© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090 Q.1.63 April 2019 KE2 ComboDisplay Temperature Display-Controller Combo: for Lights, Door Heaters, Panic Buon etc. - OR - Use with the KE2 Evap OEM Controller (pn 21231) for refrigeraon system control This reference should remain on site with the installed KE2 Combo Display. Contents Specifications Page 2 Accessories - Part Numbers Page 2 Combinations of Control Page 2 Dimensions Page 3 Connecting the Controllers Page 4 Menus and Parameters KE2 Combo Display - Stand Alone - Variables & Alarms Page 5 - Setpoints Page 6 KE2 Evap OEM Controller - Variables Page 7 - Setpoints Page 8-9 - Refrigerants Page 10 - Aux Input Modes Page 10 - Manual Menu Page 10 Alarms Page 11-12 Communications Page 12 The KE2 Combo Display brings together the funconality of a temperature display, lighng control, panic alarm, temperature alarm, and a door heater controller. It has three configu- raons: Stand-alone, Paired with one KE2 Evap OEM controller, and Paired with two KE2 Evap OEM controllers: When applied in stand-alone mode: Controls the door heaters to a specified temperature, reducing the energy required to maintain a freezer’s frost free door frame. Combined with KE2 Therm’s Panic buon, it provides a safety for associates working in the freezer in the unlikely event they are unable to exit the space. Lighng control can be integrated with a door switch to automacally turn the lights on and off. It serves as a temperature display and alarm, for one or two controlled spaces. Panic Buon: When pressed and held, the panic buon will display HELP on the display, sound the integrated audible alarm, acvate the alarm relay(de-energizes), and turn on the lights. Once the Alarm has been acvated the Alarm Silence buon will not work. The Panic Buon must be pressed and held for 3 seconds to reset the alarm. Door Switch: It may be used to monitor and alarm on door posion or it may be combined with the Lights Relay. When combined with the Lights relay, the controller will turn the lights on for the amount of me determined by the user and input in the Lights Off Delay aſter the door is closed. The lights will turn on and stay on for the me alloed. The last 30 seconds the lights will blink to indicate the lights are going to be turned off soon. This allows anyone in the space to make it to the door safely before the lights go out. Temperature Alarm: Input 1 will alarm for High Door Temp, Low Door Temp, and Door Temp1 Sensor Alarm. Input 2 & 3 will alarm for Room temp, Monitor Temp, Door Switch, and External Alarm. Baery Backup: When equipped with the control’s baery backup, the end user is able to view the space temperature(s), without opening the door and adding heat to the space. Aſter power loss, the controller sounds the buzzer for 60 seconds and the display alternates between each of the temperature inputs. The buzzer can be silenced by pressing the Silence Alarm buon. To view the temperature aſter the display has gone blank, press the Silence Alarm buon. The buzzer will chirp every 3 seconds. When used with the KE2 Evap OEM version 2.0 or newer: Includes everything available in stand-alone mode Informaon from the KE2 Combo Display is added to the Home and Status Pages E-mail alerts will be sent for Alarms originang from the KE2 Combo Display, as well as from the KE2 Evap OEM controller(s) KE2 Evap OEM controller’s informaon is accessible from the KE2 Combo Display includ- ing: Variables, Alarms, Setpoints and Manual Menu. KE2 Combo Display provides the ability to change addional KE2 Evap OEM setpoints not available from the Basic Display Audible Alarm will sound for Alarms originang from either controller

Contents This reference should remain on site with the ... · Temp1 Sensor Alarm. Input 2 & 3 will alarm for Room temp, Monitor Temp, Door Switch, and External Alarm. Battery Backup:

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Contents This reference should remain on site with the ... · Temp1 Sensor Alarm. Input 2 & 3 will alarm for Room temp, Monitor Temp, Door Switch, and External Alarm. Battery Backup:

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

Q.1.63April 2019

KE2 ComboDisplay Temperature Display-Controller Combo: for Lights, Door Heaters, Panic Button etc. - OR - Use with the KE2 Evap OEM Controller (pn 21231) for refrigeration system control

This reference should remain on site with the installed KE2 Combo Display.ContentsSpecifications Page 2

Accessories - Part Numbers Page 2

Combinations of Control Page 2

Dimensions Page 3

Connecting the Controllers Page 4

Menus and Parameters KE2 Combo Display - Stand Alone - Variables & Alarms Page 5 - Setpoints Page 6 KE2 Evap OEM Controller - Variables Page 7 - Setpoints Page 8-9 - Refrigerants Page 10 - Aux Input Modes Page 10 - Manual Menu Page 10

Alarms Page 11-12

Communications Page 12

The KE2 Combo Display brings together the functionality of a temperature display, lighting control, panic alarm, temperature alarm, and a door heater controller. It has three configu-rations: Stand-alone, Paired with one KE2 Evap OEM controller, and Paired with two KE2 Evap OEM controllers:

When applied in stand-alone mode:▪ Controls the door heaters to a specified temperature, reducing the energy required to

maintain a freezer’s frost free door frame.

▪ Combined with KE2 Therm’s Panic button, it provides a safety for associates working in the freezer in the unlikely event they are unable to exit the space.

▪ Lighting control can be integrated with a door switch to automatically turn the lights on and off.

▪ It serves as a temperature display and alarm, for one or two controlled spaces.

Panic Button: When pressed and held, the panic button will display HELP on the display, sound the integrated audible alarm, activate the alarm relay(de-energizes), and turn on the lights. Once the Alarm has been activated the Alarm Silence button will not work. The Panic Button must be pressed and held for 3 seconds to reset the alarm.

Door Switch: It may be used to monitor and alarm on door position or it may be combined with the Lights Relay. When combined with the Lights relay, the controller will turn the lights on for the amount of time determined by the user and input in the Lights Off Delay after the door is closed. The lights will turn on and stay on for the time allotted. The last 30 seconds the lights will blink to indicate the lights are going to be turned off soon. This allows anyone in the space to make it to the door safely before the lights go out.

Temperature Alarm: Input 1 will alarm for High Door Temp, Low Door Temp, and Door Temp1 Sensor Alarm. Input 2 & 3 will alarm for Room temp, Monitor Temp, Door Switch, and External Alarm.

