18
FIRE FIGHTING EQUIPMENT DATA SHEET JOB NO. : RFQ. NO. : ISSUE : SHEET OF 01 CUSTOMER : ITEM NO. : 02 PROJECT : QUANTITY : 03 LOCATION : SERVICE : FOAM SYSTEM 04 05 06 MODEL NO. YS-FT- 07 APPROVALS UL LISTED FM APPROVED KFEIC KISCO OTHERS 08 CODE & STANDARDS NFPA BS KFPL OTHERS 09 OPERATING CONDITIONS 10 TEMPERATURE MIN. : ( ) OPER. : ( ) DESIGN : ( ) 11 PRESSURE OPER. : ( ) kg/cm² DESIGN : ( ) kg/cm² HYDRO TEST : ( ) kg/cm² 12 FLUID HANDLED WATER AND / OR SEA WATER FOAM-WATER SOLUTION 13 INSTALLATION OUTDOOR AND / OR INDOOR 14 DESIGN FEATURES 15 TANK TYPE HORIZONTAL VERTICAL ATMOSPHERIC INTERNAL BLADDER 16 TANK CAPACITY LITER ( GALON ) 17 TANK SIZE mm(L) x mm(I.D) 18 INSULATION * 19 FOAM PROPORTIONING (1) PROPORTIONER PUMP PROPORTIONER LINE PROPORTIONER 20 PRESSURE PROPORTIONER PRESSURE SIDE PROPORTIONER 21 (2) SIZE 1" 1-1/2" 2" 2-1/2" 22 3" 4" 6" 8" 23 ANSI KS R.F F.F 24 150LBS 300LBS 10K 20K 25 (3) PROPORTIONING 1% 3% 6% 3% x 6% 26 RATE AFFF FFFP ATC AFFF / ATC 27 (4) ACCESSORIES BLANCED DIAPHRAGM CONTROL VALVE 28 FOAM LIQUID PUMP 29 : GENERAL WEATHER PROOF EXPLOSION PROOF 30 CONTROL VALVE 31 : PNEUMATIC MOTER OPERATED MANUAL 32 : GENERAL WEATHER PROOF EXPLOSION PROOF 33 : BALL BYTTERFLY GATE 34 FOAM FLUSH-IN & FLUSH OUT CONNECTOR 35 FOAM SKID CONTROL PANEL 36 : GENERAL WEATHER PROOF EXPLOSION PROOF 37 PRESSURE RELIEF VALVE 38 PIPING, PRESSURE GAUGE 39 FILLING, DRAIN & OTHER VALVES, ETC. 40 MATERIALS 41 SHELL & BODY CARBON STEEL STAINLESS STEEL 42 LUG & SUPPORT CARBON STEEL STAINLESS STEEL 43 44 45 46 47 48 49 4 3 2 1 DESCRIPTION 0 2006-11-25 J. K. JEONG Y. K. AN S. M. LEE FOR STANDARDIZATION REV DATE PRP'D CHK'D APP'D FOAM TANK (1/2) DATA SHEET AMB CODE & STANDARDS * * * *

DATA SHEET - Siemens fighting equipment data sheet job no. : rfq. no. : issue : sheet of 01 materials 02 pump casing fcast iron fcast steel fstainless steel 03 balanced diaphragm

Embed Size (px)

Citation preview

FIRE FIGHTING EQUIPMENT DATA SHEET

JOB NO. :

RFQ. NO. :

