  • GRUNDFOS DATABOOKLET

    Control 2000, Delta Control 2000Controllers for pumps connected in parallel

  • 2

    Contents

    General dataApplication Page 3Control 2000 Page 3Delta Control 2000 Page 3

    General data, Control 2000System configuration Page 4

    Functions, Control 2000Functions Page 5Type key Page 6Examples of functioning Page 8Control parameters Page 10

    Technical data, Control 2000Dimensions and weight Page 13Product numbers Page 18

    General data, Delta Control 2000System configuration Page 24

    Functions, Delta Control 2000Functions Page 25Type key Page 26Examples of functioning Page 28Control parameters Page 30Systems with PMU 2000 Page 31

    Technical data, Delta Control 2000Dimensions and weights Page 34Product numbers Page 38

    Optional equipmentPMU 2000 Page 42Switching off of neutral lead Page 42Emergency operation switch Page 42Phase-failure protection Page 43Lightning protection Page 43Voltmeter Page 43Ammeter Page 43Operating light Page 43Fault light Page 43Panel light Page 43Extra documentation Page 43Enclosure class Page 43

    AccessoriesPMU 2000 Page 44PCU 2000 Page 44

  • Control 2000Delta Control 2000

    General data

    Application

    Control 2000

    The Control 2000 controller is used for pumps connectedin parallel in systems which should supply a geometrichead.

    Typical systems are water supply systems, pressureboosting systems or other systems characterized by avarying water consumption and in which a constantpressure should be maintained.

    The Control 2000 controller features all the necessarycomponents to control and monitor 2 - 6 pumpsconnected in parallel.

    Delta Control 2000

    The Delta Control 2000 controller is used for pumpsconnected in parallel in closed systems with the purposeof circulating a pumped liquid.

    Typical systems are heating or air-conditioning systemscharacterized by a variable need for pumping and inwhich a constant differential pressure should be main-tained. The control of pumps according to temperatureor flow is also possible using the Delta Control 2000.

    The Delta Control 2000 controller features all the neces-sary components to control and monitor 1 - 4 pumpsconnected in parallel.

    General data, Control 2000

    TM0

    1 28

    56 2

    598

    TM0

    1 28

    55 2

    598

    Pumps

    Control 2000

    System characteristics

    Geometrichead

    TM0

    1 28

    58 2

    598

    TM0

    1 28

    57 2

    598

    Delta Control 2000

    Pumps

    Boiler orrefrigeration unit

    Heating orair-conditioning system

    3

  • 4

    General data

    Control 2000

    System configurationThe Control 2000 consists of three main groups:

    1. Control 2000 S is used for mains operation (on/offoperation) of standard pumps with standard motors.

    2. Control 2000 F features a standard frequencyconverter and can be used together with pumps withstandard motors.

    3. Control 2000 E is used when the system comprisesE-pumps (Grundfos pumps equipped with GrundfosMGE motors).

    Each main group consists of subgroups, see the tablebelow:

    Abbreviations:

    M: The Control 2000 features a microprocessor for thecontrol of all functions.

    S: Some or all of the pumps in the system are on/off-operated.

    F: The Control 2000 features a frequency converter forthe speed control of some of the pumps in thesystem. One pump only is speed-controlled at atime.

    E: Some or all of the pumps in the system are E-pumps(pumps with integrated frequency converter).

    H: The system has one or two half-size pumps (one half-size pump provides approximately thesame head as one full-size pump, but only approximately half the flow).

    Main groupSub-

    group

    Description of pumps

    Size NumberNumber of controlled

    pumps Mode of operation Comments

    Co

    ntr

    ol 2

    00

    0 S

    (on

    /off

    )

    MS Full-size All Mains operation (on/off).

    MSH

    Half-size 1 Mains operation (on/off).

    Full-sizeAll other pumps

    Mains operation (on/off).

    Co

    ntr

    ol 2

    00

    0 F

    (Var

    iab

    le s

    pee

    d)

    MF Full-size

    1 1Speed control via frequency con-verter mounted in control cabinet.

    Frequency-converter control rotates among all pumps in the system.

    All other pumps

    Mains operation (on/off).

    MFH

    Half-size 2 1Speed control via frequency con-verter mounted in control cabinet.

    Frequency-converter control alter-nates between the two pumps. The uncontrolled pump is mains operated (on/off).

    Full-sizeAll other pumps

    Mains operation (on/off).

    Co

    ntr

    ol 2

    00

    0 E

    (Var

    iab

    le s

    pee

    d)

    ME Full-size All AllSpeed control via frequency con-verter integrated in the motor.

    All pumps in operation run at the same speed (cascade control).

    MEH

    Half-size 2 2Speed control via frequency con-verter integrated in the motor.

    The two pumps run at the same speed when both are in operation.

    Full-sizeAll other pumps

    Mains operation (on/off).

    MES

    Full-size 1 1Speed control via frequency con-verter integrated in the motor.

    Full-sizeAll other pumps

    Mains operation (on/off).

  • Control 2000

    Functions

    Functions

    Control 2000

    A standard Control 2000 always includes the electronicsunit PFU 2000 (Pump Functional Unit 2000) built intothe control cabinet. The PFU 2000 front cover with resetbutton and indicator lights is mounted in the front doorof the control cabinet.

    Alternatively, the Control 2000 can be supplied with thePMU 2000 (Pump Management Unit 2000) mounted inthe front door of the control cabinet.The PMU 2000 enables the read-out of operating dataand the optimisation of operation according to systemconditions.

    The Control 2000 without PMU 2000 offers thefollowing functions:

    Constant pressure control of the system.

    On/off operation at low flow.

    Automatic changeover to mains operation in case of defective frequency converter (Control 2000 F only).

    Automatic cascade control of pumps.

    Possibility of setpoint influence:proportional influence (proportional pressure), external setpoint influence.

    Possibility of remote control:system on/off.

    Pump and system monitoring functions:inlet pressuremotor protection.

    Display and indication functions:green indicator light for operating indications and

    red indicator light for fault indications,potential-free changeover contacts for operation

    and fault.

    GRUNDFOS BUS communication.

    The Control 2000 with PMU 2000 offers the followingfunctions:

    Constant pressure control of the system.

    On/Off operation at low flow.

    Automatic changeover to mains operation in case ofdefective frequency converter (Control 2000 F only).

    Automatic cascade control of pumps.

    Selection of switching sequences, automatic pumpchangeover and pump priority.

    Manual operation.

    Possibility of setpoint influence:proportional influence (proportional pressure), external setpoint influence.

    Possibility of digital remote-control functions:system on/off,reduced operation,setpoint control with two-point switch,setpoint control with three-point switch,alternative setpoint.

    Pump and system monitoring functions:minimum and maximum limits of actual value,inlet pressure,motor protection.

    Display and indication functions:2 x 24 character LCD display,green indicator light for operating indications and

    red indicator light for fault indications,potential-free changeover contacts for operation

    and fault.

    Clock functions.

    GRUNDFOS BUS communication.

    PCU 2000

    A PCU 2000 (Pump Communication Unit 2000) can beconnected to the Control 2000 via the BUS input. ThePCU 2000 enables remote operating and fault indicationfor each individual pump.The PCU 2000 also enables external setpoint influenceand system on/off.

    Functions, Control 2000

    Functions

    5

  • 6

    Functions

    Control 2000

    Type keyExample Control 2000 MEH 2 x 5.5 SD + 2 x 3.0 E PMU 3 x 400/230 V, 50 Hz IP 54

    Type range

    Supgroup:MS - MSH - MF - MFH - ME - MEH - MES

    Number of full-size pumps 1 - 4

    Power, full-size pumps [kW]

    Starting method of full size pumps:DOL: Direct-on-line startingSD: Star-delta startingE: Electronic soft start (MGE motor)

    Number of half-size pumps 1 - 2

    Power, half-size pumps [kW]

    Starting method of half-size pumps:DOL: Direct-on-line startingSD: Star-delta startingE: Electronic soft start (MGE motor)

    Control panel:PMU: PMU 2000PFU: PFU 2000

    Supply voltage/frequency

    Enclosure class:IP 54IP 00

  • 7

  • 8

    Control 2000

    Functions

    Examples of functioningThe following table shows examples of Control 2000 systems using constant pressure control.

    On/off Variable speed

    GRUNDFOSControl 2000 MS

    GRUNDFOSControl 2000 MSH

    GRUNDFOSControl 2000 MF

    GRUNDFOSControl 2000 MFH

    TM0

    0 2

    674

    029

    4

    TM0

    0 2

    678

    029

    4

    TM0

    026

    80 0

    294

    TM0

    026

    77 0

    294

    One pump in operation. The half-size pump in opera-tion.

    One pump in operation viafrequency converter.

    One half-size pump in opera-tion via frequency converter.

    TM0

    0 2

    749

    029

    4

    TM0

    0 2

    773

    029

    4

    TM0

    0 2

    757

    029

    4

    TM0

    0 2

    781

    029

    4

    Three pumps in operation. One full-size pump and thehalf-size pump in operation.

    One pump in operation viafrequency converter and twopumps on mains operation.

    One half-size pump in opera-tion via frequency converterand one full-size pump onmains operation

    TM0

    0 2

    751

    029

    4

    TM0

    0 2

    775

    029

    4

    TM0

    0 2

    759

    029

    4

    TM0

    0 2

    783

    029

    4 Maintains an almost con-

    stant pressure through cutting in/out the re-quired number of pumps.

    Changeover among the pumps is automatic and depends on load, time and fault.

    The cut-out pressure (Hstop) cannot be set but is calculated automatically.

    Maintains an almost con-stant pressure through cutting in/out the half-size pump and the full-size pumps.

    The half-size pump will al-ways start first, and will be cut out again when a full-size pump is cut in.

    Changeover among the full-size pumps is auto-matic and depends on load, time and fault.

    The cut-out pressure (Hstop) cannot be set but is calculated automatically.

    Maintains a constant pressure through continu-ously variable adjust-ment of the speed of one pump. The other pumps are mains-operated (on/off) according to the de-mand.

    The frequency-converter controlled pump will al-ways start first.

    Pump changeover is auto-matic and depends on load, time and fault.

    Besides, all pumps will be controlled by the fre-quency converter in rota-tion.

    Maintains a constant pressure through continu-ously variable adjust-ment of the speed of one half-size pump. The rest of the pumps are mains-operated.

    The half-size pump con-trolled by the frequency converter will always start first.

    Pump changeover is auto-matic and depends on load, time and fault.

    PFU 2000 PFU 2000 PFU 2000 PFU 2000

    Q

    stop

    set

    H

    H

    H

    Q

    stop

    set

    H

    H

    H

    Q

    set H

    H

    Q

    set H

    H

    Q

    stop

    set

    H

    H

    H

    Q

    stop

    set

    H

    H

    H

    Q

    set H

    H

    Q

    set H

    H

  • Functions

    Control 2000

    Examples of functioning, cont.The following table shows examples of Control 2000 systems using constant pressure control.

    Variable speed

    GRUNDFOSControl 2000 ME

    GRUNDFOSControl 2000 MEH

    GRUNDFOSControl MES

    TM0

    0 7

    98

    3 22

    96

    TM0

    0 7

    98

    4 22

    96

    TM0

    0 7

    98

    5 22

    96

    One pump in operation. The half-size pump in opera-tion.

    One half-size pump in opera-tion via frequency converter.

    TM0

    0 7

    99

    5 22

    96

    TM0

    0 7

    99

    4 22

    96

    TM0

    0 7

    99

    3 22

    96

    Three pumps in operation. One full-size pump and thehalf-size pump in operation.

    One half-size pump in opera-tion via frequency converterand one full-size pump onmains operation

    TM0

    0 7

    99

    6 2

    296

    TM0

    0 7

    99

    7 22

    96

    TM0

    0 7

    99

    8 22

    96

    Maintains a constant pressure through continu-ously variable adjust-ment of the speed of the pumps connected.

    The system performance is adjusted to the demand through cutting in/out the required number of pumps and through paral-lel control of the pumps in operation.

    Pump changeover is auto-matic and depends on load, time and fault.

    Maintains a constant pressure through continu-ously variable adjust-ment of the speed of the two half-size pumps with MGE motors, while the full-size pump is mains-operated. (on/off).

    The half-size pumps al-ways start first.

    Pump changeover is auto-matic and depends on load, time and fault.

    Maintains a constant pressure through continu-ously variable adjust-ment of the speed of one pump. The other pumps are cut in/out on mains operation according to de-mand thus achieving a performance correspond-ing to the consumption.

