csit/seniorprojects/SeniorProjects... · Web view2020. 5. 9. · Where provided, the manual fire...
64
Proposal Report Spring 2020 Construction of a Non-Denominational Church Et 494: Senior Design II Participants: William Maley, Michael Ryals, and Austin Girod
csit/seniorprojects/SeniorProjects... · Web view2020. 5. 9. · Where provided, the manual fire alarm box shall not be located in an area that is accessible to the public. [F]
Participants: William Maley, Michael Ryals, and Austin Girod
Instructor: Dr. Mohammad Saadeh
Advisor: R. Edward Rode’
Abstract
This semester we are completing the tasks that we agreed too last
semester these include the prebuilding design, construction
materials, the zoning, and building codes, finding possible
locations, and LEED investigation. But, this semester we have also
added design of footings and slabs, steel design where applicable,
design of retention pond, completion of working drawings,
estimation of materials needed, take off for building, and schedule
for construction process. Along with these task we will also be
working with the theatre department to design and construct props
and stage designs. These task build upon the work we completed last
semester and allow us to go more in-depth with our project and
allow us to complete many vital parts of the construction
process.
Table of Contents
Abstract Page 2
Pre-Building Design Page 5-10
Working Drawings Page 12
Retainage Pond Page 13
Estimation of Materials Needed Take Off for Building Page 33
Possible Site Locations Page 37-40
Scheduling Page 39-40
Figure 3: Ceiling Joist Plan Page 6
Figure 4: Reinforced Concrete Foundation Page 9
Figure 5: Steel Columns Page 9
Figure 6: Steel Joist Page 9
Figure 7: Metal Studs Page 10
Figure 8: Porous Concrete Parking Lot Page 10
Figure 9: Gypsum Board Walls Page 10
Figure 10: Gypsum Board Ceilings Page 10
Figure 11: Architectural Asphalt Roof Page 11
Figure 12: Cut Stone Page 11
Figure 13: Future Stained Glass Page 11
Figure 14: Face Brick Page 12
Figure 15: Location 1 Page 38
Figure 16: Location 2 Page 38
Figure 17: Location 3 Page 39
Figure 18: Loan Information Page 42
Pre-Building Design
Preliminary Design:
We were approached by an individual to construct a church in
Hammond, Louisiana. We were given a large amount of design freedom
by this individual so we opted for a very simplistic design. The
church is 83’-4” by 55’-10” which, gives it an area of 4654 ft2. We
came up with the preliminary design by using AutoCAD Architectural
2019. The building is the shape of a rectangle which, makes
construction and preparation of the site simple. It has 11 rooms
including the main worship room and 2 corridors that run along the
west and south sides of the building. Along with the general design
we have also included detailed drawings of the foundation plan and
the footings that we will use. In addition, the rafter and ceiling
joist plans are also included along with the foundational plans. We
have determined that the building will have an occupancy of 250 and
it will have 7 entry and exit points. The chapel will be the
largest room in the church since this is where the occupants will
be gathering. It will have an area of around 1430 ft2 and have
multiple windows from the ceiling down to a few feet from the
floor. Figure 1 below shows the preliminary drawing of the church
with the overall measurements of the church. Figure 2 shows the
foundational drawings and figure 3 shows the rafters and ceiling
joist.
The method we have selected to construct our church is one that has
become popular in the past few years and this is an all-steel
construction. This method has many distinct advantages as compared
to standard wooden structures. It can be assembled very quickly
with less manpower than if you were to construct this church out of
wood and also it will have a much longer service life too. With the
premade trusses, columns, and beams this structure could be erected
in less than 6 months from the time the slab is cured and the
pieces have been manufactured.
List of Rooms:
Pastors Office
Description of Materials:
Reinforced Concrete Foundation:
We have chosen to utilize a 5,000 Psi reinforced concrete
post-tension slab because of its a cost-effective solution. It also
has exceptionally good strength and can handle the large amounts of
live and dead loads the slab will be subjected to. (See Figure 4).
In the figures above we showed the foundational plan and footings
plan. These footings will be strong enough to hold the dead and
live loads our building will be subjected too. Again we chose 5,000
Psi concrete for the footings and this will be reinforced by rebar
and the slab will have expanded metal sheets tied together to offer
more structural support. The foundation will be built on top of a
six-inch layer of unwashed gravel. This is for proper compaction
and to aid in the strength of the subsoil.
Steel Columns:
Steel columns will be utilized in the construction of this building
for their strength and the speed at which they can be erected into
a functioning structure. Through the life of this structure, the
columns will also provide more reliable support and an increased
life span. The columns will directly tie into the footings of the
building through anchor bolts. Where the columns attach to the
footing it will be slightly larger and deeper because of the
concentrated load that will be applied at each anchor point. The
steel columns and girders that are designed to fit into the church
were designed using SAP2000 to model the basic shape and to let all
of the loads be calculated. Then the Steel Manual will be used to
find the correct members to fill in the sections of the joist and
column
(See Figure 3)
Steel Joist:
Steel joist is used in the construction of buildings with metal
frames because they are lightweight and extremely strong. They also
allow for a suspended ceiling to be installed or the contractors
can opt to leave the ceiling exposed. They are prefabricated and
shipped to the construction site so installation is as simple as
moving the pieces to their desired locations and dropping them into
place. We plan to use steel joist for the roof around the chapel
but, in the chapel, we will utilize 1’-6” laminated beams premade
into trusses. The use of these steel trusses will allow us to
construct the building in less time and allow us to use a flat
asphalt roof. The joist is made of single angles. The open webs
joist in SAP2000 shows the forces and shows the maximum compression
and tension for the members.
(See Figure 4)
Metal Studs:
Metal studs are very similar to wood studs in the construction and
design aspects. But, they have a distinct advantage over wood
studs. They are often coated with a zinc coating to prevent rust
and these coatings last much longer than wood studs can. They are
also much stronger and can be prefabricated to allow for quick and
easy installation. Although this will raise the cost of the project
some we see this as a small price to pay to ensure the overall
strength and longevity of the structure.
(See Figure 5)
Porous Concrete Parking Lot:
Porous concrete is an amazing innovation that not only protects our
environment from contaminants and runoff from vehicles but also
gives the parish points. These points go toward lowering the flood
insurance cost. Our parking lot takes up 51,000 ft2. It is located
on the south end of our lot and directly to the northeast is the
structure. Adjacent to the structure is our retaining pond. This
retaining pond will be large enough and deep enough to withstand
average rainfall accumulation for Hammond, Louisiana, and will also
have an emergency overflow that allows the water to drain from the
pond into a nearby waterway. The concrete will be sitting on top of
6 inches of washed limestone that will allow water to pass through
without blocking it. There will also be a geotechnical fabric that
is laid out under the rocks to keep the soil from seeping up into
the gravel and impeding the flow. The parking lot grades slightly 1
inch over 50 feet to the lake. This is ideal because it will allow
the water to be filtered by the gravel which, is more
environmentally friendly than just storm drains.
(See Figure 6)
Gypsum Board Walls:
Also, known as drywall, this material is cheap and also durable
with a clean finish when installed correctly. This wall will be
utilized where it is needed in the interior of the building. We
will not be using it on the interior walls of the chapel or on the
border walls of the building because these will be concrete blocks.
Gypsum not only provides a clean-finished appearance but, it also
insulates and provides more sound deadening.
(See Figure 7)
Gypsum Board Ceiling:
Similar to the drywall that will be used for the walls in the
structure. The gypsum board ceilings are a cost-effective and
efficient solution. This will be utilized in the office areas and
rooms adjacent to the main chapel. The main chapel will have
exposed beam ceilings and will utilize the gypsum board ceiling in
between the beams. Gyp. Board is a fantastic alternative to other
ceiling tiles and provides good insulation and fast repairs if
damaged.
(See Figure 8)
Architectural Asphalt Roof:
This type of roof is beneficial for flat roofs such as the one
utilized by this building. It is beneficial because it is
relatively few layers that have to be applied keeping the weight
down while still being an excellent way to repel rain. It also
offers easy maintenance and easy access to the whole roof. Asphalt
roofs also have a long service life. These types of roofs have
become commonplace in commercial applications. We will utilize an
asphalt shingle roof for the chapel with three-tab shingles over #4
felt and ½” OSB plywood.