ISSUE : SHEET OF

01 CUSTOMER : ITEM NO. :

02 PROJECT : QUANTITY :

03 LOCATION : SERVICE : FOAM SYSTEM

04

05

06 MODEL NO. YS-FT-

07 APPROVALS UL LISTED FM APPROVED KFEIC KISCO □ OTHERS

08 CODE & STANDARDS NFPA □ BS KFPL □ OTHERS

09 OPERATING CONDITIONS

10 TEMPERATURE MIN. : ( ) ℃ OPER. : ( ) ℃ DESIGN : ( ) ℃

11 PRESSURE OPER. : ( ) kg/cm² DESIGN : ( ) kg/cm² HYDRO TEST : ( ) kg/cm²

12 FLUID HANDLED WATER AND / OR SEA WATER FOAM-WATER SOLUTION

13 INSTALLATION OUTDOOR AND / OR INDOOR

14 DESIGN FEATURES

15 TANK TYPE HORIZONTAL VERTICAL ATMOSPHERIC INTERNAL BLADDER

16 TANK CAPACITY LITER ( GALON )

17 TANK SIZE mm(L) x mm(I.D)

18 INSULATION *

19 FOAM PROPORTIONING (1) PROPORTIONER PUMP PROPORTIONER LINE PROPORTIONER

20 PRESSURE PROPORTIONER PRESSURE SIDE PROPORTIONER

21 (2) SIZE 1" 1-1/2" 2" 2-1/2"

22 3" 4" 6" 8"

23 ANSI KS R.F F.F

24 150LBS 300LBS 10K 20K

25 (3) PROPORTIONING 1% 3% 6% 3% x 6%

26 RATE AFFF FFFP ATC AFFF / ATC

27 (4) ACCESSORIES BLANCED DIAPHRAGM CONTROL VALVE

28 FOAM LIQUID PUMP

29 : GENERAL WEATHER PROOF EXPLOSION PROOF

30 CONTROL VALVE

31 : PNEUMATIC MOTER OPERATED MANUAL

32 : GENERAL WEATHER PROOF EXPLOSION PROOF

33 : BALL BYTTERFLY GATE

34 FOAM FLUSH-IN & FLUSH OUT CONNECTOR

35 FOAM SKID CONTROL PANEL

36 : GENERAL WEATHER PROOF EXPLOSION PROOF

37 PRESSURE RELIEF VALVE

38 PIPING, PRESSURE GAUGE

39 FILLING, DRAIN & OTHER VALVES, ETC.

40 MATERIALS

41 SHELL & BODY CARBON STEEL STAINLESS STEEL

42 LUG & SUPPORT CARBON STEEL STAINLESS STEEL

43

44

45

46

47

48

49 4

3

2

1

DESCRIPTION

0 2006-11-25 J. K. JEONG Y. K. AN S. M. LEE FOR STANDARDIZATION

REV DATE PRP'D CHK'D APP'D

FOAM TANK (1/2)DATA SHEET

AMB

CODE & STANDARDS

* *

* *

FIRE FIGHTING EQUIPMENT DATA SHEET

JOB NO. :

RFQ. NO. :