    The pump with MGE mo-tor will always start first.

    Pump changeover is auto-matic and depends on load, time and fault.

    PFU 2000

    MGE MGE MGE

    PFU 2000

    MGE MGE

    PFU 2000

    MGE

    Q

    H

    set H

    Q

    H

    set H

    Q

    H

    set H

    Q

    H

    set H

    Q

    H

    set H

    Q

    H

    set H

    9

  • 10

    Functions

    Control 2000

    Control parameters

    Systems without PMU 2000

    Controllers without the PMU 2000 can be used insystems having small time constants and are preset tothe control parameter "pressure".

    Cascade control:

    Cascade control ensures automatic adjustment ofperformance to the system demand by cutting in/outthe required number of pumps.The controller will operate the system with as fewpumps as possible.

    Automatic pump changeover:

    Automatic pump changeover is made as follows:

    Fault-dependent pump changeover.If a pump is faulty, it will be switched off and the next pump ready for operation will be switched on.

    Time-dependent pump changeover.This ensures that the operating hours are distributed evenly on the pumps connected. This function is combined with the test run function.

    Test run:To eliminate the risk of pump seizure caused by longperiods of standstill, a test run lasting 1 sec. is carried outonce every 24 hours.

    Setpoint:The setpoint is set by means of the function selector inthe PFU 2000. It is also possible to stop all pumps, or toset all pumps to operate at maximum performance.

    Remote setpoint setting:

    A 0 - 10 V or 0 - 20 mA signal can be connected for remotesetpoint setting.

    The locally set setpoint is set by means of the functionselector in the PFU 2000.

    Sensor input:

    Sensors giving the following analog signals can beconnected: 0 - 10 V, 0 - 20 mA, 4 - 20 mA.

    Input for external start/stop:

    A potential-free contact for external start/stop of allpumps can be connected.

    Systems with PMU 2000

    The PMU 2000 is designed for the control of variouspumps or pump systems. As an example, the PMU 2000can be used for the control of GRUNDFOS circulatorpumps of the UPE type and pumping systems andcontrollers based on the PFU 2000, such as the Control2000.Using the Control 2000 it is possible to control thepumps according to a constant pressure (fig. 1) or aconstant pressure with pre-pressure measuring (fig. 2).

    Fig. 1.

    Fig. 2

    TM

    01 2

    504

    1898

    TM

    00 5

    217

    2796

    PFU 2000

    P

    Pressure

    100%0%

    MAXSTOP

    Setpoint

    Function selector in the PFU 2000

    TM

    00 7

    048

    0296

    TM

    01 2

    504

    1898

    TM

    01 2

    505

    1898

    0 10 V

    Locally set setpoint

    100%

    Current setpoint

    Tran

    smitt

    er ra

    nge

    Actual setpoint

    Tran

    smit

    terr

    ang

    e Locally set setpoint

    100%

    10V20 mA

    Setpoint via external signals

    PFU 2000

    P

    Pressure

    PFU 2000

    PP

    Pressure with pre-pressure measuring

  • Functions

    Control 2000

    Cascade control:

    Cascade control ensures automatic adjustment ofperformance to the system demand by cutting in/outthe required number of pumps.

    The controller will operate the system with as fewpumps as possible.

    The on/off rate is limited by setting the switchingsequences.

    Automatic pump changeover:

    Automatic pump changeover is made as follows:

    Fault-dependent pump changeover.If a pump is faulty, it will be switched off and the next pump ready for operation will be switched on.

    Time-dependent pump changeover.This ensures that the operating hours are distributed evenly on the pumps connected. This function is combined with the test run function.

    Test run:

    To eliminate the risk of pump seizure caused by longperiods of standstill, a test run lasting 1 sec. is carried outonce every 24 hours.

    Clock functions:

    If the system demand varies during the day and/orduring the week, the pump performance required willalso vary. In this case, a clock program can be set in orderto achieve optimum performance of the pumps. It is possible to set a total of 10 switching times, allhaving individual setpoints.

    Standby pumps:

    In systems with more than one pump, standby pumpscan be selected. A standby pump is started only if one ofthe duty pumps is faulty.

    Example: In a system with four pumps of which onepump has been selected as standby-pump, themaximum number of pumps in operation at the sametime will be three. The standby pump is started only ifone of the duty pumps is faulty.

    Setpoint:

    The max. setpoint is set in the PMU 2000 menu

    Friction loss compensation:

    The control unit is capable of compensating for frictionloss. The setpoint increases from an adjustablepercentage at zero flow to 100% at max. flow.The actual flow is estimated based on internal operatingdata without the flow being measured directly.

    Remote setpoint setting:

    In view of optimizing system operation, it is often bestfor the system to operate according to a variablesetpoint instead of a constant setpoint. The selectedsettings influencing the setpoint will reduce "setpointmax".The following possibilities are available:

    "extern" (%)An external analog signal or potential-free contact influences the setpoint in accordance with a table.

    "timer" (minutes)An internal timer program in the PMU 2000 controls the setpoint in accordance with a table.

    "level" (m, cm, ft, in)The level signal controls the setpoint in accordance with a table.

    "flow" (m3/h, l/h, l/s, gpm)The flow signal controls the setpoint in accordance with a table.

    "flow/I" (%), (applies only to Delta Control 2000 F) An internal flow signal controls the setpoint in accord-ance with a table.

    Sensor input:

    Sensors giving the following analog signals can beconnected:

    0 - 10 V, 0 - 20 mA, 4 - 20 mA.

    TM

    00 4

    989

    4894

    Set A

    Setpoint max. 5.0 bar

    Setpoint

    1 3

    C

    A

    2 Time

    B

    Time

    Setpoint

    Clock program with three switching times

    TM

    00 4

    991

    4894

    Setpoint max

    Q

    H

    100 %

    60 %

    Setpoint max.

    100%

    60%

    Q

    H

    Friction loss compensation

    11

  • 12

    Control 2000

    Technical data

    Dimensions and weightsDimensions and weights are for control cabinets with aPFU 2000 control panel.

    All motors must be three-phase.

    The starting methods of the motors are:

    DOL (Direct-on-line starting)

    SD (Star-delta starting)

    E (Electronic soft start via frequency converter).

    Control 2000 MS

    TM

    00 9

    394

    2402

    - T

    M01

    047

    3 24

    02

    D B

    H

    Delta Control

    2000

    D B

    HDelta C

    ontrol 2000

    Motor[kW]

    Mounting of control

    cabinet

    Star

    tin

    gfu

    ll-s

    ize

    Control 2000 MS for 2 pumps

    Control 2000 MS for 3 pumps

    Control 2000 MS for 4 pumps

    Control 2000 MS for 5 pumps

    Control 2000 MS for 6 pumps

    Dimensions [mm] Weight

    [kg]

    Dimensions [mm] Weight

    [kg]

    Dimensions [mm] Weight

    [kg]

    Dimensions [mm] Weight

    [kg]

    Dimensions[mm] Weight

    [kg]H B D H B D H B D H B D H B D

    0.37 Wall mount. DOL 600 380 210 20 600 380 210 21 600 600 210 31 600 600 210 31 600 600 210 32

    0.55 Wall mount. DOL 600 380 210 20 600 380 210 21 600 600 210 31 600 600 210 31 600 600 210 32

    0.75 Wall mount. DOL 600 380 210 20 600 380 210 21 600 600 210 31 600 600 210 31 600 600 210 32

    1.1 Wall mount. DOL 600 380 210 20 600 380 210 21 600 600 210 31 600 600 210 31 600 600 210 32

    1.5 Wall mount. DOL 600 380 210 20 600 380 210 21 600 600 210 31 600 600 210 31 600 600 210 32

    2.2 Wall mount. DOL 600 380 210 20 600 380 210 21 600 600 210 31 600 600 210 31 600 600 210 32

    3 Wall mount. DOL 600 380 210 20 600 380 210 21 600 600 210 31 600 600 210 31 600 600 210 32

    4 Wall mount. SD 600 600 210 31 600 600 210 32 1000 800 300 66 1000 800 300 68 1000 800 300 69

    5.5 Wall mount. SD 600 600 210 31 600 600 210 32 1000 800 300 66 1000 800 300 68 1800 1000 400 163!

    7.5 Wall mount. SD 600 600 210 31 600 600 210 33 1000 800 300 66 1800 1000 400 161! 1800 1000 400 164!

    11 Wall mount. SD 600 600 210 31 1000 800 300 65 1000 800 300 67 1800 1000 400 162! 1800 1000 400 165!

    15 Wall mount. SD 600 600 210 32 1000 800 300 67 1000 800 300 69 1800 1000 400 164! 1800 1000 400 168!

    18.5 Wall mount. SD 1000 800 300 65 1000 800 300 68 1000 800 300 70 1800 1200 400 202! 1800 1200 400 204!

    22 Wall mount. SD 1000 800 300 66 1000 800 300 69 1000 800 300 71 1800 1200 400 203! 1800 1200 400 206!

    30 Wall mount. SD 1200 1000 300 97 1200 1000 300 101 1200 1000 300 105 1900 1200 400 218! 1900 1200 400 222!

    ! The control cabinet is prepared for floor mounting. Technical data, Control 2000

  • Technical data

    Control 2000

    Control 2000 MSH

    MotorMountingof control

    cabinet

    Startingfull-size

    Startinghalf-size

    Control 2000 MSH for 2 pumps

    (1 full-size and1 half-size)

    Control 2000 MSH for 3 pumps

    (2 full-size and1 half-size)

    Control 2000 MSH for 4 pumps

    (3 full-size and1 half-size)

    Full-size[kW]

    Half-size[kW]

    Dimensions [mm] Weight

    [kg]

    Dimensions [mm] Weight

    [kg]

    Dimensions[mm] Weight

    [kg]H B D H B D H B D

    1.1 0.75 Wall mounting DOL DOL 600 380 210 20 600 380 210 21 600 600 210 32

    1.5 1.1 Wall mounting DOL DOL 600 380 210 20 600 380 210 21 600 600 210 32

    2.2 1.1 Wall mounting DOL DOL 600 380 210 20 600 380 210 21 600 600 210 32

    3 1.5 Wall mounting DOL DOL 600 380 210 20 600 380 210 21 600 600 210 32

    3 2.2 Wall mounting DOL DOL 600 380 210 20 600 380 210 21 600 600 210 32

    4 2.2 Wall mounting SD DOL 600 600 210 31 600 600 210 32 1000 800 300 66

    4 3.0 Wall mounting SD DOL 600 600 210 31 600 600 210 32 1000 800 300 66

    5.5 3.0 Wall mounting SD DOL 600 600 210 31 600 600 210 32 1000 800 300 66

    5.5 4.0 Wall mounting SD SD 600 600 210 31 600 600 210 32 1000 800 300 66

    7.5 4.0 Wall mounting SD SD 600 600 210 32 600 600 210 34 1000 800 300 67

    7.5 5.5 Wall mounting SD SD 600 600 210 32 600 600 210 34 1000 800 300 67

    11 5.5 Wall mounting SD SD 600 600 210 32 600 600 210 34 1000 800 300 68

    11 7.5 Wall mounting SD SD 600 600 210 32 600 600 210 34 1000 800 300 68

    11 11 Wall mounting SD SD 600 600 210 32 600 600 210 34 1000 800 300 68

    15 7.5 Wall mounting SD SD 600 600 210 33 1000 800 300 67 1000 800 300 69

    15 11 Wall mounting SD SD 600 600 210 33 1000 800 300 67 1000 800 300 69

    18.5 11 Wall mounting SD SD 600 600 210 33 1000 800 300 67 1000 800 300 69

    22 11 Wall mounting SD SD 1000 800 300 65 1000 800 300 68 1000 800 300 71

    22 15 Wall mounting SD SD 1000 800 300 66 1000 800 300 69 1000 800 300 71

    30 15 Wall mounting SD SD 1200 1000 300 97 1200 1000 300 101 1200 1000 300 104

    30 18.5 Wall mounting SD SD 1200 1000 300 97 1200 1000 300 101 1200 1000 300 104

    Dimensions and weight

    13

  • 14

    Technical data

    Control 2000

    Dimensions and weightsDimensions and weights are for control cabinets with aPFU 2000 control panel.

    All motors must be three-phase.

