IM 05P03D21-11EN page 1/8
Contents1. SafetyPrecautions2. ModelandSuffixCodes3. HowtoInstall4. HardwareSpecifications5. HowtoConnectWires6. TerminalWiringDiagrams
IntroductionThankyouforpurchasingtheUM33ADigitalIndicatorwithAlarms.ThisoperationguidedescribesthebasicoperationsoftheUM33A.Theguideshouldbeprovidedtotheenduserofthisproduct.Besure to read thisoperationguidebeforeusing theproduct inorder toensurecorrectoperation.Fordetailsofeachfunction,refertotheelectronicmanual.Beforeusingtheproduct,refertothetableofModelandSuffixCodestomakesurethatthedeliveredproductisconsistentwiththemodelandsuffixcodesyouordered.Alsomakesurethatthefollowingitemsareincludedinthepackage.
•DigitalIndicatorwithAlarms(themodelyouordered)............................x1•SetofBrackets........................................................................................x1•UnitLabel(L4502VZ)..............................................................................x1•TagLabel(L4502VE)(Onlywhenordered.)...........................................x1•OperationGuide(thisdocument)............................................................x4(A3size)(InstallationandWiring,InitialSettings,Operations,andParameters)
lTargetReadersThisguideisintendedforthefollowingpersonnel;• Engineersresponsibleforinstallation,wiring,andmaintenanceoftheequipment.• Personnelresponsiblefornormaldailyoperationoftheequipment.
1. Safety PrecautionsThefollowingsymbol isusedonthe instrument. It indicatesthepossibilityof injuryto theuserordamageto the instrument,andsignifies that theusermustrefer totheuser’smanual forspecial instructions.Thesamesymbol isused in theuser’smanualonpagesthattheuserneedstoreferto,togetherwiththeterm“WARNING”or“CAUTION.”
WARNING
Calls attention to actions or conditions that could cause serious or fatal injury to the user, and indicates precautions that should be taken to prevent such occurrences.
CAUTION
Calls attention to actions or conditions that could cause injury to the user or damage to the instrument or property and indicates pre-cautions that should be taken to prevent such occurrences.
AC
AC/DC
Theequipmentwhollyprotectedbydoubleinsulationorreinforcedinsulation.
Functionalgroundingterminals (Donotusethisterminalasaprotectivegroundingterminal).
NoteIdentifiesimportantinformationrequiredtooperatetheinstrument.
n Warning and Disclaimer(1)YOKOGAWAmakesnowarrantiesregardingtheproductexceptthosestatedin
theWARRANTYthatisprovidedseparately.(2)Theproductisprovidedonan"asis"basis.YOKOGAWAassumesnoliabilityto
anypersonorentity forany lossordamage,director indirect,arisingfromtheuseoftheproductorfromanyunpredictabledefectoftheproduct.
nSafety,Protection,andModificationoftheProduct(1) Inorder toprotect thesystemcontrolledbythisproductandtheproduct itself,
andtoensuresafeoperation,observethesafetyprecautionsdescribed in theuser’smanual.Useof the instrument inamannernotprescribedhereinmaycompromisetheproduct's functionsandtheprotectionfeatures inherent in thedevice.Weassumenoliabilityforsafety,orresponsibilityfortheproduct'squality,performanceorfunctionalityshouldusersfailtoobservetheseinstructionswhenoperatingtheproduct.
(2) Installationof protectionand/or safety circuitswith respect toa lightningprotector;protectiveequipmentforthesystemcontrolledbytheproductandtheproduct itself; foolproofor failsafedesignofaprocessor lineusingthesystemcontrolledbytheproductortheproductitself;and/orthedesignandinstallationofotherprotectiveandsafetycircuitsaretobeappropriatelyimplementedasthecustomerdeemsnecessary.
(3)BesuretousethesparepartsapprovedbyYOKOGAWAwhenreplacingpartsorconsumables.
(4)Thisproduct isnotdesignedormanufacturedtobeusedincriticalapplicationsthatdirectlyaffector threatenhuman lives.Suchapplications includenuclearpower equipment, devices using radioactivity, railway facilities, aviationequipment,airnavigation facilities,aviation facilities,andmedicalequipment.If soused, it is theuser’s responsibility to include in thesystemadditionalequipmentanddevicesthatensurepersonnelsafety.
(5)Modificationoftheproductisstrictlyprohibited.(6)Thisproduct is intendedtobehandledbyskilled/trainedpersonnel forelectric
devices.
WARNING
lPower Supply Ensure that the instrument’s supply voltage matches the voltage
of the power supply before turning ON the power.l Do Not Use in an Explosive Atmosphere Do not operate the instrument in locations with combustible
or explosive gases or steam. Operation in such environments constitutes an extreme safety hazard. Use of the instrument in environments with high concentrations of corrosive gas (H2S, SOX, etc.) for extended periods of time may cause a failure.
l Do Not Remove Internal Unit The internal unit should not be removed by anyone other than
YOKOGAWA's service personnel. There are dangerous high voltage parts inside. Additionally, do not replace the fuse by yourself.
l Damage to the Protective Construction Operation of the instrument in a manner not specified in the
user’s manual may damage its protective construction.