Battery Backup: When equipped with the control’s battery backup, the end user is able to view the space temperature(s), without opening the door and adding heat to the space. After power loss, the controller sounds the buzzer for 60 seconds and the display alternates between each of the temperature inputs. The buzzer can be silenced by pressing the Silence Alarm button. To view the temperature after the display has gone blank, press the Silence Alarm button. The buzzer will chirp every 3 seconds.

When used with the KE2 Evap OEM version 2.0 or newer:▪ Includes everything available in stand-alone mode

▪ Information from the KE2 Combo Display is added to the Home and Status Pages

▪ E-mail alerts will be sent for Alarms originating from the KE2 Combo Display, as well as from the KE2 Evap OEM controller(s)

▪ KE2 Evap OEM controller’s information is accessible from the KE2 Combo Display includ-ing: Variables, Alarms, Setpoints and Manual Menu.

▪ KE2 Combo Display provides the ability to change additional KE2 Evap OEM setpoints not available from the Basic Display

▪ Audible Alarm will sound for Alarms originating from either controller

Page 2: Contents This reference should remain on site with the ... · Temp1 Sensor Alarm. Input 2 & 3 will alarm for Room temp, Monitor Temp, Door Switch, and External Alarm. Battery Backup:

KE2 ComboDisplayTemperature Display, Lighting and Door Heater Control, Temp Alarm and Panic Alarm Notifications- OR - Use with the KE2 Evap OEM Controller for refrigeration system control

Q.1.63 April 2019Page 2

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

SpecificationsControllerInput Voltage: 120V or 208V-240VAmbient Temp: -40°F to 140°F (-40°C to 60°C)Operating Temp: -40°F to 140°F (-40°C to 60°C)Operating Humidity Range 0% to 95%, non-condensable

Temperature/Digital Inputs

(3) multi-use (temp sensor or digital input)(1) designated as digital input for door switch

Input (1) designated for Panic button

Relays Outputs:Door Heater Relay - Max 3A @ 120 VACLights Relay - Max 5A @ 120/240 VACAlarm Relay - Max 5A @ 120/240 VAC

Communication: (1) RJ-11 connection for RS-485 serial communication to the KE2 Evap OEM controller

Buzzer 95dBBattery Backup 9 VDC, rechargeable battery

Temperature Sensor pn 20175 (45 in. leads), pn 20199 (10 ft. leads), pn 20220 (40 ft. leads)

Sensor Specs:-60°F to 150°F (-51°C to 65°C) moisture resistant package;stainless steel housing; 2K Ω @ 77°F

Accessories Remote DisplaysPart Number Description

21782 KE2 Combo Display Junction Box21320 KE2 Combo Display Less Junction Box21786 KE2 Combo Display Cable - 25 Ft.21781 Replacement 9V Recargeable Battery21375 1A 250V Slow Blow - 5mm x 20mm Fuse - TSC1A250-1A

NO NCCOM

EA

RTH

Combo Display Combo Display + (1) KE2 Evap OEM Board

PanicAlarm

LightControl

TempAlarm

Door Heater Control

Remote Display

PanicAlarm

LightControl

TempAlarm

Door Heater Control

Remote Display

+TEV/EEV

EvaporatorFans

DefrostHeaters

RoomTemperature

MultipleAlarms

Compressor/Liquid LineSolenoid

Remote Access& Control

DataLogging

Combo Display + (2) KE2 Evap OEM Boards

PanicAlarm

LightControl

TempAlarm

Door Heater Control

Remote Display

+ NO NCCOM

EA

RTH

TEV/EEV

EvaporatorFans

DefrostHeaters

RoomTemperature

MultipleAlarms

Compressor/Liquid LineSolenoid

Remote Access& Control

DataLogging

+ NO NCCOM

EA

RTH

TEV/EEV

EvaporatorFans

DefrostHeaters

RoomTemperature

MultipleAlarms

Compressor/Liquid LineSolenoid

Remote Access& Control

DataLogging

❶ ❷

Combinations of Control

Page 3: Contents This reference should remain on site with the ... · Temp1 Sensor Alarm. Input 2 & 3 will alarm for Room temp, Monitor Temp, Door Switch, and External Alarm. Battery Backup:

KE2 ComboDisplayTemperature Display, Lighting and Door Heater Control, Temp Alarm and Panic Alarm Notifications- OR - Use with the KE2 Evap OEM Controller for refrigeration system control

Q.1.63 April 2019Page 3

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

12-5/8

1-3/4 +wall thickness of walk-in

2-11/16

14FRONT OF ENCLOSURE

SIDE OF ENCLOSURE

BACK OF ENCLOSURE

2-11/16

14

1-1/2

3/4

11-1/2

10-9/16

6-1/169/16

1-7/8

3/16

1-1/16BACK OF BOARD

SIDE OF BOARDOnly the highest and lowest features depicted

3/16

1/16

1-1/8

Electrical Grounding Screw

Dimensions - Inches

Page 4: Contents This reference should remain on site with the ... · Temp1 Sensor Alarm. Input 2 & 3 will alarm for Room temp, Monitor Temp, Door Switch, and External Alarm. Battery Backup:

KE2 ComboDisplayTemperature Display, Lighting and Door Heater Control, Temp Alarm and Panic Alarm Notifications- OR - Use with the KE2 Evap OEM Controller for refrigeration system control

Q.1.63 April 2019Page 4

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

REL

AY

2

AU

X 3

TEM

P

AU

X 2

TEM

P

AU

X 1

TEM

P

DO

OR

SW

ITC

H

REL

AY

1

LIG

HTS

REL

AY

ALA

RM

S R

ELA

YD

e-en

ergi

zed

whe

n ac

tive

DO

OR

HEA

TER

R

ELA

Y

PO

WER

INP

UT

85

-26

5/

1/

50

-60

BA

TTER

Y

9 V

DC

/2

50

mA

h /

NiM

H

GN

D (b

lack

)S

IG (g

reen

)+

5V

DC

(red

) - li

ght

PA

NIC

BU

TTO

N

NO

CO

M NC

NO

CO

M NCIN

OU

T

RJ-

11

con

nect

ion

for

RS

-48

5

Com

mun

icat

ion

GR

OU

ND

6P

6C

Str

aigh

t

NONC

COM

TSuc

Aux

3

Aux

2

Aux

1

TCoi

l

TAir

0 -

10

V O

UTP

UT

ETH

ERN

ETD

ISP

LAY

DEF

RO

ST

REL

AY

SO

LEN

OID

(C

OM

PR

ESS

OR

) REL

AY

Blu

eO

rang

eY

ello

wR

ed

Bla

ck

Empt

yR

edG

reen

Whi

teB

lack

EEV

A B Shi

eld

RS

48

5

Red

B

lack

Gre

enP

SI

NO

CO

M

NC

EARTH

GR

OU

ND

NO

CO

M (L

2)