    The starting methods of the motors are:

    DOL (Direct-on-line starting)

    SD (Star-delta starting)

    Control 2000 MF

    Control 2000 MFH

    TM

    01 0

    473

    2402

    D B

    HDelta C

    ontrol 2000

    Motor[kW]

    Mounting of control

    cabinet

    Star

    tin

    gfu

    ll-s

    ize

    Control 2000 MFfor 2 pumps

    Control 2000 MFfor 3 pumps

    Control 2000 MFfor 4 pumps

    Control 2000 MFfor 5 pumps

    Control 2000 MFfor 6 pumps

    Dimensions [mm] Weight

    [kg]

    Dimensions [mm] Weight

    [kg]

    Dimensions [mm] Weight

    [kg]

    Dimensions [mm] Weight

    [kg]

    Dimensions[mm] Weight

    [kg]H B D H B D H B D H B D H B D

    0.37 Floor mount. DOL 1400 600 300 77 1400 800 300 93 1400 800 300 94 1400 1000 300 111 1400 1000 300 112

    0.55 Floor mount. DOL 1400 600 300 77 1400 800 300 93 1400 800 300 94 1400 1000 300 111 1400 1000 300 112

    0.75 Floor mount. DOL 1400 600 300 77 1400 800 300 93 1400 800 300 94 1400 1000 300 111 1400 1000 300 112

    1.1 Floor mount. DOL 1400 600 300 77 1400 800 300 93 1400 800 300 94 1400 1000 300 111 1400 1000 300 112

    1.5 Floor mount. DOL 1400 600 300 77 1400 800 300 93 1400 800 300 94 1400 1000 300 111 1400 1000 300 112

    2.2 Floor mount. DOL 1400 600 300 77 1400 800 300 93 1400 800 300 94 1400 1000 300 111 1400 1000 300 112

    3 Floor mount. DOL 1400 600 300 77 1400 800 300 93 1400 800 300 94 1400 1000 300 111 1400 1000 300 112

    4 Floor mount. SD 1400 800 300 102 1400 1000 300 120 1400 1000 300 122 1400 1000 300 124 1900 1000 400 190

    5.5 Floor mount. SD 1400 800 300 102 1400 1000 300 120 1400 1000 300 122 1900 1000 400 188 1900 1000 400 190

    7.5 Floor mount. SD 1400 800 300 94 1400 1000 300 120 1400 1000 300 178 1900 1000 400 181 1900 1000 400 182

    11 Floor mount. SD 1900 1000 400 185 1900 1200 400 221 1900 1200 400 224 1900 1200 400 226 1900 1200 400 228

    15 Floor mount. SD 1900 1000 400 188 1900 1200 400 226 1900 1200 400 228 1900 1600 400 274 1900 1600 400 276

    18.5 Floor mount. SD 1900 1000 400 197 1900 1600 400 279 1900 1600 400 283 1900 1800 400 392 1900 1800 400 396

    22 Floor mount. SD 1900 1000 400 198 1900 1600 400 280 1900 1600 400 285 1900 1800 400 394 1900 1800 400 399

    30 Floor mount. SD 1900 1200 400 262 1900 1800 400 380 1900 2200 400 461 1900 2200 400 466 1900 2000 400 471

    MotorMounting of control

    cabinet

    Startingfull-size

    Startinghalf-size

    Control 2000 MFH for 3 pumps

    (1 full-size and2 half-size)

    Control 2000 MFH for 4 pumps

    (2 full-size and2 half-size)

    Full-size[kW]

    Half-size[kW]

    Dimensions [mm] Weight

    [kg]

    Dimensions [mm] Weight

    [kg]H B D H B D

    3 2.2 Floor mounting DOL DOL 1500 800 300 93 1500 800 300 94

    4 3 Floor mounting SD DOL 1500 800 300 94 1500 800 300 95

    5.5 3 Floor mounting SD DOL 1500 800 300 94 1500 800 300 95

    5.5 4 Floor mounting SD SD 1500 1000 300 120 1500 1000 300 121

    7.5 4 Floor mounting SD SD 1500 1000 300 120 1500 1000 300 121

    7.5 5.5 Floor mounting SD SD 1500 1000 300 120 1500 1000 300 121

    11 5.5 Floor mounting SD SD 1500 1000 300 120 1900 1000 400 178

    11 7.5 Floor mounting SD SD 1500 1000 300 112 1900 1000 400 185

    15 7.5 Floor mounting SD SD 1500 1000 300 112 1900 1000 400 179

    15 11 Floor mounting SD SD 1900 1000 400 187 1900 1000 400 189

    18.5 11 Floor mounting SD SD 1900 1000 400 187 1900 1000 400 180

    22 11 Floor mounting SD SD 1900 1000 400 190 1900 1000 400 193

    22 15 Floor mounting SD E/SD 1900 1000 400 190 1900 1000 400 193

    30 15 Floor mounting SD E/SD 1900 1200 400 227 1900 1600 400 273

    30 18.5 Floor mounting SD E/SD 1900 1600 400 282 1900 1600 400 283

  • Technical data

    Control 2000

    Dimensions and weightsDimensions and weights are for control cabinets with aPFU 2000 control panel.

    All motors must be three-phase.

    The starting methods of the motors are:

    E (Electronic soft start via frequency converter).

    Note: E-pumps marked with """ must be with single-phase mains connection.

    Control 2000 ME

    TM

    00 9

    394

    2402

    D B

    H

    Delta Control

    2000

    Motor [kW]

    Mounting of control

    cabinet

    Startingfull-size

    Control 2000 MEfor 2 pumps

    Control 2000 MEfor 3 pumps

    Control 2000 MEfor 4 pumps

    Dimensions [mm] Weight

    [kg]

    Dimensions[mm] Weight

    kg]

    Dimensions[mm] Weight

    [kg]H B D H B D H B D

    1.1 " Wall mounting E 400 400 210 14 600 400 210 20

    1.1 Wall mounting E 400 400 210 14 600 400 210 20 600 400 210 20

    1.5 Wall mounting E 600 400 210 20 600 400 210 20 600 400 210 20

    2.2 Wall mounting E 600 400 210 20 600 400 210 20 600 400 210 20

    3 Wall mounting E 600 400 210 20 600 400 210 20 600 400 210 20

    4 Wall mounting E 600 400 210 20 600 400 210 20 600 400 210 20

    5.5 Wall mounting E 600 400 210 20 600 400 210 20 600 400 210 20

    7.5 Wall mounting E 600 400 210 24 600 400 210 26 600 400 210 37

    11 Wall mounting E 600 380 210 25 600 380 210 26 600 600 210 37

    15 Wall mounting E 600 380 210 25 600 600 210 37 760 760 210 56

    18.5 Wall mounting E 600 380 210 26 760 760 210 55 760 760 210 57

    22 Wall mounting E 600 600 210 37 760 760 210 56 760 760 210 58

    15

  • 16

    Technical data

    Control 2000

    The starting methods of the motors are:

    DOL (Direct-on-line starting)

    SD (Star-delta starting)

    E (Electronic soft start via frequency converter)

    Control 2000 MEH

    MotorMounting of control

    cabinet

    Startingfull-size

    Startinghalf-size

    Control 2000 MEH for 3 pumps

    (1 full-size and 2 half-size)

    Control 2000 MEHfor 4 pumps

    (2 full-size and 2 half-size)

    Full-size[kW]

    Half-size[kW]

    Dimensions[mm] Weight

    [kg]

    Dimensions [mm] Weight

    [kg]H B D H B D

    1.1 0.75 " Wall mounting DOL E 600 400 210 20 600 400 210 21

    1.5 1.1 " Wall mounting DOL E 600 400 210 20 600 400 210 21

    2.2 1.1 " Wall mounting DOL E 600 400 210 20 600 400 210 21

    2.2 1.5 Wall mounting DOL E 600 400 210 20 600 400 210 21

    3 1.5 Wall mounting DOL E 600 400 210 20 600 400 210 21

    3 2.2 Wall mounting DOL E 600 400 210 20 600 400 210 21

    4 2.2 Wall mounting SD E 600 600 210 31 600 600 210 33

    4 3 Wall mounting SD E 600 600 210 31 600 600 210 33

    5.5 3 Wall mounting SD E 600 600 210 31 600 600 210 33

    5.5 4 Wall mounting SD E 600 600 210 32 600 600 210 33

    7.5 4 Wall mounting SD E 600 600 210 32 600 600 210 65

    7.5 5.5 Wall mounting SD E 600 600 210 32 600 600 210 65

    11 5.5 Wall mounting SD E 600 600 210 32 600 600 210 65

    11 7.5 Wall mounting SD E 600 600 210 32 600 600 210 65

    15 7.5 Wall mounting SD E 1000 600 300 63 1000 800 300 66

    15 11 Wall mounting DOL E 600 600 210 37 760 760 210 57

    15 11 Wall mounting SD E 600 600 210 37 760 760 210 58

    18.5 11 Wall mounting DOL E 600 600 210 38 760 760 210 58

    18.5 11 Wall mounting SD E 600 600 210 38 760 760 210 59

    18.5 15 Wall mounting DOL E 600 600 210 38 760 760 210 59

    18.5 15 Wall mounting SD E 600 600 210 38 760 760 210 59

    22 11 Wall mounting DOL E 600 600 210 40 1000 800 300 81

    22 11 Wall mounting SD E 600 600 210 39 760 760 210 60

    22 15 Wall mounting DOL E 1000 800 300 76 1000 800 300 81

    22 15 Wall mounting SD E 760 760 210 57 760 760 210 60

    22 18.5 Wall mounting DOL E 1000 800 300 76 1000 800 300 81

    22 18.5 Wall mounting SD E 760 760 210 57 760 760 210 60

    30 15 Wall mounting DOL E 1000 800 300 77 1000 800 300 83

    30 15 Wall mounting SD E 100 800 300 76 1000 800 300 81

    30 18.5 Wall mounting DOL E 1000 800 300 77 1000 800 300 83

    30 18.5 Wall mounting SD E 1000 800 300 77 1000 800 300 81

    30 22 Wall mounting DOL E 1000 800 300 78 1200 800 300 122

    30 22 Wall mounting SD E 1000 800 300 77 1200 800 300 121

    37 18.5 Wall mounting DOL E 1000 800 300 80 1200 800 300 129

    37 18.5 Wall mounting SD E 1000 800 300 77 1200 800 300 124

    37 22 Wall mounting DOL E 1000 800 300 81 1200 800 300 130

    37 22 Wall mounting SD E 1000 800 300 78 1200 800 300 125

    45 22 Wall mounting DOL E 1200 800 300 116 1200 800 300 130

    45 22 Wall mounting SD E 1200 800 300 114 1200 800 300 125

  • Technical data

    Control 2000

    Control 2000 MES

    Motor [kW]

    Mounting of control

    cabinet

    Startingfull-size

    Control 2000 MES for 2 pumps

    Control 2000 MES for 3 pumps

    Control 2000 MES for 4 pumps

    Dimensions[mm] Weight

    [kg]

    Dimensions [mm] Weight

    [kg]

    Dimensions[mm] Weight

    [kg]H B D H B D H B D

    1.1 Wall mounting E/DOL 600 400 210 20 600 400 210 20 600 600 210 31

    1.1 Wall mounting E/DOL 600 400 210 20 600 400 210 20 600 600 210 31

    1.5 Wall mounting E/DOL 600 400 210 20 600 400 210 21 600 600 210 31

    2.2 Wall mounting E/DOL 600 400 210 20 600 400 210 21 600 600 210 31

    3 Wall mounting E/DOL 600 400 210 20 600 400 210 21 600 600 210 31

    4 Wall mounting E/SD 600 600 210 31 600 600 210 33 600 600 210 34

    5.5 Wall mounting E/SD 600 600 210 31 600 600 210 33 600 600 210 34

    7.5 Wall mounting E/SD 600 600 210 31 600 600 210 33 1000 800 300 66

    11 Wall mounting E/DOL 600 400 210 25 600 600 210 37 600 600 210 38

    11 Wall mounting E/SD 600 600 210 36 600 600 210 38 600 600 210 41

    15 Wall mounting E/DOL 600 600 210 36 600 600 210 38 760 760 210 57

    15 Wall mounting E/SD 600 600 210 36 600 600 210 39 760 760 210 60

    18.5 Wall mounting E/DOL 600 600 210 37 760 760 210 57 760 760 210 60

    18.5 Wall mounting E/SD 600 600 210 37 760 760 210 58 760 760 210 62

    22 Wall mounting E/DOL 600 600 210 39 1000 800 300 80 1000 800 300 84

    22 Wall mounting E/SD 600 600 210 38 760 760 210 59 760 760 210 63

    17

  • 18

    Technical data

    Control 2000

    Product numbersProduct numbers for control cabinets with a PFU 2000control panel.

