IM 05P03D21-11EN page 1/8 Contents 1. Safety Precautions 2. Model and Suffix Codes 3. How to Install 4. Hardware Specifications 5. How to Connect Wires 6. Terminal Wiring Diagrams Introduction Thank you for purchasing the UM33A Digital Indicator with Alarms. This operation guide describes the basic operations of the UM33A. The guide should be provided to the end user of this product. Be sure to read this operation guide before using the product in order to ensure correct operation. For details of each function, refer to the electronic manual. Before using the product, refer to the table of Model and Suffix Codes to make sure that the delivered product is consistent with the model and suffix codes you ordered. Also make sure that the following items are included in the package. • Digital Indicator with Alarms (the model you ordered) ............................ x1 • Set of Brackets ........................................................................................x1 • Unit Label (L4502VZ) ..............................................................................x1 • Tag Label (L4502VE) (Only when ordered.) ...........................................x1 • Operation Guide (this document) ............................................................x4 (A3 size) (Installation and Wiring, Initial Settings, Operations, and Parameters) l Target Readers This guide is intended for the following personnel; • Engineers responsible for installation, wiring, and maintenance of the equipment. • Personnel responsible for normal daily operation of the equipment. 1. Safety Precautions The following symbol is used on the instrument. It indicates the possibility of injury to the user or damage to the instrument, and signifies that the user must refer to the user’s manual for special instructions. The same symbol is used in the user’s manual on pages that the user needs to refer to, together with the term “WARNING” or “CAUTION.” WARNING Calls attention to actions or conditions that could cause serious or fatal injury to the user, and indicates precautions that should be taken to prevent such occurrences. CAUTION Calls attention to actions or conditions that could cause injury to the user or damage to the instrument or property and indicates pre- cautions that should be taken to prevent such occurrences. AC AC/DC The equipment wholly protected by double insulation or reinforced insulation. Functional grounding terminals (Do not use this terminal as a protective grounding terminal). Note Identifies important information required to operate the instrument. n Warning and Disclaimer (1) YOKOGAWA makes no warranties regarding the product except those stated in the WARRANTY that is provided separately. (2) The product is provided on an "as is" basis. YOKOGAWA assumes no liability to any person or entity for any loss or damage, direct or indirect, arising from the use of the product or from any unpredictable defect of the product. n Safety, Protection, and Modification of the Product (1) In order to protect the system controlled by this product and the product itself, and to ensure safe operation, observe the safety precautions described in the user’s manual. Use of the instrument in a manner not prescribed herein may compromise the product's functions and the protection features inherent in the device. We assume no liability for safety, or responsibility for the product's quality, performance or functionality should users fail to observe these instructions when operating the product. (2) Installation of protection and/or safety circuits with respect to a lightning protector; protective equipment for the system controlled by the product and the product itself; foolproof or failsafe design of a process or line using the system controlled by the product or the product itself; and/or the design and installation of other protective and safety circuits are to be appropriately implemented as the customer deems necessary. (3) Be sure to use the spare parts approved by YOKOGAWA when replacing parts or consumables. (4) This product is not designed or manufactured to be used in critical applications that directly affect or threaten human lives. Such applications include nuclear power equipment, devices using radioactivity, railway facilities, aviation equipment, air navigation facilities, aviation facilities, and medical equipment. If so used, it is the user’s responsibility to include in the system additional equipment and devices that ensure personnel safety. (5) Modification of the product is strictly prohibited. (6) This product is intended to be handled by skilled/trained personnel for electric devices. WARNING l Power Supply Ensure that the instrument’s supply voltage matches the voltage of the power supply before turning ON the power. l Do Not Use in an Explosive Atmosphere Do not operate the instrument in locations with combustible or explosive gases or steam. Operation in such environments constitutes an extreme safety hazard. Use of the instrument in environments with high concentrations of corrosive gas (H 2 S, SO X , etc.) for extended periods of time may cause a failure. l Do Not Remove Internal Unit The internal unit should not be removed by anyone other than YOKOGAWA's service personnel. There are dangerous high voltage parts inside. Additionally, do not replace the fuse by yourself. l Damage to the Protective Construction Operation of the instrument in a manner not specified in the user’s manual may damage its protective construction. CAUTION This instrument is an EMC class A product. In a domestic environ- ment this product may cause radio interference in which case the user needs to take adequate measures. 2. Model and Suffix Codes n UM33A [Style:S1] Model Suffix code Optional suffix code Description UM33A Digital Indicator with Alarms (provided with retransmission output or 15 V DC loop power supply, 2 DIs, and 3 DOs) (Power supply: 100-240 V AC) Type 1: Basic -0 Standard type Type 2: Functions 0 None 1 1 additional DO (c-contact relay), RS-485 communication (Max. 38.4 kbps, 2-wire/4-wire) 2 1 additional DO (c-contact relay) 3 6 additional DOs (c-contact relay: 1 point, open collector: 5 points) Type 3: Open networks 0 None Display language (*1) -1 English -2 German -3 French -4 Spanish Case color 0 White (Light gray) 1 Black (Light charcoal gray) Optional suffix codes /LP 24 V DC loop power supply (*2) /DC Power supply 24 V AC/DC /CT Coating (*3) *1: English, German, French, and Spanish can be displayed as the guide display. *2: The /LP option can be specified only when the code for Type 2 is "0", "1" or "2." Additionally, the RS-485 communication for "1" of the Type 2 code is 2-wire system. *3: When the /CT option is specified, the UM33A does not conform to the safety standards (UL and CSA) and CE marking. n Accessories (sold separately) The following is an accessory sold separately. • LL50A Parameter Setting Software Model Suffix code Description LL50A -00 Parameter Setting Software • Terminal Cover For UM33A: Model UTAP002 • User’s Manual (A4 size) Note: User’s Manual can be downloaded from a website. • User’s Manual (CD-ROM), Model: UTAP003 Note: Contains all manuals. 3. How to Install n Installation Location The instrument should be installed in indoor locations meeting the following conditions: • Instrumented panel This instrument is designed to be mounted in an instrumented panel. Mount the instrument in a location where its terminals will not inadvertently be touched. • Well ventilated locations Mount the instrument in well ventilated locations to prevent the instrument’s inter- nal temperature from rising. However, make sure that the terminal portions are not exposed to wind. Exposure to wind may cause the temperature sensor accuracy to deteriorate. To mount mul- tiple indicators, see the external dimensions/panel cutout dimensions which follow. If mounting other instruments adjacent to the instrument, comply with these panel cut- out dimensions to provide sufficient clearance between the instruments. • Locations with little mechanical vibration Install the instrument in a location subject to little mechanical vibration. • Horizontal location Mount the instrument horizontally and ensure that it is level, with no inclination to the right or left. Front panel of the indicator 30° Keep this angle within 30° Note If the instrument is moved from a location with low temperature and low humidity to a place with high temperature and high humidity, or if the temperature changes rapidly, condensation will result. Moreover, in the case of thermocouple inputs, measurement errors will result. To avoid such a situation, leave the instrument in the new environment under ambient conditions for more than 1 hour prior to using it. Do not mount the instrument in the following locations: • Outdoors • Locations subject to direct sunlight or close to a heater Install the instrument in a location with stable temperatures that remain close to an average temperature of 23°C. Do not mount it in locations subject to direct sunlight or close to a heater. Doing so adversely affects the instrument. • Locations with substantial amounts of oily fumes, steam, moisture, dust, or corrosive gases The presence of oily fumes, steam, moisture, dust, or corrosive gases adversely affects the instrument. Do not mount the instrument in locations subject to any of these substances. • Areas near electromagnetic field generating sources Do not place magnets or tools that generate magnetism near the instrument. If the instrument is used in locations close to a strong electromagnetic field generating source, the magnetic field may cause measurement errors. • Locations where the display is difficult to see The instrument uses an LCD for the display unit, and this can be difficult to see from extremely oblique angles. Mount the instrument in a location where it can be seen as much as possible from the front. • Areas close to flammable articles Absolutely do not place the instrument directly on flam- mable surfaces. If such a circumstance is unavoidable and the instrument must be placed close to a flammable item, provide a shield for it made of 1.43 mm thick plated steel or 1.6 mm thick unplated steel with a space of at least 150 mm between it and the instrument on the top, bottom, and sides. • Areas subject to being splashed with water WARNING Be sure to turn OFF the power supply to the indicator before install- ing it on the panel to avoid an electric shock. 150 mm 150 mm 150 mm 150 mm 150 mm 150 mm 150 mm n Mounting the Instrument Main Unit Provide an instrumented panel steel sheet of 1 to 10 mm thickness. After opening the mounting hole on the panel, follow the procedures below to install the indicator: 1) Insert the indicator into the opening from the front of the panel so that the terminal board on the rear is at the far side. 2) Set the brackets in place on the right and left of the indicator as shown in the figure below, then tighten the screws of the brackets. Take care not to overtighten them. Direction to insert the indicator Insert the indicator into the opening at the front of the panel. Panel Bracket (side mounting hardware) Bracket (side mounting hardware) Terminal board Insert a screwdriver into the brackets to tighten the screws. Appropriate tightening torque: 0.25 Nm CAUTION Tighten the screws with appropriate tightening torque within 0.25 N•m. Otherwise it may cause the case deformation or the bracket damage. Make sure that foreign materials do not enter the inside of the instrument through the case’s slit holes. n External Dimensions and Panel Cutout Dimensions UM33A Unit: mm (approx. inch) Normal tolerance: ±(value of JIS B 0401-1998 tolerance class IT18)/2 96 (3.78) 48 (1.89) Bracket 20 (0.79) 65 (2.56) 11 (0.43) Terminal cover Bracket 94.6 (3.72) 91.6 (3.61) 105.2 (4.14) 1 to 10 (0.04 to 0.39) (panel thickness) (25) (0.98) (53) (2.09) • General mounting 145 (5.71)min. +0.03 0 (3.62 ) +0.6 0 45 +0.02 0 (1.77 ) +0.8 0 92 70 (2.76) min. Operation Guide IM 05P03D21-11EN UM33A Digital Indicator with Alarms Operation Guide This operation guide describes installation, wiring, and other tasks required to make the indicator ready for operation. 1st Edition : Aug. 2010 Installation and Wiring n Waste Electrical and Electronic Equipment (WEEE), Directive 2002/96/EC This is an explanation of how to dispose of this product based on Waste Electrical and Electronic Equipment (WEEE), Directive 2002/96/EC. This directive is only valid in the EU. Marking This product complies with the WEEE Directive (2002/96/EC) marking requirement. This marking indicates that you must not discard this electrical/ electronic product in domestic household waste. Product Category With reference to the equipment types in the WEEE directive Annex 1, this product is classified as a “Monitoring and Control instrumentation” product. Do not dispose in domestic household waste. When disposing products in the EU, contact your local Yokogawa Europe B.V. office. www.yokogawa.com/ns YOKOGAWA ELECTRIC CORPORATION Network Solutions Business Division 2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 JAPAN YOKOGAWA CORPORATION OF AMERICA Head office and for product sales 2 Dart Road, Newnan, Georgia 30265, USA YOKOGAWA EUROPE B.V. Headquarters Euroweg 2, 3825 HD Amersfoort, THE NETHERLANDS All Rights Reserved, Copyright © 2010 Yokogawa Electric Corporation