(See Figure 9)
Cut Stone:
Cut stone will cover some of the outside faces of the building with
higher traffic. This is because of its appeal to the eye with
natural stone roughness but, still remaining semi-symmetrical to
give a clean outer façade. This stone is not a structural component
and will be attached to the cement block walls on the South face of
the chapel and Eastside.
(See Figure 10)
Future Stained Glass:
Future stained glass is going to be used to add contrast to the
relatively uniform colors of the outside of the church. We have
been considering putting in a large stained glass window with an
inlaid cross in the entryway. This will utilize most of the future
stained glass that will be installed on the structure. (See Figure
11)
Face Brick:
Face brick is a brick that has multiple advantages; it increases
efficiency, looks, is a structural component, and the overall value
of the building. We plan to use face brick as much as possible on
the outside of the building. This will include the Northside of the
building along with the Westside. This brick is often used on
commercial applications because of its ruggedness and also its ease
of cleaning and maintenance.
(See Figure 12)
Figure 4:
Figure 5:
Figure 6:
Figure 7:
Figure 8:
Figure 9/10:
Figure 11:
Figure 12:
Figure 13:
Figure 14:
Working Drawings
Working Drawings:
These drawings include all of the necessary components that a
contractor would need to construct the building. This would be the
mechanical, electrical, structural, and civil sections of the
drawings. These drawings will also allow us to accurately complete
the materials take-off and estimations necessary to plan the
construction process. We have completed much of the necessary
components of the working drawings last semester but, the
mechanical and civil sections still need to be completed before
this task is done. The working drawings have sectional cut-outs of
each one of the members we designed. This includes the foundation,
structural, and superimposed drawings.
Design of Footings and Slabs
Design of Footings:
The design of footings is a very in-depth process involving finding
the loads per sqft on each wall and determining the highest load
for the structure. After finding the induvial weights of the
building materials needed and adding them together you take this
number and use it as your dead load. The dead load is mostly the
weight of the building and objects that will not be moved in the
life span of the building. After the dead load is considered, the
next step is to have a geotechnical survey done to determine the
properties of the soil mechanics and also the bearing weight of the
soil. This is a vital part of the design phase because without this
information the footing could either be too small and fail or could
be designed too large and waste money unnecessarily. But, once the
geotechnical survey is taken into consideration the footing can be
determined through a few simple calculations. We were able to take
the footings that were supplied to us in the drawing and reengineer
footings that will work with our design. This was done by using the
equations from the class soils and foundations that Dr. Zeidan
teaches. The equation we used was the Terzaghi equation. This
equation takes into account the amount of force that it takes to
cause the ground to slip and fail to push up and out away from the
footing or slab and causing it to tip over.
Design of Reinforced Concrete Slab:
The design of a reinforced concrete slab is very similar to the
design of the footing except that there will be a dead load and a
live load. The thickness of the slab will be determined by the
footings and the bearing capacity of the soil. We plan to use a
post-tensioned concrete slab which, means that after the
construction process and the slab is cured there are cables running
horizontally and vertically that will be pneumatically tightened
compressing the slab and keeping it from being exposed to tension.
The benefits of this are that if some sag happens in the soil the
cables will actually keep the concrete from sagging or cracking. It
will also extend the life of the slab exponentially. The slab will
have a six-inch backfill of the subbase. This sub base will consist
of #57 gravel and will be compacted will a vibratory packer. This
will give our slab a sturdy foundation to be poured on and it will
alow shrinkage and expansion without causing failure.
Design of Retention Pond
Retention Ponds:
The purpose of these retention ponds is to capture rainwater that
would otherwise propagate on the surface of the soil for long
periods of time and moving it into a holding area. Our retention
pond will be filled by the land surrounding it this includes the
parking lot, church, and area surrounding the church. Once we have
determined the area of the lot we can determine the depth of the
pond and also where we need to position it. Before the pond reaches
a level where it overflows we will install an overflow that will
allow the pond to relieve some of the water that has been contained
in it without doing potential harm to our structure or foundation.
The retention pond also has to be 30 feet from any boundary lines
so the shape had to be changed and made much longer East to West.
It will be 8 feet deep and will have a slope of 6 inches per foot.
The water level will be around 3 feet standard level. When full of
rainwater there is a drain that drains into the city stormwater
drainage system. It is located on the west side of the pond.
Building Codes and Zoning
Classification of Building Codes:
These classifications will come from the hierarchy of building
codes which is; International, National, State, Parish, and City.
We will examine these codes from their respective divisions and
design our building within specifications. This is a very integral
part of our design process to make sure that the owners and
inhabitants of the building are safe and happy.
Zoning Codes:
Land Usage
Flood Zones
Commercial Zoning
Zoning:
Our structure is considered commercial so we will have to find land
that is zoned for commercial use. We will also take into
consideration the flood history of the area and the possible flood
zones and codes. These will help us make the most responsible
decision and use of our clients’ money and time.
International Building Codes (IBC):
· Electrical
· 2701.1 Scope. This chapter governs the electrical components,
equipment and systems used in buildings and structures covered by
this code. Electrical components, equipment and systems shall be
designed and constructed in accordance with the provisions of NFPA
70
· 2702.1 Installation. Emergency and standby power systems required
by this code or the International Fire Code shall be installed in
accordance with this code, NFPA 110 and 111
· 2702.2 Where required Emergency and standby power systems shall
be provided where required by Sections 2702.2.1 through
2702.20
· 2702.2.3 Exit Signs. Emergency power shall be provided for exit
signs in accordance with section 1011.6.3
· 2702.2.4 Means of egress illumination. Emergency power shall be
provided for means f egress illumination in accordance with section
1006.3
· 2702.3 Maintenance. Emergency and standby power systems shall be
maintained and tested in accordance with the International Fire
Code.
· Building
· 501.1 Scope. The provisions of this chapter control the height
and area of structures hereafter erected and additions to existing
structures. [F] 501.2 Address identification. New and existing
buildings shall be provided with approved address numbers or
letters. Each character shall be not less than 4 inches (102 mm) in
height and not less than 0.5 inch (12.7 mm) in width. They shall be
installed on a contrasting background and be plainly visible from
the street or road fronting the property. When required by the fire
code official, address numbers shall be provided in additional
approved locations to facilitate emergency response. Where access
is by means of a private road and the building address cannot be
viewed from the public way, a monument, pole or other approved sign
or means shall be used to identify the structure. Address numbers
shall be maintained.
· 503.1 General. The building height and area shall not exceed the
limits specified in Table 503 based on the type of construction as
determined by Section 602 and the occupancies as determined by
Section 302 except as modified hereafter. Each portion of a
building separated by one or more fire walls complying with Section
706 shall be considered to be a separate building.
· 504.1 General. The building height permitted by Table 503 shall
be increased in accordance with Sections 504.2 and 504.3.
· 504.2 Automatic sprinkler system increase. Where a building is
equipped throughout with an approved automatic sprinkler system in
accordance with Section 903.3.1.1, the value specified in Table 503
for maximum building height is increased by 20 feet (6096 mm) and
the maximum number of stories is increased by one. These increases
are permitted in addition to the building area increase in
accordance with Sections 506.2 and 506.3. For Group R buildings
equipped throughout with an approved automatic sprinkler system in
accordance with Section 903.3.1.2, the value specified in Table 503
for maximum building height is increased by 20 feet (6096 mm) and
the maximum number of stories is increased by one, but shall not
exceed 60 feet (18 288 mm) or four stories, respectively.
· 506.1 General. The building areas limited by Table 503 shall be
permitted to be increased due to frontage (If) and automatic
sprinkler system protection (Is) in accordance with Equation 5-1:
Aa = {At + [At × If] + [At × Is]} (Equation 5-1) where: Aa =
Allowable building area per story (square feet). At = Tabular
building area per story in accordance with Table 503 (square feet).
If = Area increase factor due to frontage as calculated in
accordance with Section 506.2. Is = Area increase factor due to
sprinkler protection as calculated in accordance with Section
506.3.