    Supply voltage: 3 x 400 V +6%/10%, 50 Hz, N, PE.

    All motors must be three-phase.

    Enclosure class: IP 54.

    The starting methods of the motors are:

    DOL (Direct-on-line starting)

    SD (Star-delta starting)

    Control 2000 MS

    Motoroutput

    [kW]

    Mounting of control

    cabinet Star

    tin

    gfu

    ll-s

    ize Product numbers

    Control 2000 MS for 2 pumps

    Control 2000 MSfor 3 pumps

    Control 2000 MS for 4 pumps

    Control 2000 MS for 5 pumps

    Control 2000 MS for 6 pumps

    0.37 Wall mount. DOL 96 01 11 97 96 01 12 11 96 01 12 25 96 01 12 39 96 01 12 50

    0.55 Wall mount. DOL 96 01 11 98 96 01 12 12 96 01 12 26 96 01 12 40 96 01 12 51

    0.75 Wall mount. DOL 96 01 11 99 96 01 12 13 96 01 12 27 96 01 12 41 96 01 12 52

    1.1 Wall mount. DOL 96 01 12 00 96 01 12 14 96 01 12 28 96 01 12 42 96 01 12 53

    1.5 Wall mount. DOL 96 01 12 01 96 01 12 15 96 01 12 29 96 01 12 43 96 01 12 54

    2.2 Wall mount. DOL 96 01 12 02 96 01 12 16 96 01 12 30 96 01 12 44 96 01 12 55

    3 Wall mount. DOL 96 01 12 03 96 01 12 17 96 01 12 31 96 01 12 45 96 01 12 56

    4 Wall mount. SD 96 01 12 04 96 01 12 18 96 01 12 32 96 01 12 46 96 01 12 57

    5.5 Wall mount. SD 96 01 12 05 96 01 12 19 96 01 12 33 96 01 12 47 96 01 12 58 !

    7.5 Wall mount. SD 96 01 12 06 96 01 12 20 96 01 12 34 96 01 12 48 ! 96 01 12 59 !

    11 Wall mount. SD 96 01 12 07 96 01 12 21 96 01 12 35 96 01 12 49 ! 96 01 13 58 !

    15 Wall mount. SD 96 01 12 08 96 01 12 22 96 01 12 36 96 01 14 09 ! 96 01 14 12 !

    18.5 Wall mount. SD 96 01 12 09 96 01 12 23 96 01 12 37 96 01 14 10 ! 96 01 14 13 !

    22 Wall mount. SD 96 01 12 10 96 01 12 24 96 01 12 38 96 01 14 11 ! 96 01 14 14 !

    30 Wall mount. SD 96 01 24 46 96 01 24 47 96 01 24 48 96 01 24 49 ! 96 01 24 50!

    ! The control cabinet is prepared for floor mounting.

  • Technical data

    Control 2000

    Control 2000 MSH

    Motor output

    Mountingof control

    cabinet

    Starting full-size

    Startinghalf-size

    Product numbers

    Full-size[kW]

    Half-size[kW]

    Control 2000 MSH

    for 2 pumps(1 full-size and

    1 half-size)

    Control 2000 MSH

    for 3 pumps(2 full-size and

    1 half-size)

    Control 2000 MSH

    for 4 pumps(3 full-size and

    1 half-size)

    1.1 0.75 Wall mounting DOL DOL 96 01 12 60 96 01 12 72 96 01 12 83

    1.5 1.1 Wall mounting DOL DOL 96 01 12 61 96 01 12 73 96 01 12 84

    2.2 1.1 Wall mounting DOL DOL 96 01 12 62 96 01 12 74 96 01 12 85

    3 1.5 Wall mounting DOL DOL 96 01 12 63 96 01 12 75 96 01 12 86

    3 2.2 Wall mounting DOL DOL 96 01 20 43 96 01 20 48 96 01 20 53

    4 2.2 Wall mounting SD DOL 96 01 12 64 96 01 12 76 96 01 12 87

    4 3 Wall mounting SD DOL 96 01 20 46 96 01 20 51 96 01 20 56

    5.5 3 Wall mounting SD DOL 96 01 20 21 96 01 12 77 96 01 12 88

    5.5 4 Wall mounting SD SD 96 01 20 59 96 01 20 69 96 01 20 79

    7.5 4 Wall mounting SD SD 96 01 12 67 96 01 12 78 96 01 12 89

    7.5 5.5 Wall mounting SD SD 96 01 20 62 96 01 20 72 96 01 20 82

    11 5.5 Wall mounting SD SD 96 01 12 68 96 01 12 79 96 01 12 90

    11 7.5 Wall mounting SD SD 96 01 20 64 96 01 20 74 96 01 20 84

    11 11 Wall mounting SD SD 96 01 20 66 96 01 20 76 96 01 20 86

    15 7.5 Wall mounting SD SD 96 01 12 69 96 01 12 80 96 01 12 91

    15 11 Wall mounting SD SD 96 01 20 16 96 01 20 18 96 01 20 20

    18.5 11 Wall mounting SD SD 96 01 12 70 96 01 12 81 96 01 12 92

    22 11 Wall mounting SD SD 96 01 12 71 96 01 12 82 96 01 12 93

    22 15 Wall mounting SD SD 96 01 24 68 96 01 24 69 96 01 24 70

    30 15 Wall mounting SD SD 96 01 24 71 96 01 24 72 96 01 24 73

    30 18.5 Wall mounting SD SD 96 01 24 74 96 01 24 75 96 01 24 76

    19

  • 20

    Technical data

    Control 2000

    Product numbersProduct numbers for control cabinets with a PFU 2000control panel.

    Supply voltage: 3 x 400 V +6%/10%, 50 Hz, N, PE.

    All motors must be three-phase.

    Enclosure class: IP 54.

    The starting methods of the motors are:

    DOL (Direct-on-line starting)

    SD (Star-delta starting)

    Control 2000 MF

    Control 2000 MFH

    Motoroutput

    [kW]

    Mounting of control

    cabinet

    Startingfull-size

    Product numbers

    Control 2000 MF for 2 pumps

    Control 2000 MFfor 3 pumps

    Control 2000 MF for 4 pumps

    Control 2000 MF for 5 pumps

    Control 2000 MF for 6 pumps

    0.37 Floor mount. DOL 96 01 13 74 96 01 13 82 96 01 13 90 96 01 13 99 96 01 14 08

    0.55 Floor mount. DOL 96 01 13 67 96 01 13 75 96 01 13 83 96 01 13 91 96 01 14 00

    0.75 Floor mount. DOL 96 01 13 68 96 01 13 76 96 01 13 84 96 01 13 92 96 01 14 01

    1.1 Floor mount. DOL 96 01 13 69 96 01 13 77 96 01 13 85 96 01 13 93 96 01 14 02

    1.5 Floor mount. DOL 96 01 13 70 96 01 13 78 96 01 13 86 96 01 13 94 96 01 14 03

    2.2 Floor mount. DOL 96 01 13 71 96 01 13 79 96 01 13 87 96 01 13 95 96 01 14 04

    3 Floor mount. DOL 96 01 13 72 96 01 13 80 96 01 13 88 96 01 13 96 96 01 14 05

    4 Floor mount. SD 96 01 13 73 96 01 13 81 96 01 13 89 96 01 13 97 96 01 14 06

    5.5 Floor mount. SD 96 01 12 94 96 01 13 00 96 01 13 06 96 01 13 98 96 01 14 07

    7.5 Floor mount. SD 96 01 12 95 96 01 13 01 96 01 13 07 96 01 13 12 96 01 13 14

    11 Floor mount. SD 96 01 12 96 96 01 13 02 96 01 13 08 96 01 13 13 96 01 13 15

    15 Floor mount. SD 96 01 12 97 96 01 13 03 96 01 13 09 96 01 13 61 96 01 13 64

    18.5 Floor mount. SD 96 01 12 98 96 01 13 04 96 01 13 10 96 01 13 62 96 01 13 65

    22 Floor mount. SD 96 01 12 99 96 01 13 05 96 01 13 11 96 01 13 63 96 01 13 66

    30 Floor mount. SD 96 01 24 14 96 01 24 15 96 01 24 16 96 01 24 17 96 01 24 18

    Motor output

    Mounting of control

    cabinet

    Starting full-size

    Startinghalf-size

    Product numbers

    Full-size[kW]

    Half-size[kW]

    Control 2000 MFH for 3 pumps

    (1 full-size and2 half-size)

    Control 2000 MFH for 4 pumps

    (2 full-size and2 half-size)

    3 2.2 Floor mounting DOL DOL 96 01 13 16 96 01 13 28

    4 3 Floor mounting SD DOL 96 01 13 17 96 01 13 29

    5.5 3 Floor mounting SD DOL 96 01 13 18 96 01 13 30

    5.5 4 Floor mounting SD SD 96 01 13 19 96 01 13 31

    7.5 4 Floor mounting SD SD 96 01 13 20 96 01 13 32

    7.5 5.5 Floor mounting SD SD 96 01 13 21 96 01 13 33

    11 5.5 Floor mounting SD SD 96 01 13 22 96 01 13 34

    11 7.5 Floor mounting SD SD 96 01 13 23 96 01 13 35

    15 7.5 Floor mounting SD SD 96 01 13 24 96 01 13 36

    15 11 Floor mounting SD SD 96 01 13 25 96 01 13 37

    18.5 11 Floor mounting SD SD 96 01 13 26 96 01 13 38

    22 11 Floor mounting SD SD 96 01 20 33 96 01 20 35

    22 15 Floor mounting SD E/SD 96 01 13 27 96 01 13 39

    30 15 Floor mounting SD E/SD 96 01 24 30 96 01 24 31

    30 18.5 Floor mounting SD E/SD 96 01 24 32 96 01 24 33

  • Technical data

    Control 2000

    Product numbersProduct numbers for control cabinets with a PFU 2000control panel.

    Supply voltage: 3 x 400 V +6%/10%, 50 Hz, N, PE.

    All motors must be three-phase.

    Note: CRE-pumps marked with """ must be with single-phase mains connection.

    Enclosure class: IP 54.

    The starting methods of the motors are:

    DOL (Direct-on-line starting)

    SD (Star-delta starting)

    E (Electronic soft start via frequency converter).

    Control 2000 ME

    Motor output[kW]

    Mounting of control

    cabinet

    Startingfull-size

    Product numbers

    Control 2000 ME for 2 pumps

    Control 2000 ME for 3 pumps

    Control 2000 ME for 4 pumps

    1.1 " Wall mounting E 96 01 11 52 96 01 14 15

    1.1 Wall mounting E 96 01 20 89 96 01 20 90 96 01 23 15

    1.5 Wall mounting E 96 01 11 68 96 01 14 16 96 01 23 02

    2.2 Wall mounting E 96 01 11 69 96 01 14 17 96 01 23 03

    3 Wall mounting E 96 01 11 70 96 01 14 18 96 01 23 04

    4 Wall mounting E 96 01 11 71 96 01 14 19 96 01 23 05

    5.5 Wall mounting E 96 01 11 72 96 01 14 20 96 01 23 06

    7.5 Wall mounting E 96 01 23 87 96 01 23 88 96 01 23 89

    11 Wall mounting E 96 01 33 45 96 01 33 49 96 01 33 53

    15 Wall mounting E 96 01 33 46 96 01 33 50 96 01 33 54

    18.5 Wall mounting E 96 01 33 47 96 01 33 51 96 01 33 55

    22 Wall mounting E 96 01 33 48 96 01 33 52 96 01 33 56

    21

  • 22

    Technical data

    Control 2000

    Control 2000 MEH

    Motor outputMountingof control

    cabinet

    Startingfull-size

    Startinghalf-size

    Product numbers

    Full-size[kW]

    Half-size[kW]

    Control 2000 MEH for 3 pumps

    (1 full-size and 2 half-size)

    Control 2000 MEHfor 4 pumps

    (2 full-size and 2 half-size)