Contents 3. How to Install Introduction · 2013. 3. 24. · Functional grounding terminals (Do not use this terminal as a protective grounding terminal). Note Identifies important

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Contents 3. How to Install Introduction · 2013. 3. 24. · Functional grounding terminals (Do not use this terminal as a protective grounding terminal). Note Identifies important

IM 05P03D21-11EN page 1/8

Contents1. SafetyPrecautions2. ModelandSuffixCodes3. HowtoInstall4. HardwareSpecifications5. HowtoConnectWires6. TerminalWiringDiagrams

IntroductionThankyouforpurchasingtheUM33ADigitalIndicatorwithAlarms.ThisoperationguidedescribesthebasicoperationsoftheUM33A.Theguideshouldbeprovidedtotheenduserofthisproduct.Besure to read thisoperationguidebeforeusing theproduct inorder toensurecorrectoperation.Fordetailsofeachfunction,refertotheelectronicmanual.Beforeusingtheproduct,refertothetableofModelandSuffixCodestomakesurethatthedeliveredproductisconsistentwiththemodelandsuffixcodesyouordered.Alsomakesurethatthefollowingitemsareincludedinthepackage.

•DigitalIndicatorwithAlarms(themodelyouordered)............................x1•SetofBrackets........................................................................................x1•UnitLabel(L4502VZ)..............................................................................x1•TagLabel(L4502VE)(Onlywhenordered.)...........................................x1•OperationGuide(thisdocument)............................................................x4(A3size)(InstallationandWiring,InitialSettings,Operations,andParameters)

lTargetReadersThisguideisintendedforthefollowingpersonnel;• Engineersresponsibleforinstallation,wiring,andmaintenanceoftheequipment.• Personnelresponsiblefornormaldailyoperationoftheequipment.

1. Safety PrecautionsThefollowingsymbol isusedonthe instrument. It indicatesthepossibilityof injuryto theuserordamageto the instrument,andsignifies that theusermustrefer totheuser’smanual forspecial instructions.Thesamesymbol isused in theuser’smanualonpagesthattheuserneedstoreferto,togetherwiththeterm“WARNING”or“CAUTION.”

WARNING

Calls attention to actions or conditions that could cause serious or fatal injury to the user, and indicates precautions that should be taken to prevent such occurrences.

CAUTION

Calls attention to actions or conditions that could cause injury to the user or damage to the instrument or property and indicates pre-cautions that should be taken to prevent such occurrences.

AC

AC/DC

Theequipmentwhollyprotectedbydoubleinsulationorreinforcedinsulation.

Functionalgroundingterminals (Donotusethisterminalasaprotectivegroundingterminal).

NoteIdentifiesimportantinformationrequiredtooperatetheinstrument.

n Warning and Disclaimer(1)YOKOGAWAmakesnowarrantiesregardingtheproductexceptthosestatedin

theWARRANTYthatisprovidedseparately.(2)Theproductisprovidedonan"asis"basis.YOKOGAWAassumesnoliabilityto

anypersonorentity forany lossordamage,director indirect,arisingfromtheuseoftheproductorfromanyunpredictabledefectoftheproduct.

nSafety,Protection,andModificationoftheProduct(1) Inorder toprotect thesystemcontrolledbythisproductandtheproduct itself,

andtoensuresafeoperation,observethesafetyprecautionsdescribed in theuser’smanual.Useof the instrument inamannernotprescribedhereinmaycompromisetheproduct's functionsandtheprotectionfeatures inherent in thedevice.Weassumenoliabilityforsafety,orresponsibilityfortheproduct'squality,performanceorfunctionalityshouldusersfailtoobservetheseinstructionswhenoperatingtheproduct.

(2) Installationof protectionand/or safety circuitswith respect toa lightningprotector;protectiveequipmentforthesystemcontrolledbytheproductandtheproduct itself; foolproofor failsafedesignofaprocessor lineusingthesystemcontrolledbytheproductortheproductitself;and/orthedesignandinstallationofotherprotectiveandsafetycircuitsaretobeappropriatelyimplementedasthecustomerdeemsnecessary.

(3)BesuretousethesparepartsapprovedbyYOKOGAWAwhenreplacingpartsorconsumables.

(4)Thisproduct isnotdesignedormanufacturedtobeusedincriticalapplicationsthatdirectlyaffector threatenhuman lives.Suchapplications includenuclearpower equipment, devices using radioactivity, railway facilities, aviationequipment,airnavigation facilities,aviation facilities,andmedicalequipment.If soused, it is theuser’s responsibility to include in thesystemadditionalequipmentanddevicesthatensurepersonnelsafety.

(5)Modificationoftheproductisstrictlyprohibited.(6)Thisproduct is intendedtobehandledbyskilled/trainedpersonnel forelectric

devices.

WARNING

lPower Supply Ensure that the instrument’s supply voltage matches the voltage

of the power supply before turning ON the power.l Do Not Use in an Explosive Atmosphere Do not operate the instrument in locations with combustible

or explosive gases or steam. Operation in such environments constitutes an extreme safety hazard. Use of the instrument in environments with high concentrations of corrosive gas (H2S, SOX, etc.) for extended periods of time may cause a failure.

l Do Not Remove Internal Unit The internal unit should not be removed by anyone other than

YOKOGAWA's service personnel. There are dangerous high voltage parts inside. Additionally, do not replace the fuse by yourself.

l Damage to the Protective Construction Operation of the instrument in a manner not specified in the

user’s manual may damage its protective construction.

CAUTION

This instrument is an EMC class A product. In a domestic environ-ment this product may cause radio interference in which case the user needs to take adequate measures.

2. ModelandSuffixCodesn UM33A

[Style:S1]

Model SuffixcodeOptional suffixcode

Description

UM33A

DigitalIndicatorwithAlarms(providedwithretransmissionoutputor15VDClooppowersupply,2DIs,and3DOs)(Powersupply:100-240VAC)

Type1:Basic -0 Standardtype

Type2:Functions

0 None

1 1additionalDO(c-contactrelay),RS-485communication(Max.38.4kbps,2-wire/4-wire)

2 1additionalDO(c-contactrelay)

3 6additionalDOs(c-contactrelay:1point,opencollector:5points)

Type3:Opennetworks 0 None

Displaylanguage(*1)

-1 English-2 German-3 French-4 Spanish

Casecolor0 White(Lightgray)1 Black(Lightcharcoalgray)

Optionalsuffixcodes/LP 24VDClooppowersupply(*2)/DC Powersupply24VAC/DC/CT Coating(*3)

*1: English,German,French,andSpanishcanbedisplayedastheguidedisplay.*2: The/LPoptioncanbespecifiedonlywhenthecodeforType2is"0","1"or"2." Additionally,theRS-485communicationfor"1"oftheType2codeis2-wiresystem.*3: Whenthe/CToptionisspecified,theUM33Adoesnotconformtothesafetystandards(UL

andCSA)andCEmarking.

n Accessories (sold separately)Thefollowingisanaccessorysoldseparately.

• LL50AParameterSettingSoftwareModel Suffixcode Description

LL50A -00 ParameterSettingSoftware

• TerminalCover ForUM33A:ModelUTAP002• User’sManual(A4size) Note:User’sManualcanbedownloadedfromawebsite.•User’sManual(CD-ROM),Model:UTAP003 Note:Containsallmanuals.

3. How to Install

n Installation LocationThe instrument shouldbe installed in indoor locationsmeeting the followingconditions:• Instrumented panel This instrument isdesignedtobemounted inan instrumentedpanel.Mount theinstrumentinalocationwhereitsterminalswillnotinadvertentlybetouched.

• Well ventilated locations Mounttheinstrumentinwellventilatedlocationstopreventtheinstrument’sinter-naltemperaturefromrising.

However,makesurethattheterminalportionsarenotexposedtowind.Exposuretowindmaycausethetemperaturesensoraccuracytodeteriorate.Tomountmul-tipleindicators,seetheexternaldimensions/panelcutoutdimensionswhichfollow.Ifmountingotherinstrumentsadjacenttotheinstrument,complywiththesepanelcut-outdimensionstoprovidesufficientclearancebetweentheinstruments.

• Locations with little mechanical vibration Installtheinstrumentinalocationsubjecttolittlemechanicalvibration.• Horizontal location Mounttheinstrumenthorizontallyandensurethatitislevel,withnoinclinationtotherightorleft.

Front panelof the indicator

30°

Keep this anglewithin 30°

NoteIf the instrument ismovedfroma locationwith lowtemperatureand lowhumiditytoaplacewithhightemperatureandhighhumidity,or if thetemperaturechangesrapidly,condensationwill result.Moreover, in thecaseof thermocouple inputs,measurementerrorswillresult.Toavoidsuchasituation,leavetheinstrumentinthenewenvironmentunderambientconditionsformorethan1hourpriortousingit.

Donotmounttheinstrumentinthefollowinglocations:• Outdoors• Locations subject to direct sunlight or close to a heater Installtheinstrumentinalocationwithstabletemperaturesthatremainclosetoanaveragetemperatureof23°C.Donotmountitinlocationssubjecttodirectsunlightorclosetoaheater.Doingsoadverselyaffectstheinstrument.

• Locations with substantial amounts of oily fumes, steam, moisture, dust, or corrosive gases

Thepresenceofoily fumes,steam,moisture,dust,orcorrosivegasesadverselyaffectstheinstrument.Donotmounttheinstrumentinlocationssubjecttoanyofthesesubstances.

• Areasnearelectromagneticfieldgeneratingsources Donotplacemagnetsortoolsthatgeneratemagnetismneartheinstrument.Iftheinstrument isusedin locationsclosetoastrongelectromagneticfieldgeneratingsource,themagneticfieldmaycausemeasurementerrors.

• Locationswherethedisplayisdifficulttosee The instrumentusesanLCDfor thedisplayunit,andthiscanbedifficult toseefromextremelyobliqueangles.Mounttheinstrumentinalocationwhereitcanbeseenasmuchaspossiblefromthefront.

• Areasclosetoflammablearticles Absolutelydonotplacetheinstrumentdirectlyonflam-mablesurfaces. Ifsuchacircumstance isunavoidableandtheinstrumentmustbeplacedclosetoaflammableitem,provideashieldforitmadeof1.43mmthickplatedsteelor1.6mmthickunplatedsteelwithaspaceofatleast150mmbetweenitandtheinstrumentonthetop,bottom,andsides.