· 506.2 Frontage increase. Every building shall adjoin or have
access to a public way to receive a building area increase for
frontage. Where a building has more than 25 percent of its
perimeter on a public way or open space having a width of not less
than 20 feet (6096 mm), the frontage increase shall be determined
in accordance with Equation 5-2: If = [F/P - 0.25]W/30 (Equation
5-2) where: If = Area increase due to frontage. F = Building
perimeter that fronts on a public way or open space having 20 feet
(6096 mm) open minimum width (feet). P = Perimeter of entire
building (feet). W = Width of public way or open space (feet) in
accordance with Section 506.2.1.
· 506.2.1 Width limits. To apply this section the value of W shall
be not less than 20 feet (6096 mm). Where the value of W varies
along the perimeter of the building, the calculation performed in
accordance with Equation 5-2 shall be based on the weighted average
calculated in accordance with Equation 5-3 for portions of the
exterior perimeter walls where the value of W is greater than or
equal to 20 feet (6096 mm). Where the value of W is greater than 30
feet (9144 mm), a value of 30 feet (9144 mm) shall be used in
calculating the weighted average, regardless of the actual width of
the open space. W shall be measured perpendicular from the face of
the building to the closest interior lot line. Where the building
fronts on a public way, the entire width of the public way shall be
used. Where two or more buildings are on the same lot, W shall be
measured from the exterior face of each building to the opposing
exterior face of each adjacent building, as applicable. Weighted
average W = (L1 × w1 + L2 × w2 + L3 × w3…)/F. (Equation 5-3) where:
Ln = Length of a portion of the exterior perimeter wall. wn = Width
of open space associated with that portion of the exterior
perimeter wall. F = Building perimeter that fronts on a public way
or open space having a width of 20 feet (6096 mm) or more.
· 506.2.2 Open space limits. Such open space shall be either on the
same lot or dedicated for public use and shall be accessed from a
street or approved fire lane.
· 506.3 Automatic sprinkler system increase. Where a building is
equipped throughout with an approved automatic sprinkler system in
accordance with Section 903.3.1.1, the building area limitation in
Table 503 is permitted to be increased by an additional 200 percent
(Is = 2) for buildings with more than one story above grade plane
and an additional 300 percent (Is = 3) for buildings with no more
than one story above grade plane. These increases are permitted in
addition to the height and story increases in accordance with
Section 504.2.
· 506.2.2 Open space limits. Such open space shall be either on the
same lot or dedicated for public use and shall be accessed from a
street or approved fire lane. 506.3 Automatic sprinkler system
increase. Where a building is equipped throughout with an approved
automatic sprinkler system in accordance with Section 903.3.1.1,
the building area limitation in Table 503 is permitted to be
increased by an additional 200 percent (Is = 2) for buildings with
more than one story above grade plane and an additional 300 percent
(Is = 3) for buildings with no more than one story above grade
plane. These increases are permitted in addition to the height and
story increases in accordance with Section 504.2.
· 507.3.1 Mixed occupancy buildings with Groups A-1 and A-2. Group
A-1 and A-2 occupancies of other than Type V construction shall be
permitted within mixed occupancy buildings of unlimited area
complying with Section 507.3, provided:
· 1. Group A-1 and A-2 occupancies are separated from other
occupancies as required for separated occupancies in Section
508.4.4 with no reduction allowed in the fire-resistance rating of
the separation based upon the installation of an automatic
sprinkler system;
· 2. Each area of the portions of the building used for Group A-1
or A-2 occupancies shall not exceed the maximum allowable area
permitted for such occupancies in Section 503.1; and
· 3. Exit doors from Group A-1 and A-2 occupancies shall discharge
directly to the exterior of the building.
· 507.5 Reduced open space. The public ways or yards of 60 feet (18
288 mm) in width required in Sections 507.2, 507.3, 507.4, 507.6
and 507.11 shall be permitted to be reduced to not less than 40
feet (12 192 mm) in width provided all of the following
requirements are met:
· 1. The reduced width shall not be allowed for more than 75
percent of the perimeter of the building.
· 2. The exterior walls facing the reduced width shall have a
fire-resistance rating of not less than 3 hours.
· 3. Openings in the exterior walls facing the reduced width shall
have opening protectives with a fire protection rating of not less
than 3 hours.
· Plumbing (Chapter 29)
· [P] 2901.1 Scope. The provisions of this chapter and the
International Plumbing Code shall govern the erection,
installation, alteration, repairs, relocation, replacement,
addition to, use or maintenance of plumbing equipment and systems.
Toilet and bathing rooms shall be constructed in accordance with
Section 1210. Plumbing systems and equipment shall be constructed,
installed and maintained in accordance with the International
Plumbing Code. Private sewage disposal systems shall conform to the
International Private Sewage Disposal Code.
· [P] 2902.1 Minimum number of fixtures. Plumbing fixtures shall be
provided for the type of occupancy and in the minimum number shown
in Table 2902.1. Types of occupancies not shown in Table 2902.1
shall be considered individually by the building official. The
number of occupants shall be determined by this code. Occupancy
classification shall be determined in accordance with Chapter
3.
· [P] 2902.1.1 Fixture calculations. To determine the occupant load
of each sex, the total occupant load shall be divided in half. To
determine the required number of fixtures, the fixture ratio or
ratios for each fixture type shall be applied to the occupant load
of each sex in accordance with Table 2902.1. Fractional numbers
resulting from applying the fixture ratios of Table 2902.1 shall be
rounded up to the next whole number. For calculations involving
multiple occupancies, such fractional numbers for each occupancy
shall first be summed and then rounded up to the next whole
number.
· Exception: The total occupant load shall not be required to be
divided in half where approved statistical data indicate a
distribution of the sexes of other than 50 percent of each
sex.
· [P] 2902.1.2 Family or assisted-use toilet and bath fixtures.
Fixtures located within family or assisted-use toilet and bathing
rooms required by Section 1109.2.1 are permitted to be included in
the number of required fixtures for either the male or female
occupants in assembly and mercantile occupancies.
· [P] 2902.2 Separate facilities. Where plumbing fixtures are
required, separate facilities shall be provided for each sex.
· Exceptions:
· 1. Separate facilities shall not be required for dwelling units
and sleeping units.
· 2. Separate facilities shall not be required in structures or
tenant spaces with a total occupant load, including both employees
and customers, of 15 or less.
· 3. Separate facilities shall not be required in mercantile
occupancies in which the maximum occupant load is 100 or
less.
· [P] 2902.2.1 Family or assisted-use toilet facilities serving as
separate facilities. Where a building or tenant space requires a
separate toilet facility for each sex and each toilet facility is
required to have only one water closet, two family/assisted-use
toilet facilities shall be permitted to serve as the required
separate facilities. Family or assisted-use toilet facilities shall
not be required to be identified for exclusive use by either sex as
required by Section 2902.4.
· [P] 2902.4 Signage. Required public facilities shall be
designated by a legible sign for each sex. Signs shall be readily
visible and located near the entrance to each toilet facility.
Signs for accessible toilet facilities shall comply with Section
1110.
· [P] 2902.4.1 Directional signage. Directional signage indicating
the route to the public facilities shall be posted in accordance
with Section 3107. Such signage shall be located in a corridor or
aisle, at the entrance to the facilities for customers and
visitors.
· [P] 2902.5 Drinking fountain location. Drinking fountains shall
not be required to be located in individual tenant spaces provided
that public drinking fountains are located within a travel distance
of 500 feet of the most remote location in the tenant space and not
more than one story above or below the tenant space. Where the
tenant space is in a covered or open mall, such distance shall not
exceed 300 feet. Drinking fountains shall be located on an
accessible route.
· Mechanical
· 2801.1 Scope. Mechanical appliances, equipment and systems shall
be constructed, installed and maintained in accordance with the
International Mechanical Code and the International Fuel Gas Code.
Masonry chimneys, fireplaces and barbecues shall comply with the
International Mechanical Code and Chapter 21 of this code.
· Fire
· 901.1 Scope. The provisions of this chapter shall specify where
fire protection systems are required and shall apply to the design,
installation and operation of fire protection systems.
· 901.2 Fire protection systems. Fire protection systems shall be
installed, repaired, operated and maintained in accordance with
this code and the International Fire Code. Any fire protection
system for which an exception or reduction to the provisions of
this code has been granted shall be considered to be a required
system.
· Exception: Any fire protection system or portion thereof not
required by this code shall be permitted to be installed for
partial or complete protection provided that such system meets the
requirements of this code.