ISSUE : SHEET OF

01 MATERIALS

02 PUMP CASING CAST IRON CAST STEEL STAINLESS STEEL

03 BALANCED DIAPHRAGM CONTROL VALVE BRASS BRASS STAINLESS STEEL

04 CONTROL VALE CAST IRON CAST STEEL STAINLESS STEEL

05 FOAM SKID CONTROL PNAEL CARBON STEEL STAINLESS STEEL

06 PRESSURE RELIEF VALVE BRASS BRASS STAINLESS STEEL

07 FOAM SUCTION & DISCHARGE PIPE, FITTING, VALVE CARBON STEEL STAINLESS STEEL

08 WATER LINE & FOAM SOLUTION DISCHARGE LINE CARBON STEEL STAINLESS STEEL

09 ACCESSORIES

10 LEVEL GAUGE VENT VALVE FILLING CAP DRAIN VALVE WATER INLET PIPING

11 FOAM OUTLET PIPING VALVE BREATHER VALVE ANCHOR BOLT, NUT & WASHER

12 NAME PLATE ACCESS LADDER EXPLANATION BOARD FOR OPERATING PROCEDURE

13 TEST & INSPECTION

14 DIMENSION INSPECTION WITNESS REVIEW MATERIAL INSPECTION WITNESS REVIEW

15 VISUAL INSPECTION WITNESS REVIEW PERFORMANCE TEST YES NO

16 FINISH UNIT WEIGHT

17 PAINTING * ( ) Kg

18 COLOR *

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

FOR STANDARDIZATIONS. M. LEEJ. K. JEONG

4

2

3

Y. K. AN2006-11-250

1

CHK'D DESCRIPTIONPRP'D APP'DDATEREV

*

FOAM TANK (2/2)DATA SHEET

1JANUARY, 2006 HD191PAGE OF 4

TECHNICAL DATA :

TANK MOUNTING TYPE Vertical or Horizontal

CONCENTRATE For Vertical Tank :STORAGE 150 litres to 5000 litres.CAPACITY (40 TO 1320 Gallons(US))

For Horizontal Tank :150 litres to 10000 litres.(40 to 2640 Gallons (US))

RATED PRESSURE 12 Bar (175 PSI)

FACTORY TEST 18 Bar (261 PSI)PRESSURE

VESSEL Carbon steel as per ASMECONSTRUCTION Code Section VIII for unfired

pressure vessels.

BLADDER Thermo Plastic,Mullen burstpresure +800 PSI.Thickness 1.44 + 0.127 mm

CENTRE TUBE PVC

EXTERNAL PIPING Water side : Carbon steelseamless pipe sch 40.Foam concentrate side :SS sch 40

VENT AND DRAIN Ball valve (Bronze / SS )

OPTIONAL Sight gauge with shut offand drain valve, ladder andconcentrate supply controlvalve.

FINISH Epoxy red painted.

ORDERING Please specifyINFORMATION 1) Tank type, vertical or

horizontal2) Storage capacity of foam

concentrate3) Model number, size of

ratio controller with flowand pressure.

4) Type of foam concentrateto be used and percent-age of induction

required.

APPLICATIONThe Bladder Tank Foam Proportioning System utilisesthe water pressure to inject foam concentrate into awater supply and automatically proportions foamconcentrate over wide range of flow and pressure, withvery low pressure drop. This system does not requireconcentrate supply pump.

SPECIFICATIONThe Bladder Tank Foam Proportioning System areavailable with vertical and horizontal bladder tanks.The carbon steel tanks are designed and constructedin accordance with ASME Code Section VIII for unfiredpressure vessels. The maximum working pressure is12 Bar (175 psi) and factory tested for 18 Bar (261psi). The vertical tank assembly is supported by acontinuous skirt with provision for anchoring. Thehorizontal tanks are supported by two saddles weldedto the tank and drilled for anchoring. Tank is providedwith lifting lugs.

The system is supplied with pressure vessel, bladder,fill and drain valve for water and foam concentrate,ratio controller and vent valve. The ladder and sightglass assembly is supplied as optional item on request.

PRINCIPAL OF OPERATIONThe foam concentrate is to be filled into the bladdervery carefully to avoid rupture of the bladder. Theinstructions for filling are provided with the equipment.Once the main water flow is established and waterinlet and foam outlet valves are opened, the water

BLADDER TANK PROPORTIONING SYSTEM

2JANUARY, 2006 HD191PAGE OF 4

enters the area between vessel wall and bladder,applying pressure to the bladder. The foam concentrateis forced out of the bladder through the foam outletpipe and into the ratio controller through meteringorifice. The concentrate pressure and water inletpressure at ratio controller will be same, as the mainwater supply pressure is utilised to expel the foamfrom the bladder. The water flowing through the ratiocontroller jet creates a low pressure area commonboth to down stream water and foam concentrate.This injects the concentrate in to the ratio controllerthrough an accurate sized orifice proportioned towater venturi. This ensures correct proportioning overa wide range of flow condition.

The bladder tank proportioning system operates onsame principle as that of a balance pressureproportioning system. In bladder system, the bladderis used as diaphragm to separate the water and foamconcentrate within the tank. The foam concentrate isinjected into the ratio controller utilising waterpressure.