CAUTION
This instrument is an EMC class A product. In a domestic environ-ment this product may cause radio interference in which case the user needs to take adequate measures.
2. ModelandSuffixCodesn UM33A
[Style:S1]
Model SuffixcodeOptional suffixcode
Description
UM33A
DigitalIndicatorwithAlarms(providedwithretransmissionoutputor15VDClooppowersupply,2DIs,and3DOs)(Powersupply:100-240VAC)
Type1:Basic -0 Standardtype
Type2:Functions
0 None
1 1additionalDO(c-contactrelay),RS-485communication(Max.38.4kbps,2-wire/4-wire)
2 1additionalDO(c-contactrelay)
3 6additionalDOs(c-contactrelay:1point,opencollector:5points)
Type3:Opennetworks 0 None
Displaylanguage(*1)
-1 English-2 German-3 French-4 Spanish
Casecolor0 White(Lightgray)1 Black(Lightcharcoalgray)
Optionalsuffixcodes/LP 24VDClooppowersupply(*2)/DC Powersupply24VAC/DC/CT Coating(*3)
*1: English,German,French,andSpanishcanbedisplayedastheguidedisplay.*2: The/LPoptioncanbespecifiedonlywhenthecodeforType2is"0","1"or"2." Additionally,theRS-485communicationfor"1"oftheType2codeis2-wiresystem.*3: Whenthe/CToptionisspecified,theUM33Adoesnotconformtothesafetystandards(UL
andCSA)andCEmarking.
n Accessories (sold separately)Thefollowingisanaccessorysoldseparately.
• LL50AParameterSettingSoftwareModel Suffixcode Description
LL50A -00 ParameterSettingSoftware
• TerminalCover ForUM33A:ModelUTAP002• User’sManual(A4size) Note:User’sManualcanbedownloadedfromawebsite.•User’sManual(CD-ROM),Model:UTAP003 Note:Containsallmanuals.
3. How to Install
n Installation LocationThe instrument shouldbe installed in indoor locationsmeeting the followingconditions:• Instrumented panel This instrument isdesignedtobemounted inan instrumentedpanel.Mount theinstrumentinalocationwhereitsterminalswillnotinadvertentlybetouched.
• Well ventilated locations Mounttheinstrumentinwellventilatedlocationstopreventtheinstrument’sinter-naltemperaturefromrising.
However,makesurethattheterminalportionsarenotexposedtowind.Exposuretowindmaycausethetemperaturesensoraccuracytodeteriorate.Tomountmul-tipleindicators,seetheexternaldimensions/panelcutoutdimensionswhichfollow.Ifmountingotherinstrumentsadjacenttotheinstrument,complywiththesepanelcut-outdimensionstoprovidesufficientclearancebetweentheinstruments.
• Locations with little mechanical vibration Installtheinstrumentinalocationsubjecttolittlemechanicalvibration.• Horizontal location Mounttheinstrumenthorizontallyandensurethatitislevel,withnoinclinationtotherightorleft.
Front panelof the indicator
30°
Keep this anglewithin 30°
NoteIf the instrument ismovedfroma locationwith lowtemperatureand lowhumiditytoaplacewithhightemperatureandhighhumidity,or if thetemperaturechangesrapidly,condensationwill result.Moreover, in thecaseof thermocouple inputs,measurementerrorswillresult.Toavoidsuchasituation,leavetheinstrumentinthenewenvironmentunderambientconditionsformorethan1hourpriortousingit.
Donotmounttheinstrumentinthefollowinglocations:• Outdoors• Locations subject to direct sunlight or close to a heater Installtheinstrumentinalocationwithstabletemperaturesthatremainclosetoanaveragetemperatureof23°C.Donotmountitinlocationssubjecttodirectsunlightorclosetoaheater.Doingsoadverselyaffectstheinstrument.
• Locations with substantial amounts of oily fumes, steam, moisture, dust, or corrosive gases
Thepresenceofoily fumes,steam,moisture,dust,orcorrosivegasesadverselyaffectstheinstrument.Donotmounttheinstrumentinlocationssubjecttoanyofthesesubstances.
• Areasnearelectromagneticfieldgeneratingsources Donotplacemagnetsortoolsthatgeneratemagnetismneartheinstrument.Iftheinstrument isusedin locationsclosetoastrongelectromagneticfieldgeneratingsource,themagneticfieldmaycausemeasurementerrors.
• Locationswherethedisplayisdifficulttosee The instrumentusesanLCDfor thedisplayunit,andthiscanbedifficult toseefromextremelyobliqueangles.Mounttheinstrumentinalocationwhereitcanbeseenasmuchaspossiblefromthefront.
• Areasclosetoflammablearticles Absolutelydonotplacetheinstrumentdirectlyonflam-mablesurfaces. Ifsuchacircumstance isunavoidableandtheinstrumentmustbeplacedclosetoaflammableitem,provideashieldforitmadeof1.43mmthickplatedsteelor1.6mmthickunplatedsteelwithaspaceofatleast150mmbetweenitandtheinstrumentonthetop,bottom,andsides.
• Areas subject to being splashed with water
WARNING
Be sure to turn OFF the power supply to the indicator before install-ing it on the panel to avoid an electric shock.