+ –

+ –

NONC

COM

TSuc

Aux

3

Aux

2

Aux

1

TCoi

l

TAir

0 -

10

V O

UTP

UT

ETH

ERN

ETD

ISP

LAY

DEF

RO

ST

REL

AY

SO

LEN

OID

(C

OM

PR

ESS

OR

) REL

AY

Blu

eO

rang

eY

ello

wR

ed

Bla

ck

Empt

yR

edG

reen

Whi

teB

lack

EEV

A B Shi

eld

RS

48

5

Red

B

lack

Gre

enP

SI

NO

CO

M

NC

EARTH

GR

OU

ND

NO

CO

M (L

2)

+ –

+ –

KE2

Com

bo D

ispl

ayKE

2 Ev

ap O

EM -

Boar

d 1

KE2

Evap

OEM

- Bo

ard

2

Com

plet

e w

iring

for t

he K

E2 E

vap

OEM

is fo

und

in b

ulle

tin Q

.1.4

5

12

36

54

7

Link

/AC

T

100/

1000

Mbp

sPO

WER

NET

WO

RK

SW

ITC

H

Connecting the Controllers

Conn

ectin

g th

e Co

ntro

llers

Page 5: Contents This reference should remain on site with the ... · Temp1 Sensor Alarm. Input 2 & 3 will alarm for Room temp, Monitor Temp, Door Switch, and External Alarm. Battery Backup:

KE2 ComboDisplayTemperature Display, Lighting and Door Heater Control, Temp Alarm and Panic Alarm Notifications- OR - Use with the KE2 Evap OEM Controller for refrigeration system control

Q.1.63 April 2019Page 5

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

KE2 COMBO DISPLAY - STAND ALONE - Alarms & Variables Menu

❶ ACCESS THE ALARMSMENU. Use the or to scroll through the Alarms & Variables menu. Note: Alarms will display first, if no alarms are active only the

Variables are displayed.

NAME DESCRIPTIONRoom Temp2 SenSoR AlARm Temp 2 input is shorted or open

Room Temp3 SenSoR AlARm Temp 3 input is shorted or open

moniToR Temp2 SenSoR AlARm Temp 2 input is shorted or open

HigH moniToR Temp2 AlARm Temp 2 input is above High Temp Alarm offset for longer than High Temp Alarm Delay.

low moniToR Temp2 AlARm Temp 2 is below Low Temp Alarm Offset for longer than Low Temp Alarm Delay.

moniToR Temp3 SenSoR AlARm Temp 3 input is shorted or open

HigH moniToR Temp3 AlARm Temp 3 input is above High Temp Alarm offset for longer than High Temp Alarm Delay.

low moniToR Temp3 AlARm Temp 3 input is below Low Temp Alarm offset for longer than Low Temp Alarm Delay.

DooR open AlARm Door has been open longer that Door Alarm Delay

DooR Temp SenSoR AlARm Temp1 input is shorted or open

low DooR Temp AlARm Door Temp is below Low Door Alarm Offset for longer than Door Temp Alarm Delay

HigH DooR Temp AlARm Door Temp is above High Door Alarm Offset for longer than Door Temp Alarm Delay

exTeRnAl AlARm 1, 2, oR 3 If input is selected as external alarm, and alarm becomes active

Temp 2 ReADing

Toggle between TEMP2 and value read by controller, if ‘DOOR SWITCH’ selected, ‘T2 DOOR CLOSED, T2 DOOR OPEN’ if ‘EX-TERNAL ALARM’ selected, ‘T2 EXT ALARM ACTIVE, T2 NO EXT ALARM

The range is -87.7 to 183.0 deg F. If there is a sensor failure, value will read 888.8. Will report T2 DOOR CLOSED if reads that door is closed, T2 DOOR OPEN if reads that door is open. Will report T2 EXT ALARM ACTIVE if reads that alarm is active, T2 NO EXT ALARM if reads alarm is inactive

Temp 3 ReADing

Toggle between TEMP3 and value read by controller. if ‘DOOR SWITCH’ selected, ‘T3 DOOR CLOSED, T3 DOOR OPEN’ if ‘EXTERNAL ALARM’ selected, ‘T3 EXT ALARM ACTIVE, T3 NO EXT ALARM

The range is -87.7 to 183.0 deg F. If there is a sensor failure, value will read 888.8. Will report T3 DOOR CLOSED if reads that door is closed, T3 DOOR OPEN if reads that door is open. Will report T3 EXT ALARM ACTIVE if reads that alarm is active, T3 NO EXT ALARM if reads alarm is inactive

DooR Temp ReADing

Toggle between TEMP1 and value read by controller. if ‘DOOR SWITCH’ selected, ‘T1 DOOR CLOSED, T1 DOOR OPEN’ if ‘EXTERNAL ALARM’ selected, ‘T1 EXT ALARM ACTIVE, T1 NO EXT ALARM

The range is -87.7 to 183.0 deg F. If there is a sensor failure, value will read D888. Will report T1 DOOR CLOSED if reads that door is closed, T1 DOOR OPEN if reads that door is open. Will report T1 EXT ALARM ACTIVE if reads that alarm is active, T1 NO EXT ALARM if reads alarm is inactive

DooR SwiTcH STATeDOOR CLOSED, DOOR OPEN, DOOR SWITCH DISABLED

Will report DOOR CLOSED if reads that door is closed, DOOR OPEN if reads that door is open, DOOR SWITCH DISABLED if door switch function is disabled

Page 6: Contents This reference should remain on site with the ... · Temp1 Sensor Alarm. Input 2 & 3 will alarm for Room temp, Monitor Temp, Door Switch, and External Alarm. Battery Backup:

KE2 ComboDisplayTemperature Display, Lighting and Door Heater Control, Temp Alarm and Panic Alarm Notifications- OR - Use with the KE2 Evap OEM Controller for refrigeration system control

Q.1.63 April 2019Page 6

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

KE2 COMBO DISPLAY - STAND ALONE - Setpoints Menu

❶ ACCESS THE SETPOINTS MENU Press and hold ENTER

BACK

and

ENTER

BACK for 3 seconds to access Setpoint mode. AUX1 Function is displayed. Use the or to scroll

through the Setpoints menu. (Press ENTER

BACK

to display the current value of a Setpoint). To change the value, press and hold ENTER

BACK

for 3 seconds.