· 901.3 Modifications. No person shall remove or modify any fire
protection system installed or maintained under the provisions of
this code or the International Fire Code without approval by the
building official.
· 901.4 Threads. Threads provided for fire department connections
to sprinkler systems, standpipes, yard hydrants or any other fire
hose connection shall be compatible with the connections used by
the local fire department.
· 901.5 Acceptance tests. Fire protection systems shall be tested
in accordance with the requirements of this code and the
International Fire Code. When required, the tests shall be
conducted in the presence of the building official. Tests required
by this code, the International Fire Code and the standards listed
in this code shall be conducted at the expense of the owner or the
owner's representative. It shall be unlawful to occupy portions of
a structure until the required fire protection systems within that
portion of the structure have been tested and approved.
· 901.6 Supervisory service. Where required, fire protection
systems shall be monitored by an approved supervising station in
accordance with NFPA 72.
· 901.6.1 Automatic sprinkler systems. Automatic sprinkler systems
shall be monitored by an approved supervising station.
· Exceptions:
· 1. A supervising station is not required for automatic sprinkler
systems protecting one- and twofamily dwellings.
· 2. Limited area systems serving fewer than 20 sprinklers.
· 901.6.2 Fire alarm systems. Fire alarm systems required by the
provisions of Section 907.2 of this code and Sections 907.2 and
907.9 of the International Fire Code shallbe monitored by an
approved supervising station in accordance with Section
907.6.5.
· Exceptions:
· 1. Single- and multiple-station smoke alarms required by Section
907.2.11.
· 2. Smoke detectors in Group I-3 occupancies.
· 3. Supervisory service is not required for automatic sprinkler
systems in one- and two-family dwellings.
· 901.7 Fire areas. Where buildings, or portions thereof, are
divided into fire areas so as not to exceed the limits established
for requiring a fire protection system in accordance with this
chapter, such fire areas shall be separated by fire barriers
constructed in accordance with Section 707 or horizontal assemblies
constructed in accordance with Section 711, or both, having a
fire-resistance rating of not less than that determined in
accordance with Section 707.3.10.
· [F] 901.8 Pump and riser room size. Fire pump and automatic
sprinkler system riser rooms shall be designed with adequate space
for all equipment necessary for the installation, as defined by the
manufacturer, with sufficient working room around the stationary
equipment. Clearances around equipment to elements of permanent
construction, including other installed equipment and appliances,
shall be sufficient to allow inspection, service, repair or
replacement without removing such elements of permanent
construction or disabling the function of a required
fire-resistance-rated assembly. Fire pump and automatic sprinkler
system riser rooms shall be provided with a door(s) and
unobstructed passageway large enough to allow removal of the
largest piece of equipment.
· [F] 903.1 General. Automatic sprinkler systems shall comply with
this section.
· [F] 903.1.1 Alternative protection. Alternative automatic
fire-extinguishing systems complying with Section 904 shall be
permitted in lieu of automatic sprinkler protection where
recognized by the applicable standard and approved by the fire code
official.
· [F] 903.2 Where required. Approved automatic sprinkler systems in
new buildings and structures shall be provided in the locations
described in Sections 903.2.1 through 903.2.12.
· [F] 903.2.1 Group A. An automatic sprinkler system shall be
provided throughout buildings and portions thereof used as Group A
occupancies as provided in this section. For Group A-1, A-2, A-3
and A-4 occupancies, the automatic sprinkler system shall be
provided throughout the floor area where the Group A-1, A-2, A-3 or
A-4 occupancy is located, and in all floors from the Group A
occupancy to, and including, the nearest level of exit discharge
serving the Group A occupancy. For Group A-5 occupancies, the
automatic sprinkler system shall be provided in the spaces
indicated in Section 903.2.1.5.
· [F] 903.2.1.3 Group A-3. An automatic sprinkler system shall be
provided for Group A-3 occupancies where one of the following
conditions exists:
· 1. The fire area exceeds 12,000 square feet (1115 m2);
· 2. The fire area has an occupant load of 300 or more; or
· 3. The fire area is located on a floor other than a level of exit
discharge serving such occupancies.
· [F] 903.3 Installation requirements. Automatic sprinkler systems
shall be designed and installed in accordance with Sections 903.3.1
through 903.3.6.
· [F] 903.3.1 Standards. Sprinkler systems shall be designed and
installed in accordance with Section 903.3.1.1 unless otherwise
permitted by Sections 903.3.1.2 and 903.3.1.3 and other chapters of
this code, as applicable.
· [F] 903.3.4 Actuation. Automatic sprinkler systems shall be
automatically actuated unless specifically provided for in this
code.
· [F] 903.3.5 Water supplies. Water supplies for automatic
sprinkler systems shall comply with this section and the standards
referenced in Section 903.3.1. The potable water supply shall be
protected against backflow in accordance with the requirements of
this section and the International Plumbing Code.
· [F] 903.3.5.2 Secondary water supply. An automatic secondary
on-site water supply having a capacity not less than the
hydraulically calculated sprinkler demand, including the hose
stream requirement, shall be provided for high-rise buildings
assigned to Seismic Design Category C, D, E or F as determined by
the International Building Code. An additional fire pump shall not
be required for the secondary water supply unless needed to provide
the minimum design intake pressure at the suction side of the fire
pump supplying the automatic sprinkler system. The secondary water
supply shall have a duration of not less than 30 minutes
· as determined by the occupancy hazard classification in
accordance with NFPA 13.
· [F] 903.4 Sprinkler system supervision and alarms. All valves
controlling the water supply for automatic sprinkler systems,
pumps, tanks, water levels and temperatures, critical air pressures
and waterflow switches on all sprinkler systems shall be
electrically supervised by a listed fire alarm control unit.
· Exceptions:
· 1. Automatic sprinkler systems protecting one- and two-family
dwellings.
· 2. Limited area systems serving fewer than 20 sprinklers.
· 3. Automatic sprinkler systems installed in accordance with NFPA
13R where a common supply main is used to supply both domestic
water and the automatic sprinkler system, and a separate shutoff
valve for the automatic sprinkler system is not provided.
· 4. Jockey pump control valves that are sealed or locked in the
open position.
· 5. Control valves to commercial kitchen hoods, paint spray booths
or dip tanks that are sealed or locked in the open position.
· 6. Valves controlling the fuel supply to fire pump engines that
are sealed or locked in the open position.
· 7. Trim valves to pressure switches in dry, preaction and deluge
sprinkler systems that are sealed or locked in the open
position.
· [F] 903.4.1 Monitoring. Alarm, supervisory and trouble signals
shall be distinctly different and shall be automatically
transmitted to an approved supervising station or, when approved by
the fire code official, shall sound an audible signal at a
constantly attended location.
· Exceptions:
· 1. Underground key or hub valves in roadway boxes provided by the
municipality or public utility are not required to be
monitored.
· 2. Backflow prevention device test valves located in limited area
sprinkler system supply piping shall be locked in the open
position.In occupancies required to be equipped with a fire alarm
system, the backflow preventer valves shall be electrically
supervised by a tamper switch installed in accordance with NFPA 72
and separately annunciated.
· [F] 903.4.2 Alarms. An approved audible device, located on the
exterior of the building in an approved location, shall be
connected to each automatic sprinkler system. Such sprinkler
water-flow alarm devices shall be activated by water flow
equivalent to the flow of a single sprinkler of the smallest
orifice size installed in the system. Where a fire alarm system is
installed, actuation of the automatic sprinkler system shall
actuate the building fire alarm system.
· [F] 904.1 General. Automatic fire-extinguishing systems, other
than automatic sprinkler systems, shall be designed, installed,
inspected, tested and maintained in accordance with the provisions
of this section and the applicable referenced standards.
· [F] 904.2 Where required. Automatic fire-extinguishing systems
installed as an alternative to the required automatic sprinkler
systems of Section 903 shall be approved by the fire code official.
Automatic fire-extinguishing systems shall not be considered
alternatives for the purposes of exceptions or reductions allowed
by other requirements of this code.
· [F] 904.3 Installation. Automatic fire-extinguishing systems
shall be installed in accordance with this section.
· [F] 904.3.1 Electrical wiring. Electrical wiring shall be in
accordance with NFPA 70.
