Data Sheet Microprocessor Control of: Conductivity pH ORP Chemical Feed Biocide Feed Service Reports 4-20mA In & Outs Key Features Customizable LCD Display On Board History Graphs Simple ATM Style Menu One Point Calibration Internet Communications Option 5 Assignable Relays Relay Test Keys Customizable Notepad Multi-Level Security Code LSI or RSI Index Options 2 Year Replacement Warranty Email Alarm Capable MODbus and BACnet Options Application The MegaTron SS controllers offer all of the user friendly features of the original MegaTron at a more economical price for single water treatment systems. Units can be configured to control a wide range of digital and analog inputs. Relay activation and names plus many other features are field selectable. The “Notepad” allows the input and history gathering of service report parameters. MegaTron SS units can control a single cooling tower or boiler system with the most customization flexibility available. Controller

D MegaTronSS

Embed Size (px)

Citation preview

Page 1: D MegaTronSS

Data Sheet

Microprocessor Control of:Conductivity pH ORPChemical FeedBiocide FeedService Reports4-20mA In & Outs

Key Features• CustomizableLCDDisplay• OnBoardHistoryGraphs• SimpleATMStyleMenu• OnePointCalibration• InternetCommunicationsOption• 5AssignableRelays• RelayTestKeys• CustomizableNotepad• Multi-LevelSecurityCode• LSIorRSIIndexOptions• 2YearReplacementWarranty• EmailAlarmCapable• MODbusandBACnetOptions

ApplicationTheMegaTronSS controllers offer all ofthe user friendly features of the originalMegaTronatamoreeconomicalprice forsinglewatertreatmentsystems.

Unitscanbeconfigured tocontrolawiderangeof digitalandanalog inputs.Relayactivation and names plusmany otherfeaturesarefieldselectable.The“Notepad”allows the input and history gathering ofservicereportparameters.

MegaTronSS units can control a singlecoolingtowerorboilersystemwiththemostcustomizationflexibilityavailable.

Controller

5

4

3

2

1

ENTER

HELP

5

4

3

CHANGE

RUN

SET UP0

9

8

2

1

7

6

HOME

BACK

Page 2: D MegaTronSS

4700HaroldAbitzDrMuskogee,OK74403800-743-7431phone888-686-6212faxwww.advantagecontrols.com

Get the Advantage

SpecificationsElectrical • Input: 95-240VAC,50/60Hz • Control:Equaltoinputvoltage(95-240VAC) fusedat2.5Aperrelay Prewiredunitsaresuppliedwithan8’(248.84cm) powercordand8”(20.32cm)outputreceptacles.Operational • Display:240X128GraphicLCD • Conductivity Control:0-10,000µS/cmscale Boilersamplemethodisselectablefrom continuous,timedsamplingorsampleandhold. • pH:0-14scale • ORP:+/-1000millivoltsscale TheORPsetpointcanbetiedtoanoptional 28-dayfeedtimerasanoverride. • Accuracy:+/-1% • Feed Timers are all selectable from: Pulse-watermeteractivatedw/accumulator Percent-1-100%ofacycletime. Limit-Limitsfeedwithbleed Post-1-100%ofpostbleedorothertimewith anoveralllimit. 28 Day-biocidetimer.

EnclosureHeavydutyNEMA4XstylehighimpactthermoplasticwithpadlockablegasketedLexanviewingdoor.

Environment Ambienttemperature: 0oto125oF(-17to52oC) Relativehumidity: 0to100%ElectrodesTowerStandardelectrodesaresuppliedin3/4”(1.91cm) SCH80PVCfemaleslipteeswithquickreleasenut.•Conductivity:TE-4A150psi(10.3bar)/140oF(58oC)Max•pH: TPE-2100psi(6.8bar)/140oF(58oC)Max•ORP: TOE-2100psi(6.8bar)/140oF(58oC)Max•Temperature: TC-1150psi(10.3bar)/140oF(58oC)MaxBoilerConductivityelectrodesaresuppliedwith1”(2.54cm)MNPTSSthreads. •Conductivity: BE-32250psi@400°F/350psig@265°FPEEKcore

Shipping Weight: Approximately8lbs.(3.62kg)

Dimensions:W10”(28.4cm)xH12”(30.5cm)xD7.25”(18.4cm)

Build a ModelThemodel number starts with SS followed by thecode for each function needed for the first system.(SSCPF3E)

Once themaincontrol functionshavebeenselected,insertanother-and list thedesiredcommonoptions.(SSCPF3-H1).

Conductivity Control(1persystemmax)B2 = BE-32StandardBoilerprobeC = TE-4AStandardTowerprobe

PH Control(1persystemmax)P = TPE-21StandardTowerprobe

ORP Control(1persystemmax)R = TOE-21StandardORPprobe

Feed Timers(maxof5persystem)F1toF5(F4=Fourfeedtimers)

Flow SwitchE = FlowSwitch

OPTIONSA - ConduitconnectionA3 - ConduitwithCEapprovalH1 - InternetConnectCommunicationsH4 - InternetcardwithphonemodemH5 - InternetcardwithcellularrouterH11 - Internetcardw/CAT5&ModbusTCP/IPH21 - Internetcardw/CAT5&BACNetTCP/IPH31 - InternetcardforLonWorksN3 - (3)4-20mAInputs(nooptionU3ifselected)O3 - (3)4-20mAOutputsS - pHsaturationindexes(withpHcontrol)U3 - (3)0-5voltinputs(nooptionN3ifselected)V - 5voltD.C.outputwithwatermeterwiresW3 - (3)AuxiliaryflowmeterinputsY - AgencyApproval(ETL,US&C)

NOTES:1. Timersselectable(pulse,%,postbleed,limitor 28-day).Eachsystemhas2watermeterinputs.2. Allexpansionslotsprovided.3. MegaTronSScontrollerscanhave3probesmax.4. MegaTronSScontrollershave5relaysmax.5. ChangeH1optiontoH11forMODbusTCP/IPor H21forBACnetIPreadonlycommunications.6. Boilerconductivityshouldonlybeusedoncontinuous

orsurfacelines;notbottomblowdownlines.7. Contactthefactoryforacompleteoptionlist.

10/2013