• Areas subject to being splashed with water

WARNING

Be sure to turn OFF the power supply to the indicator before install-ing it on the panel to avoid an electric shock.

150 mm150 mm

150 mm

150 mm150 mm150 mm

150 mm

150 mm

n Mounting the Instrument Main UnitProvideaninstrumentedpanelsteelsheetof1to10mmthickness.Afteropeningthemountingholeonthepanel,followtheproceduresbelowtoinstalltheindicator:1) Insert the indicator into theopening from the frontof thepanelso that the

terminalboardontherearisatthefarside.2) Set thebrackets inplaceontherightand leftof the indicatorasshownin the

figurebelow,thentightenthescrewsofthebrackets.Takecarenottoovertightenthem.

Direction to insert theindicatorInsert the indicatorinto the opening atthe front of the panel.

Panel

Bracket(side mounting hardware)

Bracket(side mounting hardware)

Terminal boardInsert a screwdriver into thebrackets to tighten the screws.

Appropriatetightening torque:0.25 N•m

CAUTION

• Tighten the screws with appropriate tightening torque within 0.25 N•m. Otherwise it may cause the case deformation or the bracket damage.

• Make sure that foreign materials do not enter the inside of the instrument through the case’s slit holes.

n External Dimensions and Panel Cutout DimensionsUM33A Unit: mm (approx. inch)

Normal tolerance: ±(value of JIS B 0401-1998 tolerance class IT18)/2

96 (3.78)

48 (1

.89)

Bracket

20 (

0.79

)65

(2.5

6)11

(0.4

3)

Terminal cover

Bracket

94.6 (3.72)91.6 (3.61)

105.2 (4.14)

1 to 10 (0.04 to 0.39)

(panel thickness)(25) (0.98)

(53)

(2.09)

• General mounting145 (5.71)min.

+0.030(3.62 )

+0.6045

+0.020(1.77 ) +0.8

092

70 (2.76) min.

OperationGuide

IM 05P03D21-11EN

UM33ADigital Indicator with AlarmsOperation Guide

This operation guide describes installation, wiring, and other tasks required to make the indicator ready for operation.

1st Edition : Aug. 2010

Installation and Wiring

n Waste Electrical and Electronic Equipment (WEEE), Directive 2002/96/EC

This isanexplanationofhowtodisposeof thisproductbasedonWasteElectricalandElectronicEquipment(WEEE),Directive2002/96/EC.ThisdirectiveisonlyvalidintheEU.

MarkingThisproduct complieswith theWEEEDirective (2002/96/EC)markingrequirement.Thismarking indicates thatyoumustnotdiscard thiselectrical/electronicproductindomestichouseholdwaste.

Product CategoryWith reference to theequipment types in theWEEEdirectiveAnnex1, thisproduct is classifiedasa “MonitoringandControl instrumentation” product.Donotdisposeindomestichouseholdwaste.Whendisposingproducts intheEU,contactyourlocalYokogawaEuropeB.V.office.

www.yokogawa.com/ns

YOKOGAWA ELECTRIC CORPORATIONNetwork Solutions Business Division

2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 JAPANYOKOGAWA CORPORATION OF AMERICA

Head office and for product sales2 Dart Road, Newnan, Georgia 30265, USA

YOKOGAWA EUROPE B.V.Headquarters

Euroweg 2, 3825 HD Amersfoort, THE NETHERLANDS

All Rights Reserved, Copyright © 2010 Yokogawa Electric Corporation

Page 2: Contents 3. How to Install Introduction · 2013. 3. 24. · Functional grounding terminals (Do not use this terminal as a protective grounding terminal). Note Identifies important

IM 05P03D21-11EN page 2/8

4. HardwareSpecifications

WARNING

This instrument is for Measurement Category I (CAT.I). Do not use it for measurements in locations falling under Measurement Catego-ries II, III, and IV.

Internal Wiring

Outlet

Entrance IVCable

III TI

II

Category Measurement category Description Remarks

I CAT.I FormeasurementsperformedoncircuitsnotdirectlyconnectedtoMAINS. -

II CAT.II Formeasurementsperformedoncircuitsdi-rectlyconnectedtothelow-voltageinstallation.

Appliances,portableequip-ment,etc.

III CAT.III Formeasurementsperformedinthebuildinginstallation.

Distributionboard,circuitbreaker,etc.

IV CAT.IV Formeasurementsperformedatthesourceofthelow-voltageinstallation.

Overheadwire,cablesystems,etc.

n InputSpecifications

UniversalInput(Equippedasstandard)• Numberofinputs:1• Inputtype,instrumentrange,andmeasurementaccuracy:Seethetablebelow,

Input Type Instrument Range

AccuracyºC ºF

Thermo-couple

K-270.0to1370.0ºC -450.0to2500.0ºF ±0.1%ofinstrumentrange±1digitfor

0°Cormore±0.2%ofinstrumentrange±1digitforlessthan0°C±2%ofinstrumentrange±1digitforlessthan-200.0°CofthermocoupleK±1%ofinstrumentrange±1digitforlessthan-200.0°CofthermocoupleT

-270.0to1000.0ºC -450.0to2300.0ºF-200.0to500.0ºC -200.0to1000.0ºF

J -200.0to1200.0ºC -300.0to2300.0ºF

T-270.0to400.0ºC -450.0to750.0ºF

0.0to400.0ºC -200.0to750.0ºF

B 0.0to1800.0ºC 32to3300ºF

±0.15%ofinstrumentrange±1digitfor400°Cormore±5%ofinstrumentrange±1digitforlessthan400°C

S 0.0to1700.0ºC 32to3100ºF±0.15%ofinstrumentrange±1digit

R 0.0to1700.0ºC 32to3100ºF

N -200.0to1300.0ºC -300.0to2400.0ºF±0.1%ofinstrumentrange±1digit±0.25%ofinstrumentrange±1digitforlessthan0°C

E -270.0to1000.0ºC -450.0to1800.0ºF ±0.1%ofinstrumentrange±1digitfor0°Cormore±0.2%ofinstrumentrange±1digitforlessthan0°C±1.5%ofinstrumentrange±1digitforlessthan-200.0°CofthermocoupleE.

L -200.0to900.0ºC -300.0to1600.0ºF

U-200.0to400.0ºC -300.0to750.0ºF

0.0to400.0ºC -200.0to1000.0ºF

W 0.0to2300.0ºC 32to4200ºF ±0.2%ofinstrumentrange±1digit(Note2)

Platinel2 0.0to1390.0ºC 32.0to2500.0ºF ±0.1%ofinstrumentrange±1digit

PR20-40 0.0to1900.0ºC 32to3400ºF

±0.5%ofinstrumentrange±1digitfor800°CormoreAccuracyisnotguaranteedforlessthan800°C.

W97Re3-W75Re25 0.0to2000.0ºC 32to3600ºF ±0.2%ofinstrumentrange±1digit

RTD

JPt100-200.0to500.0ºC -300.0to1000.0ºF ±0.1%ofinstrumentrange±1digit

(Note1)-150.00to150.00ºC -200.0to300.0ºF ±0.1%ofinstrumentrange±1digit

Pt100-200.0to850.0ºC -300.0to1560.0ºF ±0.1%ofinstrumentrange±1digit

(Note1)-200.0to500.0ºC -300.0to1000.0ºF-150.00to150.00ºC -200.0to300.0ºF ±0.1%ofinstrumentrange±1digit

Standardsignal0.400to2.000V

±0.1%ofinstrumentrange±1digit

1.000to5.000V4.00to20.00mA

DCvoltage/current

0.000to2.000V0.00to10.00V0.00to20.00mA-10.00to20.00mV0.0to100.0mV

Theaccuracyisthatinthestandardoperatingconditions:23±2°C,55±10%RH,andpowerfrequencyat50/60Hz.

Note1: ±0.3°C±1digitintherangebetween0and100°C,±0.5°C±1digitintherange between-100and200°C.

Note2: W:W-5%Re/W-26%Re(HoskinsMfg.Co.).ASTME988

•Inputsamplingperiod:50,100,200ms•Burnoutdetection: FunctionsatTC,RTD,andstandardsignal. Upscale,downscale,andoffcanbespecified. Forstandardsignal,burnoutisdeterminedtohaveoccurredifitis0.1Vor0.4 mAorless.

•Inputbiascurrent:0.05µA(forTCorRTD)•Measuredcurrent(RTD):About0.16mA•Inputresistance: TCormVinput:1MΩormore Vinput:About1MΩ mAinput:About250Ω

•Allowablesignalsourceresistance: TCormVinput:250Ωorless Effectsofsignalsourceresistance:0.1µV/Ωorless DCvoltageinput:2kΩorless Effectsofsignalsourceresistance:About0.01%/100Ω• Allowablewiringresistance: RTDinput:Max.150Ω/wire(Theconductorresistancebetweenthethreewires shallbeequal.)

Wiringresistanceeffect:±0.1ºC/10Ω• Allowableinputvoltage/current: TC,mV,mAandRTDinput:±10VDC Vinput:±20VDC mAinput:±40mA• Noiserejectionratio: Normalmode:40dBormore(at50/60Hz) Commonmode:120dBormore(at50/60Hz) For100-240VAC, thepower frequencycanbesetmanually.Automatic detectionisalsoavailable.

