GRUNDFOS DATABOOKLET

Control 2000, Delta Control 2000Controllers for pumps connected in parallel

Page 2: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

2

Contents

General dataApplication Page 3Control 2000 Page 3Delta Control 2000 Page 3

General data, Control 2000System configuration Page 4

Functions, Control 2000Functions Page 5Type key Page 6Examples of functioning Page 8Control parameters Page 10

Technical data, Control 2000Dimensions and weight Page 13Product numbers Page 18

General data, Delta Control 2000System configuration Page 24

Functions, Delta Control 2000Functions Page 25Type key Page 26Examples of functioning Page 28Control parameters Page 30Systems with PMU 2000 Page 31

Technical data, Delta Control 2000Dimensions and weights Page 34Product numbers Page 38

Optional equipmentPMU 2000 Page 42Switching off of neutral lead Page 42Emergency operation switch Page 42Phase-failure protection Page 43Lightning protection Page 43Voltmeter Page 43Ammeter Page 43Operating light Page 43Fault light Page 43Panel light Page 43Extra documentation Page 43Enclosure class Page 43

AccessoriesPMU 2000 Page 44PCU 2000 Page 44

Page 3: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

Control 2000Delta Control 2000

General data

Application

Control 2000

The Control 2000 controller is used for pumps connectedin parallel in systems which should supply a geometrichead.

Typical systems are water supply systems, pressureboosting systems or other systems characterized by avarying water consumption and in which a constantpressure should be maintained.

The Control 2000 controller features all the necessarycomponents to control and monitor 2 - 6 pumpsconnected in parallel.

Delta Control 2000

The Delta Control 2000 controller is used for pumpsconnected in parallel in closed systems with the purposeof circulating a pumped liquid.

Typical systems are heating or air-conditioning systemscharacterized by a variable need for pumping and inwhich a constant differential pressure should be main-tained. The control of pumps according to temperatureor flow is also possible using the Delta Control 2000.

The Delta Control 2000 controller features all the neces-sary components to control and monitor 1 - 4 pumpsconnected in parallel.

General data, Control 2000

TM0

1 28

56 2

598

TM0

1 28

55 2

598

Pumps

Control 2000

System characteristics

Geometrichead

TM0

1 28

58 2

598

TM0

1 28

57 2

598

Delta Control 2000

Pumps

Boiler orrefrigeration unit

Heating orair-conditioning system

3

Page 4: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

4

General data

Control 2000

System configurationThe Control 2000 consists of three main groups:

1. Control 2000 S is used for mains operation (on/offoperation) of standard pumps with standard motors.

2. Control 2000 F features a standard frequencyconverter and can be used together with pumps withstandard motors.

3. Control 2000 E is used when the system comprisesE-pumps (Grundfos pumps equipped with GrundfosMGE motors).

Each main group consists of subgroups, see the tablebelow:

Abbreviations:

M: The Control 2000 features a microprocessor for thecontrol of all functions.

S: Some or all of the pumps in the system are on/off-operated.

F: The Control 2000 features a frequency converter forthe speed control of some of the pumps in thesystem. One pump only is speed-controlled at atime.

E: Some or all of the pumps in the system are E-pumps(pumps with integrated frequency converter).

H: The system has one or two half-size pumps (one half-size pump provides approximately thesame head as one full-size pump, but only approximately half the flow).

Main groupSub-

group

Description of pumps

Size NumberNumber of controlled

pumps Mode of operation Comments

Co

ntr

ol 2

00

0 S

(on

/off

)

MS Full-size All Mains operation (on/off).

MSH

Half-size 1 Mains operation (on/off).

Full-sizeAll other pumps

Mains operation (on/off).

Co

ntr

ol 2

00

0 F

(Var

iab

le s

pee

d)

MF Full-size

1 1Speed control via frequency con-verter mounted in control cabinet.

Frequency-converter control rotates among all pumps in the system.

All other pumps

Mains operation (on/off).

MFH

Half-size 2 1Speed control via frequency con-verter mounted in control cabinet.

Frequency-converter control alter-nates between the two pumps. The uncontrolled pump is mains operated (on/off).

Full-sizeAll other pumps

Mains operation (on/off).

Co

ntr

ol 2

00

0 E

(Var

iab

le s

pee

d)

ME Full-size All AllSpeed control via frequency con-verter integrated in the motor.

All pumps in operation run at the same speed (cascade control).

MEH

Half-size 2 2Speed control via frequency con-verter integrated in the motor.

The two pumps run at the same speed when both are in operation.

Full-sizeAll other pumps

Mains operation (on/off).

MES

Full-size 1 1Speed control via frequency con-verter integrated in the motor.

Full-sizeAll other pumps

Mains operation (on/off).

Page 5: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

Control 2000

Functions

Functions

Control 2000

A standard Control 2000 always includes the electronicsunit PFU 2000 (Pump Functional Unit 2000) built intothe control cabinet. The PFU 2000 front cover with resetbutton and indicator lights is mounted in the front doorof the control cabinet.

Alternatively, the Control 2000 can be supplied with thePMU 2000 (Pump Management Unit 2000) mounted inthe front door of the control cabinet.The PMU 2000 enables the read-out of operating dataand the optimisation of operation according to systemconditions.

The Control 2000 without PMU 2000 offers thefollowing functions:

• Constant pressure control of the system.

• On/off operation at low flow.

• Automatic changeover to mains operation in case of defective frequency converter (Control 2000 F only).

• Automatic cascade control of pumps.

• Possibility of setpoint influence:–proportional influence (proportional pressure), –external setpoint influence.

• Possibility of remote control:–system on/off.

• Pump and system monitoring functions:–inlet pressure–motor protection.

• Display and indication functions:–green indicator light for operating indications and

red indicator light for fault indications,–potential-free changeover contacts for operation

and fault.

• GRUNDFOS BUS communication.

The Control 2000 with PMU 2000 offers the followingfunctions:

• Constant pressure control of the system.

• On/Off operation at low flow.

• Automatic changeover to mains operation in case ofdefective frequency converter (Control 2000 F only).

• Automatic cascade control of pumps.

• Selection of switching sequences, automatic pumpchangeover and pump priority.

• Manual operation.

• Possibility of setpoint influence:–proportional influence (proportional pressure), –external setpoint influence.

• Possibility of digital remote-control functions:–system on/off,–reduced operation,–setpoint control with two-point switch,–setpoint control with three-point switch,–alternative setpoint.

• Pump and system monitoring functions:–minimum and maximum limits of actual value,–inlet pressure,–motor protection.

• Display and indication functions:–2 x 24 character LCD display,–green indicator light for operating indications and

red indicator light for fault indications,–potential-free changeover contacts for operation

and fault.

• Clock functions.

• GRUNDFOS BUS communication.

PCU 2000

A PCU 2000 (Pump Communication Unit 2000) can beconnected to the Control 2000 via the BUS input. ThePCU 2000 enables remote operating and fault indicationfor each individual pump.The PCU 2000 also enables external setpoint influenceand system on/off.

Functions, Control 2000

Functions

5

Page 6: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

6

Functions

Control 2000

Type keyExample Control 2000 MEH 2 x 5.5 SD + 2 x 3.0 E PMU 3 x 400/230 V, 50 Hz IP 54

Type range

Supgroup:MS - MSH - MF - MFH - ME - MEH - MES

Number of full-size pumps 1 - 4

Power, full-size pumps [kW]

Starting method of full size pumps:DOL: Direct-on-line startingSD: Star-delta startingE: Electronic soft start (MGE motor)

Number of half-size pumps 1 - 2

Power, half-size pumps [kW]

Starting method of half-size pumps:DOL: Direct-on-line startingSD: Star-delta startingE: Electronic soft start (MGE motor)

Control panel:PMU: PMU 2000PFU: PFU 2000

Supply voltage/frequency

Enclosure class:IP 54IP 00

Page 7: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

7

Page 8: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

8

Control 2000

Functions

Examples of functioningThe following table shows examples of Control 2000 systems using constant pressure control.

On/off Variable speed

GRUNDFOSControl 2000 MS

GRUNDFOSControl 2000 MSH

GRUNDFOSControl 2000 MF

GRUNDFOSControl 2000 MFH

TM0

0 2

674

029

4

TM0

0 2

678

029

4

TM0

026

80 0

294

TM0

026

77 0

294

One pump in operation. The half-size pump in opera-tion.

One pump in operation viafrequency converter.

One half-size pump in opera-tion via frequency converter.

TM0

0 2

749

029

4

TM0

0 2

773

029

4

TM0

0 2

757

029

4

TM0

0 2

781

029

4

Three pumps in operation. One full-size pump and thehalf-size pump in operation.

One pump in operation viafrequency converter and twopumps on mains operation.

One half-size pump in opera-tion via frequency converterand one full-size pump onmains operation

TM0

0 2

751

029

4

TM0

0 2

775

029

4

TM0

0 2

759

029

4

TM0

0 2

783

029

4• Maintains an almost con-

stant pressure through cutting in/out the re-quired number of pumps.

• Changeover among the pumps is automatic and depends on load, time and fault.

• The cut-out pressure (Hstop) cannot be set but is calculated automatically.

• Maintains an almost con-stant pressure through cutting in/out the half-size pump and the full-size pumps.

• The half-size pump will al-ways start first, and will be cut out again when a full-size pump is cut in.

• Changeover among the full-size pumps is auto-matic and depends on load, time and fault.

• The cut-out pressure (Hstop) cannot be set but is calculated automatically.

• Maintains a constant pressure through continu-ously variable adjust-ment of the speed of one pump. The other pumps are mains-operated (on/off) according to the de-mand.

• The frequency-converter controlled pump will al-ways start first.

• Pump changeover is auto-matic and depends on load, time and fault.

• Besides, all pumps will be controlled by the fre-quency converter in rota-tion.

• Maintains a constant pressure through continu-ously variable adjust-ment of the speed of one half-size pump. The rest of the pumps are mains-operated.

• The half-size pump con-trolled by the frequency converter will always start first.

• Pump changeover is auto-matic and depends on load, time and fault.

PFU 2000 PFU 2000 PFU 2000 PFU 2000

Q

stop

set

H

H

H

Q

stop

set

H

H

H

Q

set H

H

Q

set H

H

Q

stop

set

H

H

H

Q

stop

set

H

H

H

Q

set H

H

Q

set H

H

Page 9: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

Functions

Control 2000

Examples of functioning, cont.The following table shows examples of Control 2000 systems using constant pressure control.

Variable speed

GRUNDFOSControl 2000 ME

GRUNDFOSControl 2000 MEH

GRUNDFOSControl MES

TM0

0 7

98

3 22

96

TM0

0 7

98

4 22

96

TM0

0 7

98

5 22

96

One pump in operation. The half-size pump in opera-tion.

One half-size pump in opera-tion via frequency converter.

TM0

0 7

99

5 22

96

TM0

0 7

99

4 22

96

TM0

0 7

99

3 22

96

Three pumps in operation. One full-size pump and thehalf-size pump in operation.

One half-size pump in opera-tion via frequency converterand one full-size pump onmains operation

TM0

0 7

99

6 2

296

TM0

0 7

99

7 22

96

TM0

0 7

99

8 22

96

• Maintains a constant pressure through continu-ously variable adjust-ment of the speed of the pumps connected.

• The system performance is adjusted to the demand through cutting in/out the required number of pumps and through paral-lel control of the pumps in operation.

• Pump changeover is auto-matic and depends on load, time and fault.

• Maintains a constant pressure through continu-ously variable adjust-ment of the speed of the two half-size pumps with MGE motors, while the full-size pump is mains-operated. (on/off).

• The half-size pumps al-ways start first.

• Pump changeover is auto-matic and depends on load, time and fault.

• Maintains a constant pressure through continu-ously variable adjust-ment of the speed of one pump. The other pumps are cut in/out on mains operation according to de-mand thus achieving a performance correspond-ing to the consumption.

• The pump with MGE mo-tor will always start first.

• Pump changeover is auto-matic and depends on load, time and fault.

PFU 2000

MGE MGE MGE

PFU 2000

MGE MGE

PFU 2000

MGE

Q

H

set H

Q

H

set H

Q

H

set H

Q

H

set H

Q

H

set H

Q

H

set H

9

Page 10: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

10

Functions

Control 2000

Control parameters

Systems without PMU 2000

Controllers without the PMU 2000 can be used insystems having small time constants and are preset tothe control parameter "pressure".

Cascade control:

Cascade control ensures automatic adjustment ofperformance to the system demand by cutting in/outthe required number of pumps.The controller will operate the system with as fewpumps as possible.

