Upload
nageswar-rao
View
1.524
Download
3
Embed Size (px)
Citation preview
M.Nageswar Rao,Sr.Manager (Engg.)NESCL, Noida
Date: 16.08.13
Presentation Layout
PROTECTION SCHEMES
CURRENT TRANSFORMER
CT DESIGN REQUIREMENTS
FOR VARIOUS PROTECTION
Protection schemesOver current protectionUnit Protection
Differential protectionREF protectionLine differential (Pilot wire)
Distance Protection
Diff. protectionMonitors an area limited by CTs which
measure incoming & outgoing currentsTypes
High impedanceLow impedance (Biased diff.)
High impedance Diff. protection Scheme used for
Bus bars, generator windings and Y-connected or auto
transformer windings.CTs must be selected with
Same ratioSame magnetizing curve
(same Vkmin & same Ie at Vk/2)
Same Rctmax.
High impedance Diff. protection
High impd. Busbar diff.
REF protection of T/f
High impedance Diff. protection
Line or cable diff. protection with pilot wires
Low impedance Diff. protection
For double bus bar protection
Used for busbar diff. protectionEHV lines
CTs can have different ratiosBias is used to correct
small ratio mismatchLarger ratios can be
matched using Aux. CTs
Low impedance Diff. – slope characteristicsHave operating characteristics with pickup increasing with
higher through fault currents. This is defined by a slope of the bias characteristics.
The higher the slope, the larger is the tolerance of the relay to errors and CT saturation.
Modern numerical relays using special saturation detectors or special through fault detectors.
Automatic slope adjustment is achieved with the help of modern numerical relays using special saturation detectors or special through fault detectors. low slope is maintained (sensitive differential protection) when
When there is no saturation or when no through fault is detected,
High slope is maintained (for good stability) when, severe saturation or through fault detection.
High & Low impedance diff. protectionHigh impd. diff. Low impd. Diff.
Application • Bus bars, • Generator windings and • Y-connected or auto transformer
windings
• Bus bars• EHV lines
CT Ratio Matching CT ratio to avoid spill current during healthy state
CTs can have different ratios
CT saturation voltage
Knee point voltage is of concern. Saturation can be tolerated, hence Vk is not of much concern.
Routing of CT connection
All CT connections are looped in the yard and single cable taken to the relay
CT wires directly to the relay
CT ckt. supervision
Detected by using a 3 phase rectifier relay to effect the summation of the bus wire voltages and short the pilot wire from the affected phase
A current operated auxiliary relay is used to detect any unbalance sec current for supervision of the CT ckts. Current setting of the supvn relay must be less than that of main diff relay
Cost & space req.
Less cost & space. Very costly and space consuming, as it requires large no. of modules & matching CTs.
Current TransformerCurrent
Transformer is an instrument transformer which transforms current from one level to another level.
e.g. 1000/1A, 200/5A
Terminal Box
PP
SS
Insulator
Secondary winding
Primary winding
Core
CBBus Feeder
CTs – windings & coresCTs have
1 or more primary windings (with 1 or more taps), and
1 or more secondary windings on different cores.
• Types of CT cores• Measuring cores• Protection cores• Protection cores for
special applications
CT secondary current rating5A Secondary 1A Secondary
Applications 1. Indoor switchgear cubicles
2. Higher primary current ratings.
Outdoor
When secondary gets open
low peak voltage high peak
voltageFine turns ratio adjustment
not possible when primary rating is low
Always possible
Saturation factor
•Ips/Ipn is called• Instrument Security Factor (FS) for the measuring CTs, and• Accuracy Limit Factor (ALF) for the protective CTs.
•These two saturation factors are practically the same, •FS or ALF = (Vsat/Vrated)*Inom.
CT - Knee Point Voltage CT excitation curve
is the magnetizing characteristic (plot between secondary applied voltage and the corresponding magnetizing current)
Knee point voltage Corresponds to the point on excitation curve beyond which an increase of 10% in
exciting e.m.f. produces an increase of 50% in the exciting current is defined as the point on the excitation curve where the tangent is at 45 degree
to the abscissa. represents the point beyond which the CT becomes non-linear.
Metering class Protection class Protection special class
Application Measuring Protection Unit ProtectionCT Selection Ratio Ratio Ratio
Accuracy class(0.1,0.2,0.3, 0.5,1,3,5)
Accuracy class (5P, 10P, 15P)
Knee Point Voltage (Vk)
Burden (15,20,30VA)
ALF (5, 10, 15, 20, 25, 30)
CT Secondary winding resistance (RCT) corrected to75OC
ISF (3.5.7) Burden (15,20,30VA)
Ie (Excitation current) at Vk or a stated % of Vk.