For24VAC/DC,thepowerfrequencycanbesetmanually.• Referencejunctioncompensationerror: ±1.0ºC(15to35ºC) ±1.5ºC(-10to15ºCand35to50ºC)• Applicablestandards:JIS/IEC/DIN(ITS-90)forTCandRTD

nStepResponseTimeSpecificationsWithin500ms(whentheinputsamplingperiodis50msor100ms)Within1s(whentheinputsamplingperiodis200ms)(63%ofanalogoutputresponsetimewhenastepchangeof10to90%ofinputspanisapplied)

nRelayContactOutputSpecifications• Contacttypeandnumberofoutputs: Alarm-1to-3output:contactpoint1a;3points(commonisindependent) Alarm-4output:contactpoint1c;1point• Contactrating: Contactpoint1a(Alarm-1to-3output):240VAC,1Aor30VDC,1A(resistanceload) Contactpoint1c(Alarm-4output):250VAC,3Aor30VDC,3A(resistanceload)• Use:Alarmoutput,FAILoutput,etc.Note:Thiscannotbeusedforasmallloadof10mAorless.

n RetransmissionOutputSpecifications• Numberofoutputs:Retransmissionoutput;1,sharedwith15VDClooppower

supply• Currentoutput:4to20mADCor0to20mADC/loadresistanceof600Ωorless• Currentoutputaccuracy:±0.1%ofspan(±5%ofspanfor1mAorless) Theaccuracyisthatinthestandardoperatingconditions:23±2°C,55±10%RH,andpowerfrequencyat50/60Hz

n 15VDCLoopPowerSupplySpecifications(Sharedwithretransmissionoutput.)• Powersupply:14.5to18.0VDC• Maximumsupplycurrent:About21mA(withshort-circuitcurrentlimitingcircuit)

nContactInputSpecifications• Numberofinputs:2points• Inputtype:No-voltagecontactinputortransistorcontactinput• Inputcontactrating:12VDC,10mAormore Useacontactwithaminimumon-currentof1mAormore.• ON/OFFdetection: No-voltagecontactinput: Contactresistanceof1kΩorlessisdeterminedas“ON”andcontact resistanceof50kΩormoreas“OFF.” Transistorcontactinput: Inputvoltageof2Vorlessisdeterminedas“ON”andleakagecurrentmust notexceed100µAwhen“OFF.”• Minimumstatusdetectionholdtime:Inputsamplingperiod+50ms• Use:Eventinput

nTransistorContactOutputSpecifications• Numberofoutputs:SeethetableofModelandSuffixCodes.• Outputtype:Opencollector(SINKcurrent)• Outputcontactrating:Max.24VDC,50mA• Outputtimeresolution:Min.50ms• Use:Alarmoutput,FAILoutput,etc.

n24VDCLoopPowerSupplySpecifications• Use:Powerissuppliedtoa2-wiretransmitter.• Powersupply:21.6to28.0VDC• Ratedcurrent:4to20mADC• Maximumsupplycurrent:About30mA(withshort-circuitcurrentlimitingcircuit.)

SafetyandEMCStandards• Safety:Compliantwith IEC/EN61010-1 (CE),approvedbyCAN/CSAC22.2No.61010-1(CSA).UL61010-1ispendingapproval.

Installationcategory:CAT.IIPollutiondegree:2 Measurementcategory:I(CAT.I) Ratedmeasurementinputvoltage:Max.10VDC Ratedtransientovervoltage:1500V(Note)Note:ThisisareferencesafetystandardvalueforMeasurementCategoryIofIEC/EN/CSA/

UL61010-1.Thisvalueisnotnecessarilyaguaranteeofinstrumentperformance.

• EMCConformitystandards: CEmarking EN61326-1ClassA,Table2(Foruseinindustriallocations) EN61326-2-3 EN55011ClassA,Group1 EN61000-3-2ClassA EN61000-3-3 C-tickmark EN55011ClassA,Group1 Theinstrumentcontinuestooperateatameasurementaccuracyofwithin±20%oftherangeduringtesting.

Construction,Installation,andWiring• Dust-proofanddrip-proof:IP56(forfrontpanel)• Material:Polycarbonate(Flameretardancy:UL94V-0)• Casecolor:White(Lightgray)orBlack(Lightcharcoalgray)• Weight:0.5kgorless• Externaldimensions(mm):96(W)×48(H)×65(depthfromthepanelface) (Depthexcepttheprojectionontherearpanel)• Installation:Directpanelmounting;mountingbracket,oneeachforrightand leftmounting

• Panelcutoutdimensions(mm):92+0.8/0(W)×45+0.6/0(H)• Mountingattitude:Upto30degreesabovethehorizontal.Nodownwardtitlingallowed.• Wiring:M3screwterminalwithsquarewasher(forsignalwiringandpowerwiring)

PowerSupplySpecificationsandIsolation• Powersupply: Ratedvoltage:100-240VAC(+10%/-15%),50/60Hz 24VAC/DC(+10%/-15%)(for/DCoption)• Powerconsumption:15VA(DC:7VA,AC:11VAif/DCoptionisspecified)• Databackup:Nonvolatilememory• Powerholduptime:20ms(for100VACdrive)• Withstandingvoltage Betweenprimaryterminalsandsecondaryterminals:2300VACfor1minute Betweenprimaryterminals:1500VACfor1minute Betweensecondaryterminals:500VACfor1minute (Primaryterminals:Power*andrelayoutputterminals;Secondaryterminals: AnalogI/Osignalterminals,contactinputterminals,communicationterminals andfunctionalgroundingterminals.)

*:Powerterminalsfor24VAC/DCmodelsarethesecondaryterminals.• Insulationresistance:Betweenpowersupply terminalsandagroundingterminal20MΩormoreat500VDC

• Isolationspecifications

PV (universal ) input terminals

Alarm-1 relay (contact point a) output terminals

Alarm-2 relay (contact point a) output terminals

Alarm-3 relay (contact point a) output terminals

Contact input terminals (all)RS-485 communication terminals

24 V DC loop power supply terminals

Contact output (transistor) terminals

Retransmission (analog) output terminals(not isolated between the analog output terminals)

Internal

circuits

Power

supply

The circuits divided by lines are insulated mutually.

Alarm-4 relay (contact point c) output terminals

EnvironmentalConditions

Normal Operating Conditions• Ambienttemperature:-10to50ºC• Ambienthumidity:20to90%RH(nocondensationallowed)• Magneticfield:400A/morless• Continuousvibrationat5to9Hz:Halfamplitudeof1.5mmorless,1oct/minfor90minuteseachinthethreeaxisdirections

Continuousvibrationat9to150Hz:4.9m/s2orless,1oct/minfor90minuteseachinthethreeaxisdirections

• Short-periodvibration:14.7m/s2,15secondsorless• Shock:98m/s2orless,11ms• Altitude:2000morlessabovesealevel

• Warm-uptime:30minutesormoreafterthepoweristurnedon• Startuptime:Within10seconds *: TheLCD(aliquidcrystaldisplay)isusedforadisplayportionofthisproduct.

TheLCDhasacharacteristicthatthedisplayactionbecomeslateatthelow temperature.

Transportation and Storage Conditions• Temperature:-25to70ºC• Temperaturechangerate:20ºC/horless• Humidity:5to95%RH(nocondensationallowed)

Effects of Operating Conditions• Effectofambienttemperature: VoltageorTCinput:±1µV/ºCor±0.01%ofF.S./ºC,whicheverislarger Currentinput:±0.01%ofF.S./ºC RTDinput:±0.05ºC/ºC(ambienttemperature)orless Analogoutput:±0.02%ofF.S./ºCorless• Effectofpowersupplyvoltagefluctuation Analoginput:±0.05%ofF.S.orless Analogoutput:±0.05%ofF.S.orless (Eachwithinratedvoltagerange)

Page 3: Contents 3. How to Install Introduction · 2013. 3. 24. · Functional grounding terminals (Do not use this terminal as a protective grounding terminal). Note Identifies important

IM 05P03D21-11EN page 3/8

5. How to Connect Wires

WARNING

• Wiring work must be carried out by a person with basic electrical knowledge and practical experience.

• Be sure to turn OFF the power supply to the indicator before wiring to avoid an electric shock. Use a tester or similar device to ensure that no power is being supplied to a cable to be connected.

• As a safety measure, always install a circuit breaker (an IEC 60947-compatible product, 5 A, 100 V or 220 V AC) in an easily accessible location near the instrument. Moreover, provide indication that the switch is a device for turning off the power to the instrument.

• Install the power cable keeping a distance of more than 1 cm from other signal wires.

• The power cable is required to meet the IEC standards concerned or the requirements of the area in which the instrument is being installed.

• Wiring should be installed to conform to NEC (National Electrical Code: ANSI/NFPA-70) or the wiring construction standards in countries or regions where wiring will be installed.

• For the alarm relay output and power terminal connections, use heat-resistant cables.

• Since the insulation provided to each relay output terminal is Functional insulation, provide Reinforced insulation to the external of the device as necessary. (Refer to the drawing below.)

This product

Functionalinsulation

A safety voltage circuit

A safety voltage circuit

This product

Reinforced insulation

Reinforced insulation

Functionalinsulation

A hazardous voltage circuit

A hazardous voltage circuit

A safety voltage circuit

A safety voltage circuit

This product

Reinforced insulation

Reinforced insulation

Functionalinsulation

A hazardous voltage circuit

A hazardous voltage circuit

A hazardous voltage circuit

A hazardous voltage circuit

CAUTION

• Provide electricity from a single-phase power supply. If the power is noisy, install an isolation transformer on the primary side, and use a line filter on the secondary side. When measures against noise are taken, do not install the primary and secondary power cables close to each other.

• If there is a risk of external lightning surges, use a lightning arrester etc.

• For TC input, use shielded compensating lead wires for wiring. For RTD input, use shielded wires that have low conductor resistance and cause no significant differences in resistance between the three wires.

• Since the alarm output relay has a life span (resistance load of 100,000 times), use the auxiliary relay to perform ON/OFF control.

• The use of inductance (L) loads such as auxiliary relays, motors and solenoid valves causes malfunction or relay failure; always insert a CR filter for use with alternating current or a diode for use with direct current, as a spark-removal surge suppression circuit, into the line in parallel with the load.

• After completing the wiring, the terminal cover is recommended to use for the instrument.

RecommendedCrimp-onTerminalLugs

(A)

(F)

(ød)

5.5 3.3

Recommendedtighteningtorque:0.6N·m Applicablewiresize:Powersupplywiring1.25mm2ormoreApplicable terminal lug Applicable wire size mm2 (AWG#) (φd) (A) (F)M3 0.25to1.65(22to16) 3.3 5.5 4.2

CableSpecificationsandRecommendedCablesPurpose Name and Manufacturer

Powersupply,relaycontactoutputs 600VGradeheat-resistantPVCinsulatedwires,JISC3317(HIV),0.9to2.0mm2

Thermocouple Shieldedcompensatingleadwires,JISC1610RTD Shieldedwires(three/fourconductors),UL2482(HitachiCable)Othersignals(otherthancontactinput/output) ShieldedwiresOthersignals(contactinput/output) UnshieldedwiresRS-485communication Shieldedwires

DC Relay Wiring

R

External DC power supplyRelayO.CUM33A

UM’s contact

Diode(Mount it directlyto the relay coilterminal (socket).)

Relay(Use one with a relay coil rating

less than the UM’s contact rating.)

AC Relay Wiring

UM33A

R

UM’s contact CR filter(Mount it directlyto the relay coilterminal (socket).)

External AC power supply

Relay(Use one with a relay coilrating less than the UM’s

contact rating.)

6. Terminal Wiring Diagrams

CAUTION

• Do not use an unassigned terminal as the relay terminal. Do not use a 100-240 V AC power supply for the 24 V AC/DC

model; otherwise, the instrument will malfunction.