    1.1 0.75 " Wall mounting DOL E 96 01 11 73 96 01 11 85

    1.5 1.1 " Wall mounting DOL E 96 01 11 74 96 01 11 86

    2.2 1.1 " Wall mounting DOL E 96 01 11 75 96 01 11 87

    2.2 1.5 Wall mounting DOL E 96 01 11 76 96 01 11 88

    3 1.5 Wall mounting DOL E 96 01 11 77 96 01 11 89

    3 2.2 Wall mounting DOL E 96 01 11 78 96 01 11 90

    4 2.2 Wall mounting SD E 96 01 11 79 96 01 11 91

    4 3 Wall mounting SD E 96 01 11 80 96 01 11 92

    5.5 3 Wall mounting SD E 96 01 11 81 96 01 11 93

    5.5 4 Wall mounting SD E 96 01 11 82 96 01 11 94

    7.5 4 Wall mounting SD E 96 01 11 83 96 01 11 95

    7.5 5.5 Wall mounting SD E 96 01 13 59 96 01 13 60

    11 5.5 Wall mounting SD E 96 01 11 84 96 01 11 96

    11 7.5 Wall mounting SD E 96 01 23 91 96 01 23 95

    15 7.5 Wall mounting SD E 96 01 23 93 96 01 23 97

    15 11 Wall mounting DOL E 96 01 35 57 96 01 35 63

    15 11 Wall mounting SD E 96 01 35 58 96 01 35 64

    18.5 11 Wall mounting DOL E 96 01 35 59 96 01 35 65

    18.5 11 Wall mounting SD E 96 01 35 60 96 01 35 66

    18.5 15 Wall mounting DOL E 96 01 35 69 96 01 35 75

    18.5 15 Wall mounting SD E 96 01 35 70 96 01 35 76

    22 11 Wall mounting DOL E 96 01 35 61 96 01 35 67

    22 11 Wall mounting SD E 96 01 35 62 96 01 35 68

    22 15 Wall mounting DOL E 96 01 35 71 96 01 35 77

    22 15 Wall mounting SD E 96 01 35 72 96 01 35 78

    22 18.5 Wall mounting DOL E 96 01 35 81 96 01 35 87

    22 18.5 Wall mounting SD E 96 01 35 82 96 01 35 88

    30 15 Wall mounting DOL E 96 01 35 73 96 01 35 79

    30 15 Wall mounting SD E 96 01 35 74 96 01 35 80

    30 18.5 Wall mounting DOL E 96 01 35 83 96 01 35 89

    30 18.5 Wall mounting SD E 96 01 35 84 96 01 35 90

    30 22 Wall mounting DOL E 96 01 35 93 96 01 35 99

    30 22 Wall mounting SD E 96 01 35 94 96 01 36 00

    37 18.5 Wall mounting DOL E 96 01 35 85 96 01 35 91

    37 18.5 Wall mounting SD E 96 01 35 86 96 01 35 92

    37 22 Wall mounting DOL E 96 01 35 95 96 01 36 01

    37 22 Wall mounting SD E 96 01 35 96 96 01 36 02

    45 22 Wall mounting DOL E 96 01 35 97 96 01 36 03

    45 22 Wall mounting SD E 96 01 35 98 96 01 36 04

  • Technical data

    Control 2000

    Product numbers for control cabinets with a PFU 2000 control panel.

    Supply voltage: 3 x 400 V +6%/10%, 50 Hz, N, PE.

    All motors must be three-phase.

    The starting methods of the motors are:

    DOL (Direct-on-line starting)

    SD (Star-delta starting)

    E (Electronic soft start via frequency converter).

    Note: CRE-pumps marked with """ must be withsingle-phase mains connection.

    Enclosure class: IP 54.

    Control 2000 MES

    Motor output[kW]

    Mounting of control

    cabinet

    Startingfull-size

    Product numbers

    Control 2000 MES for 2 pumps

    Control 2000 MES for 3 pumps

    Control 2000 MES for 4 pumps

    1.1 " Wall mounting E/DOL 96 01 13 40 96 01 13 46 96 01 13 52

    1.1 Wall mounting E/DOL 96 01 20 92 96 01 20 93 96 01 20 94

    1.5 Wall mounting E/DOL 96 01 13 41 96 01 13 47 96 01 13 53

    2.2 Wall mounting E/DOL 96 01 13 42 96 01 13 48 96 01 13 54

    3 Wall mounting E/DOL 96 01 13 43 96 01 13 49 96 01 13 55

    4 Wall mounting E/SD 96 01 13 44 96 01 13 50 96 01 13 56

    5.5 Wall mounting E/SD 96 01 13 45 96 01 13 51 96 01 13 57

    7.5 Wall mounting E/SD 96 01 23 99 96 01 24 01 96 01 24 03

    11 Wall mounting E/DOL 96 01 34 37 96 01 34 39 96 01 34 41

    11 Wall mounting E/SD 96 01 34 38 96 01 34 40 96 01 34 42

    15 Wall mounting E/DOL 96 01 34 43 96 01 34 45 96 01 34 47

    15 Wall mounting E/SD 96 01 34 44 96 01 34 46 96 01 34 48

    18.5 Wall mounting E/DOL 96 01 34 49 96 01 34 51 96 01 34 53

    18.5 Wall mounting E/SD 96 01 34 50 96 01 34 52 96 01 34 54

    22 Wall mounting E/DOL 96 01 34 55 96 01 34 57 96 01 34 59

    22 Wall mounting E/SD 96 01 34 56 96 01 34 58 96 01 34 60

    23

  • 24

    Delta Control 2000General data

    System configurationGrundfos Delta Control 2000 features two main groupsand one variant:

    1. Delta Control 2000 F uses a standard frequencyconverter and can be used together with pumpswith standard motors. Delta Control 2000 F is divid-ed into subgroups.

    2. Delta Control 2000 E is used when the systemcomprises E-pumps (Grundfos pumps equippedwith Grundfos MGE motors). Delta Control 2000 Eis also divided into subgroups. (See table below).

    3. Delta Control 2000 ME (PO) should be used whena controller must be designed especially accordingto the customers needs. Delta Control 2000 ME(PO) contains only a PFU 2000 set up for the con-trol of Grundfos MGE motors. The Delta Control 2000 ME (PO) controller is sup-plied without control cabinet, fuses, main switch,etc.

    Each main group consists of subgroups, see the tablebelow:

    Abbreviations:

    M: The Delta Control 2000 features a microprocessorfor the control of all functions.

    F: Frequency-converter control rotates among all pumps in the system.

    E: Some or all of the pumps in the system areE-pumps (pumps with integrated frequency converter).

    H: The system has one or two half-size pumps.(One half-size pump provides approximatelythe same head as one full-size pump, but onlyapproximately half the flow).

    General data, Delta Control 2000

    System configuration

    Main group Sub groupDescription of pumps

    Size NumberNumber of

    controlled pumpsMode of operation Comments

    Del

    ta C

    on

    tro

    l 20

    00

    F(v

    aria

    ble

    sp

    eed

    )

    MF

    1Speed control via frequency

    converter mounted in controlcabinet.

    Frequency-converter controlrotates among all pumps in

    the systemFull-size All

    All otherpumps

    Mains operation (on/off).

    MFH

    Half-size 2 1Speed control via frequnecy con-

    verter mounted in control cabinet.

    Frequency-converter controlalternates between the two

    pumps.The uncontrolled pump is mains

    operated (on/off).

    Full-sizeAll otherpumps

    Mains operation (on/off).

    Del

    ta C

    on

    tro

    l 20

    00

    E(v

    aria

    ble

    sp

    eed

    ) ME Full-size All AllSpeed control via frequency con-

    verter integrated in the motor.All pumps in operation run at the

    same speed (cascade control).

    MEH

    Half-size 2 2Speed control via frequency con-

    verter integrated in the motor.The two pumps run at the same

    speed when both are in operation.

    Full-sizeAll otherpumps

    Mains operation (on/off).

  • Delta Control 2000

    Functions

    Functions

    Delta Control 2000

    A standard Delta Control 2000 always includes the elec-tronics unit PFU 2000 (Pump Functional Unit 2000) builtinto the control cabinet.

    The PFU 2000 front cover with reset button and indi-cator lights is mounted in the front door of the controlcabinet.

    Alternatively, the Delta Control 2000 can be suppliedwith the PMU 2000 (Pump Management Unit 2000)mounted in the front door of the control cabinet.The PMU 2000 enables the read-out of operating dataand the optimisation of operation according to systemconditions.

    The Delta Control 2000 without PMU 2000 offers thefollowing functions:

    Control according to a constant differential pressure or a constant flow.

    Automatic changeover to mains operation in case of defective frequency converter (Delta Control 2000 F only).

    Automatic cascade control of pumps.

    Possibility of setpoint influence:proportional influence (proportional pressure), external setpoint influence.

    Possibility of remote control:system on/off.

    Pump and system monitoring functions:motor protection.

    Display and indication functions:green indicator light for operating indications and

    red indicator light for fault indications,potential-free changeover contacts for operation

    and fault.

    Grundfos BUS communication.

    The Delta Control 2000 with PMU 2000 offers thefollowing functions:

    Pump control based on differential pressure, differen-tial temperature, temperature, flow or level.

    Automatic changeover to mains operation in case of defective frequency converter (Delta Control 2000 F only).

    Automatic cascade control of pumps.

    Selection of switching sequences, automatic pump changeover and pump priority.

    Manual operation.

    Possibility of setpoint influence:proportional influence (proportional pressure), external setpoint influence.

    Possibility of digital remote-control functions:system on/off,reduced operation,setpoint control with two-point switch,setpoint control with three-point switch,alternative setpoint.

    Pump and system monitoring functions:minimum and maximum limits of actual value,motor protection.

    Display and indication functions:2 x 24 character LCD display,green indicator light for operating indications and

    red indicator light for fault indications,potential-free changeover contacts for operation

    and fault.

    Clock functions.

    Grundfos BUS communication.

    PCU 2000

    A PCU 2000 (Pump Communication Unit 2000) can beconnected to the Delta Control 2000 via the BUS input.The PCU 2000 enables remote operating and fault indi-cation for each individual pump.The PCU 2000 also enables external setpoint influenceand system on/off.

    Functions, Delta Control 2000

    Functions

    25

  • 26

    Functions Del

    ta Control 2000

    Type keyExample Control 2000 MEH 2 x 5.5 SD + 2 x 3.0 E PMU 3 x 400/230 V, 50 Hz IP 54

    Type range

    Supgroup:MF - MFH - ME - MEH

    Number of full-size pumps 1 - 4

    Power, full-size pumps [kW]

    Starting method of full size pumps:DOL: Direct-on-line startingSD: Star-delta startingE: Electronic soft start (MGE motor)

    Number of half-size pumps 1 - 2

    Power, half-size pumps [kW]

    Starting method of half-size pumps:DOL: Direct-on-line startingSD: Star-delta startingE: Electronic soft start (MGE motor)

    Control panel:PMU: PMU 2000PFU: PFU 2000

    Supply voltage/frequency

    Enclosure class:IP 54IP 00

  • 27

  • 28

    Delta Control 2000

    Functions

    Examples of functioningThe following table shows examples of Delta Control 2000 systems using constant differential pressure control.

    Variable speed

    GRUNDFOSDelta Control 2000 MF

    GRUNDFOSDelta Control 2000 MFH

    TM0

    1 10

    24 3

    397

    TM0

    1 10

    25 3

    397

    One pump in operation viafrequency converter.

    The half-size pump in opera-tion via frequency converter.

    TM0

    1 10

    86 3

    69

    7

    TM0

    1 10

    88 3

    69

    7

    One pump in operation viafrequency converter. Twopumps are mains-operated(on/off).

    One half-size pump in opera-tion via frequency converter.One full-size pump is mains-operated (on/off).

    TM0

    1 10

    87 3

    69

    7

    TM0

    1 10

    89 3

    69

    7

    Maintains a constant dif-ferential pressure through continuously variable ad-justment of the speed of one pump. The other mains-operated pumps are cut in/out according to the demand.

    The pump controlled by the frequency converter always starts first.

    Pump changeover is auto-matic and depends on load, time and fault.

    All pumps will be control-led by the frequency con-verter in rotation.

    Maintains a constant dif-ferential pressure through continuously variable ad-justment of the speed of one half-size pump. The orher pumps are mains-operated.

    The half-size pump con-trolled by the frequency converter always starts first.

    Pump changeover is auto-matic and depends on load, time and fault.

    P

    PFU 2000

    P

    PFU 2000

    Q

    H

    H set

    Q

    H

    H set

    Q

    H

    H set

    Q

    H

    H set

  • Functions Delta

    Control 2000

    Examples of functioning, cont.The following table shows examples of Delta Control 2000 systems using constant differential pressure control.