Automatic pump changeover:

Automatic pump changeover is made as follows:

• Fault-dependent pump changeover.If a pump is faulty, it will be switched off and the next pump ready for operation will be switched on.

• Time-dependent pump changeover.This ensures that the operating hours are distributed evenly on the pumps connected. This function is combined with the test run function.

Test run:To eliminate the risk of pump seizure caused by longperiods of standstill, a test run lasting 1 sec. is carried outonce every 24 hours.

Setpoint:The setpoint is set by means of the function selector inthe PFU 2000. It is also possible to stop all pumps, or toset all pumps to operate at maximum performance.

Remote setpoint setting:

A 0 - 10 V or 0 - 20 mA signal can be connected for remotesetpoint setting.

The locally set setpoint is set by means of the functionselector in the PFU 2000.

Sensor input:

Sensors giving the following analog signals can beconnected:– 0 - 10 V,– 0 - 20 mA, – 4 - 20 mA.

Input for external start/stop:

A potential-free contact for external start/stop of allpumps can be connected.

Systems with PMU 2000

The PMU 2000 is designed for the control of variouspumps or pump systems. As an example, the PMU 2000can be used for the control of GRUNDFOS circulatorpumps of the UPE type and pumping systems andcontrollers based on the PFU 2000, such as the Control2000.Using the Control 2000 it is possible to control thepumps according to a constant pressure (fig. 1) or aconstant pressure with pre-pressure measuring (fig. 2).

Fig. 1.

Fig. 2

TM

01 2

504

1898

TM

00 5

217

2796

PFU 2000

P

Pressure

100%0%

MAXSTOP

Setpoint

Function selector in the PFU 2000

TM

00 7

048

0296

TM

01 2

504

1898

TM

01 2

505

1898

0 10 V

Locally set setpoint

100%

Current setpoint

Tran

smitt

er ra

nge

Actual setpoint

Tran

smit

terr

ang

e Locally set setpoint

100%

10V20 mA

Setpoint via external signals

PFU 2000

P

Pressure

PFU 2000

PP

Pressure with pre-pressure measuring

Page 11: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

Functions

Control 2000

Cascade control:

Cascade control ensures automatic adjustment ofperformance to the system demand by cutting in/outthe required number of pumps.

The controller will operate the system with as fewpumps as possible.

The on/off rate is limited by setting the switchingsequences.

Automatic pump changeover:

Automatic pump changeover is made as follows:

• Fault-dependent pump changeover.If a pump is faulty, it will be switched off and the next pump ready for operation will be switched on.

• Time-dependent pump changeover.This ensures that the operating hours are distributed evenly on the pumps connected. This function is combined with the test run function.

Test run:

To eliminate the risk of pump seizure caused by longperiods of standstill, a test run lasting 1 sec. is carried outonce every 24 hours.

Clock functions:

If the system demand varies during the day and/orduring the week, the pump performance required willalso vary. In this case, a clock program can be set in orderto achieve optimum performance of the pumps. It is possible to set a total of 10 switching times, allhaving individual setpoints.

Standby pumps:

In systems with more than one pump, standby pumpscan be selected. A standby pump is started only if one ofthe duty pumps is faulty.

Example: In a system with four pumps of which onepump has been selected as standby-pump, themaximum number of pumps in operation at the sametime will be three. The standby pump is started only ifone of the duty pumps is faulty.

Setpoint:

The max. setpoint is set in the PMU 2000 menu

Friction loss compensation:

The control unit is capable of compensating for frictionloss. The setpoint increases from an adjustablepercentage at zero flow to 100% at max. flow.The actual flow is estimated based on internal operatingdata without the flow being measured directly.

Remote setpoint setting:

In view of optimizing system operation, it is often bestfor the system to operate according to a variablesetpoint instead of a constant setpoint. The selectedsettings influencing the setpoint will reduce "setpointmax".The following possibilities are available:

• "extern" (%)An external analog signal or potential-free contact influences the setpoint in accordance with a table.

• "timer" (minutes)An internal timer program in the PMU 2000 controls the setpoint in accordance with a table.

• "level" (m, cm, ft, in)The level signal controls the setpoint in accordance with a table.

• "flow" (m3/h, l/h, l/s, gpm)The flow signal controls the setpoint in accordance with a table.

• "flow/I" (%), (applies only to Delta Control 2000 F) An internal flow signal controls the setpoint in accord-ance with a table.

Sensor input:

Sensors giving the following analog signals can beconnected:

– 0 - 10 V,– 0 - 20 mA, – 4 - 20 mA.

TM

00 4

989

4894

Set A

Setpoint max. 5.0 bar

Setpoint

1 3

C

A

2 Time

B

Time

Setpoint

Clock program with three switching times

TM

00 4

991

4894

Setpoint max

Q

H

100 %

60 %

Setpoint max.

100%

60%

Q

H

Friction loss compensation

11

Page 12: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

12

Control 2000

Technical data

Dimensions and weightsDimensions and weights are for control cabinets with aPFU 2000 control panel.

All motors must be three-phase.

The starting methods of the motors are:

• DOL (Direct-on-line starting)

• SD (Star-delta starting)

• E (Electronic soft start via frequency converter).

Control 2000 MS

TM

00 9

394

2402

- T

M01

047

3 24

02

D B

H

Delta Control 2000

D B

HDelta Control 2000

Motor[kW]

Mounting of control

cabinet

Star

tin

gfu

ll-s

ize

Control 2000 MS for 2 pumps

Control 2000 MS for 3 pumps

Control 2000 MS for 4 pumps

Control 2000 MS for 5 pumps

Control 2000 MS for 6 pumps

Dimensions [mm] Weight

[kg]

Dimensions [mm] Weight

[kg]

Dimensions [mm] Weight

[kg]

Dimensions [mm] Weight

[kg]

Dimensions[mm] Weight

[kg]H B D H B D H B D H B D H B D

0.37 Wall mount. DOL 600 380 210 20 600 380 210 21 600 600 210 31 600 600 210 31 600 600 210 32

0.55 Wall mount. DOL 600 380 210 20 600 380 210 21 600 600 210 31 600 600 210 31 600 600 210 32

0.75 Wall mount. DOL 600 380 210 20 600 380 210 21 600 600 210 31 600 600 210 31 600 600 210 32

1.1 Wall mount. DOL 600 380 210 20 600 380 210 21 600 600 210 31 600 600 210 31 600 600 210 32

1.5 Wall mount. DOL 600 380 210 20 600 380 210 21 600 600 210 31 600 600 210 31 600 600 210 32

2.2 Wall mount. DOL 600 380 210 20 600 380 210 21 600 600 210 31 600 600 210 31 600 600 210 32

3 Wall mount. DOL 600 380 210 20 600 380 210 21 600 600 210 31 600 600 210 31 600 600 210 32

4 Wall mount. SD 600 600 210 31 600 600 210 32 1000 800 300 66 1000 800 300 68 1000 800 300 69

5.5 Wall mount. SD 600 600 210 31 600 600 210 32 1000 800 300 66 1000 800 300 68 1800 1000 400 163!

7.5 Wall mount. SD 600 600 210 31 600 600 210 33 1000 800 300 66 1800 1000 400 161! 1800 1000 400 164!

11 Wall mount. SD 600 600 210 31 1000 800 300 65 1000 800 300 67 1800 1000 400 162! 1800 1000 400 165!

15 Wall mount. SD 600 600 210 32 1000 800 300 67 1000 800 300 69 1800 1000 400 164! 1800 1000 400 168!

18.5 Wall mount. SD 1000 800 300 65 1000 800 300 68 1000 800 300 70 1800 1200 400 202! 1800 1200 400 204!

22 Wall mount. SD 1000 800 300 66 1000 800 300 69 1000 800 300 71 1800 1200 400 203! 1800 1200 400 206!

30 Wall mount. SD 1200 1000 300 97 1200 1000 300 101 1200 1000 300 105 1900 1200 400 218! 1900 1200 400 222!

! The control cabinet is prepared for floor mounting. Technical data, Control 2000

Page 13: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

Technical data

Control 2000

Control 2000 MSH

MotorMountingof control

cabinet

Startingfull-size

Startinghalf-size

Control 2000 MSH for 2 pumps

(1 full-size and1 half-size)

Control 2000 MSH for 3 pumps

(2 full-size and1 half-size)

Control 2000 MSH for 4 pumps

(3 full-size and1 half-size)

Full-size[kW]

Half-size[kW]

Dimensions [mm] Weight

[kg]

Dimensions [mm] Weight

[kg]

Dimensions[mm] Weight

[kg]H B D H B D H B D

1.1 0.75 Wall mounting DOL DOL 600 380 210 20 600 380 210 21 600 600 210 32

1.5 1.1 Wall mounting DOL DOL 600 380 210 20 600 380 210 21 600 600 210 32

2.2 1.1 Wall mounting DOL DOL 600 380 210 20 600 380 210 21 600 600 210 32

3 1.5 Wall mounting DOL DOL 600 380 210 20 600 380 210 21 600 600 210 32

3 2.2 Wall mounting DOL DOL 600 380 210 20 600 380 210 21 600 600 210 32

4 2.2 Wall mounting SD DOL 600 600 210 31 600 600 210 32 1000 800 300 66

4 3.0 Wall mounting SD DOL 600 600 210 31 600 600 210 32 1000 800 300 66

5.5 3.0 Wall mounting SD DOL 600 600 210 31 600 600 210 32 1000 800 300 66

5.5 4.0 Wall mounting SD SD 600 600 210 31 600 600 210 32 1000 800 300 66

7.5 4.0 Wall mounting SD SD 600 600 210 32 600 600 210 34 1000 800 300 67

7.5 5.5 Wall mounting SD SD 600 600 210 32 600 600 210 34 1000 800 300 67

11 5.5 Wall mounting SD SD 600 600 210 32 600 600 210 34 1000 800 300 68

11 7.5 Wall mounting SD SD 600 600 210 32 600 600 210 34 1000 800 300 68

11 11 Wall mounting SD SD 600 600 210 32 600 600 210 34 1000 800 300 68

15 7.5 Wall mounting SD SD 600 600 210 33 1000 800 300 67 1000 800 300 69

15 11 Wall mounting SD SD 600 600 210 33 1000 800 300 67 1000 800 300 69

18.5 11 Wall mounting SD SD 600 600 210 33 1000 800 300 67 1000 800 300 69

22 11 Wall mounting SD SD 1000 800 300 65 1000 800 300 68 1000 800 300 71

22 15 Wall mounting SD SD 1000 800 300 66 1000 800 300 69 1000 800 300 71

30 15 Wall mounting SD SD 1200 1000 300 97 1200 1000 300 101 1200 1000 300 104

30 18.5 Wall mounting SD SD 1200 1000 300 97 1200 1000 300 101 1200 1000 300 104

Dimensions and weight

13

Page 14: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

14

Technical data

Control 2000

Dimensions and weightsDimensions and weights are for control cabinets with aPFU 2000 control panel.

All motors must be three-phase.