UM33A

301-306

201-212

101-112

306 305 304 303 302 301

212 211 210 208 207 204 203

112 111 110 109 106 105 104108 107 103

202 201

102 101

E1-terminal area

PVPV input (Equippedas standard)

TC input

202

203

RTD input

A

B

b

201

202

203

Voltage (mV, V) input

202

203

Current (mA) input

203

204

Factory default: PV input type is undefined.

RETRetransmission output (Equipped as standard)Retransmission output

4-20 mA DC or0-20 mA DC

Default: 4-20 mA DC

Default: PV retransmission

Load resistance 600 Ω or less

207

208

15 V DC loop power supply

14.5-18.0 V DC(Max. 21 mA DC)

207

208

Can be used for 15 V DC loop power supply when not used for retransmission output.

ALM (Equipped as standard)Contact output

External contact output (relay)

AL3

AL2

AL1

Relay contact rating: 240 V AC, 1 A 30 V DC, 1 A (resistance load)

Alarm-3 output(PV high limit)

Alarm-2 output( PV low limit)

Alarm-1 outputPV high limit

Common

Common

Common

UM104

105

106

107

108

109

ALM4(Suffix code: Type 2=1, 2 or 3)

Contact output

Contact rating: 250 V AC, 3 A 30 V DC, 3 A (resistance load)

AL4

(24 V AC/DC power supply: Optional suffix code /DC)

Power supply

Allowable range: 100-240 V AC (±10%) (free v(oltage) 50/60 Hz shared

100-240 V AC power supply

N

L

110

111

112

24 V AC/DC power supply

110

111

112

N

L

RS-485

RSB(+)

RSA(-)

SG

RS-485 communication/24 V DC loop power supply24 V DC loop power supply

21.6-28.0 V DC(Max. 30 mA DC)

301

302

303

305

306

RS485/LPS24(Suffix code: Type 2=1 and with optional suffix code /LP)

24 V DC loop power supply

21.6-28.0 V DC(Max. 30 mA DC)

24 V DC loop power supply

(Suffix code: Type 2=0 or 2 and with optional suffix code /LP)

305

306

LPS24RS-485

SDB(+)

SDA(-)

RDB(+)

RDA(-)

SG

RS-485 communication

301

302

303

304

305

RS485(Suffix code: Type 2=1 and without optional suffix code /LP)

(Suffix code: Type 2=3)Contact outputExternal contact output

DO12

DO11

DO13

DO14

DO15

COMCommon

UM301

302

303

304

305

306

DO

Transistor contact rating: 24 V DC, 50 mA

The function of each contact output can be changed.

Alarm-6 output( PV low limit)

Alarm-5 output(PV high limit)

Alarm-8 output( PV low limit)

FAIL

Alarm-7 output(PV high limit)

DI (Equipped as standard)Contact input

Contact rating: 12 V DC, 10 mA or more

External contact input

DI2

DI1

COMCommon

DI2

DI1

COM

+5V

+5V

No-voltagecontact

Transistor contactUM UM

210

211

212

210

211

212

The function of each contact input can be changed.

ON: PV peak and bottom values reset

OFF → ON: Latch release

101

102

Relay contact output

103

NC

NO

COM

Alarm-4 output

( PV low limit)

AL4

Page 4: Contents 3. How to Install Introduction · 2013. 3. 24. · Functional grounding terminals (Do not use this terminal as a protective grounding terminal). Note Identifies important

IM 05P03D21-11EN page 4/8

Page 5: Contents 3. How to Install Introduction · 2013. 3. 24. · Functional grounding terminals (Do not use this terminal as a protective grounding terminal). Note Identifies important

IM 05P03D21-11EN page 5/8

Contents1. NamesandFunctionsofDisplayParts2. QuickSettingFunction(SettingofInputandOutput)3. SettingAlarmType

1. Names and Functions of Display Parts

(1)

(2)

(3)(4)

(5)

(11)

(8)(6)(7)

(13)

(12)

(10)

(9)

No.infigure Name Description

(1) PVdisplay(whiteorred)

DisplaysPV.Displaysanerrorcodeifanerroroccurs.DisplaysthescrollingguideintheMenuDisplayandParameterSettingDisplaywhentheguidedisplayON/OFFissettoON.

(2) Groupdisplay(green) Displaysagroupnumber.(3) Symboldisplay(orange) Displaysaparametersymbol.(4) Datadisplay(orange) Displaysaparametersetpointandmenusymbol.

(5) Eventindicator(orange)

Litwhenthealarms1to8occur.Eventdisplaysotherthanalarmscanbesetbytheparameter.

(6) Keynavigationindica-tor(green)

LitorblinkswhentheUp/DownorLeft/Rightarrowkeyoperationispossible.

(7) Parameterdisplaylevelindicator(green)

Displaysthesettingconditionsoftheparameterdisplaylevelfunc-tion.

Parameter display level EASY PROEasysettingmode Lit UnlitStandardsettingmode Unlit UnlitProfessionalsettingmode Unlit Lit

(8) Securityindicator(red) Litifapasswordisset.Thesetupparametersettingsarelocked.

No.infigure Name Description

(9) DISPkey

UsedtoswitchtheOperationDisplays.PressthekeyintheOperationDisplaytoswitchtheprovidedSELECTDisplays.PressthekeyintheMenuDisplayorParameterSettingDisplaytoreturntotheOperationDisplay.

(10) PARAkey

Holddownthekeyfor3secondstomovetotheOperationParameterSettingDisplay.HolddownthekeyandtheLeftarrowkeysimultaneouslyfor3secondstomovetotheSetupParameterSettingDisplay.PressthekeyintheParameterSettingDisplaytoreturntotheMenuDisplay.Pressthekeyoncetocanceltheparameterset-ting(setpointisblinking).

(11)SET/ENTERkeyUp/Down/Left/Rightarrowkeys

SET/ENTERkeyPressthekeyintheMenuDisplaytomovetotheParameterSettingDisplayoftheMenu.PressthekeyintheParameterSettingDisplaytotransfertotheparametersettingmode(setpointisblinking),andtheparametercanbechanged.Pressthekeyduringparametersettingmodetoregisterthesetpoint.Up/Down/Left/RightarrowkeysPresstheLeft/RightarrowkeysintheMenuDisplaytoswitchtheDisplays.PresstheUp/DownarrowkeysintheParameterSettingDisplaytoswitchtheDisplays.PresstheUp/Downarrowkeysduringparametersettingmode(setpointisblinking)tochangeasetpoint.PresstheLeft/Rightarrowkeysduringparametersettingmode(setpointisblinking)tomovebetweendigitsaccordingtotheparameter.

(12) Light-loaderinterfaceItisthecommunicationinterfacefortheadaptercableusedwhensettingandstoringparametersfromaPC.TheLL50AParameterSettingSoftware(soldseparately)isrequired.

(13) Userfunctionkeys Fnkey.Theusercanassignafunctiontothekey.Thefunctionissetbytheparameter.

Note: Thecommunicationconnector(maintenanceport)forLL50AParameterSettingSoftwareisonthesideoftheunit.

2. Quick Setting Function (Setting of Input and Output)TheQuicksettingfunctionisafunctiontoeasilysetthebasicfunctionoftheindicator.TurnontheindicatortostarttheQuicksettingfunction.Thisfunctionallowsyoutoeasilysettheinput,andquicklystartthealarmaction.Theitems(parameters)tobesetbyQuicksettingfunctionareasfollows.(1)Inputfunction(PVinputtype,range,scale(atvoltageinput),etc.)

Afterturningontheindicator,firstdecidewhetherornottousetheQuicksettingfunction.

Operation in Initial Display· PresstheSET/ENTERkeywhileYESisdisplayedtostarttheQuicksettingfunction.· IfyouchangeYEStoNOandpresstheSET/ENTERkey,OperationDisplaywillappearwithoutstartingtheQuicksettingfunction.

Operation for Setting· Toselecttheparametersettingdisplayedastheinitialvalue,presstheDownarrowkeytomovetothenextparameter.

· Tochangeandset theparametersetting,presstheSET/ENTERkeytostart thesetpointblinking.Theblinkingstateallowsyoutomakechanges(settingmode).UsetheUp/Down/Left/Rightarrowkeystochangethesetpoint.PresstheSET/EN-TERkeytoregisterthesetting.

MakingSettingsUsingQuickSettingFunctionExample: Setting to thermocouple type K (range of 0.0 to 500.00C).Forthedetailedprocedureandswitchingofdisplays,see"FlowofQuickSettingFunction"below.Fortheparameterstoset,seethenextpage.

(1)PresstheSET/ENTERkeywhileYESforQSM(Quicksettingmode)isdisplayed.(2)SetthePVinputtypeparameter(IN)toK1(-270.0to1370.00C).(3)SetthePVinputunitparameter(UNIT)toC(DegreeCelsius).(4)SetthemaximumvalueofPVinputrangeparameter(RH)to500.0.(5)SettheminimumvalueofPVinputrangeparameter(RL)to0.0.(6)Finally,EXITisdisplayed.ChangeNOtoYESandpresstheSET/ENTERkeyto

completethesetup.OperationDisplayappears.

FlowofQuickSettingFunctionInQuicksettingmode,theparameterguideappearsonPVdisplay.Thisguidecanbeturnedon/offwiththeFnkey.

8

1.

2.

3.

4.

5.

6.

8.

9.

10.

11.

7.

8

8

8

8

Power-on

Quick setting starts

The PV input type parameter (IN) is displayed.Initial value: OFF

OFF blinks.Blinking allows you to change the setting.

K1 is displayed.

K1 has been registered.

The last digit of the upper limit value blinks.

The parameter RH (maximum value of PV input range) has been changed to 500.0.

The setpoint for the parameter RH has been registered.

The PV input unit parameter (UNIT) is displayed.Initial value: C (Degree Celsius)

Select NO with the Down arrow key and press the SET/ENTER key.

Press the SET/ENTER key while YES is displayed to start the Quick setting.

[YES][NO]

Press the SET/ENTER key.

Press the SET/ENTER key.

Press the SET/ENTER key.

Press the SET/ENTER key.

Press the Up arrow key.

Select NO to return to the Operation Display.

Press the Down arrow key.

Press the Down arrow key.

Press the Down arrow key.

The upper limit value of the setting range is displayed for the parameter RH (maximum value of PV input range).

Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.

Finally, EXIT is displayed.Press the SET/ENTER key to swtich to the setting mode.Change NO to YES and press the SET/ENTER key to complete the setup of the basic function.Operation Display appears.The Quick setting function continues in the NO state.

Operation Display

Displays the measured input value (PV).

Follow the same procedure to set RL.

OperationGuide

Initial Settings

UM33ADigital Indicator with AlarmsOperation Guide

This operation guide describes basic settings and operations of the UM33A.For details of each function, see the electronic manual.The scrolling guide is displayed on PV display in the Parameter Setting Display.This guide can be turned on/off with the Fn key.