150 mm150 mm
150 mm
150 mm150 mm150 mm
150 mm
150 mm
n Mounting the Instrument Main UnitProvideaninstrumentedpanelsteelsheetof1to10mmthickness.Afteropeningthemountingholeonthepanel,followtheproceduresbelowtoinstalltheindicator:1) Insert the indicator into theopening from the frontof thepanelso that the
terminalboardontherearisatthefarside.2) Set thebrackets inplaceontherightand leftof the indicatorasshownin the
figurebelow,thentightenthescrewsofthebrackets.Takecarenottoovertightenthem.
Direction to insert theindicatorInsert the indicatorinto the opening atthe front of the panel.
Panel
Bracket(side mounting hardware)
Bracket(side mounting hardware)
Terminal boardInsert a screwdriver into thebrackets to tighten the screws.
Appropriatetightening torque:0.25 N•m
CAUTION
• Tighten the screws with appropriate tightening torque within 0.25 N•m. Otherwise it may cause the case deformation or the bracket damage.
• Make sure that foreign materials do not enter the inside of the instrument through the case’s slit holes.
n External Dimensions and Panel Cutout DimensionsUM33A Unit: mm (approx. inch)
Normal tolerance: ±(value of JIS B 0401-1998 tolerance class IT18)/2
96 (3.78)
48 (1
.89)
Bracket
20 (
0.79
)65
(2.5
6)11
(0.4
3)
Terminal cover
Bracket
94.6 (3.72)91.6 (3.61)
105.2 (4.14)
1 to 10 (0.04 to 0.39)
(panel thickness)(25) (0.98)
(53)
(2.09)
• General mounting145 (5.71)min.
+0.030(3.62 )
+0.6045
+0.020(1.77 ) +0.8
092
70 (2.76) min.
OperationGuide
IM 05P03D21-11EN
UM33ADigital Indicator with AlarmsOperation Guide
This operation guide describes installation, wiring, and other tasks required to make the indicator ready for operation.
1st Edition : Aug. 2010
Installation and Wiring
n Waste Electrical and Electronic Equipment (WEEE), Directive 2002/96/EC
This isanexplanationofhowtodisposeof thisproductbasedonWasteElectricalandElectronicEquipment(WEEE),Directive2002/96/EC.ThisdirectiveisonlyvalidintheEU.
MarkingThisproduct complieswith theWEEEDirective (2002/96/EC)markingrequirement.Thismarking indicates thatyoumustnotdiscard thiselectrical/electronicproductindomestichouseholdwaste.
Product CategoryWith reference to theequipment types in theWEEEdirectiveAnnex1, thisproduct is classifiedasa “MonitoringandControl instrumentation” product.Donotdisposeindomestichouseholdwaste.Whendisposingproducts intheEU,contactyourlocalYokogawaEuropeB.V.office.
www.yokogawa.com/ns
YOKOGAWA ELECTRIC CORPORATIONNetwork Solutions Business Division
2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 JAPANYOKOGAWA CORPORATION OF AMERICA
Head office and for product sales2 Dart Road, Newnan, Georgia 30265, USA
YOKOGAWA EUROPE B.V.Headquarters
Euroweg 2, 3825 HD Amersfoort, THE NETHERLANDS
All Rights Reserved, Copyright © 2010 Yokogawa Electric Corporation
IM 05P03D21-11EN page 2/8
4. HardwareSpecifications
WARNING
This instrument is for Measurement Category I (CAT.I). Do not use it for measurements in locations falling under Measurement Catego-ries II, III, and IV.
Internal Wiring
Outlet
Entrance IVCable
III TI
II
Category Measurement category Description Remarks
I CAT.I FormeasurementsperformedoncircuitsnotdirectlyconnectedtoMAINS. -
II CAT.II Formeasurementsperformedoncircuitsdi-rectlyconnectedtothelow-voltageinstallation.
Appliances,portableequip-ment,etc.
III CAT.III Formeasurementsperformedinthebuildinginstallation.
Distributionboard,circuitbreaker,etc.
IV CAT.IV Formeasurementsperformedatthesourceofthelow-voltageinstallation.
Overheadwire,cablesystems,etc.
n InputSpecifications
UniversalInput(Equippedasstandard)• Numberofinputs:1• Inputtype,instrumentrange,andmeasurementaccuracy:Seethetablebelow,
Input Type Instrument Range
AccuracyºC ºF
Thermo-couple
K-270.0to1370.0ºC -450.0to2500.0ºF ±0.1%ofinstrumentrange±1digitfor
0°Cormore±0.2%ofinstrumentrange±1digitforlessthan0°C±2%ofinstrumentrange±1digitforlessthan-200.0°CofthermocoupleK±1%ofinstrumentrange±1digitforlessthan-200.0°CofthermocoupleT
-270.0to1000.0ºC -450.0to2300.0ºF-200.0to500.0ºC -200.0to1000.0ºF
J -200.0to1200.0ºC -300.0to2300.0ºF
T-270.0to400.0ºC -450.0to750.0ºF
0.0to400.0ºC -200.0to750.0ºF
B 0.0to1800.0ºC 32to3300ºF
±0.15%ofinstrumentrange±1digitfor400°Cormore±5%ofinstrumentrange±1digitforlessthan400°C
S 0.0to1700.0ºC 32to3100ºF±0.15%ofinstrumentrange±1digit
R 0.0to1700.0ºC 32to3100ºF
N -200.0to1300.0ºC -300.0to2400.0ºF±0.1%ofinstrumentrange±1digit±0.25%ofinstrumentrange±1digitforlessthan0°C
E -270.0to1000.0ºC -450.0to1800.0ºF ±0.1%ofinstrumentrange±1digitfor0°Cormore±0.2%ofinstrumentrange±1digitforlessthan0°C±1.5%ofinstrumentrange±1digitforlessthan-200.0°CofthermocoupleE.