❸ SELECT PARAMETER TO ADJUST If the if the yellow and red LEDs start blinking the setpoint has selectable options, use the or to scroll through the options.

When the value is a number, a digit starts blinking. Use the or to change the value of the digit, use the or to move to the next digit.

❹ Press and hold ENTER

BACK

for 3 seconds to save the change. Press

ENTER

BACK to return to the Setpoint menu. Repeat steps to change additional Setpoints, or press

ENTER

BACK

three times to return to the default display.

NAME Min MMax Default DESCRIPTION

AUx1 FUncTion DISABLED EXTERNAL ALARM DISABLED DISABLE/DOOR TEMP/DOOR SWITCH/EXTERNAL ALARM

AUx1 SwTcH STATe OPEN CLOSED OPEN State of input for door to be open or external alarm to be active

DooR Temp -10.0°F 100.0°F 35.0 °F Temperature where heaters are turned on

DooR Temp DiFF 0.1°F 10.0°F 3.0 °F Temperature offset above ‘DOOR TEMP’ to turn door heaters off

Hi DooR AlR oFST 0.1°F 100.0°F 100.0°F Temperature offset above ‘DOOR TEMP’ for high door temperature alarm

lo DooR AlR oFST 0.1°F 20.0°F 5.0°F Temperature offset below ‘DOOR TEMP’ for low door temperature alarm

DooR Temp AlR DlY 1 minute 1440 minutes 15 minutes Delay time when door temperature is out of range before setting alarm

DooR SwTcH STATe DISABLED CLOSED OPEN State of input for door to be open or disable function (disabled, open or closed)

DooR AlARm DelAY 0 minutes 1440 minutes 30 minutes Time for door to be open before setting door open alarm

ligHTS oFF DelAY 0 minutes 60 minutes 10 minutes Time after door closes that lights relay is de-energized

AUx2 FUncTion DISABLED EXTERNAL ALARM DISABLED DISABLE/ROOM TEMP/MONITOR TEMP/DOOR SWITCH/EXTERNAL ALARM

AUx2 SwTcH STATe OPEN CLOSED OPEN State of input for door to be open or external alarm to be active

AUx3 FUncTion DISABLED EXTERNAL ALARM DISABLED DISABLE/ROOM TEMP/MONITOR TEMP/DOOR SWITCH/EXTERNAL ALARM

AUx3 SwTcH STATe OPEN CLOSED OPEN

mon Tmp2 Hi AlRm -60.0°F 90.0°F 35.0°F If monitor temp2 is above this set point for some time, set high temp2 alarm

mon Tmp2 lo AlRm -60.0°F 90.0°F -10.0°F If monitor temp2 is below this set point for some time, set low temp2 alarm

mon Tmp2 Al DlY 1 minute 1440 minutes 15 minutes Delay time when monitor temp2 is out of range before setting alarm

mon Tmp3 Hi AlRm -60.0°F 90.0°F 35.0°F If monitor temp3 is above this set point for some time, set high temp3 alarm

mon Tmp3 lo AlRm -60.0°F 90.0°F -10.0°F If monitor temp3 is below this set point for some time, set low temp3 alarm

mon Tmp3 Al DlY 1 minute 1440 minutes 15 minutes Delay time when monitor temp3 is out of range before setting alarm

BUZZeR moDe DISABLED DOOR ALARM ONLY ENABLED Function for buzzer DISABLED, ENABLED, DOOR ALARM ONLY

DiSp BRigHTneSS 1 50 18 Dim or brighten display

ADDReSS 1 5 5 Modbus Address

DiSp cleAR AlARm – – – Press and hold ‘ENTER’ button for 3 seconds, until display changes, to clear alarms set in combo display

DiSp FAcToRY RST – – – Press and hold ‘ENTER’ button for 3 seconds, until display changes, to change set points to factory defaults

Page 7: Contents This reference should remain on site with the ... · Temp1 Sensor Alarm. Input 2 & 3 will alarm for Room temp, Monitor Temp, Door Switch, and External Alarm. Battery Backup:

KE2 ComboDisplayTemperature Display, Lighting and Door Heater Control, Temp Alarm and Panic Alarm Notifications- OR - Use with the KE2 Evap OEM Controller for refrigeration system control

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

Q.1.63 April 2019Page 7

KE2 EVAP OEM CONTROLLER - Variables Menu (Not Adjustable - View Only)

❶ ACCESS THE VARIABLES MENU The controllers should be scrolling on the Combo Display (Ex. Freezer, -10.2F, Defrost, Cooler 35.0F)

❷ Use the or to display the controller.

❸ Press ENTER

BACK

to select desired controller.

❹ Use he or to scroll through the menus (Setpoints - Variables - Manual Menu - Password - Alarms).

❺ Press ENTER

BACK

when Variables is displayed. Then use the or to scroll through the Variables column . Press

ENTER

BACK once to return to the Variable name. PressENTER

BACK three more times to return to the default display.