3. Setting Alarm TypeThefollowingoperatingprocedureshowsanexampleofchangingthealarm-1type(factorydefault:PVhighlimitalarm)toPVlowlimitalarm.

1.

2.

3.

4.

5.

6.

8

AL menu is displayed.

ALRM menu is displayed.

Show the Operation Display.

Hold down the key for 3 seconds.

Press the Right arrow key.

Press the SET/ENTER key.

Press the SET/ENTER key.

Press the SET/ENTER key.

The parameter AL1 (alarm-1 type) is displayed.

The last digit of the setpoint blinks.

Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.

The alarm-1 type setpoint 02 (PV low limit) is registered.After the setup is completed, press the DISP key once to return to the Operation Display.

To change the alarm type, change the last 2 digits of the 5-digit value.

Stand-by action and excitation are turned on or off by selecting 1 or 0. (See “ Setting Display of Alarm Type.”)

For the latch action, see User ’s Manual.

Symbol Stand-by actionEnergized/De-energizedLatch action

- -No alarm (00)

Alarm Action (De-energized)

PV high limit (01)

PV low limit (02)

PV velocity (29)

Fault diagnosis alarm (30)

FAIL (31)

Alarm Type (Alarm Setpoint) Alarm Action (Energized)

Hysteresis

Alarm setpoint PV

Closed(lit)

Open(unlit)

Alarm setpoint

Hysteresis

PV

Closed(lit)

Open(unlit)

Hysteresis

Alarm setpoint PV

Open(lit)

Closed(unlit)

Alarm setpoint

Hysteresis

PV

Open(lit)

Closed(unlit)

Burnout of PV input, ADC failure, RJC error.

For the factory default, the contact output is turned ON in normal operation, OFF at the time of FAIL. Alarm output: OFF

Note 1: “Open/closed” shows status of relay contact, and “lit/unlit” shows status of EV (event) lamp.

Setting Display of Alarm Type Stand-by Action

Energized (0) / De-energized (1)

Alarm typeWithout (0) or With (1) Stand-by action

Latch action (0/1/2/3/4)See User’s Manual.

PV low limit alarm setpoint

Treatedas normal

ºC

Power-on Time

The alarm output does not turn onin this region even if the PV valuleis below PV low limit alarm setpoint.

Normal Abnormal

The alarm outputturns on.

8

1.

2.

3.

4.

5.

6.

8.

9.

10.

11.

7.

8

8

8

8

Power-on

Quick setting starts

The PV input type parameter (IN) is displayed.Initial value: OFF

OFF blinks.Blinking allows you to change the setting.

K1 is displayed.

K1 has been registered.

The last digit of the upper limit value blinks.

The parameter RH (maximum value of PV input range) has been changed to 500.0.

The setpoint for the parameter RH has been registered.

The PV input unit parameter (UNIT) is displayed.Initial value: C (Degree Celsius)

Select NO with the Down arrow key and press the SET/ENTER key.

Press the SET/ENTER key while YES is displayed to start the Quick setting.

[YES][NO]

Press the SET/ENTER key.

Press the SET/ENTER key.

Press the SET/ENTER key.

Press the SET/ENTER key.

Press the Up arrow key.

Select NO to return to the Operation Display.

Press the Down arrow key.

Press the Down arrow key.

Press the Down arrow key.

The upper limit value of the setting range is displayed for the parameter RH (maximum value of PV input range).

Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.

Finally, EXIT is displayed.Press the SET/ENTER key to swtich to the setting mode.Change NO to YES and press the SET/ENTER key to complete the setup of the basic function.Operation Display appears.The Quick setting function continues in the NO state.

Operation Display

Displays the measured input value (PV).

Follow the same procedure to set RL.

ParameterstobesetInput Function

Parameter Symbol Name of Parameter Setting Range

IN PVinputtype

OFF:DisableK1:-270.0to1370.00C/-450.0to2500.00FK2:-270.0to1000.00C/-450.0to2300.00FK3:-200.0to500.00C/-200.0to1000.00FJ:-200.0to1200.00C/-300.0to2300.00FT1:-270.0to400.00C/-450.0to750.00FT2:0.0to400.00C/-200.0to750.00FB:0.0to1800.00C/32to33000FS:0.0to1700.00C/32to31000FR:0.0to1700.00C/32to31000FN:-200.0to1300.00C/-300.0to2400.00FE:-270.0to1000.00C/-450.0to1800.00FL:-200.0to900.00C/-300.0to1600.00FU1:-200.0to400.00C/-300.0to750.00FU2:0.0to400.00C/-200.0to1000.00FW:0.0to2300.00C/32to42000FPL2:0.0to1390.00C/32.0to2500.00FP2040:0.0to1900.00C/32to34000FWRE:0.0to2000.00C/32to36000FJPT1:-200.0to500.00C/-300.0to1000.00FJPT2:-150.00to150.000C/-200.0to300.00FPT1:-200.0to850.00C/-300.0to1560.00FPT2:-200.0to500.00C/-300.0to1000.00FPT3:-150.00to150.000C/-200.0to300.00F0.4-2V:0.400to2.000V1-5V:1.000to5.000V4-20:4.00to20.00mA0-2V:0.000to2.000V0-10V:0.00to10.00V0-20:0.00to20.00mA-1020:-10.00to20.00mV0-100:0.0to100.0mV

UNIT PVinputunit -:Nounit,C:DegreeCelsius-:Nounit,--:Nounit,---:Nounit,F:DegreeFahrenheit

RH MaximumvalueofPVinputrange

Dependsontheinputtype.-Fortemperatureinput-Setthetemperaturerangethatisactuallydisplayed.(RL<RH)-Forvoltage/currentinput-Settherangeofavoltage/currentsignalthatisapplied.Thescaleacrosswhichthevoltage/currentsignalisactuallydisplayedshouldbesetusingthemaximumvalueofinputscale(SH)andminimumvalueofinputscale(SL).(Inputisalways0%whenRL=RH.)

RL MinimumvalueofPVinputrange

SDPPVinputscaledecimalpointposition

0:Nodecimalplace1:Onedecimalplace2:Twodecimalplaces

3:Threedecimalplaces4:Fourdecimalplaces

SH MaximumvalueofPVinputscale

-19999to30000,(SL<SH),|SH-SL|≤30000SL Minimumvalueof

PVinputscale

Note1:SDP,SH,andSLaredisplayedonlyforvoltage/currentinput.Note2:W:W-5%Re/W-26%Re(HoskinsMfg.Co.),ASTME988

Page 6: Contents 3. How to Install Introduction · 2013. 3. 24. · Functional grounding terminals (Do not use this terminal as a protective grounding terminal). Note Identifies important

IM 05P03D21-11EN page 6/8

Contents1. Monitoring-purposeOperationDisplaysAvailableduringOperation2. SettingAlarmSetpoint3. Troubleshooting

1. Monitoring-purpose Operation Displays Available during Operation

OperationDisplaySwitchingDiagram

8 8

PV Display SELECT Displays (1 to 5)

PresstheDISPkeytoshowSELECTDisplay-1to-5conditionally.FortheregistrationoftheSELECTDisplays,seeUser’sManual.

OperationGuide

UM33ADigital Indicator with AlarmsOperation Guide

This operation guide describes key entries for operating the UM33A.For operations using external contact inputs, see “DI” of “6. Terminal Wiring Diagrams” in “Installation and Wiring.” If you cannot remember how to carry out an operation during setting, press the DISP key once. This brings you to the display (Operation Display) that appears at power-on. The scrolling guide is displayed on PV display in the Parameter Setting Display. This guide can be turned on/off with the Fn key.

Operations

2. Setting Alarm SetpointThefollowingoperatingprocedureshowsanexampleofsettingthealarm-1setpointto180.0.Beforesettingthealarmsetpoint,checkthealarmtype.Tochange thealarmtype,see“3.SettingAlarmType” in “Initialsettings”of thismanual.

1.

2.

3.

4.

5.

6.

8

8

AL menu is displayed.

Display the parameter that need to be changed.

Blinks during the change.

Show the Operation Display.

Hold down the PARA key for 3 seconds.

Press the SET/ENTER key.

Press the SET/ENTER key.

Press the SET/ENTER key.

The parameter A1 is displayed.A1 to A8 represent the alarm-1 to -8 setpoints.

Each parameter can be changed in the Parameter Setting Displays of alarms using Up/Down arrow keys .

Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.

The setpoint has been registered.After the setup is completed, press the DISP key once to return to the Operation Display.

3. TroubleshootingTroubleshootingFlowIftheOperationDisplaydoesnotappearafterturningontheindicator’spower,checktheproceduresinthefollowingflowchart.Ifaproblemappearstobecomplicated,contactoursalesrepresentatives.

RemediesifPowerFailureOccursduringOperations• Instantaneous power failure within 20 ms. Apowerfailureisnotdetected.Normaloperationcontinues.• Power failure for less than about 5 seconds, or for about 5 seconds or more. Affectsthe"settings"and"operationstatus." Fordetails,seeUser'sManual.

NOTEWrite down the settingsofparameters fora repairrequest.

Is the indicatordefective?

Contact us for repair. Problem solved.

No communicationcapability

Completelyinactive?

Yes

Yes

Yes

No

No

No

Keyoperationfailure?

Yes

No

Yes

Check wiring of thepower terminals.

Check the key locksetting.

Displayfailure?

*Yes

No

Turn off power, andthen turn it on again.

I/O signalfailure?

Yes

No

Check the supply voltage.

Check the specifications and polarity

of connected devices .

Check the communication-related parameters.

Check the specificationsof communication

devices.

Check thecommunication wiring.

Communicationfailure?

No Withcommuni-

cation?

Yes

Yes

Normal?Is the

key locked?

Check the specificationsof the indicator.

Yes

NoCorrect?

Correct the error(s).

Cancel the setting.

Check the I/O specificationsof the indicator.

* The LCD (a liquid crystal display) is used for a display portion of this product.

The LCD has a characteristic that the display action becomes late at the low temperature.

Additionally, the luminance and contrast degradation are caused due to aged deterioration.

However, the function is not affected.

n Errors at Power OnTheerrorsshownbelowmayoccurinthefaultdiagnosiswhenthepoweristurnedon.(FordetailsofSetpointdisplayandinput/outputactionwheneacherroroccurs,seeUser’sManual.)

PV display (Operation

Display)

Setpoint display(Operation Display)

Status indicator(Operation Display)

Parameter that displays error details Error description Cause and diagnosis Remedy

Indicationoff Indicationoff — — FaultyMCURAM/MCUROM MCURAM/MCUROMarefailed. Faulty.Contactusforrepair.

ERR

SYS-----

— Systemdataerror Systemdataiscorrupted. Faulty.Contactusforrepair.

