Converter 8305-1 UK

Embed Size (px)

Citation preview

  • 7/26/2019 Converter 8305-1 UK

    1/4Page 1Design and specifications subject to change without notice

    Data Sheet 8305-1www.baumerprocess.com

    Description

    The 4...20 mA loop current is measured and converted into 0...20 mA

    or 0...10 V, respectively, depending on the type of converter.

    The conversion is based on internal voltage and resistance references.

    The signal converter can be used to convert a 4...20 mA signal into a

    0...20 mA current signal or a 0...10 V voltage signal.

    To minimize a possible voltage drop the converter must be located as

    close to the voltage receiver as possible, whereas for current signals

    large lengths of cables may be used.

    Signal Converter I/I or I/U

    Input: 4...20 mA

    Output: 0...20 mA or 0...10 VLoop powered

    Protected against incorrect connection

    Accuracy better than 0.25% f.r.

  • 7/26/2019 Converter 8305-1 UK

    2/4Page 2Design and specifications subject to change without notice

    Data Sheet 8305-1www.baumerprocess.com

    Technical Data

    Ordering Details - Signal Converter I/I or I/U

    82 42 - 31x

    Data Common for both Types

    Input data

    Protection +/- 24 Vdc

    Current limiting 100 mA

    Output dataAccuracy < 0.25% f.r.

    Temperature drift Typ. 0.005% f.r. per C

    Max. 0.01% f.r. per C

    Environmental conditions

    Operating temperature -10...60C

    Storage temperature -35...85C

    Humidity < 90% RH, non-condensing

    Vibrations Lloyds Register, test 1

    EMC data

    Immunity EN 50082-2Emission EN 50081-1

    Mechanical data

    Dimensions 62 x 88 x 24 mm

    DIN-rail mounting DIN 46277

    Protection class Housing: IP 30

    Terminals: IP 10

    Weight 0.1 kg

    Disposal of product and packing

    According to national laws or by returning to Baumer

    Input Output 7 digit

    4...20 mA 0...20 mA

    4...20 mA 0...10 V

    Signal Converter I/I

    Input data

    Signal type 4...20 mA, 2-wire

    Voltage drop 5.5 V (excl. voltage drop across the

    output)

    Output data

    Signal type 0...20 mA, 2-wire

    Load < 400 Ohm

    Signal Converter I/U

    Input data

    Input signal 4...20 mA, 2-wire

    Voltage drop < 14 V

    Output data

    Output impedance Nom. 2 Ohm

    Output signal 0.03...10 V

    Load > 600 Ohm

    1

    2

    4

    3

    +

    Signal Converter I/I Signal Converter I/U

    4...20 mA

    0...20 mA

    4...20 mA

    0...10 V

    4

    3

    1

    2

    + +

    +

    4

    5

    Block Diagram

  • 7/26/2019 Converter 8305-1 UK

    3/4Page 3Design and specifications subject to change without notice

    Data Sheet 8305-1www.baumerprocess.com

    230 Vac 0...20 mA

    4...20 mA

    + - + - + -

    Power supply FlexTemp Iso Signal converter Indicator instrument

    RTD

    3 4 3 4 3 4

    1 2 1 2 1 2

    Example of Application

    [mm]

    88

    6265.5

    24

    Dimensional Drawings

    C

  • 7/26/2019 Converter 8305-1 UK

    4/4Page 4Design and specifications subject to change without notice

    Data Sheet 8305-1www.baumerprocess.com

    UK/2007-03-21

    Thisdat

    asheetmayonlybereproducedinfull.