2 MBit/s - <1 x 10-10
Jitter performance
n x 2 MBit/s acc. to G.823
Accuracy of internal clock ppm
Line code (optical)
Line code (electrical)
ITU/CCITT standards (PCM equipment)
7518P01/FICHT-8825852-v12 Section VI-40
Metering Equipment Unit Required Data
Bid Data
Performance and Design Criteria
Measuring instruments for (Volt, Ampere, Watt, Var, cos phi etc.)
Size mm x mm 96 x 96
Accuracy class - 1.0
Operating principle - moving coil
Meters (internal)
Accuracy class - 0.5
Meters (Billing)
Max. error % 0.3
Number of tariffs 4
Selectable recording interval min 1-60
Storage capacity for:
15 minutes interval days 45
And for No's channel No. 8
Battery capacity days 32
Optical port - yes
Serial port RS-232-C - yes
Internal clock: battery capacity years 5
Max. error per month s 0.5
Software
ST-PCQ data
analysis software of Sangamo
Programmer/Retriever
Type - ST-RP or TELXON PTC-790
Batteries - rechargeable
7518P01/FICHT-8825852-v12 Section VI-41
Metering Equipment Unit Required Data
Bid Data
Performance and Design Criteria
RS-232-C accessory module - yes
Optical port accessory module - yes
Transducers
Accuracy % 0.5
Output current mA 4-20
Auxiliary voltage Vdc 125
Max. Power consumption VA 1
Measuring Instruments
Voltmeter
Manufacturer -
Type -
Size mm x mm
Scale degree
Accuracy class -
Power consumption VA
Operating principle -
Electro-mechanical - yes/no
Electronic - yes/no
Ampere meter
Manufacturer -
Type -
Size mm x mm
Scale degree
Accuracy class -
Power consumption VA
Operating principle -
Electro-mechanical - yes/no
Electronic - yes/no
7518P01/FICHT-8825852-v12 Section VI-42
Metering Equipment Unit Required Data
Bid Data
Performance and Design Criteria
Watt meter
Manufacturer -
Type -
Size mm x mm
Scale degree
Accuracy class -
Power consumption VA
Operating principle -
Electro-mechanical - yes/no
Electronic - yes/no
VAR meter
Manufacturer -
Type -
Size mm x mm
Scale degree
Accuracy class -
Power consumption VA
Operating principle -
Electro-mechanical - yes/no
Electronic - yes/no
Meters (internal)
Watt-hour meter
Manufacturer -
Type -
Size mm x mm
Accuracy class -
Power consumption VA
7518P01/FICHT-8825852-v12 Section VI-43
Metering Equipment Unit Required Data
Bid Data
Performance and Design Criteria
Operating principle -
Electro-mechanical - yes/no
Electronic - yes/no
VAR hour meter
Manufacturer -
Type -
Size mm x mm
Accuracy class -
Power consumption VA
Operating principle -
Electro-mechanical - yes/no
Electronic - yes/no
7518P01/FICHT-8825852-v12 Section VI-44
0.4 kV Installations Unit Required Data
Bid Data
Performance and Design Criteria
0.4 kV Installations
Applicable standards - IEC 60439, 60947
Type - fixed units
Rated voltage V 400
Frequency Hz 50
Rated short-circuit current for 1 s kA 50
Test voltage kV 2.5
Type of circuit breaker driving mechanism - Hand-operated
Secondary current of current transformer A 1
Protection class - IP 41
7518P01/FICHT-8825852-v12 Section VI-45
110 V DC Equipment Unit Required Data
Bid Data
Performance and Design Criteria
110 V DC Equipment
Applicable standards - IEC 60439, 60947
Type of distribution board- fix mounted
components
Busbar P and N Insulated
Rated voltage DC V 110
Test voltage V 1500
Type of load break switch/circuit breaker- hand-
operated
Protection class - IP 41
Min. insulation resistance KW 110
Battery type - NiCd
Applicable standard - IEC 60623
Rated voltage V 110
Type of operation- parallel
stand-by
Rated capacity (for 10 hours discharge time) Ah 250
Battery charger type- Thyristor
controlled
Input voltage (three-phase) V 400 + 10%
Rated DC voltage V 110
Maximum DC voltage V 132
Residual ripple % < 1
Type of cooling- self-
ventilating
Protection class of cubicle - IP 41
7518P01/FICHT-8825852-v12 Section VI-46
240 V AC Uninterruptible Power Supply Unit Required Data
Bid Data
Performance and Design Criteria
Static UPSGeneral dataManufacturerApplicable standards IEC 62040Rated power at … °C ambient temperature kVA/ °C 120 / 40Active power kW 96Type of cooling - ANProtection class of cubicle IP 20Rated voltage, input V 3x400/230Rated voltage, output V 400/230Voltage control % < +/- 1Frequency Hz 50Frequency stability Hz +/- 0,05Frequency stability with auto-pulsing % +/- 0,1