L -200.0to900.0ºC -300.0to1600.0ºF
U-200.0to400.0ºC -300.0to750.0ºF
0.0to400.0ºC -200.0to1000.0ºF
W 0.0to2300.0ºC 32to4200ºF ±0.2%ofinstrumentrange±1digit(Note2)
Platinel2 0.0to1390.0ºC 32.0to2500.0ºF ±0.1%ofinstrumentrange±1digit
PR20-40 0.0to1900.0ºC 32to3400ºF
±0.5%ofinstrumentrange±1digitfor800°CormoreAccuracyisnotguaranteedforlessthan800°C.
W97Re3-W75Re25 0.0to2000.0ºC 32to3600ºF ±0.2%ofinstrumentrange±1digit
RTD
JPt100-200.0to500.0ºC -300.0to1000.0ºF ±0.1%ofinstrumentrange±1digit
(Note1)-150.00to150.00ºC -200.0to300.0ºF ±0.1%ofinstrumentrange±1digit
Pt100-200.0to850.0ºC -300.0to1560.0ºF ±0.1%ofinstrumentrange±1digit
(Note1)-200.0to500.0ºC -300.0to1000.0ºF-150.00to150.00ºC -200.0to300.0ºF ±0.1%ofinstrumentrange±1digit
Standardsignal0.400to2.000V
±0.1%ofinstrumentrange±1digit
1.000to5.000V4.00to20.00mA
DCvoltage/current
0.000to2.000V0.00to10.00V0.00to20.00mA-10.00to20.00mV0.0to100.0mV
Theaccuracyisthatinthestandardoperatingconditions:23±2°C,55±10%RH,andpowerfrequencyat50/60Hz.
Note1: ±0.3°C±1digitintherangebetween0and100°C,±0.5°C±1digitintherange between-100and200°C.
Note2: W:W-5%Re/W-26%Re(HoskinsMfg.Co.).ASTME988
•Inputsamplingperiod:50,100,200ms•Burnoutdetection: FunctionsatTC,RTD,andstandardsignal. Upscale,downscale,andoffcanbespecified. Forstandardsignal,burnoutisdeterminedtohaveoccurredifitis0.1Vor0.4 mAorless.
•Inputbiascurrent:0.05µA(forTCorRTD)•Measuredcurrent(RTD):About0.16mA•Inputresistance: TCormVinput:1MΩormore Vinput:About1MΩ mAinput:About250Ω
•Allowablesignalsourceresistance: TCormVinput:250Ωorless Effectsofsignalsourceresistance:0.1µV/Ωorless DCvoltageinput:2kΩorless Effectsofsignalsourceresistance:About0.01%/100Ω• Allowablewiringresistance: RTDinput:Max.150Ω/wire(Theconductorresistancebetweenthethreewires shallbeequal.)
Wiringresistanceeffect:±0.1ºC/10Ω• Allowableinputvoltage/current: TC,mV,mAandRTDinput:±10VDC Vinput:±20VDC mAinput:±40mA• Noiserejectionratio: Normalmode:40dBormore(at50/60Hz) Commonmode:120dBormore(at50/60Hz) For100-240VAC, thepower frequencycanbesetmanually.Automatic detectionisalsoavailable.
For24VAC/DC,thepowerfrequencycanbesetmanually.• Referencejunctioncompensationerror: ±1.0ºC(15to35ºC) ±1.5ºC(-10to15ºCand35to50ºC)• Applicablestandards:JIS/IEC/DIN(ITS-90)forTCandRTD
nStepResponseTimeSpecificationsWithin500ms(whentheinputsamplingperiodis50msor100ms)Within1s(whentheinputsamplingperiodis200ms)(63%ofanalogoutputresponsetimewhenastepchangeof10to90%ofinputspanisapplied)
nRelayContactOutputSpecifications• Contacttypeandnumberofoutputs: Alarm-1to-3output:contactpoint1a;3points(commonisindependent) Alarm-4output:contactpoint1c;1point• Contactrating: Contactpoint1a(Alarm-1to-3output):240VAC,1Aor30VDC,1A(resistanceload) Contactpoint1c(Alarm-4output):250VAC,3Aor30VDC,3A(resistanceload)• Use:Alarmoutput,FAILoutput,etc.Note:Thiscannotbeusedforasmallloadof10mAorless.