PAR0004(foruserdefaultvalueerroronly)

Setupparameter(PA.ER)

User(parameter)defaultvalueerror

Userparameteriscorrupted.Initializedtofactorydefaultvalue. Checkandreconfiguretheinitialized

settingparameters.Errorindicationiserasedwhenthepoweristurnedonagain.

PAR0010(forsetupparametererroronly) Setupparametererror Setupparameterdataiscorrupted.

Initializedtouserdefaultvalue.

PAR0020(foroperationparametererroronly) Operationparametererror Operationparameterdataiscorrupted.

Initializedtouserdefaultvalue.

SLOT0001 Setupparameter(OP.ER)Nonrespondinghardwareofextendedfunction(E1-terminalarea)

Inconsistenceofsystemdataandhardwareofextendedfunction.Nonrespondingcommunicationbetweenhardwareofextendedfunction(E1-terminalarea).

Faulty.Contactusforrepair.

Normalindication Normalindication

RightmostdecimalpointonPVdisplayblinks.

Setupparameter(PA.ER)Calibrationvalueerror Initializedtocalibrateddefaultvaluebecause

ofcorruptedfactorydefaultvalue. Faulty.Contactusforrepair.Rightmostdecimalpoint

onSymboldisplayblinks. FaultyFRAM Datawriting(storing)toFRAMisimpossible.

n Errors during OperationTheerrorsshownbelowmayoccurduringoperation.(Forinput/outputactionwheneacherroroccurs,seeUser’sManual.)

PV display (Operation

Display)

Setpoint display(Operation Display)

Status indicator(Operation Display)

Parameter that displayserror details Error description Cause and diagnosis Remedy

AD.ERR Normalindication — Setupparameter(AD1.E) AnaloginputterminalADCerror•PVinput AnaloginputterminalADvalueerror Faulty.

Contactusforrepair.

RJC.E(DisplaysRJC.EandPValternately.)

Normalindication — Setupparameter(AD1.E) UniversalinputterminalRJCerror•PVinput UniversalinputterminalRJCerror

Faulty.Contactusforrepair.SettheparameterRJCtoOFFtoeraseerrorindication.

B.OUT Normalindication —

Setupparameter(AD1.E) Analoginputterminalburnouterror•PVinput Analoginputterminalsensorburnout

Checkwiringandsensor.Errorindicationiserasedinnormaloperation.

Setupparameter(PV1.E) PVinputburnouterror BurnoutofanaloginputconnectedtoPV

Checkwiringandsensorofconnectedanaloginputterminals.Errorindicationiserasedinnormaloperation.

OVER-OVER

Normalindication — Setupparameter(PV1.E)PVinputover-scalePVinputunder-scale(PVvaluesoutof-5to105%)

PVinputisoutof-5to105%.Alsooccurswhenthedataoutofrangewhichistheladdercalculationresultisinput.

Checkanaloginputvalueorladderprogram.

Normalindication

0.00000000(DecimalpointontheleftoftheSymboldisplayblinks)

— Setupparameter(OP.ER) Communicationerror(RS-485communication)

FramingparityerrorBufferoverflowInter-charactertime-outChecksumerror(PClinkcommunicationwithchecksum)CRCcheckerror(Modbus/RTU)LRCcheckerror(Modbus/ASCII)

Checkthecommunicationparameters.Recoveryatnormalreceipt.Holddownanykeytostopblinking.

Normalindication Normalindication Rightmostdecimalpointon

Symboldisplayblinks. Setupparameter(PA.ER) FaultyFRAM Writing(storing)datatoFRAMisimpossible. Faulty.Contactusforrepair.

Undefined Undefined — — FaultyMCU/DCU(ROM/RAMerror,corrupted) MCU/DCUiscorrupted. Faulty.Contactusforrepair.

Page 7: Contents 3. How to Install Introduction · 2013. 3. 24. · Functional grounding terminals (Do not use this terminal as a protective grounding terminal). Note Identifies important

IM 05P03D21-11EN page 7/8

Operation ParametersHolddownthePARAkeyfor3secondstomovefromtheOperationDisplaytotheOp-erationParameterSettingDisplay.PresstheDISPkeyoncetoreturntotheOperationDisplay.

Menu

Hold down PARA keyfor 3 sec.

DISP key

SET/ENTER key PARA key

key key key

key key

Operation Dsipaly

Parameter

Parameter

Parameter

Parameter

Parameter

ParameterEND

Menu

END

Menu END

END

Menu Display and Parameter Setting Display are changed in a circular pattern.

Move to the Setup Parameter Setting Display: Hold down the PARA key and the Left arrow key simultaneously for 3 sec.

Operation for Setting· Toselecttheparametersettingdisplayedastheinitialvalue,presstheDownarrowkeytomovetothenextparameter.

· Tochangeandsettheparametersetting,presstheSET/ENTERkeytostarttheset-pointblinking.Theblinkingstateallowsyoutomakechanges(settingmode).UsetheUp/Down/Left/Rightarrowkeystochangethesetpoint.PresstheSET/ENTERkeytoregisterthesetting.

Notethattherearesomeparameterswhicharenotdisplayeddependingonthemodelandsuffixcodes.

n Alarm Setpoint Setting ParameterMenusymbol: (AL)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

to

(A1toA8)

Alarm-1to-8setpoint

SetadisplayvalueofsetpointofPValarmorvelocityalarm.-19999to30000(Setavaluewithintheinputrange.)Decimalpointpositiondependsontheinputtype

0 Tablebelow EASY

For thealarmsetpointparameter,alarm-1to-8aredisplayedfor thefactorydefault.ThenumberofalarmscanbechangedusingthesetupparameterALNO.(numberofalarms).Tochangethenumberofalarms,seeUser'sManual.Usethefollowingtabletorecordalarmsetpoints.

Parameter Setpoint Parameter Setpoint

A1 A5

A2 A6

A3 A7

A4 A8

n Alarm Function Setting ParameterMenusymbol: (ALRM)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

to

(AL1toAL8)

Alarm-1to8typeExample:Alarm-1

Stand-byaction

Latch actionEnergized/De-energize

Alarmtype

Seta5-digitvalueinthefollowingorder.[Alarmtype:2digits(seebelow)]+[Without(0)orWith(1)Stand-byac-tion]+[Energized(0)orDe-energized(1)]+[Latchaction(0/1/2/3/4)]Forlatchaction,seeUser'sManual.

AL1,AL3,AL5,AL7:

PVhighlimit(01)WithoutStand-by

action(0)

Ener-gized(0)Latchaction(0)

AL2,AL4,AL6,AL8:PVlowlimit(02)WithoutStand-by

action(0)

Ener-gized(0)

Latchaction(0)

Tablebelow

EASY

Alarmtype:2digits00:Disable01:PVhighlimit02:PVlowlimit29:PVvelocity30:Faultdiagnosis31:FAIL

to

(VT1toVT8)

PVvelocityalarmtimesetpoint1to8 0.01to99.59(minute.second) 1.00

to

(HY1toHY8)

Alarm-1to-8hysteresis

Setadisplayvalueofsetpointofhysteresis.-19999to30000(Setavaluewithintheinputrange.)Decimalpointpositiondependsontheinputtype.Whenthedecimalpointpositionfortheinputtypeissetto"1",theinitialvalueofthehysteresisis"1.0".

10

to

(DYN1toDYN8)

Alarm-1to-8On-delaytimer

AnalarmoutputisONwhenthedelaytimerexpiresafterthealarmsetpointisreached.0.00to99.59(minute.second)

0.00 STD

Forthealarmfunctionsettingparameter,8alarmsaredisplayedforthefactorydefault.Thenumberofalarmscanbechangedby thesetupparameterALNO. (numberofalarms).Tochangethenumberofalarms,seeUser'sManual.Parameter n=1 n=2 n=3 n=4 n=5 n=6 n=7 n=8

ALn

VTn

HYn

DYNn

n:alarmnumber

n PV-related Setting ParameterMenusymbol: (PVS)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(BS)PVinputbias -100.0to100.0%ofPVinputrange

span(EUS)

0.0%ofPVinputrangespan

EASY(FL)PVinputfilter OFF,1to120s OFF

(PEAK)PVpeakvalue

Displayonly(-5.0to105.0%ofPVinputrange(EU))

None

(BOTM)PVbottomvalue None

Setup ParametersHolddownthePARAkeyandLeftarrowkeysimultaneously for3secondstomovefromtheOperationDisplayorOperationParameterSettingDisplayto theSetupPa-rameterSettingDisplay.PresstheDISPkeyoncetoreturntotheOperationDisplay.

Menu

DISP key

SET/ENTER key PARA key

key key key

key key

Operation Dsipaly

Parameter

Parameter

Parameter

Parameter

Parameter

ParameterEND

Menu

END

Menu END

END

Menu Display and Parameter Setting Display are changed in a circular pattern.

Move to the Operation Parameter Setting Display: Hold down the PARA key for 3 sec.

Hold down PARA key and Left arrow key simultaneously for 3 sec.

Operation for Setting· Toselecttheparametersettingdisplayedastheinitialvalue,presstheDownarrowkeytomovetothenextparameter.

· Tochangeandsettheparametersetting,presstheSET/ENTERkeytostarttheset-pointblinking.Theblinkingstateallowsyoutomakechanges(settingmode).UsetheUp/Down/Left/Rightarrowkeystochangethesetpoint.PresstheSET/ENTERkeytoregisterthesetting.

NotethattherearesomeparameterswhicharenotdisplayeddependingontheModelandSuffixcodes.

n Function Setting ParameterMenusymbol: (CTL)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(SMP)Inputsamplingperiod 50:50ms,100:100ms,200:200ms 50 STD

n PV Input Setting ParameterMenusymbol: (PV)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(IN)PVinputtype

OFF:DisableK1:-270.0to1370.00C/-450.0to2500.00FK2:-270.0to1000.00C/-450.0to2300.00FK3:-200.0to500.00C/-200.0to1000.00FJ:-200.0to1200.00C/-300.0to2300.00FT1:-270.0to400.00C/-450.0to750.00FT2:0.0to400.00C/-200.0to750.00FB:0.0to1800.00C/32to33000FS:0.0to1700.00C/32to31000FR:0.0to1700.00C/32to31000FN:-200.0to1300.00C/-300.0to2400.00FE:-270.0to1000.00C/-450.0to1800.00FL:-200.0to900.00C/-300.0to1600.00FU1:-200.0to400.00C/-300.0to750.00FU2:0.0to400.00C/-200.0to1000.00FW:0.0to2300.00C/32to42000FPL2:0.0to1390.00C/32.0to2500.00FP2040:0.0to1900.00C/32to34000FWRE:0.0to2000.00C/32to36000FJPT1:-200.0to500.00C/-300.0to1000.00FJPT2:-150.0to150.00C/-200.0to300.00FPT1:-200.0to850.00C/-300.0to1560.00FPT2:-200.0to500.00C/-300.0to1000.00FPT3:-150.00to150.000C/-200.0to300.00F0.4-2V:0.400to2.000V1-5V:1.000to5.000V4-20:4.00to20.00mA0-2V:0.000to2.000V0-10V:0.00to10.00V0-20:0.00to20.00mA-1020:-10.00to20.00mV0-100:0.0to100.0mV

OFF EASY

(UNIT)PVinputunit

-:Nounit,C:DegreeCelsius-:Nounit,--:Nounit,---:Nounit,F:DegreeFahrenheit

C EASY

(RH)MaximumvalueofPVinputrange

Dependsontheinputtype.-Fortemperatureinput-Setthetemperaturerangethatisactuallydisplayed.(RL<RH)-Forvoltage/currentinput-Settherangeofavoltage/currentsignalthatisapplied.Thescaleacrosswhichthevoltage/currentsignalisactuallydisplayedshouldbesetusingthemaximumvalueofinputscale(SH)andminimumvalueofinputscale(SL).(Inputisalways0%whenRL=RH.)