· [F] 904.3.2 Actuation. Automatic fire-extinguishing systems shall
be automatically actuated and provided with a manual means of
actuation in accordance with Section 904.11.1. Where more than one
hazard could be simultaneously involved in fire due to their
proximity, all hazards shall be protected by a single system
designed to protect all hazards that could become involved.
· Exception: Multiple systems shall be permitted to be installed if
they are designed to operate simultaneously.
· [F] 904.3.3 System interlocking. Automatic equipment interlocks
with fuel shutoffs, ventilation controls, door closers, window
shutters, conveyor openings, smoke and heat vents and other
features necessary for proper operation of the fire-extinguishing
system shall be provided as required by the design and installation
standard utilized for the hazard.
· [F] 904.3.4 Alarms and warning signs. Where alarms are required
to indicate the operation of automatic fire-extinguishing systems,
distinctive audible and visible alarms and warning signs shall be
provided to warn of pending agent discharge. Where exposure to
automatic-extinguishing agents poses a hazard to persons and a
delay is required to ensure the evacuation of occupants before
agent discharge, a separate warning signal shall be provided to
alert occupants once agent discharge has begun. Audible signals
shall be in accordance with Section 907.5.2.
· [F] 904.3.5 Monitoring. Where a building fire alarm system is
installed, automatic fire-extinguishing systems shall be monitored
by the building fire alarm system in accordance with NFPA 72.
· [F] 904.4 Inspection and testing. Automatic fire-extinguishing
systems shall be inspected and tested in accordance with the
provisions of this section prior to acceptance.
· [F] 904.4.1 Inspection. Prior to conducting final acceptance
tests, the following items shall be inspected:
· 1. Hazard specification for consistency with design hazard.
· 2. Type, location and spacing of automatic- and manual-initiating
devices.
· 3. Size, placement and position of nozzles or discharge
orifices.
· 4. Location and identification of audible and visible alarm
devices.
· 5. Identification of devices with proper designations.
· 6. Operating instructions.
· [F] 904.4.2 Alarm testing. Notification appliances, connections
to fire alarm systems and connections to approved supervising
stations shall be tested in accordance with this section and
Section 907 to verify proper operation.
· [F] 904.4.2.1 Audible and visible signals. The audibility and
visibility of notification appliances signaling agent discharge or
system operation, where required, shall be verified.
· [F] 904.4.3 Monitor testing. Connections to protected premises
and supervising station fire alarm systems shall be tested to
verify proper identification and retransmission of alarms from
automatic fire-extinguishing systems.
· [F] 906.1 Where required. Portable fire extinguishers shall be
installed in the following locations.
· 1. In Group A, B, E, F, H, I, M, R-1, R-2, R-4 and S
occupancies.
· Exception: In Group R-2 occupancies, portable fire extinguishers
shall be required only in locations specified in Items 2 through 6
where each dwelling unit is provided with a portable fire
extinguisher having a minimum rating of 1-A:10-B:C.
· 2. Within 30 feet (9144 mm) of commercial cooking
equipment.
· 3. In areas where flammable or combustible liquids are stored,
used or dispensed.
· 4. On each floor of structures under construction, except Group
R-3 occupancies, in accordance with Section 3315.1 of the
International Fire Code.
· 5. Where required by the International Fire Code sections
indicated in Table 906.1.
· 6. Special-hazard areas, including but not limited to
laboratories, computer rooms and generator rooms, where required by
the fire code official.
· [F] 906.3 Size and distribution. The size and distribution of
portable fire extinguishers shall be in accordance with Sections
906.3.1 through 906.3.4.
· [F] 906.3.1 Class A fire hazards. The minimum sizes and
distribution of portable fire extinguishers for occupancies that
involve primarily Class A fire hazards shall comply with Table
906.3(1).
· [F] 906.5 Conspicuous location. Portable fire extinguishers shall
be located in conspicuous locations where they will be readily
accessible and immediately available for use. These locations shall
be along normal paths of travel, unless the fire code official
determines that the hazard posed indicates the need for placement
away from normal paths of travel.
· [F] 906.6 Unobstructed and unobscured. Portable fire
extinguishers shall not be obstructed or obscured from view. In
rooms or areas in which visual obstruction cannot be completely
avoided, means shall be provided to indicate the locations of
extinguishers.
· [F] 906.7 Hangers and brackets. Hand-held portable fire
extinguishers, not housed in cabinets, shall be installed on the
hangers or brackets supplied. Hangers or brackets shall be securely
anchored to the mounting surface in accordance with the
manufacturer's installation instructions.
· [F] 906.8 Cabinets. Cabinets used to house portable fire
extinguishers shall not be locked. Exceptions: 1. Where portable
fire extinguishers subject to malicious use or damage are provided
with a means of ready access. 2. In Group I-3 occupancies and in
mental health areas in Group I-2 occupancies, access to portable
fire extinguishers shall be permitted to be locked or to be located
in staff locations provided the staff has keys.
· [F] 906.9 Extinguisher installation. The installation of portable
fire extinguishers shall be in accordance with Sections 906.9.1
through 906.9.3.
· [F] 906.9.1 Extinguishers weighing 40 pounds or less. Portable
fire extinguishers having a gross weight not exceeding 40 pounds
(18 kg) shall be installed so that their tops are not more than 5
feet (1524 mm) above the floor.
· [F] 907.1 General. This section covers the application,
installation, performance and maintenance of fire alarm systems and
their components.
· [F] 907.1.1 Construction documents. Construction documents for
fire alarm systems shall be of sufficient clarity to indicate the
location, nature and extent of the work proposed and show in detail
that it will conform to the provisions of this code, the
International Fire Code, and relevant laws, ordinances, rules and
regulations, as determined by the fire code official.
· [F] 907.1.2 Fire alarm shop drawings. Shop drawings for fire
alarm systems shall be submitted for review and approval prior to
system installation, and shall include, but not be limited to, all
of the following:
· `1. A floor plan that indicates the use of all rooms.
· 2. Locations of alarm-initiating devices.
· 3. Locations of alarm notification appliances, including candela
ratings for visible alarm notification appliances.
· 4. Location of fire alarm control unit, transponders and
notification power supplies.
· 5. Annunciators.
· 9. Voltage drop calculations.
· 10. Manufacturers’ data sheets indicating model numbers and
listing information for equipment, devices and materials.
· 11. Details of ceiling height and construction.
· 12. The interface of fire safety control functions.
· 13. Classification of the supervising station.
· [F] 907.1.3 Equipment. Systems and components shall be listed and
approved for the purpose for which they are installed.
· [F] 907.2 Where required—new buildings and structures. An
approved fire alarm system installed in accordance with the
provisions of this code and NFPA 72 shall be provided in new
buildings and structures in accordance with Sections 907.2.1
through 907.2.23 and provide occupant notification in accordance
with Section 907.5, unless other requirements are provided by
another section of this code. A minimum of one manual fire alarm
box shall be provided in an approved location to initiate a fire
alarm signal for fire alarm systems employing automatic fire
detectors or waterflow detection devices. Where other sections of
this code allow elimination of fire alarm boxes due to sprinklers,
a single fire alarm box shall be installed.
· Exceptions:
· 1. The manual fire alarm box is not required for fire alarm
systems dedicated to elevator recall control and supervisory
service.
· 2. The manual fire alarm box is not required for Group R-2
occupancies unless required by the fire code official to provide a
means for fire watch personnel to initiate an alarm during a
sprinkler system impairment event. Where provided, the manual fire
alarm box shall not be located in an area that is accessible to the
public.
· [F] 907.2.1 Group A. A manual fire alarm system that activates
the occupant notification system in accordance with Section 907.5
shall be installed in Group A occupancies where the occupant load
due to the assembly occupancy is 300 or more. Group A occupancies
not separated from one another in accordance with Section 707.3.9
shall be considered as a single occupancy for the purposes of
applying this section. Portions of Group E occupancies occupied for
assembly purposes shall be provided with a fire alarm system as
required for the Group E occupancy.
· Exception: Manual fire alarm boxes are not required where the
building is equipped throughout with an automatic sprinkler system
installed in accordance with Section 903.3.1.1 and the occupant
notification appliances will activate throughout the notification
zones upon sprinkler waterflow.