The starting methods of the motors are:

• DOL (Direct-on-line starting)

• SD (Star-delta starting)

Control 2000 MF

Control 2000 MFH

TM

01 0

473

2402

D B

HDelta Control 2000

Motor[kW]

Mounting of control

cabinet

Star

tin

gfu

ll-s

ize

Control 2000 MFfor 2 pumps

Control 2000 MFfor 3 pumps

Control 2000 MFfor 4 pumps

Control 2000 MFfor 5 pumps

Control 2000 MFfor 6 pumps

Dimensions [mm] Weight

[kg]

Dimensions [mm] Weight

[kg]

Dimensions [mm] Weight

[kg]

Dimensions [mm] Weight

[kg]

Dimensions[mm] Weight

[kg]H B D H B D H B D H B D H B D

0.37 Floor mount. DOL 1400 600 300 77 1400 800 300 93 1400 800 300 94 1400 1000 300 111 1400 1000 300 112

0.55 Floor mount. DOL 1400 600 300 77 1400 800 300 93 1400 800 300 94 1400 1000 300 111 1400 1000 300 112

0.75 Floor mount. DOL 1400 600 300 77 1400 800 300 93 1400 800 300 94 1400 1000 300 111 1400 1000 300 112

1.1 Floor mount. DOL 1400 600 300 77 1400 800 300 93 1400 800 300 94 1400 1000 300 111 1400 1000 300 112

1.5 Floor mount. DOL 1400 600 300 77 1400 800 300 93 1400 800 300 94 1400 1000 300 111 1400 1000 300 112

2.2 Floor mount. DOL 1400 600 300 77 1400 800 300 93 1400 800 300 94 1400 1000 300 111 1400 1000 300 112

3 Floor mount. DOL 1400 600 300 77 1400 800 300 93 1400 800 300 94 1400 1000 300 111 1400 1000 300 112

4 Floor mount. SD 1400 800 300 102 1400 1000 300 120 1400 1000 300 122 1400 1000 300 124 1900 1000 400 190

5.5 Floor mount. SD 1400 800 300 102 1400 1000 300 120 1400 1000 300 122 1900 1000 400 188 1900 1000 400 190

7.5 Floor mount. SD 1400 800 300 94 1400 1000 300 120 1400 1000 300 178 1900 1000 400 181 1900 1000 400 182

11 Floor mount. SD 1900 1000 400 185 1900 1200 400 221 1900 1200 400 224 1900 1200 400 226 1900 1200 400 228

15 Floor mount. SD 1900 1000 400 188 1900 1200 400 226 1900 1200 400 228 1900 1600 400 274 1900 1600 400 276

18.5 Floor mount. SD 1900 1000 400 197 1900 1600 400 279 1900 1600 400 283 1900 1800 400 392 1900 1800 400 396

22 Floor mount. SD 1900 1000 400 198 1900 1600 400 280 1900 1600 400 285 1900 1800 400 394 1900 1800 400 399

30 Floor mount. SD 1900 1200 400 262 1900 1800 400 380 1900 2200 400 461 1900 2200 400 466 1900 2000 400 471

MotorMounting of control

cabinet

Startingfull-size

Startinghalf-size

Control 2000 MFH for 3 pumps

(1 full-size and2 half-size)

Control 2000 MFH for 4 pumps

(2 full-size and2 half-size)

Full-size[kW]

Half-size[kW]

Dimensions [mm] Weight

[kg]

Dimensions [mm] Weight

[kg]H B D H B D

3 2.2 Floor mounting DOL DOL 1500 800 300 93 1500 800 300 94

4 3 Floor mounting SD DOL 1500 800 300 94 1500 800 300 95

5.5 3 Floor mounting SD DOL 1500 800 300 94 1500 800 300 95

5.5 4 Floor mounting SD SD 1500 1000 300 120 1500 1000 300 121

7.5 4 Floor mounting SD SD 1500 1000 300 120 1500 1000 300 121

7.5 5.5 Floor mounting SD SD 1500 1000 300 120 1500 1000 300 121

11 5.5 Floor mounting SD SD 1500 1000 300 120 1900 1000 400 178

11 7.5 Floor mounting SD SD 1500 1000 300 112 1900 1000 400 185

15 7.5 Floor mounting SD SD 1500 1000 300 112 1900 1000 400 179

15 11 Floor mounting SD SD 1900 1000 400 187 1900 1000 400 189

18.5 11 Floor mounting SD SD 1900 1000 400 187 1900 1000 400 180

22 11 Floor mounting SD SD 1900 1000 400 190 1900 1000 400 193

22 15 Floor mounting SD E/SD 1900 1000 400 190 1900 1000 400 193

30 15 Floor mounting SD E/SD 1900 1200 400 227 1900 1600 400 273

30 18.5 Floor mounting SD E/SD 1900 1600 400 282 1900 1600 400 283

Page 15: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

Technical data

Control 2000

Dimensions and weightsDimensions and weights are for control cabinets with aPFU 2000 control panel.

All motors must be three-phase.

The starting methods of the motors are:

• E (Electronic soft start via frequency converter).

Note: E-pumps marked with """ must be with single-phase mains connection.

Control 2000 ME

TM

00 9

394

2402

D B

H

Delta Control 2000

Motor [kW]

Mounting of control

cabinet

Startingfull-size

Control 2000 MEfor 2 pumps

Control 2000 MEfor 3 pumps

Control 2000 MEfor 4 pumps

Dimensions [mm] Weight

[kg]

Dimensions[mm] Weight

kg]

Dimensions[mm] Weight

[kg]H B D H B D H B D

1.1 " Wall mounting E 400 400 210 14 600 400 210 20

1.1 Wall mounting E 400 400 210 14 600 400 210 20 600 400 210 20

1.5 Wall mounting E 600 400 210 20 600 400 210 20 600 400 210 20

2.2 Wall mounting E 600 400 210 20 600 400 210 20 600 400 210 20

3 Wall mounting E 600 400 210 20 600 400 210 20 600 400 210 20

4 Wall mounting E 600 400 210 20 600 400 210 20 600 400 210 20

5.5 Wall mounting E 600 400 210 20 600 400 210 20 600 400 210 20

7.5 Wall mounting E 600 400 210 24 600 400 210 26 600 400 210 37

11 Wall mounting E 600 380 210 25 600 380 210 26 600 600 210 37

15 Wall mounting E 600 380 210 25 600 600 210 37 760 760 210 56

18.5 Wall mounting E 600 380 210 26 760 760 210 55 760 760 210 57

22 Wall mounting E 600 600 210 37 760 760 210 56 760 760 210 58

15

Page 16: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

16

Technical data

Control 2000

The starting methods of the motors are:

• DOL (Direct-on-line starting)

• SD (Star-delta starting)

• E (Electronic soft start via frequency converter)

Control 2000 MEH

MotorMounting of control

cabinet

Startingfull-size

Startinghalf-size

Control 2000 MEH for 3 pumps

(1 full-size and 2 half-size)

Control 2000 MEHfor 4 pumps

(2 full-size and 2 half-size)

Full-size[kW]

Half-size[kW]

Dimensions[mm] Weight

[kg]

Dimensions [mm] Weight

[kg]H B D H B D

1.1 0.75 " Wall mounting DOL E 600 400 210 20 600 400 210 21

1.5 1.1 " Wall mounting DOL E 600 400 210 20 600 400 210 21

2.2 1.1 " Wall mounting DOL E 600 400 210 20 600 400 210 21

2.2 1.5 Wall mounting DOL E 600 400 210 20 600 400 210 21

3 1.5 Wall mounting DOL E 600 400 210 20 600 400 210 21

3 2.2 Wall mounting DOL E 600 400 210 20 600 400 210 21

4 2.2 Wall mounting SD E 600 600 210 31 600 600 210 33

4 3 Wall mounting SD E 600 600 210 31 600 600 210 33

5.5 3 Wall mounting SD E 600 600 210 31 600 600 210 33

5.5 4 Wall mounting SD E 600 600 210 32 600 600 210 33

7.5 4 Wall mounting SD E 600 600 210 32 600 600 210 65

7.5 5.5 Wall mounting SD E 600 600 210 32 600 600 210 65

11 5.5 Wall mounting SD E 600 600 210 32 600 600 210 65

11 7.5 Wall mounting SD E 600 600 210 32 600 600 210 65

15 7.5 Wall mounting SD E 1000 600 300 63 1000 800 300 66

15 11 Wall mounting DOL E 600 600 210 37 760 760 210 57

15 11 Wall mounting SD E 600 600 210 37 760 760 210 58

18.5 11 Wall mounting DOL E 600 600 210 38 760 760 210 58

18.5 11 Wall mounting SD E 600 600 210 38 760 760 210 59

18.5 15 Wall mounting DOL E 600 600 210 38 760 760 210 59

18.5 15 Wall mounting SD E 600 600 210 38 760 760 210 59

22 11 Wall mounting DOL E 600 600 210 40 1000 800 300 81

22 11 Wall mounting SD E 600 600 210 39 760 760 210 60

22 15 Wall mounting DOL E 1000 800 300 76 1000 800 300 81

22 15 Wall mounting SD E 760 760 210 57 760 760 210 60

22 18.5 Wall mounting DOL E 1000 800 300 76 1000 800 300 81

22 18.5 Wall mounting SD E 760 760 210 57 760 760 210 60

30 15 Wall mounting DOL E 1000 800 300 77 1000 800 300 83

30 15 Wall mounting SD E 100 800 300 76 1000 800 300 81

30 18.5 Wall mounting DOL E 1000 800 300 77 1000 800 300 83

30 18.5 Wall mounting SD E 1000 800 300 77 1000 800 300 81

30 22 Wall mounting DOL E 1000 800 300 78 1200 800 300 122

30 22 Wall mounting SD E 1000 800 300 77 1200 800 300 121

37 18.5 Wall mounting DOL E 1000 800 300 80 1200 800 300 129

37 18.5 Wall mounting SD E 1000 800 300 77 1200 800 300 124

37 22 Wall mounting DOL E 1000 800 300 81 1200 800 300 130

37 22 Wall mounting SD E 1000 800 300 78 1200 800 300 125

45 22 Wall mounting DOL E 1200 800 300 116 1200 800 300 130

45 22 Wall mounting SD E 1200 800 300 114 1200 800 300 125

Page 17: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

Technical data

Control 2000

Control 2000 MES

Motor [kW]

Mounting of control

cabinet

Startingfull-size

Control 2000 MES for 2 pumps

Control 2000 MES for 3 pumps

Control 2000 MES for 4 pumps

Dimensions[mm] Weight

[kg]

Dimensions [mm] Weight

[kg]

Dimensions[mm] Weight

[kg]H B D H B D H B D

1.1 Wall mounting E/DOL 600 400 210 20 600 400 210 20 600 600 210 31

1.1 Wall mounting E/DOL 600 400 210 20 600 400 210 20 600 600 210 31

1.5 Wall mounting E/DOL 600 400 210 20 600 400 210 21 600 600 210 31

2.2 Wall mounting E/DOL 600 400 210 20 600 400 210 21 600 600 210 31

3 Wall mounting E/DOL 600 400 210 20 600 400 210 21 600 600 210 31

4 Wall mounting E/SD 600 600 210 31 600 600 210 33 600 600 210 34

5.5 Wall mounting E/SD 600 600 210 31 600 600 210 33 600 600 210 34

7.5 Wall mounting E/SD 600 600 210 31 600 600 210 33 1000 800 300 66

11 Wall mounting E/DOL 600 400 210 25 600 600 210 37 600 600 210 38

11 Wall mounting E/SD 600 600 210 36 600 600 210 38 600 600 210 41

15 Wall mounting E/DOL 600 600 210 36 600 600 210 38 760 760 210 57

15 Wall mounting E/SD 600 600 210 36 600 600 210 39 760 760 210 60

18.5 Wall mounting E/DOL 600 600 210 37 760 760 210 57 760 760 210 60

18.5 Wall mounting E/SD 600 600 210 37 760 760 210 58 760 760 210 62

22 Wall mounting E/DOL 600 600 210 39 1000 800 300 80 1000 800 300 84

22 Wall mounting E/SD 600 600 210 38 760 760 210 59 760 760 210 63

17

Page 18: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

18

Technical data

Control 2000

Product numbersProduct numbers for control cabinets with a PFU 2000control panel.

Supply voltage: 3 x 400 V +6%/–10%, 50 Hz, N, PE.

All motors must be three-phase.

Enclosure class: IP 54.

The starting methods of the motors are:

• DOL (Direct-on-line starting)

• SD (Star-delta starting)

Control 2000 MS

Motoroutput

[kW]

Mounting of control

cabinet Star

tin

gfu

ll-s

ize Product numbers

Control 2000 MS for 2 pumps

Control 2000 MSfor 3 pumps

Control 2000 MS for 4 pumps

Control 2000 MS for 5 pumps

Control 2000 MS for 6 pumps

0.37 Wall mount. DOL 96 01 11 97 96 01 12 11 96 01 12 25 96 01 12 39 96 01 12 50

0.55 Wall mount. DOL 96 01 11 98 96 01 12 12 96 01 12 26 96 01 12 40 96 01 12 51

0.75 Wall mount. DOL 96 01 11 99 96 01 12 13 96 01 12 27 96 01 12 41 96 01 12 52

1.1 Wall mount. DOL 96 01 12 00 96 01 12 14 96 01 12 28 96 01 12 42 96 01 12 53

1.5 Wall mount. DOL 96 01 12 01 96 01 12 15 96 01 12 29 96 01 12 43 96 01 12 54

2.2 Wall mount. DOL 96 01 12 02 96 01 12 16 96 01 12 30 96 01 12 44 96 01 12 55

3 Wall mount. DOL 96 01 12 03 96 01 12 17 96 01 12 31 96 01 12 45 96 01 12 56

4 Wall mount. SD 96 01 12 04 96 01 12 18 96 01 12 32 96 01 12 46 96 01 12 57

5.5 Wall mount. SD 96 01 12 05 96 01 12 19 96 01 12 33 96 01 12 47 96 01 12 58 !

7.5 Wall mount. SD 96 01 12 06 96 01 12 20 96 01 12 34 96 01 12 48 ! 96 01 12 59 !

11 Wall mount. SD 96 01 12 07 96 01 12 21 96 01 12 35 96 01 12 49 ! 96 01 13 58 !

15 Wall mount. SD 96 01 12 08 96 01 12 22 96 01 12 36 96 01 14 09 ! 96 01 14 12 !

18.5 Wall mount. SD 96 01 12 09 96 01 12 23 96 01 12 37 96 01 14 10 ! 96 01 14 13 !

22 Wall mount. SD 96 01 12 10 96 01 12 24 96 01 12 38 96 01 14 11 ! 96 01 14 14 !

30 Wall mount. SD 96 01 24 46 96 01 24 47 96 01 24 48 96 01 24 49 ! 96 01 24 50!

! The control cabinet is prepared for floor mounting.