Dependsonthe

inputtypeEASY

(RL)MinimumvalueofPVinputrange

(SDP)PVinputscaledecimalpointposition

0:Nodecimalplace1:Onedecimalplace2:Twodecimalplaces3:Threedecimalplaces4:Fourdecimalplaces

Dependsonthe

inputtypeEASY

(SH)MaximumvalueofPVinputscale

-19999to30000,(SL<SH),|SH-SL|≤30000

Dependsonthe

inputtypeEASY

(SL)MinimumvalueofPVinputscale

(BSL)PVinputburnoutaction

OFF:DisableUP:UpscaleDOWN:Downscale

Dependsonthe

inputtypeSTD

W:W-5%Re/W-26%Re(HoskinsMfg.Co.).ASTME988WRE:W97Re3-W75Re25

nInput Range Setting ParameterMenusymbol: (MPV)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(P.UNI)DisplayPVinputunit

-:NounitC:DegreeCelsius-:Nounit--:Nounit---:NounitF:DegreeFahrenheit

SameasPVinputunit

STD

(P.DP)DisplayPVinputdecimalpointposition

0:Nodecimalplace1:Onedecimalplace2:Twodecimalplaces3:Threedecimalplaces4:Fourdecimalplaces

1

(P.RH)MaximumvalueofdisplayPVinputrange

-19999to30000,(P.RL<P.RH),|P.RH-P.RL|≤30000

Dependsonthe

inputtype

(P.RL)MinimumvalueofdisplayPVinputrange

nOutput Setting ParameterMenusymbol: (OUT)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(RTS)RetransmissionoutputtypeofRET

OFF:DisablePV1:PVLPS:15VDClooppowersupply

PV1 EASY

(RTH)

MaximumvalueofretransmissionoutputscaleofRET

WhenRTS=PV1RTL+1digitto30000-19999toRTH-1digitDecimalpointposition:When

RTS=PV1,decimalpointpositionissameasthatofPVinput.

WhenRTS=PV,decimalpointpositionissameasthatofPVinputscale.

100%ofPVinputrange

STD(RTL)

MinimumvalueofretransmissionoutputscaleofRET

0%ofPVinputrange

(RET.A)RETcurrentoutputrange

4-20:4to20mA0-20:0to20mA20-4:20to4mA20-0:20to0mA

4-20

n RS-485 Communication Setting Parameter (E1-terminal Area)Menusymbol: (R485)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(PSL)Protocolselection

PCL:PClinkcommunicationPCLSM:PClinkcommunication(withchecksum)LADR:LaddercommunicationMBASC:Modbus(ASCII)MBRTU:Modbus(RTU)

MBRTU

EASY

(BPS)Baudrate

600:600bps1200:1200bps2400:2400bps4800:4800bps9600:9600bps19200:19.2kbps38400:38.4kbps

19200

(PRI)Parity

NONE:NoneEVEN:EvenODD:Odd

EVEN

(STP)Stopbit 1:1bit,2:2bits 1

(DLN)Datalength 7:7bits,8:8bits 8

(ADR)Address 1to99 1

OperationGuide

UM33ADigital Indicator with AlarmsOperation Guide

This operation guide describes the functions of parameters briefly. The parameter symbols listed are in the order shown on the display in each group of menu symbols. In addition, each parameter table has a “User Setting” column, where you can record your setpoints when setting them in the indicator. The scrolling guide is displayed on PV display in the Parameter Setting Display. This guide can be turned on/off with the Fn key.

Yokogawa Electric Corporation

Parameters

Page 8: Contents 3. How to Install Introduction · 2013. 3. 24. · Functional grounding terminals (Do not use this terminal as a protective grounding terminal). Note Identifies important

IM 05P03D21-11EN page 8/8

KeyActionSettingParameterMenusymbol: (KEY)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(Fn)Userfunctionkey-nactionsetting

OFF:DisableLTUP:LCDbrightnessUPLTDN:LCDbrightnessDOWNBRI:AdjustLCDbrightnessLCD:LCDbacklightON/OFFswitchLAT:Latchrelease(ACK)AL:AlarmsetpointsettingRST:PVpeakandbottomvalues

reset

RST EASY

DisplayFunctionSettingParameterMenusymbol: (DISP)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(PCMD)ActivecolorPVdisplayswitch

0:Fixedinwhite1:Fixedinred2:Linktoalarm1(AlarmOFF:white,

AlarmON:red)3:Linktoalarm1(AlarmOFF:red,

AlarmON:white)4:Linktoalarm1or2(AlarmOFF:

white,AlarmON:red)5:Linktoalarm1or2(AlarmOFF:

red,AlarmON:white)6:PVlimit(Withinrange:white,Out

ofrange:red)7:PVlimit(Withinrange:red,Outof

range:white)10:LinktoDI(ON:red,OFF:white)

0

EASY

(PCH)PVcolorchangehighlimit

SetadisplayvaluewheninPVlimitorSPdeviation.-19999to30000(Setavaluewithintheinputrange.)Decimalpointpositiondependsontheinputtype.

0

(PCL)PVcolorchangelowlimit 0

(GUID)GuidedisplayON/OFF OFF:Non-display,ON:Display ON

STD

(ECO)Economymode

OFF:Disable1:EconomymodeON(AllindicationsexceptPVdisplayOFF)2:EconomymodeON(AllindicationsOFF)3:Brightness10%(wholeindication)

OFF

(BRI)Brightness (Dark)1to5(Bright) 3 EASY

(MLSD)LeastsignificantdigitalmaskofPVdisplay

OFF:WithleastsignificantdigitON:Withoutleastsignificantdigit OFF STD

SELECTDisplaySettingParameterMenusymbol: (CSEL)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

to

(CS1toCS5)

SELECTDisplay-1to-5registration

Registertheoperationparameter(excepttheOperaitonMode)thatisfrequentlymodifiedtodisplayitintheOperationDisplay.OFF,2301to5000Forthesettingrange,seeUser'sManual.

OFF STD

UsethefollowingtabletorecordSELECTDsipalysettingvalue.

Parameter n=1 n=2 n=3 n=4 n=5

CSn

KeyLockSettingParameterMenusymbol: (KLOC)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(COM.W)Communicationwriteenable/disable OFF:Enable,ON:Disable OFF

STD

(DATA)Frontpanelparameterdata(,)keylock

OFF:Unlock,ON:Lock(AvailableforOperationDisplayonly.) OFF

DIFunctionResistrationParameterMenusymbol: (DI.SL)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(RST)PVpeakandbottomvaluesreset

SetanIrelaynumberofcontactinput.Set“OFF”todisablethefunction.

StandardterminalsDI1:5025,DI2:5026

5025

STD(LAT)

Latchrelease(ACK) 5026

(LCD)LCDbacklightON/OFFswitch OFF

(PVRW)PVred/whiteswitch OFF

AL1-AL4FunctionRegistrationParameterMenusymbol: (ALM)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(AL1.S)AL1functionselection

SetanIrelaynumber.Fortheitemsotherthanbelow,seeUser'sManual.Ex.)Setthenumber4353forAL1.Stousethealarm1.Set“OFF”todisablethefunction.

Nofunction:OFFAlarm1:4353Alarm2:4354Alarm3:4355Alarm4:4357Alarm5:4358Alarm6:4359Alarm7:4361Alarm8:4362

FAIL(NormallyON)output:4256

4353

STD

(AL2.S)AL2functionselection 4354

(AL3.S)AL3functionselection 4355

(AL4.S)AL4functionselection 4357

DOSettingParameter(E1-terminalArea)Menusymbol: (DO)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(DO1.S)DO11functionselection

SameasAL1.SSet“OFF”todisablethefunction

4358

STD

(DO2.S)DO12functionselection 4359

(DO3.S)DO13functionselection 4361

(DO4.S)DO14functionselection 4362

(DO5.S)DO15functionselection 4256

SystemSettingParameterMenusymbol: (SYS)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(R.TM)Restarttimer 0to10s. 0 STD

(FREQ)Powerfrequency AUTO,60:60Hz,50:50Hz AUTO

EASY

(QSM)Quicksettingmode OFF:Disable

ON:Enable ON

(LANG)Guidedisplaylanguage

ENG:EnglishFRA:FrenchGER:GermanSPA:Spanish

Depe-ndsonthemodelandsuffixcodes

(PASS)Passwordsetting

0(Nopassword)to65535Setting“0”means“withoutpasswordprotection.”

0

ErrorandVersionConfirmationParameter(fordisplayonly)Menusymbol: (VER)

Parameter symbol Name of Parameter Status record Display

level

(PA.ER)Parametererrorstatus

EASY

(OP.ER)Optionerrorstatus

(AD1.E)A/Dconvertererrorstatus1

(PV1.E)PVinputerrorstatus

(MCU)MCUversion

(DCU)DCUversion

(ECU1)ECU-1version(E1-terminalarea)

(PARA)Parameterversion

(H.VER)Productversion

(SER1)Serialnumber1

(SER2)Serialnumber2

ParameterDisplayLevelParameterMenusymbol: (LVL)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(LEVL)Parameterdisplaylevel

EASY:EasysettingmodeSTD:StandardsettingmodePRO:Professionalsettingmode

STD EASY

*ForProfessionalsettingmode,seeUser’sManual.

Trademarks Our product names or brand names mentioned in this manual are the trademarks or registered trademarks of Yokogawa Electric Corporation. Adobe, Acrobat, and Postscript are either registered trademarks or trademarks of Adobe Systems Incorporated. We do not use the TM or ® mark to indicate these trademarks or registered trademarks in this manual. All other product names mentioned in this manual are trademarks or registered trademarks of their respective companies.