NAME DESCRIPTIONRoom Temp Room Temp as measured by controller

coil Temp Coil Temp as measured by controller

SYSTem moDe Current operating status

SUpeRHeAT Superheat as calculated by controller

SUcTion pReSSURe Suction Pressure as measured by controller

T1 SUcTion Temp Suction Temp as measured by controller

SATURATion Temp Saturation Temp as calculated by controller

VAlVe % open Percentage EEV is open

compReSSoR RelAY Current status of LLS/Compressor Relay

DeFRoST RelAY Current status of Defrost Relay

FAn RelAY Current status of Fan Relay

AUx 1 STATUS Current status/temperature as measured by controller at Aux Input 1

AUx 2 STATUS Current status/temperature as measured by controller at Aux Input 2

AUx 3 STATUS Current status/temperature as measured by controller at Aux Input 3

DiSp AUx 1 STATUS Current status/temperature as measured by Combo Display at Aux Input 1

DiSp AUx 2 STATUS Current status/temperature as measured by Combo Display at Aux Input 2

DiSp AUx 3 STATUS Current status/temperature as measured by Combo Display at Aux Input 3

DiSp AlARm RelAY Current status of Combo Display Alarm Relay

DiSp ligHT RelAY Current status of Combo Display Light Relay

DiSp HeATeR RelAY Current status of Combo Display Heater Relay

DiSp DooR Sw Current status of Combo Display Door Switch

ip ocTeT 1 First 3 digits of IP Address

ip ocTeT 2 Second 3 digits of IP Address

ip ocTeT 3 Third 3 digits of IP Address

ip ocTeT 4 Fourth 3 digits of IP Address

SUBneT mASK ocTeT 1 First 3 digits of Subnet Mast

SUBneT mASK ocTeT 2 Second 3 digits of Subnet Mast

SUBneT mASK ocTeT 3 Third 3 digits of Subnet Mast

SUBneT mASK ocTeT 4 Fourth 3 digits of Subnet Mast

FiRmwARe VeRSion Current version of firmware on controller

Page 8: Contents This reference should remain on site with the ... · Temp1 Sensor Alarm. Input 2 & 3 will alarm for Room temp, Monitor Temp, Door Switch, and External Alarm. Battery Backup:

KE2 ComboDisplayTemperature Display, Lighting and Door Heater Control, Temp Alarm and Panic Alarm Notifications- OR - Use with the KE2 Evap OEM Controller for refrigeration system control

Q.1.63 April 2019Page 8

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

KE2 EVAP OEM CONTROLLER - Setpoints Menu

❶ ACCESS THE SETPOINTS MENU The controllers should be scrolling on the Combo Display (Ex. Freezer, -10.2F, Defrost, Cooler 35.0F)

❷ Use the or until desired controller is displayed.

❸ Press ENTER

BACK

to select desired controller.

❹ Then, use the or to scroll through the menus. (Setpoints - Variables - Manual Menu - Password - Alarms). Press ENTER

BACK

when Setpoints is displayed. If you

are already logged in, go to step ❻.

❺ If you are not logged in, 0000 is displayed prompting you for the password. To enter the password (default is 2222), use the or to change the value of the

digit, use the or to move to the next digit. When the password is entered, press and hold ENTER

BACK

for 3 seconds.

❻ Then, use or to scroll through the Setpoints list. (Press ENTER

BACK

to display the current value of a Setpoint). To change the value, press and hold ENTER

BACK

for 3

seconds.

❼ SELECT PARAMETER TO ADJUST You will return the the Setpoint. If the if the yellow and red LEDs start blinking the setpoint has selectable options, use the or

to scroll through the options. When the value is a number, a digit starts blinking. Use the or to change the value of the digit, use the or to move to

the next digit.

❽ Press and hold ENTER

BACK

for 3 seconds to save the change.

❾ Press

ENTER

BACK to return to the Setpoint menu. Repeat steps to change additional Setpoints, or press

ENTER

BACK three times to return to the default display.

NAME Min MMax Default DESCRIPTIONRoom Temp -50.0°F 90.0°F 0.0°F Room Temp to be maintained

DeFRoST TYpe N/A N/A ELEC Type of Defrost for Evap: ELEC for Electric/AIR for off time/HOT GAS COMP ON for hot gas, comp is on/HOT GAS COMP OFF for hot gas, comp is off

VAlVe TYpe N/A N/A MECHANICAL Type of valve used on system; mechanical, pre-configured electric, custom EEV configuration

moToR TYpe UNIPOLAR BIPOLAR BIPOLAR UNIPOLAR if unipolar stepper used, BIPOLAR if bipolar stepper used. Only avail-able if VALVE TYPE = CUSTOM

moToR STep RATe 30 400 30 Number of steps per second. Only available if VALVE TYPE = CUSTOM

mAx VAlVe STepS 200 6400 500 Number of steps for full stroke of valve. Only available if VALVE TYPE = CUSTOM

SUpeRHeAT 5.0°F 30.0°F 8.0°F Target superheat. Only available if VALVE TYPE is any electric valve.

mAx opeRATing pReS 10.0 PSI 150.0 PSI 150.0 PSI Max Operating Pressure. Max is 300 when R-410a is selected. Max is 500 when R-744 is selected. Only available if VALVE TYPE is any electric valve

ReFRigeRAnT N/A N/A R-404A Type of refrigerant used: See table on following page

FAn SpeeD -100.0% 100.0% 0.0% Fans speed %.

min comp RUn Time 0 Min 15 Min 2 Min Minimum Compressor Run Time

min comp oFF Time 0 Min 15 Min 5 Min Minimum Compressor Off Time

ReFRig FAn moDe MANAGED, PERMANENT, ON W/ COMPRESSOR, TITLE 24

ON W/ COM-PRESSOR

MANAGED = manage fans during refrig cycle; PERMANENT = fans on permanent during refrig cycle; ON W/ COMPRESSOR = manage fan in OFF then on if refrig; TITLE 24 = cycle fans based on Title 24 regulations

DeFRoST moDe DEMAND, SCHEDULE, RUNTIME DEMAND Mode to initiate a defrost; DEMAND, SCHEDULE, RUNTIME = Comp Run time

DeFRoSTS / DAY 0 8 5 If DEFROST MODE = SCHEDULE; Number of evenly spaced defrosts per day the controller will initiate. Only available if DEFROST MODE = SCHEDULE

1ST DeFRoST DelAY 0 min 240 min 120 min Delay of 1st defrost of day when DEFROST MODE = SCHEDULE

DeFRoST FAn STATe OFF ON OFF OFF = fans off during defrost; ON = fans on during defrost

DeFRoST TeRm Temp 35.0°F 90.0°F 50.0°F The temperature the coil sensor(s) must exceed in order to terminate defrost.