    Variable speed

    GRUNDFOSDelta Control 2000 ME

    GRUNDFOSDelta Control 2000 MEH

    GRUNDFOSDelta Control ME (PO)

    TM0

    1 10

    26 3

    397

    TM0

    1 10

    27 3

    397

    TM0

    1 27

    01

    229

    8

    One pump in operation. The half-size pump with MGEmotor in operation.

    One half-size pump withMGE motor in operation.

    TM0

    1 10

    90

    36

    97

    TM0

    1 10

    93

    369

    7

    TM0

    1 10

    93

    369

    7Three pumps in operation. One half-size pump with MGE

    motor and the full-size pumpin operation.

    One half-size pump with MGEmotor and the full-size pumpin operation.

    TM0

    1 10

    91

    369

    7

    TM0

    1 10

    93

    369

    7

    TM0

    1 10

    93

    369

    7

    Maintains a constant pressure through continu-ously variable adjust-ment of the speed of the pumps connected.

    The system performance is adjusted to the demand through cutting in/out the required number of pumps and through paral-lel control of the pumps in operation.

    Pump changeover is auto-matic and depends on load, time and fault.

    Maintains a constant pressure through continu-ously variable adjust-ment of the speed of the two half-size pumps with MGE motors, while the full-size pump is mains-operated. (on/off).

    The half-size pumps al-ways start first.

    Pump changeover is auto-matic and depends on load, time and fault.

    Maintains a constant pressure through continu-ously variable adjust-ment of the speed of the pumps connected.

    The system performance is adjusted to the demand through cutting in/out the required number of pumps and through paral-lel control of the pumps in operation.

    Pump changeover is auto-matic and depends on load, time and fault.

    P

    PFU 2000

    MGE MGE MGE P

    PFU 2000

    MGE MGE P

    PFU 2000

    MGE MGE MGE

    Q

    H

    H set

    Q

    H

    H set

    Q

    H

    H set

    Q

    H

    H set

    Q

    H

    H set

    Q

    H

    H set

    29

  • 30

    Functions Del

    ta Control 2000

    Control parameters

    Systems without PMU 2000

    Controllers without the PMU 2000 can be used insystems having small time constants and are pre-set tothe control parameter "differential pressure". However,they can also be used with other control parameters,such as "flow" etc.

    Cascade control:

    Cascade control ensures automatic adjustment ofperformance to the system demand by cutting in/outthe required number of pumps.The controller will operate the system with as fewpumps as possible.

    Automatic pump changeover:

    Automatic pump changeover is made as follows:

    Fault-dependent pump changeover.If a pump is faulty, it will be switched off and the next pump ready for operation will be switched on.

    Time-dependent pump changeover.This ensures that the operating hours are distributed evenly on the pumps connected. This function is combined with the test run function.

    Test run:

    To eliminate the risk of pump seizure caused by longperiods of standstill, a test run lasting 1 second is carriedout once every 24 hours.

    Setpoint:

    The setpoint is set by means of the function selector inthe PFU 2000. It is also possible to stop all pumps, or toset all pumps to operate at maximum performance.

    Remote setpoint setting:

    A 0 - 10 V or 0 - 20 mA signal can be connected for remotesetpoint setting.

    The locally set setpoint is set by means of the functionselector in the PFU 2000.

    Sensor input:

    Sensors giving the following analog signals can beconnected:

    0 - 10 V,

    0 - 20 mA,

    4 - 20 mA.

    Input for external start/stop:

    A potential-free contact for external start/stop of allpumps can be connected.

    TM

    01 1

    124

    3897

    TM

    01 1

    125

    3897

    PFU 2000

    P

    Differential pressure

    FT

    PFU 2000

    Flow

    TM

    00 5

    217

    2796

    TM

    00 7

    048

    0296

    100%0%

    MAXSTOP

    Setpoint

    Function selector in the PFU 2000

    0 10 V

    Locally set setpoint

    100%

    Current setpointTr

    ansm

    itter

    rang

    eActual setpoint

    Tran

    smit

    ter r

    ang

    e

    Locally set setpoint

    100%

    10V

    Setpoint via external signals

    10V20mA

  • Functions Delta

    Control 2000

    Systems with PMU 2000The PMU 2000 is designed for the control of variouspumps or pumping systems. As an example, the PMU2000 can be used for the control of GRUNDFOS circulatorpumps of the UPE type and pumping systems andcontrollers based on the PFU 2000, such as the DeltaControl 2000.The control parameters offered by the Delta Control2000 are shown in the table below:

    Fig. 1

    Fig. 2

    Fig. 3

    Fig. 4

    Fig. 5

    Fig. 6

    Fig. 7

    Fig. 8

    Fig. Control parametersPossible with controller

    without PMU with PMU

    1 Differential pressure

    2 Differential temperature

    3Flow-pipe temperature with one sensor

    4Return-pipe temperature with one sensor

    5Differential temperature with one sensor signal

    6 Flow

    7 Level

    8 Open loop (uncontrolled)

    TM

    00 4

    985

    4894

    TM

    00 4

    998

    3897

    TM

    00 2

    718

    3897

    Differential pressure

    PFU 2000

    PMU 2000

    P

    BUSBUS

    Differential temperature

    PMU 2000

    BUS

    T

    PFU 2000

    BUS

    Flow-pipe temperature

    T

    PFU 2000

    PMU 2000

    BUSBUS

    TM

    00 2

    719

    3897

    TM

    01 1

    257

    4097

    TM

    00 2

    715

    3897

    TM

    01 1

    123

    3897

    TM

    00 4

    986

    4894

    Return-pipe temperature

    PMU 2000

    T

    PFU 2000

    BUS

    Differential temperature

    PMU 2000

    T

    PFU 2000

    BUSBUS

    Flow

    PMU 2000

    BUS

    FT

    PFU 2000

    BUS

    Level

    BUS

    PMU 2000

    h

    LTPFU 2000

    BUS

    Open loop

    PFU 2000

    PMU 2000

    BUSBUS

    31

  • 32

    Functions Del

    ta Control 2000

    Cascade control:

    Cascade control ensures automatic adjustment ofperformance to the system demand by cutting in/outthe required number of pumps. The controller willoperate the system with as few pumps as possible. Theon/off rate is limited by setting the switchingsequences.

    Automatic pump changeover:

    Automatic pump changeover is made as follows:

    Fault-dependent pump changeover.If a pump is faulty, it will be switched off and the next pump ready for operation will be switched on.

    Time-dependent pump changeover.This ensures that the operating hours are distributed evenly on the pumps connected. This function is combined with the test run function.

    Test run:

    To eliminate the risk of pump seizure caused by longperiods of standstill, a test run lasting 1 second is carriedout once every 24 hours.

    Clock functions:

    If the system demand varies during the day and/orduring the week, the pump performance required willalso vary. In this case, a clock program can be set in orderto achieve optimum performance of the pumps.It is possible to set a total of 10 switching times, allhaving individual setpoints.

    Standby pumps:

    In systems with more than one pump, standby pumpscan be selected. A standby pump is started only if one ofthe duty pumps is faulty. Example: In a system with fourpumps, of which one pump has been selected asstandby-pump, the maximum number of pumps in oper-ation at the same time will be three. The standby pumpis started only if one of the duty pumps is faulty.

    Setpoint:

    The max. setpoint is set in the PMU 2000 menu

    Friction loss compensation:

    The control unit is capable of compensating for frictionloss. The setpoint increases from an adjustablepercentage at zero flow to 100% at max. flow.

    The actual flow is estimated based on internal operatingdata without the flow being measured directly.

    Remote setpoint setting:

    In view of optimizing system operation, it is often bestfor the system to operate according to a variablesetpoint instead of a constant setpoint. The selectedsettings influencing the setpoint will reduce "setpointmax".The following possibilities are available:

    "extern" (%)An external analog signal or potential-free contact influences the setpoint in accordance with a table.

    "timer" (minutes)An internal timer program in the PMU 2000 controls the setpoint in accordance with a table.

    "Temp Tf" (C, F)The flow-pipe temperature controls the setpoint in accordance with a table.

    "Temp Tr" (C, F)The return-pipe temperature controls the setpoint in accordance with a table.

    "Temp To" (C, F)The ambient temperature controls the setpoint in ac-cordance with a table.

    "level" (m, cm, ft, in)The level signal controls the setpoint in accordance with a table.

    "flow" (m3/h, l/h, l/s, gpm) The flow signal controls the setpoint in accordance with a table.Example of application: Differential pressure drop compensation in circulation system if a flow meter signal is available.

    "flow/I" (%), (applies only to Delta Control 2000 F)An internal flow signal controls the setpoint in ac-cordance with a table.Example of application: Differential pressure drop compensation in circulation system if no flow meter signal is available.

    Sensor input:

    Sensors giving the following analog signals can beconnected:

    0 - 10 V,

    0 - 20 mA,

    4 - 20 mA.

    TM

    00 4

    989

    4894

    Set A

    Setpoint max. 12.5 bar

    Setpoint

    1 3

    C

    A

    2 Time

    B

    Time

    Setpoint

    Clock program with three switching times

    TM

    00 4

    991

    4894

    Setpoint max

    Q

    H

    100 %

    60 %

    Setpoint max.100%

    60%

    Q

    H

    Friction loss compensation

  • Delta Control 2000

    Technical data

    Dimensions and weightsDimensions and weights are for control cabinets with aPFU 2000 control panel.

    All motors must be three-phase.

    The starting methods of the motors are:

    DOL (Direct-on-line starting)

    SD (Star-delta starting)

    E (Electronic soft start via frequency converter).

    Delta Control 2000 MF

    TM

    01 0

    473

    2402

    D B

    HDelta C

    ontrol 2000

    Motor[kW]

    Mounting of control

    cabinetStartingfull-size

    Delta Control 2000 MF for 1 pump

    Delta Control 2000 MF for 2 pumps

    Delta Control 2000 MF for 3 pumps

    Delta Control 2000 MF for 4 pumps

    Dimensions [mm] Weight

    [kg]

    Dimensions [mm] Weight

    [kg]

    Dimensions [mm] Weight

    [kg]

    Dimensions [mm] Weight

    [kg]H B D H B D H B D H B D

    0.75 Floor mount. DOL 1000 800 300 78 1000 800 300 79 1000 800 300 80 1000 800 300 81

    1.1 Floor mount. DOL 1000 800 300 78 1000 800 300 79 1000 800 300 80 1000 800 300 81

    1.5 Floor mount. DOL 1000 800 300 78 1000 800 300 79 1000 800 300 80 1000 800 300 81

    2.2 Floor mount. DOL 1000 800 300 78 1000 800 300 79 1000 800 300 80 1000 800 300 81

    3 Floor mount.DOL 1000 800 300 78 1000 800 300 79 1000 800 300 80 1000 800 300 81

    SD 1000 800 300 78 1000 800 300 80 1200 800 300 95 1200 1000 300 113

    4 Floor mount.DOL 1200 800 300 100 1200 800 300 101 1200 800 300 102 1200 800 300 103

    SD 1200 800 300 100 1200 800 300 102 1200 800 300 104 1200 1000 300 122

    5.5 Floor mount.DOL 1200 800 300 100 1200 800 300 101 1200 800 300 103 1200 800 300 104

    SD 1200 800 300 100 1200 800 300 103 1200 800 300 105 1200 1000 300 122

    7.5 Floor mount.DOL 1200 800 300 92 1200 800 300 93 1200 800 300 94 1200 800 300 96

    SD 1200 800 300 92 1200 800 300 94 1200 800 300 96 1200 1000 300 114

    11 Floor mount.DOL 1900 800 400 168 1900 800 400 172 1900 1000 400 202 1900 1000 400 205

    SD 1900 800 400 171 1900 800 400 174 1900 1000 400 204 1900 1000 400 208

    15 Floor mount.DOL 1900 800 400 174 1900 800 400 179 1900 1000 400 206 1900 1000 400 209

    SD 1900 1000 400 200 1900 1000 400 204 1900 1200 400 244 1900 1200 400 247

    18.5 Floor mount.DOL 1900 1000 400 207 1900 1000 400 212 1900 1200 400 253 1900 1200 400 258

    SD 1900 1000 400 208 1900 1000 400 213 1900 1600 400 301 1900 1600 400 306

    22 Floor mount.DOL 1900 1000 400 208 1900 1000 400 213 1900 1200 400 253 1900 1200 400 258

    SD 1900 1000 400 208 1900 1000 400 214 1900 1600 400 303 1900 1600 400 310

    30 Floor mount.DOL 1900 1200 400 262 1900 1200 400 260 1900 1800 400 409 1900 2000 400 441

    SD 1900 1200 400 264 1900 1200 400 264 1900 1800 400 414 1900 2200 400 499

    37 Floor mount.DOL 1900 1200 400 269 1900 1200 400 266 1900 1800 400 416 1900 2000 400 449

    SD 1900 1200 400 271 1900 1200 400 271 1900 1800 400 424 1900 2200 400 510

    45 Floor mount.DOL 1900 1200 400 269 1900 1800 400 403 1900 1800 400 416 1900 2000 400 449

    SD 1900 1200 400 271 1900 1800 400 408 1900 1800 400 424 1900 2200 400 510

    55 Floor mount.DOL 1900 2000 500 552 1900 2200 500 612 1900 2600 500 690 1900 3000 500 794

    SD 1900 2000 500 553 1900 2200 500 614 1900 2600 500 693 1900 3000 500 794

    75 Floor mount.DOL 1900 2000 500 554 1900 2200 500 616 1900 2600 500 697 1900 3000 500 802

    SD 1900 2000 500 556 1900 2200 500 618 1900 2600 500 700 1900 3000 500 804

    Technical data, Delta Control 2000

    33

  • 34

    Technical data Del

    ta Control 2000

    Dimensions and weightsDimensions and weights are for control cabinets with aPFU 2000 control panel.