· [F] 907.3 Fire safety functions. Automatic fire detectors
utilized for the purpose of performing fire safety functions shall
be connected to the building's fire alarm control unit where a fire
alarm system is required by Section 907.2. Detectors shall, upon
actuation, perform the intended function and activate the alarm
notification appliances or activate a visible and audible
supervisory signal at a constantly attended location. In buildings
not equipped with a fire alarm system, the automatic fire detector
shall be powered by normal electrical service and, upon actuation,
perform the intended function. The detectors shall be located in
accordance with NFPA 72.
· [F] 907.3.1 Duct smoke detectors. Smoke detectors installed in
ducts shall be listed for the air velocity, temperature and
humidity present in the duct. Duct smoke detectors shall be
connected to the building's fire alarm control unit when a fire
alarm system is required by Section 907.2. Activation of a duct
smoke detector shall initiate a visible and audible supervisory
signal at a constantly attended location and shall perform the
intended fire safety function in accordance with this code and the
International Mechanical Code. Duct smoke detectors shall not be
used as a substitute for required open area detection.
· Exceptions:
· 1. The supervisory signal at a constantly attended location is
not required where duct smoke detectors activate the building's
alarm notification appliances.
· 2. In occupancies not required to be equipped with a fire alarm
system, actuation of a smoke detector shall activate a visible and
an audible signal in an approved location. Smoke detector trouble
conditions shall activate a visible or audible signal in an
approved location and shall be identified as air duct detector
trouble.
· [F] 907.3.2 Delayed egress locks. Where delayed egress locks are
installed on means of egress doors in accordance with Section
1008.1.9.7, an automatic smoke or heat detection system shall be
installed as required by that section.
· [F] 907.4 Initiating devices. Where manual or automatic alarm
initiation is required as part of a fire alarm system, the
initiating devices shall be installed in accordance with Sections
907.4.1 through 907.4.3.1.
· [F] 907.4.1 Protection of fire alarm control unit. In areas that
are not continuously occupied, a single smoke detector shall be
provided at the location of each fire alarm control unit,
notification appliance circuit power extenders, and supervising
station transmitting equipment.
· Exception: Where ambient conditions prohibit installation of a
smoke detector, a heat detector shall be permitted.
· [F] 907.4.2 Manual fire alarm boxes. Where a manual fire alarm
system is required by another section of this code, it shall be
activated by fire alarm boxes installed in accordance with Sections
907.4.2.1 through 907.4.2.6.
· [F] 907.4.2.1 Location. Manual fire alarm boxes shall be located
not more than 5 feet (1524 mm) from the entrance to each exit.
Additional manual fire alarm boxes shall be located so that travel
distance to the nearest box does not exceed 200 feet (60 960
mm).
· [F] 907.4.2.2 Height. The height of the manual fire alarm boxes
shall be a minimum of 42 inches (1067 mm) and a maximum of 48
inches (1372 mm) measured vertically, from the floor level to the
activating handle or lever of the box.
· [F] 907.4.2.3 Color. Manual fire alarm boxes shall be red in
color.
· [F] 907.4.2.4 Signs. Where fire alarm systems are not monitored
by a supervising station, an approved permanent sign shall be
installed adjacent to each manual fire alarm box that reads: WHEN
ALARM SOUNDS CALL FIRE DEPARTMENT.
· Exception: Where the manufacturer has permanently provided this
information on the manual fire alarm box.
· [F] 907.4.2.5 Protective covers. The fire code official is
authorized to require the installation of listed manual fire alarm
box protective covers to prevent malicious false alarms or to
provide the manual fire alarm box with protection from physical
damage. The protective cover shall be transparent or red in color
with a transparent face to permit visibility of the manual fire
alarm box. Each cover shall include proper operating instructions.
A protective cover that emits a local alarm signal shall not be
installed unless approved. Protective covers shall not project more
than that permitted by Section 1003.3.3.
· [F] 907.4.2.6 Unobstructed and unobscured. Manual fire alarm
boxes shall be accessible, unobstructed, unobscured and visible at
all times.
· [F] 907.4.3 Automatic smoke detection. Where an automatic smoke
detection system is required it shall utilize smoke detectors
unless ambient conditions prohibit such an installation. In spaces
where smoke detectors cannot be utilized due to ambient conditions,
approved automatic heat detectors shall be permitted.
· [F] 907.4.3.1 Automatic sprinkler system. For conditions other
than specific fire safety functions noted in Section 907.3, in
areas where ambient conditions prohibit the installation of smoke
detectors, an automatic sprinkler system installed in such areas in
accordance with Section 903.3.1.1 or 903.3.1.2 and that is
connected to the fire alarm system shall be approved as automatic
heat detection.
· [F] 907.5 Occupant notification systems. A fire alarm system
shall annunciate at the fire alarm control unit and shall initiate
occupant notification upon activation, in accordance with Sections
907.5.1 through 907.5.2.3.4. Where a fire alarm system is required
by another section of this code, it shall be activated by:
· 1. Automatic fire detectors.
· 3. Manual fire alarm boxes.
· 4. Automatic fire-extinguishing systems.
· Exception: Where notification systems are allowed elsewhere in
Section 907 to annunciate at a constantly attended location.
· [F] 907.5.1 Presignal feature. A presignal feature shall not be
installed unless approved by the fire code official and the fire
department. Where a presignal feature is provided, a signal shall
be annunciated at a constantly attended location approved by the
fire department, in order that occupant notification can be
activated in the event of fire or other emergency.
· [F] 907.5.2 Alarm notification appliances. Alarm notification
appliances shall be provided and shall be listed for their
purpose.
· [F] 907.5.2.1 Audible alarms. Audible alarm notification
appliances shall be provided and emit a distinctive sound that is
not to be used for any purpose other than that of a fire
alarm.
· Exceptions:
· 1. Visible alarm notification appliances shall be allowed in lieu
of audible alarm notification appliances in critical care areas of
Group I-2 occupancies.
· 2. Where provided, audible notification appliances located in
each occupant evacuation elevator lobby in accordance with Section
3008.5.1 shall be connected to a separate notification zone for
manual paging only.
· [F] 907.5.2.1.1 Average sound pressure. The audible alarm
notification appliances shall provide a sound pressure level of 15
decibels (dBA) above the average ambient sound level or 5 dBA above
the maximum sound level having a duration of at least 60 seconds,
whichever is greater, in every occupiable space within the
building.
· [F] 907.5.2.1.2 Maximum sound pressure. The maximum sound
pressure level for audible alarm notification appliances shall be
110 dBA at the minimum hearing distance from the audible appliance.
Where the average ambient noise is greater than 95 dBA, visible
alarm notification appliances shall be provided in accordance with
NFPA 72 and audible alarm notification appliances shall not be
required.
· [F] 907.5.2.2 Emergency voice/alarm communication systems.
Emergency voice/alarm communication systems required by this code
shall be designed and installed in accordance with NFPA 72. The
operation of any automatic fire detector, sprinkler waterflow
device or manual fire alarm box shall automatically sound an alert
tone followed by voice instructions giving approved information and
directions for a general or staged evacuation in accordance with
the building's fire safety and evacuation plans required by Section
404 of the International Fire Code. In high-rise buildings, the
system shall operate on a minimum of the alarming floor, the floor
above and the floor below. Speakers shall be provided throughout
the building by paging zones. At a minimum, paging zones shall be
provided as follows:
· 1. Elevator groups.
· 2. Exit stairways.
· 3. Each floor.
· 4. Areas of refuge as defined in Section 1002.1.
· [F] 907.5.2.2.1 Manual override. A manual override for emergency
voice communication shall be provided on a selective and all-call
basis for all paging zones.
· [F] 907.5.2.2.2 Live voice messages. The emergency voice/alarm
communication system shall also have the capability to broadcast
live voice messages by paging zones on a selective and all-call
basis.
· [F] 907.5.2.2.3 Alternate uses. The emergency voice/alarm
communication system shall be allowed to be used for other
announcements, provided the manual fire alarm use takes precedence
over any other use.
· [F] 907.5.2.2.4 Emergency voice/alarm communication captions.