DeFRoST pARAmeTeR 0 90 30 Coefficient to KE2 Defrost algorithm. Only available if DEFROST MODE = DE-MAND

mAx DeFRoST Time 0 min 90 min 45 min Maximum amount of time the defrost relay is energized. Only available if DE-FROST MODE = SCHEDULE

DRAin Time 0 min 15 min 2 min Time to be in drain mode (drip time)

Page 9: Contents This reference should remain on site with the ... · Temp1 Sensor Alarm. Input 2 & 3 will alarm for Room temp, Monitor Temp, Door Switch, and External Alarm. Battery Backup:

KE2 ComboDisplayTemperature Display, Lighting and Door Heater Control, Temp Alarm and Panic Alarm Notifications- OR - Use with the KE2 Evap OEM Controller for refrigeration system control

Q.1.63 April 2019 Page 9

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

KE2 EVAP OEM CONTROLLER - Setpoints Menu (continued)NAME Min MMax Default DESCRIPTION

mAx Time FoR lpco 0 min 15 min 0 min LPCO is disabled if set to 0 min; Only available if VALVE TYPE is set to any electric valve type

low pReSSURe cUT oUT -5.0 PSIG 138.0 PSIG 8.0 PSIG Only available if VALVE TYPE is set to any electric valve type and MAX TIME FOR LPCO is greater than 0 min

pReSS DiFF FoR lpco 1.0 PSIG 50.0 PSIG 15.0 PSIG Only available if VALVE TYPE is set to any electric valve type and MAX TIME FOR LPCO is greater than 0 min

comp RUn Time 0 hrs 24 hrs 6 hrs Number of hours of cooling before starting defrost. Only available when DE-FROST MODE = RUNTIME

elecTRic DeFRoST moDe PULSE PERMANENT PULSE PULSE = utilize advanced defrost algorithm, PERMANENT = Leave defrost relay energized. Only available if DEFROST TYPE = ELEC

FAn DelAY Temp -40.0°F 35.0°F 20.0°F Fan Delay Temperature

mAx FAn DelAY Time 0 min 20 min 2 min Max Fan Delay time

pUmp Down Time 0 min 90 min 0 min Pump Down Time

mUlTi AiR Temp cTRl WARMEST AIR AVERAGE AIR WARMEST AIR WARMEST AIR = use the warmest air temp from bonded controls; AVERAGE AIR = use the average air temp from bonded controls

mUlTi eVAp cool SYNCHRONIZED INDEPENDENT SYNCHRONIZEDSYNCHRONIZED = synchronize bonded controllers in refrigeration mode; INDE-PENDENT = bonded controllers control temperature independently in refrigera-tion mode

mUlTi eVAp DeFRoST SYNCHRONIZED INDEPENDENT SYNCHRONIZED SYNCHRONIZED = synchronize bonded controllers in defrost mode; INDEPEN-DENT = bonded controllers defrost independently

mUlTi eVAp SenSoR SHARED NOT SHARED SHARED SHARED = share sensor readings from bonded controllers; NOT SHARED = use local sensor readings only

HigH Temp AlARm oFFSeT 0.0°F 99.9°F 10.0°F Number of degrees above ROOM TEMP for a HIGH TEMP ALARM condition

HigH Temp AlARm DelAY 0 min 120 min 60 min Minutes the room temperature must remain above ROOM TEMP + HIGH TEMP ALARM OFFSET before issuing a HIGH TEMP ALARM

low Temp AlARm oFFSeT 0.0°F 20.0°F 4.0°F Number of degrees below ROOM TEMP for a LOW TEMP ALARM condition

low Temp AlARm DelAY 0 min 30 min 10 min Minutes the room temperature must remain below ROOM TEMP - LOW TEMP ALARM OFFSET before issuing a LOW TEMP ALARM

DooR AlARm DelAY 0 min 180 min 30 min Minutes any door is open and room temperature is 5 deg F above ROOM TEMP + AIR DIFF before issuing an alarm condition

AUx in 1 moDe N/A N/A DISABLED See Auxiliary Input Modes table on the following page

AUx in 1 STATe OPEN CLOSED CLOSED OPEN = active if input is an open CLOSED = active if input is a short

AUx in 2 moDe N/A N/A DISABLED See Auxiliary Input Modes table on the following page

AUx in 2 STATe OPEN CLOSED CLOSED OPEN = active if input is an open CLOSED = active if input is a short

AUx in 3 moDe N/A N/A DISABLED See Auxiliary Input Modes table on the following page

AUx in 3 STATe OPEN CLOSED CLOSED OPEN = active if input is an open CLOSED = active if input is a short

2nD Room Temp -50.0°F 99.9°F -50.0°F If AUX IN (1,2, and/or3) MODE = 2nd ROOM TEMP, this value becomes the ROOM TEMP set point when the digital input is active

SUcT pReS oFFSeT -5.0 PSI 5.0 PSI 0.0 PSI An offset added or subtracted from the suction pressure transducer reading

SUcT Temp oFFSeT -5.0°F 5.0°F 0.0°F An offset added or subtracted from the suction temperature sensor reading

AiR Temp oFFSeT -5.0°F 5.0°F 0.0°F An offset added or subtracted from the air temperature sensor reading

coil Temp oFFSeT -5.0°F 5.0°F 0.0°F An offset added or subtracted from the coil temperature sensor reading

AUx1 oFFSeT -5.0°F 5.0°F 0.0°FWhen Aux1, Aux2, or Aux3 are used as a temperature sensor, an offset is added or subtracted from sensor readingAUx2 oFFSeT -5.0°F 5.0°F 0.0°F

AUx3 oFFSeT -5.0°F 5.0°F 0.0°F

Temp UniTS FAHRENHEIT CELSIUS FAHRENHEIT Units for temperature’s display in deg F for FAHRENHEIT, or deg C for CELSIUS

AiR Temp DiFF 0.1°F 5.0 °F 1.0°F The number of degrees above ROOM TEMP before the controller will go into REFRIGERATION mode

exTReme Temp DiFF 0.0°F 99.9°F 20.0°F Advanced topic: Call KE2 Therm for assistance

pRopoRTionAl 0 255 3 A coefficient to the valve control algorithm that increase valve responsiveness as the value increases

inTegRAl 0 255 5 A coefficient to the valve control algorithm that increase valve responsiveness as the value increases

DeRiVATiVe 0 255 3 Should not be adjusted unless instructed by KE2 Therm

Page 10: Contents This reference should remain on site with the ... · Temp1 Sensor Alarm. Input 2 & 3 will alarm for Room temp, Monitor Temp, Door Switch, and External Alarm. Battery Backup:

KE2 ComboDisplayTemperature Display, Lighting and Door Heater Control, Temp Alarm and Panic Alarm Notifications- OR - Use with the KE2 Evap OEM Controller for refrigeration system control

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

Q.1.63 April 2019Page 10

RefrigerantsNAME SCROLLING TEXTR-404a 404A

R-507 R507

R-407a 407A

R-407C 407c

R-422a 422A

R-422d 422D

R-134a 134A

R-22 R22

R-717 R717

R-438a 438A

R-408a 408A

R-409a 409A

R-407F 407F

R-410a 410A

R-744 R744

R-448a 448A

R-449a 449A

R-450a 450A

R-513a 513A

R-452a 452A

Aux Input ModesNAME DESCRIPTIONDiSABleD Input not used

Room Temp Temperature input used as another Room Temp

coil Temp Temperature input used as another Coil Temp

moniToR Temperature input used for monitoring only

2nD Temp Inactive = 2ND ROOM TEMP SP off Active = WND ROOM TEMP SP on

DooR SwiTcH Inactive = Door Closed, Active = Door Open

exT AlARm (1) (2) (3) Inactive = No alarm, Active = External Alarm is set

SYS oFF Inactive = normal operation, Active = system off

DFR inTeRlocK Inactive = defrost heaters normal control, Active = defrost heaters off

DFR locK Inactive = defrost normal, Active = defrost not allowed

KE2 EVAP OEM CONTROLLER - Manual Menufor the selected controller

❶ Press ENTER

BACK

and Password prompt will appear. Press ENTER

BACK

to display 0000 . To enter the password (default is 2222), use the or to change the value of

the digit, use the or to move to the next digit. When password is entered, press and hold ENTER

BACK

for 3 seconds.

mAnUAl menU, SETPOINTS, VARIABLES, ALARMS,

❷ SELECT PARAMETER TO ADJUST Use the or to scroll through the Manual Menu. When desired Parameter Name is displayed, press ENTER

BACK

. Then use the

or to move through the Range of options for that Parameter, or if entering a number, use the or to change the value of the digit, use the or

to move to the next digit. Press and hold ENTER

BACK

for 3 seconds to save the change.

NAME DESCRIPTIONmAnUAl conTRol Force the controller into the next operating mode

mAnUAl VAlVe Manually open or close the EEV in percentage increments

cleAR AlARmS Press and hold ENTER for 5 seconds to clear all alarms

mAnUAl compReSSoR RelAY Manually energize or de-energize liquid line solenoid /compressor relay

mAnUAl DeFRoST RelAY Manually energize or de-energize defrost relay

mAnUAl FAn RelAY Manually energize or de-energize fan relay

FAcToRY ReSeT Press and hold ENTER for 5 seconds to put all setpoints back to default

weB pASSwoRD ReSeT Reset the web password to the factory default

DoD iniT Turn KE2 Smart Access on or off

SmART AcceSS Turn DHCP Mode on or off

DHcp moDe Re-initialize KE2 defrost algorithm

Page 11: Contents This reference should remain on site with the ... · Temp1 Sensor Alarm. Input 2 & 3 will alarm for Room temp, Monitor Temp, Door Switch, and External Alarm. Battery Backup:

KE2 ComboDisplayTemperature Display, Lighting and Door Heater Control, Temp Alarm and Panic Alarm Notifications- OR - Use with the KE2 Evap OEM Controller for refrigeration system control

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

Q.1.63 April 2019Page 11

KE2 EVAP OEM CONTROLLER - Alarms Menufor the selected controller (Not adjustable, View Only)

❶ ACCESS THE ALARMS MENU Use the or to move through the Menus (Setpoints - Variables - Manual Menu - Password - Alarms). Press ENTER

BACK

when

Alarms is displayed.

❷ Use the or to scroll through the Alarms list . Press

ENTER

BACK once to return to the Menus.

❸ Press

ENTER

BACK two more times to return to the default display.

❹ Press to silence the alarm. Alarm is silenced for 1 hour while alarm condition is addressed. If system is not corrected by 1 hour alarm will sound again.

NAME DESCRIPTIONpReSSURe SenSoR Suction pressure sensor is shorted, open or pressure out of range

SUcTion Temp SenSoR Suction temperature sensor is shorted or open

AiR Temp SenSoR Return air temperature sensor is shorted or open

coil Temp SenSoR Coil temperature sensor is shorted or open

HigH SUpeRHeAT Superheat above upper limit

low SUpeRHeAT Superheat below lower limit

HigH AiR Temp Room temperature is above ROOM TEMP + AIR TEMP DIFF + HIGH TEMP ALARM OFFSET for longer than HIGH TEMP ALARM DELAY

low AiR Temp Room temperature is below ROOM TEMP - LOW TEMP ALARM OFFSET for longer than LOW TEMP ALARM DELAY

exceSS DeFRoST 32 or more defrosts within 48 hours

DeFR TeRm on Time Defrost terminated on time instead of temperature for two consecutive cycles

DooR open AlARm If any door input from main controller or combo display is open and room temperature is 5°F above ROOM TEMP + AIR TEMP DIFF for DOOR ALARM DELAY time

commUnicATion eRRoR ONLY FOR BONDED CONTROLLERS: No communication between controllers for one minute or more

exTeRnAl AlARm 1 If main AUX1 IN MODE = EXT ALARM: the digital input is in an active state

exTeRnAl AlARm 2 If main AUX2 IN MODE = EXT ALARM: the digital input is in an active state

exTeRnAl AlARm 3 If main AUX3 IN MODE = EXT ALARM: the digital input is in an active state

emAil FAilURe Email alert was not confirmed by email server provided after 7 consecutive attempts

DiSplAY AUx2 SenSoR Set if display AUX2 Function set to one of the temperature inputs and input is shorted or open

pUmpDown TimeoUT Max time for LPCO pumpdown exceeded

SHoRT comp cYcle Compressor is started an excessive number of times to maintain suction pressure

low pReSSURe Suction pressure dropped below expected point excessive number of times

AUx1 SenSoR Set if main AUX1 input set to a temperature input and input is shorted or open

AUx2 SenSoR Set if main AUX2 input set to a temperature input and input is shorted or open