The system is also supplied with foam concentratecontrol valve as an optional item. The valve allowsconcentrate flow only when minimum of 3.0 kg/sq.cm.water pressure is established in the system. Forpressure drop and flow characteristics refer catalogueof ratio controller.

INSTALLATION, INSPECTIONAND MAINTENANCEAn installation, inspection and maintenance manual isprovided with each unit. The manual provides detailschematic, initial procedure, inspection andmaintenance procedures. The instruction manual mustbe read carefully and followed during installation andcommissioning of the system.

After few initial successful tests an authorised personmust be trained to perform inspection and testing ofthe system. It is recommended to carry out physicalinspection of the system regularly, the inspectionshould verify that no damages have taken place to anycomponent and all the valves are in their properposition as per the system requirement. The systemshould be fully tested at least once in a year and inaccordance with applicable NFPA/TAC code or inaccordance to the guidelines of the organisation havinglocal jurisdiction.

Do not turn off the system or any valve to repair ortest the system, without placing a roving Fire Patrolin the area covered by the system. The patrol shouldcontinue until the system is put back in service. Alsoinform the local security personnel and the controlroom so that a false alarm is not signalled.

CAUTION1. Do not weld on the tank as it may damage the

bladder.

2. Release pressure before an inspection and

maintenance of the system.

3. Sight glass is not pressure tight, so before takingconcentrate level reading, tank pressure must bereleased.

4. The bladder tank is to be installed under a shade toavoid direct sunlight on the equipment.

NOTE1. The foam concentrate is to be filled in the

bladder very carefully to avoid rupture ofthe bladder. The filling guideline provided withthe equipment must be adhered to strictly.

2. Air supply with regulator (0 to 1.0 kg/sqcm) requiredduring filling procedure, to be provided by user/installer

3.Water supply at 0-1.5 kg/sqcm required for tankfilling during commissioning , to be provided byinstaller/user.

3JANUARY, 2006 HD191PAGE OF 4

MATERIAL OF CONSTRUCTIONSR.NO. DESCRIPTION SPECIFICATION

1 VALVE SS/BRONZE

2 FOAM CONCENTRATE SS/BRONZESHUT OFF VALVE

3 WATER SHUT OFF VALVE SS/BRONZE4 LEVEL INDICATOR GLASS/ACRYLIC

5 PRESSURE GAUGE 0-16 KG/SQCM6 CHECK VALVE SS/BRONZE

7 SPOOL PIECE CARBON STEEL8 RATIO CONTROLLER BRONZE9 BLADDER THERMOPLASTIC RUBBER

10 TANK CARBON STEEL11 NAME PLATE BRASS

12 WATER LINE PIPING CARBON STEEL13 FOAM CONCENTRATE SS

PIPING

VERTICAL BLADDER TANK PROPORTIONING SYSTEM

(OPTIONAL)

4JANUARY, 2006 HD191PAGE OF 4

HORIZONTAL BLADDER TANK PROPORTIONING SYSTEM

MATERIAL OF CONSTRUCTIONSR.NO. DESCRIPTION SPECIFICATION

1 VALVE SS / BRONZE

2 FOAM CONCENTRATE SS / BRONZESHUT OFF VALVE

3 WATER SHUT OFF VALVE SS / BRONZE4 LEVEL INDICATOR GLASS/ ACRYLIC5 PRESSURE GAUGE 0-16 KG/ SQCM

6 CHECK VALVE SS/ BRONZE7 SPOOL PIECE CARBON STEEL

8 RATIO CONTROLLER BRONZE9 BLADDER THERMOPLASTIC RUBBER

10 TANK CARBON STEEL11 NAME PLATE BRASS12 WATER LINE PIPING CARBON STEEL

13 FOAM CONCENTRATE SSPIPING

(OPTIONAL)