Page 19: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

Technical data

Control 2000

Control 2000 MSH

Motor output

Mountingof control

cabinet

Starting full-size

Startinghalf-size

Product numbers

Full-size[kW]

Half-size[kW]

Control 2000 MSH

for 2 pumps(1 full-size and

1 half-size)

Control 2000 MSH

for 3 pumps(2 full-size and

1 half-size)

Control 2000 MSH

for 4 pumps(3 full-size and

1 half-size)

1.1 0.75 Wall mounting DOL DOL 96 01 12 60 96 01 12 72 96 01 12 83

1.5 1.1 Wall mounting DOL DOL 96 01 12 61 96 01 12 73 96 01 12 84

2.2 1.1 Wall mounting DOL DOL 96 01 12 62 96 01 12 74 96 01 12 85

3 1.5 Wall mounting DOL DOL 96 01 12 63 96 01 12 75 96 01 12 86

3 2.2 Wall mounting DOL DOL 96 01 20 43 96 01 20 48 96 01 20 53

4 2.2 Wall mounting SD DOL 96 01 12 64 96 01 12 76 96 01 12 87

4 3 Wall mounting SD DOL 96 01 20 46 96 01 20 51 96 01 20 56

5.5 3 Wall mounting SD DOL 96 01 20 21 96 01 12 77 96 01 12 88

5.5 4 Wall mounting SD SD 96 01 20 59 96 01 20 69 96 01 20 79

7.5 4 Wall mounting SD SD 96 01 12 67 96 01 12 78 96 01 12 89

7.5 5.5 Wall mounting SD SD 96 01 20 62 96 01 20 72 96 01 20 82

11 5.5 Wall mounting SD SD 96 01 12 68 96 01 12 79 96 01 12 90

11 7.5 Wall mounting SD SD 96 01 20 64 96 01 20 74 96 01 20 84

11 11 Wall mounting SD SD 96 01 20 66 96 01 20 76 96 01 20 86

15 7.5 Wall mounting SD SD 96 01 12 69 96 01 12 80 96 01 12 91

15 11 Wall mounting SD SD 96 01 20 16 96 01 20 18 96 01 20 20

18.5 11 Wall mounting SD SD 96 01 12 70 96 01 12 81 96 01 12 92

22 11 Wall mounting SD SD 96 01 12 71 96 01 12 82 96 01 12 93

22 15 Wall mounting SD SD 96 01 24 68 96 01 24 69 96 01 24 70

30 15 Wall mounting SD SD 96 01 24 71 96 01 24 72 96 01 24 73

30 18.5 Wall mounting SD SD 96 01 24 74 96 01 24 75 96 01 24 76

19

Page 20: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

20

Technical data

Control 2000

Product numbersProduct numbers for control cabinets with a PFU 2000control panel.

Supply voltage: 3 x 400 V +6%/–10%, 50 Hz, N, PE.

All motors must be three-phase.

Enclosure class: IP 54.

The starting methods of the motors are:

• DOL (Direct-on-line starting)

• SD (Star-delta starting)

Control 2000 MF

Control 2000 MFH

Motoroutput

[kW]

Mounting of control

cabinet

Startingfull-size

Product numbers

Control 2000 MF for 2 pumps

Control 2000 MFfor 3 pumps

Control 2000 MF for 4 pumps

Control 2000 MF for 5 pumps

Control 2000 MF for 6 pumps

0.37 Floor mount. DOL 96 01 13 74 96 01 13 82 96 01 13 90 96 01 13 99 96 01 14 08

0.55 Floor mount. DOL 96 01 13 67 96 01 13 75 96 01 13 83 96 01 13 91 96 01 14 00

0.75 Floor mount. DOL 96 01 13 68 96 01 13 76 96 01 13 84 96 01 13 92 96 01 14 01

1.1 Floor mount. DOL 96 01 13 69 96 01 13 77 96 01 13 85 96 01 13 93 96 01 14 02

1.5 Floor mount. DOL 96 01 13 70 96 01 13 78 96 01 13 86 96 01 13 94 96 01 14 03

2.2 Floor mount. DOL 96 01 13 71 96 01 13 79 96 01 13 87 96 01 13 95 96 01 14 04

3 Floor mount. DOL 96 01 13 72 96 01 13 80 96 01 13 88 96 01 13 96 96 01 14 05

4 Floor mount. SD 96 01 13 73 96 01 13 81 96 01 13 89 96 01 13 97 96 01 14 06

5.5 Floor mount. SD 96 01 12 94 96 01 13 00 96 01 13 06 96 01 13 98 96 01 14 07

7.5 Floor mount. SD 96 01 12 95 96 01 13 01 96 01 13 07 96 01 13 12 96 01 13 14

11 Floor mount. SD 96 01 12 96 96 01 13 02 96 01 13 08 96 01 13 13 96 01 13 15

15 Floor mount. SD 96 01 12 97 96 01 13 03 96 01 13 09 96 01 13 61 96 01 13 64

18.5 Floor mount. SD 96 01 12 98 96 01 13 04 96 01 13 10 96 01 13 62 96 01 13 65

22 Floor mount. SD 96 01 12 99 96 01 13 05 96 01 13 11 96 01 13 63 96 01 13 66

30 Floor mount. SD 96 01 24 14 96 01 24 15 96 01 24 16 96 01 24 17 96 01 24 18

Motor output

Mounting of control

cabinet

Starting full-size

Startinghalf-size

Product numbers

Full-size[kW]

Half-size[kW]

Control 2000 MFH for 3 pumps

(1 full-size and2 half-size)

Control 2000 MFH for 4 pumps

(2 full-size and2 half-size)

3 2.2 Floor mounting DOL DOL 96 01 13 16 96 01 13 28

4 3 Floor mounting SD DOL 96 01 13 17 96 01 13 29

5.5 3 Floor mounting SD DOL 96 01 13 18 96 01 13 30

5.5 4 Floor mounting SD SD 96 01 13 19 96 01 13 31

7.5 4 Floor mounting SD SD 96 01 13 20 96 01 13 32

7.5 5.5 Floor mounting SD SD 96 01 13 21 96 01 13 33

11 5.5 Floor mounting SD SD 96 01 13 22 96 01 13 34

11 7.5 Floor mounting SD SD 96 01 13 23 96 01 13 35

15 7.5 Floor mounting SD SD 96 01 13 24 96 01 13 36

15 11 Floor mounting SD SD 96 01 13 25 96 01 13 37

18.5 11 Floor mounting SD SD 96 01 13 26 96 01 13 38

22 11 Floor mounting SD SD 96 01 20 33 96 01 20 35

22 15 Floor mounting SD E/SD 96 01 13 27 96 01 13 39

30 15 Floor mounting SD E/SD 96 01 24 30 96 01 24 31

30 18.5 Floor mounting SD E/SD 96 01 24 32 96 01 24 33

Page 21: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

Technical data

Control 2000

Product numbersProduct numbers for control cabinets with a PFU 2000control panel.

Supply voltage: 3 x 400 V +6%/–10%, 50 Hz, N, PE.

All motors must be three-phase.

Note: CRE-pumps marked with """ must be with single-phase mains connection.

Enclosure class: IP 54.

The starting methods of the motors are:

• DOL (Direct-on-line starting)

• SD (Star-delta starting)

• E (Electronic soft start via frequency converter).

Control 2000 ME

Motor output[kW]

Mounting of control

cabinet

Startingfull-size

Product numbers

Control 2000 ME for 2 pumps

Control 2000 ME for 3 pumps

Control 2000 ME for 4 pumps

1.1 " Wall mounting E 96 01 11 52 96 01 14 15

1.1 Wall mounting E 96 01 20 89 96 01 20 90 96 01 23 15

1.5 Wall mounting E 96 01 11 68 96 01 14 16 96 01 23 02

2.2 Wall mounting E 96 01 11 69 96 01 14 17 96 01 23 03

3 Wall mounting E 96 01 11 70 96 01 14 18 96 01 23 04

4 Wall mounting E 96 01 11 71 96 01 14 19 96 01 23 05

5.5 Wall mounting E 96 01 11 72 96 01 14 20 96 01 23 06

7.5 Wall mounting E 96 01 23 87 96 01 23 88 96 01 23 89

11 Wall mounting E 96 01 33 45 96 01 33 49 96 01 33 53

15 Wall mounting E 96 01 33 46 96 01 33 50 96 01 33 54

18.5 Wall mounting E 96 01 33 47 96 01 33 51 96 01 33 55

22 Wall mounting E 96 01 33 48 96 01 33 52 96 01 33 56

21

Page 22: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

22

Technical data

Control 2000

Control 2000 MEH

Motor outputMountingof control

cabinet

Startingfull-size

Startinghalf-size

Product numbers

Full-size[kW]

Half-size[kW]

Control 2000 MEH for 3 pumps

(1 full-size and 2 half-size)

Control 2000 MEHfor 4 pumps

(2 full-size and 2 half-size)

1.1 0.75 " Wall mounting DOL E 96 01 11 73 96 01 11 85

1.5 1.1 " Wall mounting DOL E 96 01 11 74 96 01 11 86

2.2 1.1 " Wall mounting DOL E 96 01 11 75 96 01 11 87

2.2 1.5 Wall mounting DOL E 96 01 11 76 96 01 11 88

3 1.5 Wall mounting DOL E 96 01 11 77 96 01 11 89

3 2.2 Wall mounting DOL E 96 01 11 78 96 01 11 90

4 2.2 Wall mounting SD E 96 01 11 79 96 01 11 91

4 3 Wall mounting SD E 96 01 11 80 96 01 11 92

5.5 3 Wall mounting SD E 96 01 11 81 96 01 11 93

5.5 4 Wall mounting SD E 96 01 11 82 96 01 11 94

7.5 4 Wall mounting SD E 96 01 11 83 96 01 11 95

7.5 5.5 Wall mounting SD E 96 01 13 59 96 01 13 60

11 5.5 Wall mounting SD E 96 01 11 84 96 01 11 96

11 7.5 Wall mounting SD E 96 01 23 91 96 01 23 95

15 7.5 Wall mounting SD E 96 01 23 93 96 01 23 97

15 11 Wall mounting DOL E 96 01 35 57 96 01 35 63

15 11 Wall mounting SD E 96 01 35 58 96 01 35 64

18.5 11 Wall mounting DOL E 96 01 35 59 96 01 35 65

18.5 11 Wall mounting SD E 96 01 35 60 96 01 35 66

18.5 15 Wall mounting DOL E 96 01 35 69 96 01 35 75

18.5 15 Wall mounting SD E 96 01 35 70 96 01 35 76

22 11 Wall mounting DOL E 96 01 35 61 96 01 35 67

22 11 Wall mounting SD E 96 01 35 62 96 01 35 68

22 15 Wall mounting DOL E 96 01 35 71 96 01 35 77

22 15 Wall mounting SD E 96 01 35 72 96 01 35 78

22 18.5 Wall mounting DOL E 96 01 35 81 96 01 35 87

22 18.5 Wall mounting SD E 96 01 35 82 96 01 35 88

30 15 Wall mounting DOL E 96 01 35 73 96 01 35 79

30 15 Wall mounting SD E 96 01 35 74 96 01 35 80

30 18.5 Wall mounting DOL E 96 01 35 83 96 01 35 89

30 18.5 Wall mounting SD E 96 01 35 84 96 01 35 90

30 22 Wall mounting DOL E 96 01 35 93 96 01 35 99

30 22 Wall mounting SD E 96 01 35 94 96 01 36 00

37 18.5 Wall mounting DOL E 96 01 35 85 96 01 35 91

37 18.5 Wall mounting SD E 96 01 35 86 96 01 35 92

37 22 Wall mounting DOL E 96 01 35 95 96 01 36 01

37 22 Wall mounting SD E 96 01 35 96 96 01 36 02

45 22 Wall mounting DOL E 96 01 35 97 96 01 36 03

45 22 Wall mounting SD E 96 01 35 98 96 01 36 04

Page 23: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

Technical data

Control 2000

Product numbers for control cabinets with a PFU 2000 control panel.