AUx3 SenSoR Set if main AUX3 input set to a temperature input and input is shorted or open

FlASH mem eRRoR Internal Controller Alarm

comp SeQ comm eRRoR If set to communicate with Compressor Sequencer, but no communication detected

wATcHDog eRRoR Internal Controller Alarm

Help - pAnic Display Panic button pressed and in panic mode

DooR Temp SenSoR Set if display AUX1 Function set to DOOR TEMP and input is shorted or open

DooR Temp HigH Display Door temperature is above DOOR TEMP + DOOR TEMP DIFF + HI DOOR ALR OFST for longer than DOOR TMP ALR DLY

DooR Temp low Display Door temperature is below DOOR TEMP - LO DOOR ALR OFST for longer than DOOR TMP ALR DLY

HigH moniToR Temp2 Display Monitor2 temperature is above MON TMP2 HI ALRM for longer than MON TMP2 AL DLY

low moniToR Temp2 Display Monitor2 temperature is below MON TMP2 LO ALRM for longer than MON TMP2 AL DLY

DiSplAY AUx3 SenSoR Set if display AUX3 Function set to one of the temperature inputs and input is shorted or open

HigH moniToR Temp3 Display Monitor3 temperature is above MON TMP3 HI ALRM for longer than MON TMP3 AL DLY

low moniToR Temp3 Display Monitor3 temperature is below MON TMP3 LO ALRM for longer than MON TMP3 AL DLY

DiSp exTeRnAl AlARm 1 If display AUX1 FUNCTION = EXT ALARM: the digital input is in an active state

DiSp exTeRnAl AlARm 2 If display AUX2 FUNCTION = EXT ALARM: the digital input is in an active state

DiSp exTeRnAl AlARm 3 If display AUX3 FUNCTION = EXT ALARM: the digital input is in an active state

Page 12: Contents This reference should remain on site with the ... · Temp1 Sensor Alarm. Input 2 & 3 will alarm for Room temp, Monitor Temp, Door Switch, and External Alarm. Battery Backup:

KE2 ComboDisplayTemperature Display, Lighting and Door Heater Control, Temp Alarm and Panic Alarm Notifications- OR - Use with the KE2 Evap OEM Controller for refrigeration system control

© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090

Q.1.63 April 2019Page 12

KE2 Therm Solutions 12 Chamber Drive . Washington, MO 63090

1.888.337.3358 . www.ke2therm.com

On

Site

- Lo

cally

Rem

ote

Acce

ss

Joe’s C-Store & Gas

Joe’s C-Store & Gas

On the goXYZ Refrigeration

XYZ Refrigeration

At home At workOn siteAccess your

controllers:

Ways to connect:

Option 1: Directly ConnectedOption 2: Using the KE2 Smart GateOption 3: Using a KE2-LDA or KE2-EM35Option 4: Using the KE2 WiFi Service Tool Option 5: KE2 Smart Access PortalOption 6: KE2 Smart Access Portal w. Local DashboardOption 7: Customer VPN w. Local Dashboard

❶ Add KE2 Switch 8-port (pn 20166) or KE2 Switch 16-port (pn 21011) when connecting more than one controller.

❷ Typically DHCP should be enabled on the controllers when connecting directly to the customer network, unless directed by the customer’s IT department to set a static IP address.

Option 1: Directly Connected - Single Controller

Ethernet Cable

Computer

NOTE: Computer requires Static IP. See bulletin Q.5.11 or Video 124 at youtube.com/ke2therm

Option 4: Using the KE2 WiFi Service Tool (pn 20906)

thermsolutionsPWR WIFILANWAN 3G/4G

Superheat0.0 F

Suct Pressure96.2 F

Suct Temp87.7 F

Computer, Tablet, or Smart Phone

Ethernet Cable

KE2 WiFi Service Tool

KE2 Smart Gate

RB201 1UAS-2HND-IN

USB

SFP

POE GIGABIT ETHERNET

ETH1 ETH5ETH3 ETH4ETH2 ETH6 ETH10ETH8 ETH9ETH76 7 8 9 10

1 2 3 4 5FAST ETHERNET

Option 2: Using a KE2 Smart Gate (pn 20695) - Quick Multi-Controller Access

Ethernet Cable

Ethernet Cable

- or -

Superheat0.0 F

Suct Pressure96.2 F

Suct Temp87.7 F

Computer, Tablet, or Smart Phone

Option 3: Using a KE2-LDA (pn 21253) or KE2-EM35 (pn 21634)

Superheat0.0 F

Suct Pressure96.2 F

Suct Temp87.7 F

Computer, Tablet, or Smart Phone

WANLAN

Ethernet Cable

- or -❶ ❶ Ethernet Cable

- or -

Option 7: Customer VPN with Local Dashboard

Customer Network 1 2 3 654 7

Link/ACT

100/1000MbpsPOWER

Superheat0.0 F

Suct Pressure96.2 F

Suct Temp87.7 F

Computer, Tablet, or Smart Phone

WANLAN

- or -Internet

Customer VPN❶ ❶

Ethernet Cable

KE2-LDA KE2-EM35Ethernet Cable

- or -

1 2 3 654 7

Link/ACT

100/1000MbpsPOWER

Option 5: KE2 Smart Access Portal

InternetKE2 Smart Access

Customer NetworkEthernet Cable

Superheat0.0 F

Suct Pressure96.2 F

Suct Temp87.7 F

Computer, Tablet, or Smart Phone❷

RJ-11

Ethernet Cable

Option 6: KE2 SmartAccess Portal with Local Dashboard

1 2 3 654

7

Link/ACT

100/1000MbpsPOWER

Superheat0.0 F

Suct Pressure96.2 F

Suct Temp87.7 F

Computer, Tablet, or Smart Phone

WANLAN

- or -

Ethernet Cable

- or -Internet

KE2 Smart Access❶ ❶

KE2-LDA KE2-EM35Customer Network

NO NCCOM

EA

RTH

DisplayPort

Ethernet

RJ-11

EthernetPort

KE2 Evap OEMKE2 Evap OEM

KE2 Combo Display

Remote communication with the KE2 Combo Display is only possible through the KE2 Evap OEM.

Communications - Remote commmunication with the KE2 Combo Display is only possible through the KE2 Evap OEM