Overload capability125 % - 10 min
150 % - 60 s
Max. power loss at rated load W
Acoustic level on 100 % load dB(A) < 63 (in 1m)
Efficiency at 75 - 100 % linear load,at 75 - 100 % nonlinear load % > 95
> 93Total Harmonic Distortion of Current (THDI) % < 9Static transfer switch yes / no yesNetwork card yes / no yesInterfaces:RS-232, RJ 45, ModBus alternative ProfiBus yes / no yes
Relais cards for operating and malfunction messages yes / no yes
Dimensions:- height mm
7518P01/FICHT-8825852-v12 Section VI-47
240 V AC Uninterruptible Power Supply Unit Required Data
Bid Data
Performance and Design Criteria
- width mm- depth mmTotal weight kg
Rectifier dataManufacturer - -Type - -Power supply - TN-S
400 V ± 10 %
50 Hz ± 2 %
Rated voltage DC V -Rated current DC A -Maximum ambient temperature for operating at rated current
°C -
Constance of the output voltage: static (0 – 100 % of rated current) % ± 0,5 dynamic % -Residual undulation w/o battery % ss 5Constance of the direct current % -Current undulation % ss -Funkentstörung - IEC 61000-
6-2criterion A
Type of cooling - self ventilating
Efficiency % -Power factor - -Batterie dataBatterie type (maintenance free) - OPzS
7518P01/FICHT-8825852-v12 Section VI-48
240 V AC Uninterruptible Power Supply Unit Required Data
Bid Data
Performance and Design Criteria
Rated voltage V -Count of cellsRated capacity (C10, 1,8V/Cell, 20 °C) Ah -Discharge time h 8
Life period of the battery 10 years at 20 °C
Weight kgDimensions:- height mm
- width mm- depth mmBattery mounted in cubicle / on racks yesDrip pan for electrolyte yesBattery junction box yes
Inverter data:Input voltage V DC 110 ± 15 %Rated power kVA 120Maximum ambient temperature for operating at rated current.
°C -
power factor range (ind. to cap.) - -Output voltage V TN-S
system400 / 230
Output frequency Hz 50 ± 1 %Distortion factor:linear load % < 2nonlinear load % -Overload capability:for 10 min. x IN 1,25for 60 sec. x IN 1,5voltage tolerance:
7518P01/FICHT-8825852-v12 Section VI-49
240 V AC Uninterruptible Power Supply Unit Required Data
Bid Data
Performance and Design Criteria
static % < 2dynamic (100 % load changes) % < 10Efficiency (at cos = 0,8) % -Funkentstörung - IEC 61000-
6-2criterion A
Static transfer switch yes / no yesManual bypass switch yes / no yesNoise level at 1 m distance(any range 0 % till 100 % rated current)
dB(A) 60
Protection class - IP 31Type of cooling - self
ventilatingManual transfer yes / no yes
7518P01/FICHT-8825852-v12 Section VI-50
Cable Equipment Unit Required Data
Bid Data
Performance and Design Criteria
33 kV power cables, single-core
Applicable standards IEC 60502
Type - XLPE
Specified voltage E0/E kV 21/35
Highest system voltage kV 35
Rated frequency Hz 50
Test voltage kV 52.5
Conductor material - Cooper
Bending radius (single core cables) mm approx.15 x d
Rated short circuit current (1 s.)
Conductor kA 16
Screen kA 10
0.4 kV power cables, four-core
Applicable standards IEC 60502
Type - PVC
Specified voltage E0/E kV 0.6/1
Highest system voltage kV 0.44
Rated frequency Hz 50
Test voltage kV 2.5
Conductor material - Cooper
Bending radius (single core cables) mm approx.15 x d
Rated short circuit current (1 s.)
Conductor kA 25
Screen kA 15
7518P01/FICHT-8825852-v12 Section VI-51
Earthing System Unit Required Bid Data
Performance and Design Criteria
Earthing System
Applicable standards- IEEE 80, IEC
60621
Size of standards copper conductor mm2 70
Mode of connection- by
compression
Diameter of round copper rods for lightning protection
mm 8
Equipotential Bonding
IEC 60950
yes
To be verified by
CONTRACTOR
Power and Lighting Installation
Subdistribution boards
Type - Fixed
Rated voltage V 400/230
Rated frequency - 50
Test voltage kV 2.5
Degree of protection IP41/IP54
Lighting fixtures
indoor fluorescent W 1 x 58/2 x 58
indoor halogenW 1 x 250/1 x
400
outdoor high-pressure mercury W 400
Power and domestic sockets
Type - CEE form
Installation mode
power socket combination -
domestic sockets - Surface
7518P01/FICHT-8825852-v12 Section VI-52
Earthing System Unit Required Bid Data
Degree of protection - IP54
7518P01/FICHT-8825852-v12 Section VI-53