    All motors must be three-phase.

    Delta Control 2000 MFH

    TM

    01 0

    473

    2402

    D B

    HDelta C

    ontrol 2000

    Motor

    Startingfull-size

    Startinghalf-size

    Delta Control 2000 MFH for 3 pumps

    (1 full-size and 2 half-size)

    Delta Control 2000 MFH for 4 pumps

    (2 full-size and 2 half-size)

    Full-size[kW]

    Mounting of control

    cabinet

    Half-size[kW]

    Dimensions[mm] Weight

    [kg]

    Dimensions[mm] Weight

    [kg]H B D H B D

    11Floor

    mounting7.5

    DOL DOL 1200 800 300 95 1200 800 300 100

    SD SD 1200 1000 300 97 1200 1000 300 123

    15Floor

    mounting7.5

    DOL DOL 1200 1000 300 115 1200 1000 300 118

    SD SD 1200 1000 300 118 1200 1000 300 125

    15Floor

    mounting11

    DOL DOL 1900 1000 400 202 1900 1000 400 205

    SD SD 1900 1000 400 205 1900 1000 400 208

    18.5Floor

    mounting11

    DOL DOL 1900 1000 400 204 1900 1000 400 207

    SD SD 1900 1000 400 205 1900 1000 400 209

    22Floor

    mounting11

    DOL DOL 1900 1000 400 204 1900 1000 400 207

    SD SD 1900 1000 400 206 1900 1000 400 210

    22Floor

    mounting15

    DOL DOL 1900 1200 400 207 1900 1000 400 210

    SD SD 1900 1200 400 244 1900 1200 400 248

    30Floor

    mounting15

    DOL DOL 1900 1600 400 208 1900 1400 400 320

    SD SD 1900 1200 400 247 1900 1600 400 299

    30Floor

    mounting18.5

    DOL DOL 1900 1600 400 218 1900 1400 400 330

    SD SD 1900 1600 400 304 1900 1600 400 308

    37Floor

    mounting18.5

    DOL DOL 1900 1000 400 218 1900 1400 400 330

    SD SD 1900 1600 400 305 1900 1600 400 310

    37Floor

    mounting22

    DOL DOL 1900 1000 400 254 1900 1400 400 330

    SD SD 1900 1600 400 305 1900 1600 400 310

    45Floor

    mounting30

    DOL DOL 1900 1600 400 319 1900 1600 400 323

    SD SD 1900 1600 400 325 1900 1600 400 331

    55Floor

    mounting30

    DOL DOL 1900 1600 400 323 1900 1600 400 330

    SD SD 1900 1600 400 325 1900 1600 400 333

    75Floor

    mounting37

    DOL DOL 1900 1600 400 330 1900 1600 400 339

    SD SD 1900 1800 400 424 1900 1800 400 431

    75Floor

    mounting45

    DOL DOL 1900 1600 400 330 1900 1600 400 339

    SD SD 1900 1800 400 424 1900 1800 400 431

  • Technical data Delta

    Control 2000

    Dimensions and weights Dimensions and weights are for control cabinets with aPFU 2000 control panel.

    All motors must be three-phase.

    Note: E-pumps marked with """ must be with single-phase mains connection.

    Delta Control 2000 ME

    TM

    00 9

    394

    2402

    D B

    H

    Delta Control

    2000

    Motor[kW]

    Startingfull-size

    [kW]

    Delta Control 2000 ME for 1 pump

    Delta Control 2000 ME for 2 pumps

    Delta Control 2000 ME for 3 pumps

    Delta Control 2000 ME for 4 pumps

    Dimensions [mm] Weight

    [kg]

    Dimensions[mm] Weight

    [kg]

    Dimensions[mm] Weight

    [kg]

    Dimensions[mm] Weight

    [kg]H B D H B D H B D H B D

    1.1 " E 380 380 210 15.0 380 380 210 14.2 600 380 210 19.8 600 380 210 20.1

    1.1 E 380 380 210 15.0 380 380 210 14.2 600 380 210 19.8 600 380 210 20.1

    1.5 E 600 380 210 23.0 600 380 210 19.8 600 380 210 20.2 600 380 210 20.6

    2.2 E 600 380 210 23.0 600 380 210 19.8 600 380 210 20.2 600 380 210 20.6

    3 E 600 380 210 23.0 600 380 210 19.8 600 380 210 20.2 600 380 210 20.6

    4 E 600 380 210 23.0 600 380 210 19.8 600 380 210 20.2 600 380 210 20.6

    5.5 E 600 380 210 24.0 600 380 210 19.8 600 380 210 20.2 600 380 210 20.9

    7.5 E 600 380 210 24.0 600 380 210 35.0 600 380 210 36.0 600 600 210 47.0

    11 E 600 380 210 24.0 600 380 210 35.0 600 380 210 37.0 600 600 210 48.0

    15 E 600 380 210 24.0 600 380 210 36.0 600 600 210 47.0 760 760 210 67.0

    18.5 E 600 380 210 24.0 600 380 210 36.0 760 760 210 66.0 760 760 210 67.0

    22 E 600 380 210 25.0 600 600 210 47.0 760 760 210 67.0 760 760 210 68.0

    35

  • 36

    Technical data Del

    ta Control 2000

    Delta Control 2000 MEH

    Delta Control 2000 MES

    Motor

    Startingfull-size

    Startinghalf-size

    Delta Control 2000 MEH for 3 pumps

    (1 full-size and 2 half-size)

    Delta Control 2000 MEH for 4 pumps

    (2 full-size and 2 half-size)

    Full-size

    [kW]

    Mountingof control

    cabinet

    Half-size

    [kW]

    Dimensions[mm] Weight

    [kg]

    Dimensions[mm] Weight

    [kg]H B D H B D

    1.1 Wall mount. 0.75 " DOL E 600 380 210 20.1 600 380 210 20.6

    1.5 Wall mount. 1.1 " DOL E 600 380 210 20.1 600 380 210 20.6

    2.2 Wall mount. 1.1 " DOL E 600 380 210 20.1 600 380 210 20.6

    2.2 Wall mount. 1.5 DOL E 600 380 210 20.3 600 380 210 20.9

    3 Wall mount. 1.5DOL E 600 380 210 20.3 600 380 210 20.9

    SD E 600 380 210 20.3 600 380 210 22.3

    3 Wall mount. 2.2DOL E 600 380 210 20.3 600 380 210 20.9

    SD E 600 380 210 20.3 600 380 210 22.3

    4 Wall mount. 2.2DOL E 600 380 210 31.1 600 380 210 31.1

    SD E 600 600 210 31.1 600 600 210 32.5

    4 Wall mount. 3DOL E 600 380 210 31.1 600 380 210 31.1

    SD E 600 600 210 31.1 600 600 210 32.5

    5.5 Wall mount. 3DOL E 600 600 210 31.1 600 600 210 31.1

    SD E 600 600 210 31.1 600 600 210 32.9

    5.5 Wall mount. 4DOL E 600 600 210 31.5 600 600 210 31.5

    SD E 600 600 210 31.5 600 600 210 32.9

    7.5 Wall mount. 4DOL E 600 600 210 31.5 1000 800 300 31.5

    SD E 600 600 210 31.5 1000 800 300 65.0

    11 Wall mount. 5.5DOL E 600 600 210 31.5 1000 800 300 31.5

    SD E 600 600 210 31.5 1000 800 300 65.0

    15 Wall mount. 11DOL E 600 600 210 47.0 760 760 210 67.0

    SD E 600 600 210 48.0 760 760 210 68.0

    18.5 Wall mount. 11DOL E 600 600 210 48.0 760 760 210 69.0

    SD E 600 600 210 48.0 760 760 210 69.0

    22 Wall mount. 11DOL E 600 600 210 50.0 1000 800 300 91.0

    SD E 600 600 210 49.0 760 760 210 70.0

    18.5 Wall mount. 15DOL E 600 600 210 49.0 760 760 210 69.0

    SD E 600 600 210 49.0 760 760 210 70.0

    22 Wall mount. 15DOL E 1000 800 300 86.0 1000 800 300 91.0

    SD E 760 760 210 67.0 760 760 210 71.0

    22 Wall mount. 18.5DOL E 1000 800 300 86.0 1000 800 300 91.0

    SD E 760 760 210 67.0 1000 800 300 71.0

    Motor [kW]

    Mountingof control

    cabinet

    Startingfull-size

    Delta Control 2000 MES for 2 pumps

    Delta Control 2000 MES for 3 pumps

    Delta Control 2000 MES for 4 pumps

    Dimensions[mm] Weight

    [kg]

    Dimensions [mm] Weight

    [kg]

    Dimensions[mm] Weight

    [kg]H B D H B D H B D

    11 Wall mount. E/DOL 600 380 210 36.0 600 600 210 47.0 600 600 210 49.0

    11 Wall mount. E/SD 600 600 210 46.0 600 600 210 48.0 600 600 210 51.0

    15 Wall mount. E/DOL 600 600 210 46.0 600 600 210 48.0 760 760 210 67.0

    15 Wall mount. E/SD 600 600 210 47.0 600 600 210 49.0 760 760 210 70.0

    18.5 Wall mount. E/DOL 600 600 210 47.0 760 760 210 68.0 760 760 210 71.0

    18.5 Wall mount. E/SD 600 600 210 48.0 760 760 210 68.0 760 760 210 72.0

    22 Wall mount. E/DOL 600 600 210 50.0 1000 800 300 90.0 1000 800 300 94.0

    22 Wall mount. E/SD 600 600 210 49.0 760 760 210 70.0 760 760 210 73.0

  • Technical data Delta

    Control 2000

    Dimensions and weightsThe Delta Control 2000 ME (PO) is prepared for DIN-railmounting.

    Delta Control 2000 ME (PO)

    VersionWeight [kg]

    Net weight Gross Weight

    Delta Control 2000 ME (PO) 1.4 1.7

    TM

    00 2

    734

    2402

    80

    60 5

    150

    200

    200

    140

    98

    37

  • 38

    Technical data Del

    ta Control 2000

    Product numbersProduct numbers for control cabinets with a PFU 2000control panel.

    All motors must be three-phase.

    Supply voltage:3 x 400 V +6%/10%, N, 50 Hz, PE.

    Enclosure class: IP 54.

    The starting methods of the motors are:

    DOL (Direct-on-line starting)

    SD (Star-delta starting).