Where stadiums, arenas and grandstands are required to caption
audible public announcements in accordance with Section 1108.2.7.2,
the emergency/voice alarm communication system shall also be
captioned. Prerecorded or live emergency captions shall be from an
approved location constantly attended by personnel trained to
respond to an emergency.
· [F] 907.5.2.2.5 Emergency power. Emergency voice/alarm
communications systems shall be provided with an approved emergency
power source.
· [F] 907.5.2.3 Visible alarms. Visible alarm notification
appliances shall be provided in accordance with Sections
907.5.2.3.1 through 907.5.2.3.4.
· Exceptions:
· 1. Visible alarm notification appliances are not required in
alterations, except where an existing fire alarm system is upgraded
or replaced, or a new fire alarm system is installed.
· 2. Visible alarm notification appliances shall not be required in
exits as defined in Section 1002.1.
· 3. Visible alarm notification appliances shall not be required in
elevator cars.
· [F] 907.5.2.3.1 Public and common areas. Visible alarm
notification appliances shall be provided in public areas and
common areas.
· [F] 907.6 Installation. A fire alarm system shall be installed in
accordance with this section and NFPA 72.
· [F] 907.6.1 Wiring. Wiring shall comply with the requirements of
NFPA 70 and NFPA 72. Wireless protection systems utilizing
radio-frequency transmitting devices shall comply with the special
requirements for supervision of low-power wireless systems in NFPA
72.
· [F] 907.6.2 Power supply. The primary and secondary power supply
for the fire alarm system shall be provided in accordance with NFPA
72.
· Exception: Back-up power for single-station and multiple-station
smoke alarms as required in Section 907.2.11.4.
· [F] 907.6.3 Zones. Each floor shall be zoned separately and a
zone shall not exceed 22,500 square feet (2090 m2). The length of
any zone shall not exceed 300 feet (91 440 mm) in any
direction.
· Exception: Automatic sprinkler system zones shall not exceed the
area permitted by NFPA 13.
· [F] 907.6.3.1 Zoning indicator panel. A zoning indicator panel
and the associated controls shall be provided in an approved
location. The visual zone indication shall lock in until the system
is reset and shall not be canceled by the operation of an
audiblealarm silencing switch.
· [F] 907.6.3.2 High-rise buildings. In high-rise buildings, a
separate zone by floor shall be provided for each of the following
types of alarm-initiating devices where provided:
· 1. Smoke detectors.
· 3. Manual fire alarm boxes.
· 4. Other approved types of automatic fire detection devices or
suppression systems.
· [F] 907.6.4 Access. Access shall be provided to each fire alarm
device and notification appliance for periodic inspection,
maintenance and testing.
· [F] 907.6.5 Monitoring. Fire alarm systems required by this
chapter or by the International Fire Code shall be monitored by an
approved supervising station in accordance with NFPA 72.
· Exception: Monitoring by a supervising station is not required
for:
· 1. Single- and multiple-station smoke alarms required by Section
907.2.11.
· 2. Smoke detectors in Group I-3 occupancies.
· 3. Automatic sprinkler systems in one- and twofamily
dwellings.
· [F] 907.6.5.1 Automatic telephone-dialing devices. Automatic
telephone-dialing devices used to transmit an emergency alarm shall
not be connected to any fire department telephone number unless
approved by the fire chief.
· [F] 907.6.5.2 Termination of monitoring service. Termination of
fire alarm monitoring services shall be in accordance with Section
901.9 of the International Fire Code.
· [F] 907.7 Acceptance tests and completion. Upon completion of the
installation, the fire alarm system and all fire alarm components
shall be tested in accordance with NFPA 72.
· [F] 907.7.1 Single- and multiple-station alarm devices. When the
installation of the alarm devices is complete, each device and
interconnecting wiring for multiple-station alarm devices shall be
tested in accordance with the smoke alarm provisions of NFPA
72.
· [F] 907.7.2 Record of completion. A record of completion in
accordance with NFPA 72 verifying that the system has been
installed and tested in accordance with the approved plans and
specifications shall be provided.
· [F] 907.7.3 Instructions. Operating, testing and maintenance
instructions and record drawings (“as-builts”) and equipment
specifications shall be provided at an approved location.
· [F] 907.8 Inspection, testing and maintenance. The maintenance
and testing schedules and procedures for fire alarm and fire
detection systems shall be in accordance with Section 907.8 of the
International Fire Code.
· Use and Occupancy Classification
· 302.1 General. Structures or portions of structures shall be
classified with respect to occupancy in one or more of the groups
listed in this section. A room or space that is intended to be
occupied at different times for different purposes shall comply
with all of the requirements that are applicable to each of the
purposes for which the room or space will be occupied. Structures
with multiple occupancies or uses shall comply with section 508.
Where a structure is proposed for a purpose that is not
specifically provided for in this code, such structure shall be
classified in the group that the occupancy most nearly resembles,
according to the fire safety and relative hazard involved.303.1
Assembly Group A. Assembly Group A occupancy includes, among
others, the use of a building or structure, or a portion thereof,
for the gathering of persons for purposes such as civic, social or
religious functions; recreation, food or drink consumption or
awaiting transportation.
· 303.4 Assembly Group A-3. Assembly uses intended for worship,
recreation or amusement and other assembly uses not classified
elsewhere in Group A including, but not limited to: Amusement
arcades, Art galleries, Bowling alleys, Community halls,
Courtrooms, Dance halls (not including food or drink consumption),
exhibition halls, funeral parlors, gymnasiums (without spectator
seating), Indoor swimming pools (without spectator seating), Indoor
tennis courts (without spectator seating) lecture halls, Libraries,
Museums, Places of religious worship, Pool and billiard parlors,
Waiting areas in transportation terminals
Louisiana Code Council:
(Amendments made to the IBC made by the council)
· A. International Building Code (IBC), 2015 Edition, not including
Chapter 1, Administration, Chapter 11, Accessibility, Chapter 27,
Electrical. The applicable standards referenced in that code are
included for regulation of construction within this state.
Furthermore, IBC shall be amended as follows and shall only apply
to the International Building Code.
· Fire
· b. Section 903.2.1.3, Group A-3
· i. Add Item Number (4). Open air pavilions on three sides or
more, not exceeding 12,000 square feet, shall not be required to
comply with 903.2.1.3(2) where each side has unobstructed access to
a public way (10’-0” wide by 10’-0” high). No fixed elements,
equipment, seating, etc. are permitted within the 10’-0” by 10’-0”
access.
· ii. Exception
· (a). The requirements of Sections 903.2.1.2(1) and 903.2.1.2(2)
shall not apply to a single multi-purpose room less than 12,000 sf
when all of the following conditions are met.
· (i). The single multi-purpose room shall not be used for display
or exhibition.
· (ii). The single multi-purpose room shall not share exit access
with other occupancies. Non-separated accessory uses that are
incidental or ancillary to the single multi-purpose room shall be
considered as part of the assembly occupancy. The accessory uses
shall not be limited to 10 percent of the single multi-purpose room
floor area and/or building, but shall be included and considered as
part of the limited assembly room floor area.
· (iii). The single multi-purpose room shall not be part of a fire
area containing other assembly occupancies.
· (iv). A single multi-purpose room with an occupant load greater
than 300 persons shall be provided with a fire alarm system in
accordance with 907.2.1.
· (v). The single multi-purpose room with its accessory or
ancillary uses shall be separated, when part of a multiple
occupancy, in accordance with Table 508.4 and Section 707 from the
remainder of the building. The single multi- purpose room fire area
containing the single multipurpose room and its accessory or
ancillary uses shall be less than 12,000 sf.
· (vi). Provide system smoke detection in all areas in accordance
with Section 907 throughout the entire building.
· Plumbing Systems
· a. Section 2901, Scope
· i. The provisions of this Chapter and the International Plumbing
Code shall govern the erection, installation, alteration, repairs,
relocation, replacement, addition to, use or maintenance of
plumbing equipment and systems. Toilet and bathing rooms shall be
constructed in accordance with Section 1210. Plumbing and equipment
shall be constructed, installed and maintained in accordance with
the International Plumbing Code.
· (a). Delete Private Sewage disposal systems shall conform to the
International Private Sewage Disposal Code.