n RetransmissionOutputSpecifications• Numberofoutputs:Retransmissionoutput;1,sharedwith15VDClooppower
supply• Currentoutput:4to20mADCor0to20mADC/loadresistanceof600Ωorless• Currentoutputaccuracy:±0.1%ofspan(±5%ofspanfor1mAorless) Theaccuracyisthatinthestandardoperatingconditions:23±2°C,55±10%RH,andpowerfrequencyat50/60Hz
n 15VDCLoopPowerSupplySpecifications(Sharedwithretransmissionoutput.)• Powersupply:14.5to18.0VDC• Maximumsupplycurrent:About21mA(withshort-circuitcurrentlimitingcircuit)
nContactInputSpecifications• Numberofinputs:2points• Inputtype:No-voltagecontactinputortransistorcontactinput• Inputcontactrating:12VDC,10mAormore Useacontactwithaminimumon-currentof1mAormore.• ON/OFFdetection: No-voltagecontactinput: Contactresistanceof1kΩorlessisdeterminedas“ON”andcontact resistanceof50kΩormoreas“OFF.” Transistorcontactinput: Inputvoltageof2Vorlessisdeterminedas“ON”andleakagecurrentmust notexceed100µAwhen“OFF.”• Minimumstatusdetectionholdtime:Inputsamplingperiod+50ms• Use:Eventinput
nTransistorContactOutputSpecifications• Numberofoutputs:SeethetableofModelandSuffixCodes.• Outputtype:Opencollector(SINKcurrent)• Outputcontactrating:Max.24VDC,50mA• Outputtimeresolution:Min.50ms• Use:Alarmoutput,FAILoutput,etc.
n24VDCLoopPowerSupplySpecifications• Use:Powerissuppliedtoa2-wiretransmitter.• Powersupply:21.6to28.0VDC• Ratedcurrent:4to20mADC• Maximumsupplycurrent:About30mA(withshort-circuitcurrentlimitingcircuit.)
SafetyandEMCStandards• Safety:Compliantwith IEC/EN61010-1 (CE),approvedbyCAN/CSAC22.2No.61010-1(CSA).UL61010-1ispendingapproval.
Installationcategory:CAT.IIPollutiondegree:2 Measurementcategory:I(CAT.I) Ratedmeasurementinputvoltage:Max.10VDC Ratedtransientovervoltage:1500V(Note)Note:ThisisareferencesafetystandardvalueforMeasurementCategoryIofIEC/EN/CSA/
UL61010-1.Thisvalueisnotnecessarilyaguaranteeofinstrumentperformance.
• EMCConformitystandards: CEmarking EN61326-1ClassA,Table2(Foruseinindustriallocations) EN61326-2-3 EN55011ClassA,Group1 EN61000-3-2ClassA EN61000-3-3 C-tickmark EN55011ClassA,Group1 Theinstrumentcontinuestooperateatameasurementaccuracyofwithin±20%oftherangeduringtesting.
Construction,Installation,andWiring• Dust-proofanddrip-proof:IP56(forfrontpanel)• Material:Polycarbonate(Flameretardancy:UL94V-0)• Casecolor:White(Lightgray)orBlack(Lightcharcoalgray)• Weight:0.5kgorless• Externaldimensions(mm):96(W)×48(H)×65(depthfromthepanelface) (Depthexcepttheprojectionontherearpanel)• Installation:Directpanelmounting;mountingbracket,oneeachforrightand leftmounting
• Panelcutoutdimensions(mm):92+0.8/0(W)×45+0.6/0(H)• Mountingattitude:Upto30degreesabovethehorizontal.Nodownwardtitlingallowed.• Wiring:M3screwterminalwithsquarewasher(forsignalwiringandpowerwiring)
PowerSupplySpecificationsandIsolation• Powersupply: Ratedvoltage:100-240VAC(+10%/-15%),50/60Hz 24VAC/DC(+10%/-15%)(for/DCoption)• Powerconsumption:15VA(DC:7VA,AC:11VAif/DCoptionisspecified)• Databackup:Nonvolatilememory• Powerholduptime:20ms(for100VACdrive)• Withstandingvoltage Betweenprimaryterminalsandsecondaryterminals:2300VACfor1minute Betweenprimaryterminals:1500VACfor1minute Betweensecondaryterminals:500VACfor1minute (Primaryterminals:Power*andrelayoutputterminals;Secondaryterminals: AnalogI/Osignalterminals,contactinputterminals,communicationterminals andfunctionalgroundingterminals.)
*:Powerterminalsfor24VAC/DCmodelsarethesecondaryterminals.• Insulationresistance:Betweenpowersupply terminalsandagroundingterminal20MΩormoreat500VDC
• Isolationspecifications
PV (universal ) input terminals
Alarm-1 relay (contact point a) output terminals
Alarm-2 relay (contact point a) output terminals
Alarm-3 relay (contact point a) output terminals
Contact input terminals (all)RS-485 communication terminals
24 V DC loop power supply terminals
Contact output (transistor) terminals
Retransmission (analog) output terminals(not isolated between the analog output terminals)
Internal
circuits
Power
supply
The circuits divided by lines are insulated mutually.
Alarm-4 relay (contact point c) output terminals
EnvironmentalConditions
Normal Operating Conditions• Ambienttemperature:-10to50ºC• Ambienthumidity:20to90%RH(nocondensationallowed)• Magneticfield:400A/morless• Continuousvibrationat5to9Hz:Halfamplitudeof1.5mmorless,1oct/minfor90minuteseachinthethreeaxisdirections
Continuousvibrationat9to150Hz:4.9m/s2orless,1oct/minfor90minuteseachinthethreeaxisdirections
• Short-periodvibration:14.7m/s2,15secondsorless• Shock:98m/s2orless,11ms• Altitude:2000morlessabovesealevel
• Warm-uptime:30minutesormoreafterthepoweristurnedon• Startuptime:Within10seconds *: TheLCD(aliquidcrystaldisplay)isusedforadisplayportionofthisproduct.