    Delta Control 2000 MF

    Motor[kW]

    Mountingof Control

    Cabinet

    Startingfull-size

    Product numbers

    Delta Control 2000 MF for 1 pump

    Delta Control 2000 MF for 2 pumps

    Delta Control 2000 MF for 3 pumps

    Delta Control 2000 MFfor 4 pumps

    0.75 Floor mounting DOL 96 01 15 15 96 01 15 45 96 01 15 75 96 01 16 05

    1.1 Floor mounting DOL 96 01 15 16 96 01 15 46 96 01 15 76 96 01 16 06

    1.5 Floor mounting DOL 96 01 15 17 96 01 15 47 96 01 15 77 96 01 16 07

    2.2 Floor mounting DOL 96 01 15 18 96 01 15 48 96 01 15 78 96 01 16 08

    3 Floor mountingDOL 96 01 15 19 96 01 15 49 96 01 15 79 96 01 16 09

    SD 96 01 15 32 96 01 15 62 96 01 15 92 96 01 16 22

    4 Floor mountingDOL 96 01 15 20 96 01 15 50 96 01 15 80 96 01 16 10

    SD 96 01 15 33 96 01 15 63 96 01 15 93 96 01 16 23

    5.5 Floor mountingDOL 96 01 15 21 96 01 15 51 96 01 15 81 96 01 16 11

    SD 96 01 15 34 96 01 15 64 96 01 15 94 96 01 16 24

    7.5 Floor mountingDOL 96 01 15 22 96 01 15 52 96 01 15 82 96 01 16 12

    SD 96 01 15 35 96 01 15 65 96 01 15 95 96 01 16 25

    11 Floor mountingDOL 96 01 15 23 96 01 15 53 96 01 15 83 96 01 16 13

    SD 96 01 15 36 96 01 15 66 96 01 15 96 96 01 16 26

    15 Floor mountingDOL 96 01 15 24 96 01 15 54 96 01 15 84 96 01 16 14

    SD 96 01 15 37 96 01 15 67 96 01 15 97 96 01 16 27

    18.5 Floor mountingDOL 96 01 15 25 96 01 15 55 96 01 15 85 96 01 16 15

    SD 96 01 15 38 96 01 15 68 96 01 15 98 96 01 16 28

    22 Floor mountingDOL 96 01 15 26 96 01 15 56 96 01 15 86 96 01 16 16

    SD 96 01 15 39 96 01 15 69 96 01 15 99 96 01 16 29

    30 Floor mountingDOL 96 01 15 27 96 01 15 57 96 01 15 87 96 01 16 17

    SD 96 01 15 40 96 01 15 70 96 01 16 00 96 01 16 30

    37 Floor mountingDOL 96 01 15 28 96 01 15 58 96 01 15 88 96 01 16 18

    SD 96 01 15 41 96 01 15 71 96 01 16 01 96 01 16 31

    45 Floor mountingDOL 96 01 15 29 96 01 15 59 96 01 15 89 96 01 16 19

    SD 96 01 15 42 96 01 15 72 96 01 16 02 96 01 16 32

    55 Floor mountingDOL 96 01 15 30 96 01 15 60 96 01 15 90 96 01 16 20

    SD 96 01 15 43 96 01 15 73 96 01 16 03 96 01 16 33

    75 Floor mountingDOL 96 01 15 31 96 01 15 61 96 01 15 91 96 01 16 21

    SD 96 01 15 44 96 01 15 74 96 01 16 04 96 01 16 34

  • Technical data Delta

    Control 2000

    Product numbersProduct numbers for control cabinets with a PFU 2000control panel.

    All motors must be three-phase.

    Supply voltage:3 x 400 V +6%/10%, N, 50 Hz, PE.

    Enclosure class: IP 54.

    The starting methods of the motors are:

    DOL (Direct-on-line starting)

    SD (Star-delta starting).

    Delta Control 2000 MFH

    MotorMountingof Control

    Cabinet

    Startingfull-size

    Startinghalf-size

    Product numbers

    Full-size[kW]

    Half-size[kW]

    Delta Control 2000 MFH for 3 pumps

    (1 full-size and 2 half-size)

    Delta Control 2000 MFH for 4 pumps

    (2 full-size and 2 half-size)

    11 7.5 Floor mountingDOL DOL 96 01 16 35 96 01 16 63

    SD SD 96 01 16 49 96 01 16 77

    15 7.5 Floor mountingDOL DOL 96 01 16 36 96 01 16 64

    SD SD 96 01 16 50 96 01 16 78

    15 11 Floor mountingDOL DOL 96 01 16 37 96 01 16 65

    SD SD 96 01 16 51 96 01 16 79

    18.5 11 Floor mountingDOL DOL 96 01 16 38 96 01 16 66

    SD SD 96 01 16 52 96 01 16 80

    22 11 Floor mountingDOL DOL 96 01 16 39 96 01 16 67

    SD SD 96 01 16 53 96 01 16 81

    22 15 Floor mountingDOL DOL 96 01 16 40 96 01 16 68

    SD SD 96 01 16 54 96 01 16 82

    30 15 Floor mountingDOL DOL 96 01 16 41 96 01 16 69

    SD SD 96 01 16 55 96 01 16 83

    30 18.5 Floor mountingDOL DOL 96 01 16 42 96 01 16 70

    SD SD 96 01 16 56 96 01 16 84

    37 18.5 Floor mountingDOL DOL 96 01 16 43 96 01 16 71

    SD SD 96 01 16 57 96 01 16 85

    37 22 Floor mountingDOL DOL 96 01 16 44 96 01 16 72

    SD SD 96 01 16 58 96 01 16 86

    45 22 Floor mountingDOL DOL 96 01 16 45 96 01 16 73

    SD SD 96 01 16 59 96 01 16 88

    55 30 Floor mountingDOL DOL 96 01 16 46 96 01 16 74

    SD SD 96 01 16 60 96 01 16 88

    75 37 Floor mountingDOL DOL 96 01 16 47 96 01 16 75

    SD SD 96 01 16 61 96 01 16 89

    75 45 Floor mountingDOL DOL 96 01 16 48 96 01 16 76

    SD SD 96 01 16 62 96 01 16 90

    39

  • 40

    Technical data Del

    ta Control 2000

    Product numbersProduct numbers for control cabinets with a PFU 2000control panel.

    All motors must be three-phase

    Note: E-pumps marked with """ must be with single-phase mains connection.

    Supply voltage:3 x 400 V +6%/10%, N, 50 Hz, PE.

    Enclosure class: IP 54.

    The starting methods of the motors are:

    DOL (Direct-on-line starting)

    SD (Star-delta starting).

    Delta Control 2000 ME

    Motor[kW]

    Mountingof control

    cabinet

    Startingfull-size

    Product numbers

    Delta Control 2000 ME for 1 pump

    Delta Control 2000 ME for 2 pumps

    Delta Control 2000 ME for 3 pumps

    Delta Control 2000 ME for 4 pumps

    1.1 " Wall mounting E 96 01 14 88 96 01 14 95 96 01 15 02 96 01 15 09

    1.1 Wall mounting E 96 01 90 70 96 01 90 78 96 01 90 86 96 01 90 94

    1.5 Wall mounting E 96 01 14 89 96 01 14 96 96 01 15 03 96 01 15 10

    2.2 Wall mounting E 96 01 14 90 96 01 14 97 96 01 15 04 96 01 15 11

    3 Wall mounting E 96 01 14 91 96 01 14 98 96 01 15 05 96 01 15 12

    4 Wall mounting E 96 01 14 92 96 01 14 99 96 01 15 06 96 01 15 13

    5.5 Wall mounting E 96 01 14 93 96 01 15 00 96 01 15 07 96 01 15 14

    7.5 Wall mounting E 96 01 52 97 96 01 25 91 96 01 25 93 96 01 25 94

    11 Wall mounting E 96 01 33 57 96 01 33 61 96 01 33 65 96 01 33 69

    15 Wall mounting E 96 01 33 58 96 01 33 62 96 01 33 66 96 01 33 70

    18.5 Wall mounting E 96 01 33 59 96 01 33 63 96 01 33 67 96 01 33 71

    22 Wall mounting E 96 01 33 60 96 01 33 64 96 01 33 68 96 01 33 72

  • Technical data Delta

    Control 2000

    Delta Control 2000 MEH

    Delta Control MES

    Delta Control 2000 ME (PO)

    Supply voltage:1 x 230 V +6%/10%, N, 50 Hz, PE.

    Enclosure class: IP 42.

    MotorMountingof control

    cabinet

    Startingfull-size

    Startinghalf-size

    Product numbers

    Full-size[kW]

    Half-size[kW]

    Delta Control 2000 MEH for 3 pumps

    (1 full-size and 2 half-size)

    Delta Control 2000 MEH for 4 pumps

    (2 full-size and 2 half-size)

    1.1 0.75 " Wall mounting DOL E 96 01 16 91 96 01 17 11

    1.5 1.1 " Wall mounting DOL E 96 01 16 92 96 01 17 12

    2.2 1.1 " Wall mounting DOL E 96 01 16 93 96 01 17 13

    2.2 1.5 Wall mounting DOL E 96 01 16 94 96 01 17 14

    3 1.5 Wall mountingDOL E 96 01 16 95 96 01 17 15

    SD E 96 01 17 03 96 01 17 23

    3 2.2 Wall mountingDOL E 96 01 16 96 96 01 17 16

    SD E 96 01 17 04 96 01 17 24

    4 2.2 Wall mountingDOL E 96 01 16 97 96 01 17 17

    SD E 96 01 17 05 96 01 17 25

    4 3 Wall mountingDOL E 96 01 16 98 96 01 17 18

    SD E 96 01 17 06 96 01 17 26

    5.5 3 Wall mountingDOL E 96 01 16 99 96 01 17 19

    SD E 96 01 17 07 96 01 17 27

    5.5 4 Wall mountingDOL E 96 01 17 00 96 01 17 20

    SD E 96 01 17 08 96 01 17 28

    7.5 4 Wall mountingDOL E 96 01 17 01 96 01 17 21

    SD E 96 01 17 09 96 01 17 29

    11 5.5 Wall mountingDOL E 96 01 17 02 96 01 17 22

    SD E 96 01 17 10 96 01 17 30

    15 11 Wall mountingDOL E 96 01 36 05 96 01 36 11

    SD E 96 01 36 06 96 01 36 12

    18,5 11 Wall mountingDOL E 96 01 36 07 96 01 36 13

    SD E 96 01 36 08 96 01 36 14

    22 11 Wall mountingDOL E 96 01 36 09 96 01 36 15

    SD E 96 01 36 10 96 01 36 16

    18.5 15 Wall mountingDOL E 96 01 36 17 96 01 36 23

    SD E 96 01 36 18 96 01 36 24

    22 15 Wall mountingDOL E 96 01 36 19 96 01 36 25

    SD E 96 01 36 20 96 01 36 26

    22 18.5 Wall mountingDOL E 96 01 36 29 96 01 36 35

    SD E 96 01 36 30 96 01 36 36

    Motor[kW]

    Mountingof control

    cabinet

    Startingfull-size

    Product numbers

    Delta Control 2000 MES for 2 pumps

    Delta Control 2000 MES for 3 pumps

    Delta Control 2000 MES for 4 pumps

    11 Wall mounting E/DOL 96 01 3461 96 01 34 63 96 01 34 65

    11 Wall mounting E/SD 96 01 34 62 96 01 34 64 96 01 34 66

    15 Wall mounting E/DOL 96 01 34 67 96 01 34 69 96 01 34 71

    15 Wall mounting E/SD 96 01 34 68 96 01 34 70 96 01 34 72

    18,5 Wall mounting E/DOL 96 01 34 73 96 01 34 75 96 01 34 77

    18,5 Wall mounting E/SD 96 01 34 74 96 01 34 76 96 01 34 78

    22 Wall mounting E/DOL 96 01 34 79 96 01 34 81 96 01 34 83

    22 Wall mounting E/SD 96 01 34 80 96 01 34 82 96 01 34 84

    Description Product number

    Delta Control 2000 ME (PO) 96 01 20 91

    41

  • 42

    Control 2000Delta Control 2000

    Optional equipment

    Optional equipment is fitted from factory prior todelivery. Therefore, it is necessary to order the requiredoptional equipment at the same time as ordering theControl 2000 or Delta Control 2000.

    PMU 2000The PMU 2000 is fitted in the front door of the controlcabinet instead of the PFU 2000 control panel.

    The PMU 2000 enables regular optimization of opera-tion and read-out of operating data.

    Switching off of neutral leadAs standard, the Control 2000 and Delta Control 2000are supplied with a main switch switching off all threephases. If required, the controller 2000 can be suppliedwith a main switch switching off the three phases andthe neutral lead.

    Emergency operation switchThe emergency operation switch enables emergencyoperation if fault occurs in the control cabinet.Order one emergency operation switch for each pump.

    Example:If emergency operation switches are required for DeltaControl 2000 MFH with four pumps, order the following:

    two 96 02 00 98 (for mains-operated pumps) and

    two 96 02 00 99 (for half-size pumps).

    Description(language)

    MountingReference

    number

    Danish In front door 96 02 00 52

    English In front door 96 02 00 53

    French In front door 96 02 00 54

    Dutch In front door