CT Selection example:
e.g.: 2000/1, Class 0.2, 20VA, ISF – 5
e.g. : 5P20, 40VA, ALF-5
e.g. : 200/1, PS Class, Vk > 200V, RCT < 2.0 ohms, Ie < 30mA at Vk/4
Application
IEC 60044-1
IEC 60044-6
IEEE C57.13 / ANSI
Metering 0.1,0.2,0.3, 0.5,1,3,5
0.3, 0.6, 1.2 (burden @ p.f. 0.9)
Protection 5P, 10P, 15P
C100, T100, C200, T200, C400, T400, C800, T800 (burden@ p.f. 0.5)
Protection special
PX TPS, TPX, TPY, TPZ
CT - RemananceRemanance flux is the value of flux, that would
remain in the core, 3 mins after interruption of exciting current of sufficient magnitude to induce the saturation flux.
CT Class
Air gap Remanance Application
TPS No High upto 85%
high impedance circulating current protection
TPX No High upto 85%
line protection.
TPY small Low <10% line protection with auto-reclose.
TPZ Large Negligible 0% special applications such as differential protection of large generators
CT specification – ANSI (IEEE Std C57.13- 1993)CT classes as per ANSI
C
CT is furnished with excitation characteristics which can be used to “Calculate” the CT performance.
K
same as C rating but the knee-point voltage must be at least 70% of the secondary terminal voltage rating.
Tthe ratio error must be determined by ‘Test’.
ANSIVolt at 100A
Burden (ohm)
C100 100 1
C200 200 2
C400 400 4
C800 800 8
•The standard current transformer secondary winding is rated at 5A as per ANSI standards. (20times of 5A is max. recommended CT secondary current).
CT Saturation
In case of Rl (lead resistance)
1Φ to ground faults
Two-way
3Φ faults One-way
AC saturationTo avoid saturation, the CT
shall develop adequate voltage such that Vx > If (Rct+Rl+Rb)where, If = Fault current on CT secondary (Amps) Rct = CT Secondary resistance (Ohms) Rl = CT Secondary total lead resistance
(Ohms) Rb =CT secondary connected burden
(Ohms)
CT SaturationDC saturation
Decaying dc current introduces during a fault.
CT Saturation - Excursion of flux waveform Φ
Is well within the saturation limits with AC current waveforms
shoots past the saturation limits quickly with DC transients
CT SaturationCT shall have enough
capacity to develop the following voltage not to saturate at all for a combination of AC and DC transient. Vx > If (1+X/R) (Rct+Rl+Rb)
Saturation due to DC transient distorts the AC waveform output as well
CT saturation – how to avoidCT saturation can be avoided
By increasing the CT ratio (thereby reducing actual secondary current during fault to less than 100A)
By reducing the secondary connected burden by reducing the connected relay burden, reducing the lead resistance (by either
reducing the distance between the relay to the CT, multiple parallel runs of CT leads, thicker wire size etc.)
Most of the faults are ground faults which tend to have lesser DC offset and associated saturation issues. The ground faults tend to have more resistance (lower X/R ratio)
Protection Current demand
Operating time
Transient saturation
AC saturation
Remarks
Time OC 20-30 In NO YESHigh-set Phase or Ground OC
1 cycle YES YES high speed ofOperation is to be ensured.
Distance Protection
1.5 In YES NO Saturation is accepted after the operation of the Zone-1 operation.
Differential protection (Biased)
YES Saturation voltage is of concern
Differential protection (High impedance)
1 cycle knee point voltage rather is of concern
High Impedance Diff. Protection
setting VR >K x If x (RL + RCT ) (Volts) If = Secondary Fault current (Amps) RL = CT secondary lead resistance (Ohms) RCT = CT secondary resistance (Ohms) K = Margin Factor (=1 for full saturation)
CT requirements -for various Protection applications High Impedance Differential scheme
Vk≥2.If.(Rct+2.Rl) RCT= CT secondary winding resistance Rlead = lead resistance of the farthest CT in parallel group If = Maximum through fault current up to which relay should remain stable (referred to CT
secondary) Biased Differential scheme
Vk≥ K.2.IR.(Rct+2.Rl) IR= Relay rated current K = Constant specified by the manufacturer usually based on conjunction test (the constant is
usually chosen to ensure positive operation of highest differential unit on severe internal fault with extreme CT saturation)
Distance Protection schemeVk≥ (1+X/R).If.(Rr+Rct+n.Rl) X/R = Primary system reactance/resistance ratio (to account for the DC component
of the fault current) If= Maximum CT secondary current for fault at zone1 reach point Zrelay = Relay ohmic burden RCT= CT secondary winding resistance; nRlead= Lead resistance
If limited byTransformer Maximum through fault
currentZ1%
Busbar Maximum through fault current
switchgear breaking capacity
Generator Maximum through fault current
Xd”
Motor Maximum starting current
6x load current for DOL Motors
Shunt reactors
Maximum charging current
X
Short feeders
Maximum through fault current
for fault at busbar