Supply voltage: 3 x 400 V +6%/–10%, 50 Hz, N, PE.

All motors must be three-phase.

The starting methods of the motors are:

• DOL (Direct-on-line starting)

• SD (Star-delta starting)

• E (Electronic soft start via frequency converter).

Note: CRE-pumps marked with """ must be withsingle-phase mains connection.

Enclosure class: IP 54.

Control 2000 MES

Motor output[kW]

Mounting of control

cabinet

Startingfull-size

Product numbers

Control 2000 MES for 2 pumps

Control 2000 MES for 3 pumps

Control 2000 MES for 4 pumps

1.1 " Wall mounting E/DOL 96 01 13 40 96 01 13 46 96 01 13 52

1.1 Wall mounting E/DOL 96 01 20 92 96 01 20 93 96 01 20 94

1.5 Wall mounting E/DOL 96 01 13 41 96 01 13 47 96 01 13 53

2.2 Wall mounting E/DOL 96 01 13 42 96 01 13 48 96 01 13 54

3 Wall mounting E/DOL 96 01 13 43 96 01 13 49 96 01 13 55

4 Wall mounting E/SD 96 01 13 44 96 01 13 50 96 01 13 56

5.5 Wall mounting E/SD 96 01 13 45 96 01 13 51 96 01 13 57

7.5 Wall mounting E/SD 96 01 23 99 96 01 24 01 96 01 24 03

11 Wall mounting E/DOL 96 01 34 37 96 01 34 39 96 01 34 41

11 Wall mounting E/SD 96 01 34 38 96 01 34 40 96 01 34 42

15 Wall mounting E/DOL 96 01 34 43 96 01 34 45 96 01 34 47

15 Wall mounting E/SD 96 01 34 44 96 01 34 46 96 01 34 48

18.5 Wall mounting E/DOL 96 01 34 49 96 01 34 51 96 01 34 53

18.5 Wall mounting E/SD 96 01 34 50 96 01 34 52 96 01 34 54

22 Wall mounting E/DOL 96 01 34 55 96 01 34 57 96 01 34 59

22 Wall mounting E/SD 96 01 34 56 96 01 34 58 96 01 34 60

23

Page 24: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

24

Delta Control 2000General data

System configurationGrundfos Delta Control 2000 features two main groupsand one variant:

1. Delta Control 2000 F uses a standard frequencyconverter and can be used together with pumpswith standard motors. Delta Control 2000 F is divid-ed into subgroups.

2. Delta Control 2000 E is used when the systemcomprises E-pumps (Grundfos pumps equippedwith Grundfos MGE motors). Delta Control 2000 Eis also divided into subgroups. (See table below).

3. Delta Control 2000 ME (PO) should be used whena controller must be designed especially accordingto the customer’s needs. Delta Control 2000 ME(PO) contains only a PFU 2000 set up for the con-trol of Grundfos MGE motors. The Delta Control 2000 ME (PO) controller is sup-plied without control cabinet, fuses, main switch,etc.

Each main group consists of subgroups, see the tablebelow:

Abbreviations:

M: The Delta Control 2000 features a microprocessorfor the control of all functions.

F: Frequency-converter control rotates among all pumps in the system.

E: Some or all of the pumps in the system areE-pumps (pumps with integrated frequency converter).

H: The system has one or two half-size pumps.(One half-size pump provides approximatelythe same head as one full-size pump, but onlyapproximately half the flow).

General data, Delta Control 2000

System configuration

Main group Sub groupDescription of pumps

Size NumberNumber of

controlled pumpsMode of operation Comments

Del

ta C

on

tro

l 20

00

F(v

aria

ble

sp

eed

)

MF

1Speed control via frequency

converter mounted in controlcabinet.

Frequency-converter controlrotates among all pumps in

the systemFull-size All

All otherpumps

Mains operation (on/off).

MFH

Half-size 2 1Speed control via frequnecy con-

verter mounted in control cabinet.

Frequency-converter controlalternates between the two

pumps.The uncontrolled pump is mains

operated (on/off).

Full-sizeAll otherpumps

Mains operation (on/off).

Del

ta C

on

tro

l 20

00

E(v

aria

ble

sp

eed

) ME Full-size All AllSpeed control via frequency con-

verter integrated in the motor.All pumps in operation run at the

same speed (cascade control).

MEH

Half-size 2 2Speed control via frequency con-

verter integrated in the motor.The two pumps run at the same

speed when both are in operation.

Full-sizeAll otherpumps

Mains operation (on/off).

Page 25: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

Delta Control 2000

Functions

Functions

Delta Control 2000

A standard Delta Control 2000 always includes the elec-tronics unit PFU 2000 (Pump Functional Unit 2000) builtinto the control cabinet.

The PFU 2000 front cover with reset button and indi-cator lights is mounted in the front door of the controlcabinet.

Alternatively, the Delta Control 2000 can be suppliedwith the PMU 2000 (Pump Management Unit 2000)mounted in the front door of the control cabinet.The PMU 2000 enables the read-out of operating dataand the optimisation of operation according to systemconditions.

The Delta Control 2000 without PMU 2000 offers thefollowing functions:

• Control according to a constant differential pressure or a constant flow.

• Automatic changeover to mains operation in case of defective frequency converter (Delta Control 2000 F only).

• Automatic cascade control of pumps.

• Possibility of setpoint influence:–proportional influence (proportional pressure), –external setpoint influence.

• Possibility of remote control:–system on/off.

• Pump and system monitoring functions:–motor protection.

• Display and indication functions:–green indicator light for operating indications and

red indicator light for fault indications,–potential-free changeover contacts for operation

and fault.

• Grundfos BUS communication.

The Delta Control 2000 with PMU 2000 offers thefollowing functions:

• Pump control based on differential pressure, differen-tial temperature, temperature, flow or level.

• Automatic changeover to mains operation in case of defective frequency converter (Delta Control 2000 F only).

• Automatic cascade control of pumps.

• Selection of switching sequences, automatic pump changeover and pump priority.

• Manual operation.

• Possibility of setpoint influence:–proportional influence (proportional pressure), –external setpoint influence.

• Possibility of digital remote-control functions:–system on/off,–reduced operation,–setpoint control with two-point switch,–setpoint control with three-point switch,–alternative setpoint.

• Pump and system monitoring functions:–minimum and maximum limits of actual value,–motor protection.

• Display and indication functions:–2 x 24 character LCD display,–green indicator light for operating indications and

red indicator light for fault indications,–potential-free changeover contacts for operation

and fault.

• Clock functions.

• Grundfos BUS communication.

PCU 2000

A PCU 2000 (Pump Communication Unit 2000) can beconnected to the Delta Control 2000 via the BUS input.The PCU 2000 enables remote operating and fault indi-cation for each individual pump.The PCU 2000 also enables external setpoint influenceand system on/off.

Functions, Delta Control 2000

Functions

25

Page 26: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

26

Functions Del

ta Control 2000

Type keyExample Control 2000 MEH 2 x 5.5 SD + 2 x 3.0 E PMU 3 x 400/230 V, 50 Hz IP 54

Type range

Supgroup:MF - MFH - ME - MEH

Number of full-size pumps 1 - 4

Power, full-size pumps [kW]

Starting method of full size pumps:DOL: Direct-on-line startingSD: Star-delta startingE: Electronic soft start (MGE motor)

Number of half-size pumps 1 - 2

Power, half-size pumps [kW]

Starting method of half-size pumps:DOL: Direct-on-line startingSD: Star-delta startingE: Electronic soft start (MGE motor)

Control panel:PMU: PMU 2000PFU: PFU 2000

Supply voltage/frequency

Enclosure class:IP 54IP 00

Page 27: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

27

Page 28: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

28

Delta Control 2000

Functions

Examples of functioningThe following table shows examples of Delta Control 2000 systems using constant differential pressure control.

Variable speed

GRUNDFOSDelta Control 2000 MF

GRUNDFOSDelta Control 2000 MFH

TM0

1 10

24 3

397

TM0

1 10

25 3

397

One pump in operation viafrequency converter.

The half-size pump in opera-tion via frequency converter.

TM0

1 10

86 3

69

7

TM0

1 10

88 3

69

7

One pump in operation viafrequency converter. Twopumps are mains-operated(on/off).

One half-size pump in opera-tion via frequency converter.One full-size pump is mains-operated (on/off).

TM0

1 10

87 3

69

7

TM0

1 10

89 3

69

7

• Maintains a constant dif-ferential pressure through continuously variable ad-justment of the speed of one pump. The other mains-operated pumps are cut in/out according to the demand.

• The pump controlled by the frequency converter always starts first.

• Pump changeover is auto-matic and depends on load, time and fault.

• All pumps will be control-led by the frequency con-verter in rotation.

• Maintains a constant dif-ferential pressure through continuously variable ad-justment of the speed of one half-size pump. The orher pumps are mains-operated.

• The half-size pump con-trolled by the frequency converter always starts first.

• Pump changeover is auto-matic and depends on load, time and fault.

P

PFU 2000

P

PFU 2000

Q

H

H set

Q

H

H set

Q

H

H set

Q

H

H set

Page 29: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

Functions Delta

Control 2000

Examples of functioning, cont.The following table shows examples of Delta Control 2000 systems using constant differential pressure control.

Variable speed

GRUNDFOSDelta Control 2000 ME

GRUNDFOSDelta Control 2000 MEH

GRUNDFOSDelta Control ME (PO)

TM0

1 10

26 3

397

TM0

1 10

27 3

397

TM0

1 27

01

229

8

One pump in operation. The half-size pump with MGEmotor in operation.

One half-size pump withMGE motor in operation.

TM0

1 10

90

36

97

TM0

1 10

93

369

7

TM0

1 10

93

369

7Three pumps in operation. One half-size pump with MGE

motor and the full-size pumpin operation.

One half-size pump with MGEmotor and the full-size pumpin operation.

TM0

1 10

91

369

7

TM0

1 10

93

369

7

TM0

1 10

93

369

7

• Maintains a constant pressure through continu-ously variable adjust-ment of the speed of the pumps connected.

• The system performance is adjusted to the demand through cutting in/out the required number of pumps and through paral-lel control of the pumps in operation.

• Pump changeover is auto-matic and depends on load, time and fault.

• Maintains a constant pressure through continu-ously variable adjust-ment of the speed of the two half-size pumps with MGE motors, while the full-size pump is mains-operated. (on/off).

• The half-size pumps al-ways start first.

• Pump changeover is auto-matic and depends on load, time and fault.

• Maintains a constant pressure through continu-ously variable adjust-ment of the speed of the pumps connected.

• The system performance is adjusted to the demand through cutting in/out the required number of pumps and through paral-lel control of the pumps in operation.

• Pump changeover is auto-matic and depends on load, time and fault.

P

PFU 2000

MGE MGE MGE P

PFU 2000

MGE MGE P

PFU 2000

MGE MGE MGE

Q

H

H set

Q

H

H set

Q

H

H set

Q

H

H set

Q

H

H set

Q

H

H set

29

Page 30: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

30

Functions Del

ta Control 2000

Control parameters

Systems without PMU 2000

Controllers without the PMU 2000 can be used insystems having small time constants and are pre-set tothe control parameter "differential pressure". However,they can also be used with other control parameters,such as "flow" etc.

Cascade control:

Cascade control ensures automatic adjustment ofperformance to the system demand by cutting in/outthe required number of pumps.The controller will operate the system with as fewpumps as possible.

Automatic pump changeover:

Automatic pump changeover is made as follows:

• Fault-dependent pump changeover.If a pump is faulty, it will be switched off and the next pump ready for operation will be switched on.

• Time-dependent pump changeover.This ensures that the operating hours are distributed evenly on the pumps connected. This function is combined with the test run function.

Test run:

To eliminate the risk of pump seizure caused by longperiods of standstill, a test run lasting 1 second is carriedout once every 24 hours.

Setpoint:

The setpoint is set by means of the function selector inthe PFU 2000. It is also possible to stop all pumps, or toset all pumps to operate at maximum performance.

Remote setpoint setting:

A 0 - 10 V or 0 - 20 mA signal can be connected for remotesetpoint setting.

The locally set setpoint is set by means of the functionselector in the PFU 2000.

Sensor input:

Sensors giving the following analog signals can beconnected:

– 0 - 10 V,

– 0 - 20 mA,

– 4 - 20 mA.

Input for external start/stop:

A potential-free contact for external start/stop of allpumps can be connected.