TheLCDhasacharacteristicthatthedisplayactionbecomeslateatthelow temperature.
Transportation and Storage Conditions• Temperature:-25to70ºC• Temperaturechangerate:20ºC/horless• Humidity:5to95%RH(nocondensationallowed)
Effects of Operating Conditions• Effectofambienttemperature: VoltageorTCinput:±1µV/ºCor±0.01%ofF.S./ºC,whicheverislarger Currentinput:±0.01%ofF.S./ºC RTDinput:±0.05ºC/ºC(ambienttemperature)orless Analogoutput:±0.02%ofF.S./ºCorless• Effectofpowersupplyvoltagefluctuation Analoginput:±0.05%ofF.S.orless Analogoutput:±0.05%ofF.S.orless (Eachwithinratedvoltagerange)
IM 05P03D21-11EN page 3/8
5. How to Connect Wires
WARNING
• Wiring work must be carried out by a person with basic electrical knowledge and practical experience.
• Be sure to turn OFF the power supply to the indicator before wiring to avoid an electric shock. Use a tester or similar device to ensure that no power is being supplied to a cable to be connected.
• As a safety measure, always install a circuit breaker (an IEC 60947-compatible product, 5 A, 100 V or 220 V AC) in an easily accessible location near the instrument. Moreover, provide indication that the switch is a device for turning off the power to the instrument.
• Install the power cable keeping a distance of more than 1 cm from other signal wires.
• The power cable is required to meet the IEC standards concerned or the requirements of the area in which the instrument is being installed.
• Wiring should be installed to conform to NEC (National Electrical Code: ANSI/NFPA-70) or the wiring construction standards in countries or regions where wiring will be installed.
• For the alarm relay output and power terminal connections, use heat-resistant cables.
• Since the insulation provided to each relay output terminal is Functional insulation, provide Reinforced insulation to the external of the device as necessary. (Refer to the drawing below.)
This product
Functionalinsulation
A safety voltage circuit
A safety voltage circuit
This product
Reinforced insulation
Reinforced insulation
Functionalinsulation
A hazardous voltage circuit
A hazardous voltage circuit
A safety voltage circuit
A safety voltage circuit
This product
Reinforced insulation
Reinforced insulation
Functionalinsulation
A hazardous voltage circuit
A hazardous voltage circuit
A hazardous voltage circuit
A hazardous voltage circuit
CAUTION
• Provide electricity from a single-phase power supply. If the power is noisy, install an isolation transformer on the primary side, and use a line filter on the secondary side. When measures against noise are taken, do not install the primary and secondary power cables close to each other.
• If there is a risk of external lightning surges, use a lightning arrester etc.
• For TC input, use shielded compensating lead wires for wiring. For RTD input, use shielded wires that have low conductor resistance and cause no significant differences in resistance between the three wires.
• Since the alarm output relay has a life span (resistance load of 100,000 times), use the auxiliary relay to perform ON/OFF control.
• The use of inductance (L) loads such as auxiliary relays, motors and solenoid valves causes malfunction or relay failure; always insert a CR filter for use with alternating current or a diode for use with direct current, as a spark-removal surge suppression circuit, into the line in parallel with the load.
• After completing the wiring, the terminal cover is recommended to use for the instrument.
RecommendedCrimp-onTerminalLugs
(A)
(F)
(ød)
5.5 3.3
Recommendedtighteningtorque:0.6N·m Applicablewiresize:Powersupplywiring1.25mm2ormoreApplicable terminal lug Applicable wire size mm2 (AWG#) (φd) (A) (F)M3 0.25to1.65(22to16) 3.3 5.5 4.2
CableSpecificationsandRecommendedCablesPurpose Name and Manufacturer
Powersupply,relaycontactoutputs 600VGradeheat-resistantPVCinsulatedwires,JISC3317(HIV),0.9to2.0mm2
Thermocouple Shieldedcompensatingleadwires,JISC1610RTD Shieldedwires(three/fourconductors),UL2482(HitachiCable)Othersignals(otherthancontactinput/output) ShieldedwiresOthersignals(contactinput/output) UnshieldedwiresRS-485communication Shieldedwires
DC Relay Wiring
R
External DC power supplyRelayO.CUM33A
UM’s contact
Diode(Mount it directlyto the relay coilterminal (socket).)
Relay(Use one with a relay coil rating
less than the UM’s contact rating.)
AC Relay Wiring
UM33A
R
UM’s contact CR filter(Mount it directlyto the relay coilterminal (socket).)
External AC power supply
Relay(Use one with a relay coilrating less than the UM’s
contact rating.)
6. Terminal Wiring Diagrams
CAUTION
• Do not use an unassigned terminal as the relay terminal. Do not use a 100-240 V AC power supply for the 24 V AC/DC
model; otherwise, the instrument will malfunction.