· b. Delete Section 2902. AUTHORITY NOTE: Promulgated in accordance
with R.S. 40:1730.22(C) and (D) and 40:1730.26(1). HISTORICAL NOTE:
Promulgated by the Department of Public Safety and Corrections,
State Uniform Construction Code Council, LR 33:291 (February 2007),
amended LR 34:93 (January 2008), LR 34:883 (May 2008), LR 34:2205
(October 2008), LR 35:1904 (September 2009), LR 36:2574 (November
2010), effective January 1, 2011, LR 37:601 (February 2011), LR
37:913 (March 2011), repromulgated LR 37:2187 (July 2011),
repromulgated LR 37:2726 (September 2011), LR 37:3065 (October
2011), LR 38:1994 (August 2012), amended by the Department of
Public Safety and Corrections, Uniform Construction Code Council,
LR 39:1825 (July 2013), LR 39:2512 (September 2013), LR 40:2609
(December 2014), amended by the Department of Public Safety and
Corrections, Office of the State Fire Marshal, LR 41:2380 (November
2015), amended by the Department of Public Safety and Corrections,
Office of the State Fire Marshal, Uniform Construction Code
Council, LR 44:000 (January 2018).
Estimation of Materials Needed and Take Off
Estimation Process/Take Off:
The estimation and takeoff portion of our project will give us a
general view of how much material we will need and how much it
could cost. Some of the items included in a takeoff could include
the lumber for the wall studs and base (2x4s), lumber for the
ceilings and rafters which could range in size from 2x6s to 2x10s.
We will also need to take into fact that we will need some treated
lumber for when it is touching the ground or a wall that leads to
the outside. Foundation and footing materials including wire mesh,
wire chairs, rebar, and concrete. Some other items that are in a
construction takeoff are (but not limited to) blots, screws, nails,
insulation, windows, and doors.
Concrete
73.5 yd^3
56
Mesh
6" x 6" - #6 #6 Concrete Mesh---- 6' x 6' sheets
126 sheets
Rebar Ties
5 boxes
3 rolls
83' 4"
Granular Fill
73.5 yd^3
#3 x 1'-6" @ 18" o.c. (grease one end) @ all columns
247.5 ft^2
194
10.1 yd^3
36.91 yd^3
3.5 yd^3
1.7 yd^3
5
3
Concrete
.12 yd^3
2 - 5/8" Rebar in Boiler Room footing and 8' walls
13
1
2162 blocks
8 50lb bags
59
2 x 4 x 8 Metal Studs 16" on center
301
26
26
6
Columns
1
Stone
556 ft^2
298.75 ft^2
Face Brick on North and East side walls and Chimney
1258.4 ft^2
145.2 ft^2
35 anchors
At connection from High roof wall to low roof ceiling
72'-5"
219'-3"
4 boxes
Gypsum Board
166
78
Tape
31 sheets
46
287.5 ft
188' 5"
144' 10"
21
T2
10
1,123 ft^2
1,123 ft^2
144'-10"
Fascia
5
F1
12
Bridging
1
9
6
12 WF 27 with L - 4 x 4 x 5/16
1
Lintel 2
8 WF 17 with L- 4 x 3 1/2 x 5/16
2
3
1
6 WF 15.5 1/2 with 11 1/2 x 3/8 plate
2
8 WF 17 with L 4 x 3 x 5/16
1
Glass
5
Glass
6
Glass
6
Sill
38' 6"
1
Mirror
1
Toilets
5 (2 M, 3 W)
Hand Dryer
2( 1 in each)
Stalls
5 (2 M, 3 W)
Baffles
1 2'-10", 1 1"
1
10.1 ft^2
5 boxes
5 boxes
1
2
Nails
· 1.89 Acres
· 1.75 Acres
· 2.76 Acres
· Seller: Keller Williams
· Flood Zone: AE
Explanation of Locations:
We have chosen these locations because they all have multiple
access points. Meaning multiple roads that pass on the property
lines. This is going to be important with an occupancy of 250
because there will be a large amount of vehicles arriving and
leaving at around the same time. These locations all have pros and
cons. Over the next few weeks we will narrow these down into one
property that we think will be the best and most responsible choice
to acquire and build on.
Flood Zones:
All but, one of these locations is in a flood zone. But, two are in
good zones that will not have nearly as many potential occurrences
of floods. The property that is in a severe flood zone will need to
have its elevation raised a considerable amount and this will
factor into our decision for the choice of the best location.
Figure 15:
Figure 16:
Figure 17:
SITE SELECTION:
After doing an investigation on all three possible church site
locations we decided to go with 2410 West Church St. Hammond, LA
70401. We chose this location because the size of the property was
an adequate size for all the project’s needs. The price was also in
the proper range for the size in the location. The property is also
not in a known flood zone. Although the location is in a non-flood
zone, we still recommend flood insurance for the owner because
flood zones change all the time. The location is also in a great
area of Hammond surrounded by many different stores and restaurants
for the members to indulge in after services.
Scheduling
Scheduling:
There are various methods in creating a construction schedule such
as, Microsoft Project, Microsoft Visio, Microsoft excel, and even
Microsoft Word. With any easy search the manager can find the
software that suits them the best. In addition to the different
types of software you can use, there are also different methods you
can go about using to create the schedule. Some of the schedules
include the Gantt chart, flowchart, critical path method, and even
just a normal calendar, although not as effective. In the project
the Gantt chart seemed the most effective to us because it shows
how the project progresses and how the tasks overlap with other
tasks to see how many people on each task you need and also how
much time for each task to be completed. The Gantt chart is also
very easy for any employee, contractor, or client to pick up and
understand.
To be able to create the schedule you need to be able to identify
what tasks need to be completed and in which order they need to be
completed. In our schedule we included the foundation, layout
footings, install reinforcement, build block foundation, materials
delivered, waterproofing, rough carpentry, set steel, framing,
install windows and doors, concrete slabs, HVAC, facilities rough
in, roofing, finish exterior work, insulation, drywall, finish
floor, paint, exterior landscaping, install hardware, final punch
out and the project close out. The schedule is made up with extra
time for whenever unforeseen problems will inevitably occur.
LEED Certification
Purpose of LEED:
LEED is a program that was developed to determine and measure the
sustainability of a structure. It has become very popular overseas
and has risen in popularity in the United States in the past
decade. LEED utilizes a rating system to determine how successful
the designer and contractors are able to be sustainable in the
construction and everyday function of a structure. The
sustainability of the structure is important because it lowers the
cost over the lifetime of a building and can earn more return on
investment.
Benefits of LEED:
There are many benefits to using LEED. Having a LEED certification
of any level will automatically give your building recognition,
your building has faster lease up rates, your building has a better
and healthier indoor space, and it also helps lower your usage of
all the resources you use like energy and water. Probably the most
important benefit is it is better for building occupants, the
community, and the environment. Once you have a LEED certification,
you are established as a leader in Green building.
Certification:
Building Design
LEED Zero
LEED Zero:
LEED Zero is a type of certification that LEED gives out when a
building has a net zero goals in carbons and resources. LEED Zero
with our resources would include having our energy use a balance of
zero over a 12-month period, achieving a portable water use balance
of zero over 12 months, and having zero waste in waste which would
lower our carbon footprint. LEED Zero is looked highly upon and it
is the goal of all certified LEED projects around the world.
Key Areas:
Financial Aspects
We looked into the financial aspects of the project and how much it
will cost. Also we investigated how the aspects of a loan would
work out. We chose to go with the square footage method and
multiply our square footage of 4328ft^2 x $175 = $757,400. That
number combined with the cost of the land we came out with an
estimate of $1,312,400. We looked into what the aspects of a
commercial loan would look like and this is what we got.
Figure 18
The interest rate for a commercial loan commonly runs between 4% -
12%. You can pay the monthly note and pay it off in 30 years and
accrue all the interest or you can pay the full balloon payment in
5 years and eliminate a lot of the interest.
Reference
LEED green building certification. (n.d.). Retrieved from
https://new.usgbc.org/leed .
LEED minimum program requirements. (n.d.). Retrieved from
https://new.usgbc.org/minimum-program-requirements-leed
Membership. (n.d.). Retrieved from https://new.usgbc.org/membership
.
Omen, A. (2019, April 1). USGBC Embraces Legal Marijuana. Retrieved
from https://www.buildinggreen.com/leed .
Images From Google Images