TM

01 1

124

3897

TM

01 1

125

3897

PFU 2000

P

Differential pressure

FT

PFU 2000

Flow

TM

00 5

217

2796

TM

00 7

048

0296

100%0%

MAXSTOP

Setpoint

Function selector in the PFU 2000

0 10 V

Locally set setpoint

100%

Current setpointTr

ansm

itter

rang

eActual setpoint

Tran

smit

ter r

ang

e

Locally set setpoint

100%

10V

Setpoint via external signals

10V20mA

Page 31: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

Functions Delta

Control 2000

Systems with PMU 2000The PMU 2000 is designed for the control of variouspumps or pumping systems. As an example, the PMU2000 can be used for the control of GRUNDFOS circulatorpumps of the UPE type and pumping systems andcontrollers based on the PFU 2000, such as the DeltaControl 2000.The control parameters offered by the Delta Control2000 are shown in the table below:

Fig. 1

Fig. 2

Fig. 3

Fig. 4

Fig. 5

Fig. 6

Fig. 7

Fig. 8

Fig. Control parametersPossible with controller

without PMU with PMU

1 Differential pressure ● ●

2 Differential temperature ●

3Flow-pipe temperature with one sensor

4Return-pipe temperature with one sensor

5Differential temperature with one sensor signal

6 Flow ● ●

7 Level ●

8 Open loop (uncontrolled) ●

TM

00 4

985

4894

TM

00 4

998

3897

TM

00 2

718

3897

Differential pressure

PFU 2000

PMU 2000

P

BUSBUS

Differential temperature

PMU 2000

BUS

T

PFU 2000

BUS

Flow-pipe temperature

T

PFU 2000

PMU 2000

BUSBUS

TM

00 2

719

3897

TM

01 1

257

4097

TM

00 2

715

3897

TM

01 1

123

3897

TM

00 4

986

4894

Return-pipe temperature

PMU 2000

T

PFU 2000

BUS

Differential temperature

PMU 2000

T

PFU 2000

BUSBUS

Flow

PMU 2000

BUS

FT

PFU 2000

BUS

Level

BUS

PMU 2000

h

LTPFU 2000

BUS

Open loop

PFU 2000

PMU 2000

BUSBUS

31

Page 32: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

32

Functions Del

ta Control 2000

Cascade control:

Cascade control ensures automatic adjustment ofperformance to the system demand by cutting in/outthe required number of pumps. The controller willoperate the system with as few pumps as possible. Theon/off rate is limited by setting the switchingsequences.

Automatic pump changeover:

Automatic pump changeover is made as follows:

• Fault-dependent pump changeover.If a pump is faulty, it will be switched off and the next pump ready for operation will be switched on.

• Time-dependent pump changeover.This ensures that the operating hours are distributed evenly on the pumps connected. This function is combined with the test run function.

Test run:

To eliminate the risk of pump seizure caused by longperiods of standstill, a test run lasting 1 second is carriedout once every 24 hours.

Clock functions:

If the system demand varies during the day and/orduring the week, the pump performance required willalso vary. In this case, a clock program can be set in orderto achieve optimum performance of the pumps.It is possible to set a total of 10 switching times, allhaving individual setpoints.

Standby pumps:

In systems with more than one pump, standby pumpscan be selected. A standby pump is started only if one ofthe duty pumps is faulty. Example: In a system with fourpumps, of which one pump has been selected asstandby-pump, the maximum number of pumps in oper-ation at the same time will be three. The standby pumpis started only if one of the duty pumps is faulty.

Setpoint:

The max. setpoint is set in the PMU 2000 menu

Friction loss compensation:

The control unit is capable of compensating for frictionloss. The setpoint increases from an adjustablepercentage at zero flow to 100% at max. flow.

The actual flow is estimated based on internal operatingdata without the flow being measured directly.

Remote setpoint setting:

In view of optimizing system operation, it is often bestfor the system to operate according to a variablesetpoint instead of a constant setpoint. The selectedsettings influencing the setpoint will reduce "setpointmax".The following possibilities are available:

• "extern" (%)An external analog signal or potential-free contact influences the setpoint in accordance with a table.

• "timer" (minutes)An internal timer program in the PMU 2000 controls the setpoint in accordance with a table.

• "Temp Tf" (°C, °F)The flow-pipe temperature controls the setpoint in accordance with a table.

• "Temp Tr" (°C, °F)The return-pipe temperature controls the setpoint in accordance with a table.

• "Temp To" (°C, °F)The ambient temperature controls the setpoint in ac-cordance with a table.

• "level" (m, cm, ft, in)The level signal controls the setpoint in accordance with a table.

• "flow" (m3/h, l/h, l/s, gpm) The flow signal controls the setpoint in accordance with a table.Example of application: Differential pressure drop compensation in circulation system if a flow meter signal is available.

• "flow/I" (%), (applies only to Delta Control 2000 F)An internal flow signal controls the setpoint in ac-cordance with a table.Example of application: Differential pressure drop compensation in circulation system if no flow meter signal is available.

Sensor input:

Sensors giving the following analog signals can beconnected:

– 0 - 10 V,

– 0 - 20 mA,

– 4 - 20 mA.

TM

00 4

989

4894

Set A

Setpoint max. 12.5 bar

Setpoint

1 3

C

A

2 Time

B

Time

Setpoint

Clock program with three switching times

TM

00 4

991

4894

Setpoint max

Q

H

100 %

60 %

Setpoint max.100%

60%

Q

H

Friction loss compensation

Page 33: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

Delta Control 2000

Technical data

Dimensions and weightsDimensions and weights are for control cabinets with aPFU 2000 control panel.

All motors must be three-phase.

The starting methods of the motors are:

• DOL (Direct-on-line starting)

• SD (Star-delta starting)

• E (Electronic soft start via frequency converter).

Delta Control 2000 MF

TM

01 0

473

2402

D B

HDelta Control 2000

Motor[kW]

Mounting of control

cabinetStartingfull-size

Delta Control 2000 MF for 1 pump

Delta Control 2000 MF for 2 pumps

Delta Control 2000 MF for 3 pumps

Delta Control 2000 MF for 4 pumps

Dimensions [mm] Weight

[kg]

Dimensions [mm] Weight

[kg]

Dimensions [mm] Weight

[kg]

Dimensions [mm] Weight

[kg]H B D H B D H B D H B D

0.75 Floor mount. DOL 1000 800 300 78 1000 800 300 79 1000 800 300 80 1000 800 300 81

1.1 Floor mount. DOL 1000 800 300 78 1000 800 300 79 1000 800 300 80 1000 800 300 81

1.5 Floor mount. DOL 1000 800 300 78 1000 800 300 79 1000 800 300 80 1000 800 300 81

2.2 Floor mount. DOL 1000 800 300 78 1000 800 300 79 1000 800 300 80 1000 800 300 81

3 Floor mount.DOL 1000 800 300 78 1000 800 300 79 1000 800 300 80 1000 800 300 81

SD 1000 800 300 78 1000 800 300 80 1200 800 300 95 1200 1000 300 113

4 Floor mount.DOL 1200 800 300 100 1200 800 300 101 1200 800 300 102 1200 800 300 103

SD 1200 800 300 100 1200 800 300 102 1200 800 300 104 1200 1000 300 122

5.5 Floor mount.DOL 1200 800 300 100 1200 800 300 101 1200 800 300 103 1200 800 300 104

SD 1200 800 300 100 1200 800 300 103 1200 800 300 105 1200 1000 300 122

7.5 Floor mount.DOL 1200 800 300 92 1200 800 300 93 1200 800 300 94 1200 800 300 96

SD 1200 800 300 92 1200 800 300 94 1200 800 300 96 1200 1000 300 114

11 Floor mount.DOL 1900 800 400 168 1900 800 400 172 1900 1000 400 202 1900 1000 400 205

SD 1900 800 400 171 1900 800 400 174 1900 1000 400 204 1900 1000 400 208

15 Floor mount.DOL 1900 800 400 174 1900 800 400 179 1900 1000 400 206 1900 1000 400 209

SD 1900 1000 400 200 1900 1000 400 204 1900 1200 400 244 1900 1200 400 247

18.5 Floor mount.DOL 1900 1000 400 207 1900 1000 400 212 1900 1200 400 253 1900 1200 400 258

SD 1900 1000 400 208 1900 1000 400 213 1900 1600 400 301 1900 1600 400 306

22 Floor mount.DOL 1900 1000 400 208 1900 1000 400 213 1900 1200 400 253 1900 1200 400 258

SD 1900 1000 400 208 1900 1000 400 214 1900 1600 400 303 1900 1600 400 310

30 Floor mount.DOL 1900 1200 400 262 1900 1200 400 260 1900 1800 400 409 1900 2000 400 441

SD 1900 1200 400 264 1900 1200 400 264 1900 1800 400 414 1900 2200 400 499

37 Floor mount.DOL 1900 1200 400 269 1900 1200 400 266 1900 1800 400 416 1900 2000 400 449

SD 1900 1200 400 271 1900 1200 400 271 1900 1800 400 424 1900 2200 400 510

45 Floor mount.DOL 1900 1200 400 269 1900 1800 400 403 1900 1800 400 416 1900 2000 400 449

SD 1900 1200 400 271 1900 1800 400 408 1900 1800 400 424 1900 2200 400 510

55 Floor mount.DOL 1900 2000 500 552 1900 2200 500 612 1900 2600 500 690 1900 3000 500 794

SD 1900 2000 500 553 1900 2200 500 614 1900 2600 500 693 1900 3000 500 794

75 Floor mount.DOL 1900 2000 500 554 1900 2200 500 616 1900 2600 500 697 1900 3000 500 802

SD 1900 2000 500 556 1900 2200 500 618 1900 2600 500 700 1900 3000 500 804

Technical data, Delta Control 2000

33

Page 34: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

34

Technical data Del

ta Control 2000

Dimensions and weightsDimensions and weights are for control cabinets with aPFU 2000 control panel.

All motors must be three-phase.

Delta Control 2000 MFH

TM

01 0

473

2402

D B

HDelta Control 2000

Motor

Startingfull-size

Startinghalf-size

Delta Control 2000 MFH for 3 pumps

(1 full-size and 2 half-size)

Delta Control 2000 MFH for 4 pumps

(2 full-size and 2 half-size)

Full-size[kW]

Mounting of control

cabinet

Half-size[kW]

Dimensions[mm] Weight

[kg]

Dimensions[mm] Weight

[kg]H B D H B D

11Floor

mounting7.5

DOL DOL 1200 800 300 95 1200 800 300 100

SD SD 1200 1000 300 97 1200 1000 300 123

15Floor

mounting7.5

DOL DOL 1200 1000 300 115 1200 1000 300 118

SD SD 1200 1000 300 118 1200 1000 300 125

15Floor

mounting11

DOL DOL 1900 1000 400 202 1900 1000 400 205

SD SD 1900 1000 400 205 1900 1000 400 208

18.5Floor

mounting11

DOL DOL 1900 1000 400 204 1900 1000 400 207

SD SD 1900 1000 400 205 1900 1000 400 209

22Floor

mounting11

DOL DOL 1900 1000 400 204 1900 1000 400 207

SD SD 1900 1000 400 206 1900 1000 400 210

22Floor

mounting15

DOL DOL 1900 1200 400 207 1900 1000 400 210

SD SD 1900 1200 400 244 1900 1200 400 248

30Floor

mounting15

DOL DOL 1900 1600 400 208 1900 1400 400 320

SD SD 1900 1200 400 247 1900 1600 400 299

30Floor

mounting18.5

DOL DOL 1900 1600 400 218 1900 1400 400 330

SD SD 1900 1600 400 304 1900 1600 400 308

37Floor

mounting18.5

DOL DOL 1900 1000 400 218 1900 1400 400 330

SD SD 1900 1600 400 305 1900 1600 400 310

37Floor

mounting22

DOL DOL 1900 1000 400 254 1900 1400 400 330

SD SD 1900 1600 400 305 1900 1600 400 310

45Floor

mounting30

DOL DOL 1900 1600 400 319 1900 1600 400 323

SD SD 1900 1600 400 325 1900 1600 400 331

55Floor

mounting30

DOL DOL 1900 1600 400 323 1900 1600 400 330

SD SD 1900 1600 400 325 1900 1600 400 333

75Floor

mounting37

DOL DOL 1900 1600 400 330 1900 1600 400 339

SD SD 1900 1800 400 424 1900 1800 400 431

75Floor

mounting45

DOL DOL 1900 1600 400 330 1900 1600 400 339

SD SD 1900 1800 400 424 1900 1800 400 431

Page 35: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

Technical data Delta

Control 2000

Dimensions and weights Dimensions and weights are for control cabinets with aPFU 2000 control panel.