UM33A
301-306
201-212
101-112
306 305 304 303 302 301
212 211 210 208 207 204 203
112 111 110 109 106 105 104108 107 103
202 201
102 101
E1-terminal area
PVPV input (Equippedas standard)
TC input
202
203
RTD input
A
B
b
201
202
203
Voltage (mV, V) input
202
203
Current (mA) input
203
204
Factory default: PV input type is undefined.
RETRetransmission output (Equipped as standard)Retransmission output
4-20 mA DC or0-20 mA DC
Default: 4-20 mA DC
Default: PV retransmission
Load resistance 600 Ω or less
207
208
15 V DC loop power supply
14.5-18.0 V DC(Max. 21 mA DC)
207
208
Can be used for 15 V DC loop power supply when not used for retransmission output.
ALM (Equipped as standard)Contact output
External contact output (relay)
AL3
AL2
AL1
Relay contact rating: 240 V AC, 1 A 30 V DC, 1 A (resistance load)
Alarm-3 output(PV high limit)
Alarm-2 output( PV low limit)
Alarm-1 outputPV high limit
Common
Common
Common
UM104
105
106
107
108
109
ALM4(Suffix code: Type 2=1, 2 or 3)
Contact output
Contact rating: 250 V AC, 3 A 30 V DC, 3 A (resistance load)
AL4
(24 V AC/DC power supply: Optional suffix code /DC)
Power supply
Allowable range: 100-240 V AC (±10%) (free v(oltage) 50/60 Hz shared
100-240 V AC power supply
N
L
110
111
112
24 V AC/DC power supply
110
111
112
N
L
RS-485
RSB(+)
RSA(-)
SG
RS-485 communication/24 V DC loop power supply24 V DC loop power supply
21.6-28.0 V DC(Max. 30 mA DC)
301
302
303
305
306
RS485/LPS24(Suffix code: Type 2=1 and with optional suffix code /LP)
24 V DC loop power supply
21.6-28.0 V DC(Max. 30 mA DC)
24 V DC loop power supply
(Suffix code: Type 2=0 or 2 and with optional suffix code /LP)
305
306
LPS24RS-485
SDB(+)
SDA(-)
RDB(+)
RDA(-)
SG
RS-485 communication
301
302
303
304
305
RS485(Suffix code: Type 2=1 and without optional suffix code /LP)
(Suffix code: Type 2=3)Contact outputExternal contact output
DO12
DO11
DO13
DO14
DO15
COMCommon
UM301
302
303
304
305
306
DO
Transistor contact rating: 24 V DC, 50 mA
The function of each contact output can be changed.
Alarm-6 output( PV low limit)
Alarm-5 output(PV high limit)
Alarm-8 output( PV low limit)
FAIL
Alarm-7 output(PV high limit)
DI (Equipped as standard)Contact input
Contact rating: 12 V DC, 10 mA or more
External contact input
DI2
DI1
COMCommon
DI2
DI1
COM
+5V
+5V
No-voltagecontact
Transistor contactUM UM
210
211
212
210
211
212
The function of each contact input can be changed.
ON: PV peak and bottom values reset
OFF → ON: Latch release
101
102
Relay contact output
103
NC
NO
COM
Alarm-4 output
( PV low limit)
AL4
IM 05P03D21-11EN page 4/8
IM 05P03D21-11EN page 5/8
Contents1. NamesandFunctionsofDisplayParts2. QuickSettingFunction(SettingofInputandOutput)3. SettingAlarmType
1. Names and Functions of Display Parts
(1)
(2)
(3)(4)
(5)
(11)
(8)(6)(7)
(13)
(12)
(10)
(9)
No.infigure Name Description
(1) PVdisplay(whiteorred)
DisplaysPV.Displaysanerrorcodeifanerroroccurs.DisplaysthescrollingguideintheMenuDisplayandParameterSettingDisplaywhentheguidedisplayON/OFFissettoON.
(2) Groupdisplay(green) Displaysagroupnumber.(3) Symboldisplay(orange) Displaysaparametersymbol.(4) Datadisplay(orange) Displaysaparametersetpointandmenusymbol.
(5) Eventindicator(orange)
Litwhenthealarms1to8occur.Eventdisplaysotherthanalarmscanbesetbytheparameter.
(6) Keynavigationindica-tor(green)
LitorblinkswhentheUp/DownorLeft/Rightarrowkeyoperationispossible.
(7) Parameterdisplaylevelindicator(green)
Displaysthesettingconditionsoftheparameterdisplaylevelfunc-tion.
Parameter display level EASY PROEasysettingmode Lit UnlitStandardsettingmode Unlit UnlitProfessionalsettingmode Unlit Lit
(8) Securityindicator(red) Litifapasswordisset.Thesetupparametersettingsarelocked.
No.infigure Name Description
(9) DISPkey
UsedtoswitchtheOperationDisplays.PressthekeyintheOperationDisplaytoswitchtheprovidedSELECTDisplays.PressthekeyintheMenuDisplayorParameterSettingDisplaytoreturntotheOperationDisplay.
(10) PARAkey
Holddownthekeyfor3secondstomovetotheOperationParameterSettingDisplay.HolddownthekeyandtheLeftarrowkeysimultaneouslyfor3secondstomovetotheSetupParameterSettingDisplay.PressthekeyintheParameterSettingDisplaytoreturntotheMenuDisplay.Pressthekeyoncetocanceltheparameterset-ting(setpointisblinking).