All motors must be three-phase.

Note: E-pumps marked with """ must be with single-phase mains connection.

Delta Control 2000 ME

TM

00 9

394

2402

D B

H

Delta Control 2000

Motor[kW]

Startingfull-size

[kW]

Delta Control 2000 ME for 1 pump

Delta Control 2000 ME for 2 pumps

Delta Control 2000 ME for 3 pumps

Delta Control 2000 ME for 4 pumps

Dimensions [mm] Weight

[kg]

Dimensions[mm] Weight

[kg]

Dimensions[mm] Weight

[kg]

Dimensions[mm] Weight

[kg]H B D H B D H B D H B D

1.1 " E 380 380 210 15.0 380 380 210 14.2 600 380 210 19.8 600 380 210 20.1

1.1 E 380 380 210 15.0 380 380 210 14.2 600 380 210 19.8 600 380 210 20.1

1.5 E 600 380 210 23.0 600 380 210 19.8 600 380 210 20.2 600 380 210 20.6

2.2 E 600 380 210 23.0 600 380 210 19.8 600 380 210 20.2 600 380 210 20.6

3 E 600 380 210 23.0 600 380 210 19.8 600 380 210 20.2 600 380 210 20.6

4 E 600 380 210 23.0 600 380 210 19.8 600 380 210 20.2 600 380 210 20.6

5.5 E 600 380 210 24.0 600 380 210 19.8 600 380 210 20.2 600 380 210 20.9

7.5 E 600 380 210 24.0 600 380 210 35.0 600 380 210 36.0 600 600 210 47.0

11 E 600 380 210 24.0 600 380 210 35.0 600 380 210 37.0 600 600 210 48.0

15 E 600 380 210 24.0 600 380 210 36.0 600 600 210 47.0 760 760 210 67.0

18.5 E 600 380 210 24.0 600 380 210 36.0 760 760 210 66.0 760 760 210 67.0

22 E 600 380 210 25.0 600 600 210 47.0 760 760 210 67.0 760 760 210 68.0

35

Page 36: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

36

Technical data Del

ta Control 2000

Delta Control 2000 MEH

Delta Control 2000 MES

Motor

Startingfull-size

Startinghalf-size

Delta Control 2000 MEH for 3 pumps

(1 full-size and 2 half-size)

Delta Control 2000 MEH for 4 pumps

(2 full-size and 2 half-size)

Full-size

[kW]

Mountingof control

cabinet

Half-size

[kW]

Dimensions[mm] Weight

[kg]

Dimensions[mm] Weight

[kg]H B D H B D

1.1 Wall mount. 0.75 " DOL E 600 380 210 20.1 600 380 210 20.6

1.5 Wall mount. 1.1 " DOL E 600 380 210 20.1 600 380 210 20.6

2.2 Wall mount. 1.1 " DOL E 600 380 210 20.1 600 380 210 20.6

2.2 Wall mount. 1.5 DOL E 600 380 210 20.3 600 380 210 20.9

3 Wall mount. 1.5DOL E 600 380 210 20.3 600 380 210 20.9

SD E 600 380 210 20.3 600 380 210 22.3

3 Wall mount. 2.2DOL E 600 380 210 20.3 600 380 210 20.9

SD E 600 380 210 20.3 600 380 210 22.3

4 Wall mount. 2.2DOL E 600 380 210 31.1 600 380 210 31.1

SD E 600 600 210 31.1 600 600 210 32.5

4 Wall mount. 3DOL E 600 380 210 31.1 600 380 210 31.1

SD E 600 600 210 31.1 600 600 210 32.5

5.5 Wall mount. 3DOL E 600 600 210 31.1 600 600 210 31.1

SD E 600 600 210 31.1 600 600 210 32.9

5.5 Wall mount. 4DOL E 600 600 210 31.5 600 600 210 31.5

SD E 600 600 210 31.5 600 600 210 32.9

7.5 Wall mount. 4DOL E 600 600 210 31.5 1000 800 300 31.5

SD E 600 600 210 31.5 1000 800 300 65.0

11 Wall mount. 5.5DOL E 600 600 210 31.5 1000 800 300 31.5

SD E 600 600 210 31.5 1000 800 300 65.0

15 Wall mount. 11DOL E 600 600 210 47.0 760 760 210 67.0

SD E 600 600 210 48.0 760 760 210 68.0

18.5 Wall mount. 11DOL E 600 600 210 48.0 760 760 210 69.0

SD E 600 600 210 48.0 760 760 210 69.0

22 Wall mount. 11DOL E 600 600 210 50.0 1000 800 300 91.0

SD E 600 600 210 49.0 760 760 210 70.0

18.5 Wall mount. 15DOL E 600 600 210 49.0 760 760 210 69.0

SD E 600 600 210 49.0 760 760 210 70.0

22 Wall mount. 15DOL E 1000 800 300 86.0 1000 800 300 91.0

SD E 760 760 210 67.0 760 760 210 71.0

22 Wall mount. 18.5DOL E 1000 800 300 86.0 1000 800 300 91.0

SD E 760 760 210 67.0 1000 800 300 71.0

Motor [kW]

Mountingof control

cabinet

Startingfull-size

Delta Control 2000 MES for 2 pumps

Delta Control 2000 MES for 3 pumps

Delta Control 2000 MES for 4 pumps

Dimensions[mm] Weight

[kg]

Dimensions [mm] Weight

[kg]

Dimensions[mm] Weight

[kg]H B D H B D H B D

11 Wall mount. E/DOL 600 380 210 36.0 600 600 210 47.0 600 600 210 49.0

11 Wall mount. E/SD 600 600 210 46.0 600 600 210 48.0 600 600 210 51.0

15 Wall mount. E/DOL 600 600 210 46.0 600 600 210 48.0 760 760 210 67.0

15 Wall mount. E/SD 600 600 210 47.0 600 600 210 49.0 760 760 210 70.0

18.5 Wall mount. E/DOL 600 600 210 47.0 760 760 210 68.0 760 760 210 71.0

18.5 Wall mount. E/SD 600 600 210 48.0 760 760 210 68.0 760 760 210 72.0

22 Wall mount. E/DOL 600 600 210 50.0 1000 800 300 90.0 1000 800 300 94.0

22 Wall mount. E/SD 600 600 210 49.0 760 760 210 70.0 760 760 210 73.0

Page 37: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

Technical data Delta

Control 2000

Dimensions and weightsThe Delta Control 2000 ME (PO) is prepared for DIN-railmounting.

Delta Control 2000 ME (PO)

VersionWeight [kg]

Net weight Gross Weight

Delta Control 2000 ME (PO) 1.4 1.7

TM

00 2

734

2402

80

60 ø5

150

200

200

140

98

37

Page 38: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

38

Technical data Del

ta Control 2000

Product numbersProduct numbers for control cabinets with a PFU 2000control panel.

All motors must be three-phase.

Supply voltage:3 x 400 V +6%/–10%, N, 50 Hz, PE.

Enclosure class: IP 54.

The starting methods of the motors are:

• DOL (Direct-on-line starting)

• SD (Star-delta starting).

Delta Control 2000 MF

Motor[kW]

Mountingof Control

Cabinet

Startingfull-size

Product numbers

Delta Control 2000 MF for 1 pump

Delta Control 2000 MF for 2 pumps

Delta Control 2000 MF for 3 pumps

Delta Control 2000 MFfor 4 pumps

0.75 Floor mounting DOL 96 01 15 15 96 01 15 45 96 01 15 75 96 01 16 05

1.1 Floor mounting DOL 96 01 15 16 96 01 15 46 96 01 15 76 96 01 16 06

1.5 Floor mounting DOL 96 01 15 17 96 01 15 47 96 01 15 77 96 01 16 07

2.2 Floor mounting DOL 96 01 15 18 96 01 15 48 96 01 15 78 96 01 16 08

3 Floor mountingDOL 96 01 15 19 96 01 15 49 96 01 15 79 96 01 16 09

SD 96 01 15 32 96 01 15 62 96 01 15 92 96 01 16 22

4 Floor mountingDOL 96 01 15 20 96 01 15 50 96 01 15 80 96 01 16 10

SD 96 01 15 33 96 01 15 63 96 01 15 93 96 01 16 23

5.5 Floor mountingDOL 96 01 15 21 96 01 15 51 96 01 15 81 96 01 16 11

SD 96 01 15 34 96 01 15 64 96 01 15 94 96 01 16 24

7.5 Floor mountingDOL 96 01 15 22 96 01 15 52 96 01 15 82 96 01 16 12

SD 96 01 15 35 96 01 15 65 96 01 15 95 96 01 16 25

11 Floor mountingDOL 96 01 15 23 96 01 15 53 96 01 15 83 96 01 16 13

SD 96 01 15 36 96 01 15 66 96 01 15 96 96 01 16 26

15 Floor mountingDOL 96 01 15 24 96 01 15 54 96 01 15 84 96 01 16 14

SD 96 01 15 37 96 01 15 67 96 01 15 97 96 01 16 27

18.5 Floor mountingDOL 96 01 15 25 96 01 15 55 96 01 15 85 96 01 16 15

SD 96 01 15 38 96 01 15 68 96 01 15 98 96 01 16 28

22 Floor mountingDOL 96 01 15 26 96 01 15 56 96 01 15 86 96 01 16 16

SD 96 01 15 39 96 01 15 69 96 01 15 99 96 01 16 29

30 Floor mountingDOL 96 01 15 27 96 01 15 57 96 01 15 87 96 01 16 17

SD 96 01 15 40 96 01 15 70 96 01 16 00 96 01 16 30

37 Floor mountingDOL 96 01 15 28 96 01 15 58 96 01 15 88 96 01 16 18

SD 96 01 15 41 96 01 15 71 96 01 16 01 96 01 16 31

45 Floor mountingDOL 96 01 15 29 96 01 15 59 96 01 15 89 96 01 16 19

SD 96 01 15 42 96 01 15 72 96 01 16 02 96 01 16 32

55 Floor mountingDOL 96 01 15 30 96 01 15 60 96 01 15 90 96 01 16 20

SD 96 01 15 43 96 01 15 73 96 01 16 03 96 01 16 33

75 Floor mountingDOL 96 01 15 31 96 01 15 61 96 01 15 91 96 01 16 21

SD 96 01 15 44 96 01 15 74 96 01 16 04 96 01 16 34

Page 39: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

Technical data Delta

Control 2000

Product numbersProduct numbers for control cabinets with a PFU 2000control panel.

All motors must be three-phase.

Supply voltage:3 x 400 V +6%/–10%, N, 50 Hz, PE.

Enclosure class: IP 54.

The starting methods of the motors are:

• DOL (Direct-on-line starting)

• SD (Star-delta starting).

Delta Control 2000 MFH

MotorMountingof Control

Cabinet

Startingfull-size

Startinghalf-size

Product numbers

Full-size[kW]

Half-size[kW]

Delta Control 2000 MFH for 3 pumps

(1 full-size and 2 half-size)

Delta Control 2000 MFH for 4 pumps

(2 full-size and 2 half-size)

11 7.5 Floor mountingDOL DOL 96 01 16 35 96 01 16 63

SD SD 96 01 16 49 96 01 16 77

15 7.5 Floor mountingDOL DOL 96 01 16 36 96 01 16 64

SD SD 96 01 16 50 96 01 16 78

15 11 Floor mountingDOL DOL 96 01 16 37 96 01 16 65

SD SD 96 01 16 51 96 01 16 79

18.5 11 Floor mountingDOL DOL 96 01 16 38 96 01 16 66

SD SD 96 01 16 52 96 01 16 80

22 11 Floor mountingDOL DOL 96 01 16 39 96 01 16 67

SD SD 96 01 16 53 96 01 16 81

22 15 Floor mountingDOL DOL 96 01 16 40 96 01 16 68

SD SD 96 01 16 54 96 01 16 82

30 15 Floor mountingDOL DOL 96 01 16 41 96 01 16 69

SD SD 96 01 16 55 96 01 16 83

30 18.5 Floor mountingDOL DOL 96 01 16 42 96 01 16 70

SD SD 96 01 16 56 96 01 16 84

37 18.5 Floor mountingDOL DOL 96 01 16 43 96 01 16 71

SD SD 96 01 16 57 96 01 16 85

37 22 Floor mountingDOL DOL 96 01 16 44 96 01 16 72

SD SD 96 01 16 58 96 01 16 86

45 22 Floor mountingDOL DOL 96 01 16 45 96 01 16 73

SD SD 96 01 16 59 96 01 16 88

55 30 Floor mountingDOL DOL 96 01 16 46 96 01 16 74

SD SD 96 01 16 60 96 01 16 88

75 37 Floor mountingDOL DOL 96 01 16 47 96 01 16 75

SD SD 96 01 16 61 96 01 16 89

75 45 Floor mountingDOL DOL 96 01 16 48 96 01 16 76

SD SD 96 01 16 62 96 01 16 90

39

Page 40: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

40

Technical data Del

ta Control 2000

Product numbersProduct numbers for control cabinets with a PFU 2000control panel.

All motors must be three-phase

Note: E-pumps marked with """ must be with single-phase mains connection.

Supply voltage:3 x 400 V +6%/–10%, N, 50 Hz, PE.

Enclosure class: IP 54.

The starting methods of the motors are:

• DOL (Direct-on-line starting)

• SD (Star-delta starting).

Delta Control 2000 ME

Motor[kW]

Mountingof control

cabinet

Startingfull-size

Product numbers

Delta Control 2000 ME for 1 pump

Delta Control 2000 ME for 2 pumps

Delta Control 2000 ME for 3 pumps

Delta Control 2000 ME for 4 pumps

1.1 " Wall mounting E 96 01 14 88 96 01 14 95 96 01 15 02 96 01 15 09

1.1 Wall mounting E 96 01 90 70 96 01 90 78 96 01 90 86 96 01 90 94

1.5 Wall mounting E 96 01 14 89 96 01 14 96 96 01 15 03 96 01 15 10

2.2 Wall mounting E 96 01 14 90 96 01 14 97 96 01 15 04 96 01 15 11

3 Wall mounting E 96 01 14 91 96 01 14 98 96 01 15 05 96 01 15 12

4 Wall mounting E 96 01 14 92 96 01 14 99 96 01 15 06 96 01 15 13

5.5 Wall mounting E 96 01 14 93 96 01 15 00 96 01 15 07 96 01 15 14

7.5 Wall mounting E 96 01 52 97 96 01 25 91 96 01 25 93 96 01 25 94

11 Wall mounting E 96 01 33 57 96 01 33 61 96 01 33 65 96 01 33 69

15 Wall mounting E 96 01 33 58 96 01 33 62 96 01 33 66 96 01 33 70

18.5 Wall mounting E 96 01 33 59 96 01 33 63 96 01 33 67 96 01 33 71

22 Wall mounting E 96 01 33 60 96 01 33 64 96 01 33 68 96 01 33 72

Page 41: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

Technical data Delta

Control 2000

Delta Control 2000 MEH

Delta Control MES

Delta Control 2000 ME (PO)

Supply voltage:1 x 230 V +6%/–10%, N, 50 Hz, PE.

Enclosure class: IP 42.

MotorMountingof control

cabinet

Startingfull-size

Startinghalf-size

Product numbers

Full-size[kW]

Half-size[kW]

Delta Control 2000 MEH for 3 pumps

(1 full-size and 2 half-size)

Delta Control 2000 MEH for 4 pumps

(2 full-size and 2 half-size)

1.1 0.75 " Wall mounting DOL E 96 01 16 91 96 01 17 11

1.5 1.1 " Wall mounting DOL E 96 01 16 92 96 01 17 12

2.2 1.1 " Wall mounting DOL E 96 01 16 93 96 01 17 13

2.2 1.5 Wall mounting DOL E 96 01 16 94 96 01 17 14

3 1.5 Wall mountingDOL E 96 01 16 95 96 01 17 15

SD E 96 01 17 03 96 01 17 23

3 2.2 Wall mountingDOL E 96 01 16 96 96 01 17 16

SD E 96 01 17 04 96 01 17 24

4 2.2 Wall mountingDOL E 96 01 16 97 96 01 17 17

SD E 96 01 17 05 96 01 17 25

4 3 Wall mountingDOL E 96 01 16 98 96 01 17 18

SD E 96 01 17 06 96 01 17 26

5.5 3 Wall mountingDOL E 96 01 16 99 96 01 17 19

SD E 96 01 17 07 96 01 17 27

5.5 4 Wall mountingDOL E 96 01 17 00 96 01 17 20

SD E 96 01 17 08 96 01 17 28

7.5 4 Wall mountingDOL E 96 01 17 01 96 01 17 21

SD E 96 01 17 09 96 01 17 29

11 5.5 Wall mountingDOL E 96 01 17 02 96 01 17 22

SD E 96 01 17 10 96 01 17 30

15 11 Wall mountingDOL E 96 01 36 05 96 01 36 11

SD E 96 01 36 06 96 01 36 12

18,5 11 Wall mountingDOL E 96 01 36 07 96 01 36 13

SD E 96 01 36 08 96 01 36 14

22 11 Wall mountingDOL E 96 01 36 09 96 01 36 15

SD E 96 01 36 10 96 01 36 16

18.5 15 Wall mountingDOL E 96 01 36 17 96 01 36 23

SD E 96 01 36 18 96 01 36 24

22 15 Wall mountingDOL E 96 01 36 19 96 01 36 25

SD E 96 01 36 20 96 01 36 26

22 18.5 Wall mountingDOL E 96 01 36 29 96 01 36 35

SD E 96 01 36 30 96 01 36 36

Motor[kW]

Mountingof control

cabinet

Startingfull-size

Product numbers

Delta Control 2000 MES for 2 pumps

Delta Control 2000 MES for 3 pumps

Delta Control 2000 MES for 4 pumps

11 Wall mounting E/DOL 96 01 3461 96 01 34 63 96 01 34 65

11 Wall mounting E/SD 96 01 34 62 96 01 34 64 96 01 34 66

15 Wall mounting E/DOL 96 01 34 67 96 01 34 69 96 01 34 71

15 Wall mounting E/SD 96 01 34 68 96 01 34 70 96 01 34 72

18,5 Wall mounting E/DOL 96 01 34 73 96 01 34 75 96 01 34 77

18,5 Wall mounting E/SD 96 01 34 74 96 01 34 76 96 01 34 78

22 Wall mounting E/DOL 96 01 34 79 96 01 34 81 96 01 34 83

22 Wall mounting E/SD 96 01 34 80 96 01 34 82 96 01 34 84

Description Product number

Delta Control 2000 ME (PO) 96 01 20 91

41

Page 42: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

42

Control 2000Delta Control 2000

Optional equipment

Optional equipment is fitted from factory prior todelivery. Therefore, it is necessary to order the requiredoptional equipment at the same time as ordering theControl 2000 or Delta Control 2000.

PMU 2000The PMU 2000 is fitted in the front door of the controlcabinet instead of the PFU 2000 control panel.

The PMU 2000 enables regular optimization of opera-tion and read-out of operating data.

Switching off of neutral leadAs standard, the Control 2000 and Delta Control 2000are supplied with a main switch switching off all threephases. If required, the controller 2000 can be suppliedwith a main switch switching off the three phases andthe neutral lead.

Emergency operation switchThe emergency operation switch enables emergencyoperation if fault occurs in the control cabinet.Order one emergency operation switch for each pump.

Example:If emergency operation switches are required for DeltaControl 2000 MFH with four pumps, order the following:

• two 96 02 00 98 (for mains-operated pumps) and

• two 96 02 00 99 (for half-size pumps).

Description(language)

MountingReference

number

Danish In front door 96 02 00 52

English In front door 96 02 00 53

French In front door 96 02 00 54

Dutch In front door 96 02 00 55

Italian In front door 96 02 00 56

Swedish In front door 96 02 00 57

German In front door 96 02 00 58

Portuguese In front door 96 02 00 59

Spanish In front door 96 02 00 60

Finnish In front door 96 02 00 62

Description MountingReference

number

Main switch incorporating the switching off of the neutral lead (40 A)

In front door 96 02 00 23

Main switch incorporating the switching off of the neutral lead (100 A)

In front door 96 02 00 22

Main switch incorporating the switching off of the neutral lead (175 A)

In front door 96 02 00 21

Main switch incorporating the switching off of the neutral lead (250 A)

In front door 96 02 00 20

Main switch incorporating the switching off of the neutral lead (400 A)

In front door 96 02 00 19

Main switch incorporating the switching off of the neutral lead (630 A)

In front door 96 02 00 18

Main switch incorporating the switching off of the neutral lead (800 A)

In front door 96 02 00 17

Main switch incorporating the switching off of the neutral lead (1250 A)

In front door 96 02 00 16

Main switch incorporating the switching off of the neutral lead (1750 A)

In front door 96 02 00 15

Main switch incorporating the switching off of the neutral lead (2000 A)

In front door 96 02 00 14

Main switch incorporating the switching off of the neutral lead (2500 A)

In front door 96 02 00 13

Description MountingReference

number

Pump for mains operationInside control

cabinet96 02 00 98

Pump with externalfrequency converter

Inside control cabinet

96 02 00 99

Pump with MGE-motorInside control

cabinet96 02 01 00

Page 43: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

Optional equipment Delta

Control 2000 Control 2000

Phase-failure protectionIf required, protection against phase failure (i.e. failureof one or two phases) is available. In case of phasefailure the system is cut out.

Lightning protectionIf required, the system can be protected against strokeof lightning.

VoltmeterA voltmeter indicates the mains voltage between theindividual phases.

AmmeterAn ammeter indicates the power consumption for asingle phase.

Operating lightThe operating light for a pump is lit when the pump is inoperation.

Order one light for each pump.

Fault lightThe fault light for a pump is lit if a fault occurs in thepump.

Order one light for each pump.

Panel lightThe panel light is lit whenever the door of the controlcabinet is opened.

Extra documentationTo supplement the documentation supplied with thesystem, an extra set may be supplied, consisting of:

• Installation and Operating Instructions,

• Wiring Diagram,

• List of Default Values.

This extra set may be ordered under the followingnumbers:

Enclosure classAs standard, the system is supplied in enclosure class IP54.The Control 2000 and Delta Control 2000 are also avail-able without control cabinet in enclosure class IP 00with all components mounted on one back plateprepared for mounting in a control cabinet or panel.

Description MountingReference

number

Phase-failureprotection

Inside control cabinet

96 02 01 17

Description MountingReference

number

Lightning protectionInside control

cabinet96 02 01 25

Description MountingReference

number

Voltmeter In front door 96 02 01 18

Voltmeter(with changeover switch)

In front door 96 02 01 19

Description MountingReference

number

Ammeter (6 A) In front door 96 02 01 20

Ammeter (15 A) In front door 96 02 01 21

Ammeter (40 A) In front door 96 02 01 22

Ammeter (100 A) In front door 96 02 01 23

Ammeter (150 A) In front door 96 02 01 24

Description MountingReference

number

Operating light In front door 96 02 01 39

Description Mounting Referencenumber

Fault light In front door 96 02 01 40

Description MountingReference

number

Panel lightInside control

cabinet96 02 01 26

Description(language)

Referencenumber

English 96 02 00 37

Danish 96 02 00 38

French 96 02 00 39

Dutch 96 02 00 40

Italian 96 02 00 41

Swedish 96 02 00 42

German 96 02 00 43

Spanish 96 02 00 45

DescriptionReference

number

Built-in version IP 00 96 02 00 50

43

Page 44: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

44

Control 2000Delta Control 2000

Accessories

The following accessories can be ordered separately andfitted/replaced at any time.

Contrary to optional equipment, accessories will not befitted from factory.

PMU 2000As an accessory to all controllers, the PMU 2000 can beordered in enclosure class IP 42. The unit can be locatedoutside the control cabinet, if required.

The PMU 2000 enables regular optimization of opera-tion and read-out of operating data.

PCU 2000The PCU 2000 enables control and monitoring of thesystem via an external SCADA system. The PCU 2000 inenclosure class IP 42 is supplied separately for mountingoutside the Control 2000 or Delta Control 2000 controlcabinet. The PCU 2000 offers remote fault indication ofoperation, fault and local operation via potential-freechangeover contacts. The PCU 2000 also offers thepossibility of external setpoint influence and on/offoperation of the system.

If the system consists of more than four pumps, two PCU2000 units must be connected.

Description(language)

Referencenumber

Danish 62 57 28 41

English 62 57 28 47

French 62 57 28 45

Dutch 62 57 28 43

Italian 62 57 28 46

Swedish 62 57 28 40

German 62 57 28 44

Portuguese 62 57 28 49

Spanish 62 57 28 48

Finnish 62 57 28 42

DescriptionMax. number

of pumpsReference

number

PCU 2000 2 62 55 22 41

PCU 2000 4 62 55 24 41

Page 45: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

45

Page 46: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

46

Page 47: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected

47

Page 48: Control 2000, Delta Control 2000 - Unopomp - … · 3 Control 2000 General data Delta Control 2000 Application Control 2000 The Control 2000 controller is used for pumps connected