(11)SET/ENTERkeyUp/Down/Left/Rightarrowkeys
SET/ENTERkeyPressthekeyintheMenuDisplaytomovetotheParameterSettingDisplayoftheMenu.PressthekeyintheParameterSettingDisplaytotransfertotheparametersettingmode(setpointisblinking),andtheparametercanbechanged.Pressthekeyduringparametersettingmodetoregisterthesetpoint.Up/Down/Left/RightarrowkeysPresstheLeft/RightarrowkeysintheMenuDisplaytoswitchtheDisplays.PresstheUp/DownarrowkeysintheParameterSettingDisplaytoswitchtheDisplays.PresstheUp/Downarrowkeysduringparametersettingmode(setpointisblinking)tochangeasetpoint.PresstheLeft/Rightarrowkeysduringparametersettingmode(setpointisblinking)tomovebetweendigitsaccordingtotheparameter.
(12) Light-loaderinterfaceItisthecommunicationinterfacefortheadaptercableusedwhensettingandstoringparametersfromaPC.TheLL50AParameterSettingSoftware(soldseparately)isrequired.
(13) Userfunctionkeys Fnkey.Theusercanassignafunctiontothekey.Thefunctionissetbytheparameter.
Note: Thecommunicationconnector(maintenanceport)forLL50AParameterSettingSoftwareisonthesideoftheunit.
2. Quick Setting Function (Setting of Input and Output)TheQuicksettingfunctionisafunctiontoeasilysetthebasicfunctionoftheindicator.TurnontheindicatortostarttheQuicksettingfunction.Thisfunctionallowsyoutoeasilysettheinput,andquicklystartthealarmaction.Theitems(parameters)tobesetbyQuicksettingfunctionareasfollows.(1)Inputfunction(PVinputtype,range,scale(atvoltageinput),etc.)
Afterturningontheindicator,firstdecidewhetherornottousetheQuicksettingfunction.
Operation in Initial Display· PresstheSET/ENTERkeywhileYESisdisplayedtostarttheQuicksettingfunction.· IfyouchangeYEStoNOandpresstheSET/ENTERkey,OperationDisplaywillappearwithoutstartingtheQuicksettingfunction.
Operation for Setting· Toselecttheparametersettingdisplayedastheinitialvalue,presstheDownarrowkeytomovetothenextparameter.
· Tochangeandset theparametersetting,presstheSET/ENTERkeytostart thesetpointblinking.Theblinkingstateallowsyoutomakechanges(settingmode).UsetheUp/Down/Left/Rightarrowkeystochangethesetpoint.PresstheSET/EN-TERkeytoregisterthesetting.
MakingSettingsUsingQuickSettingFunctionExample: Setting to thermocouple type K (range of 0.0 to 500.00C).Forthedetailedprocedureandswitchingofdisplays,see"FlowofQuickSettingFunction"below.Fortheparameterstoset,seethenextpage.
(1)PresstheSET/ENTERkeywhileYESforQSM(Quicksettingmode)isdisplayed.(2)SetthePVinputtypeparameter(IN)toK1(-270.0to1370.00C).(3)SetthePVinputunitparameter(UNIT)toC(DegreeCelsius).(4)SetthemaximumvalueofPVinputrangeparameter(RH)to500.0.(5)SettheminimumvalueofPVinputrangeparameter(RL)to0.0.(6)Finally,EXITisdisplayed.ChangeNOtoYESandpresstheSET/ENTERkeyto
completethesetup.OperationDisplayappears.
FlowofQuickSettingFunctionInQuicksettingmode,theparameterguideappearsonPVdisplay.Thisguidecanbeturnedon/offwiththeFnkey.
8
1.
2.
3.
4.
5.
6.
8.
9.
10.
11.
7.
8
8
8
8
Power-on
Quick setting starts
The PV input type parameter (IN) is displayed.Initial value: OFF
OFF blinks.Blinking allows you to change the setting.
K1 is displayed.
K1 has been registered.
The last digit of the upper limit value blinks.
The parameter RH (maximum value of PV input range) has been changed to 500.0.
The setpoint for the parameter RH has been registered.
The PV input unit parameter (UNIT) is displayed.Initial value: C (Degree Celsius)
Select NO with the Down arrow key and press the SET/ENTER key.
Press the SET/ENTER key while YES is displayed to start the Quick setting.
[YES][NO]
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the Up arrow key.
Select NO to return to the Operation Display.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
The upper limit value of the setting range is displayed for the parameter RH (maximum value of PV input range).
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
Finally, EXIT is displayed.Press the SET/ENTER key to swtich to the setting mode.Change NO to YES and press the SET/ENTER key to complete the setup of the basic function.Operation Display appears.The Quick setting function continues in the NO state.
Operation Display
Displays the measured input value (PV).
Follow the same procedure to set RL.
OperationGuide
Initial Settings
UM33ADigital Indicator with AlarmsOperation Guide
This operation guide describes basic settings and operations of the UM33A.For details of each function, see the electronic manual.The scrolling guide is displayed on PV display in the Parameter Setting Display.This guide can be turned on/off with the Fn key.
3. Setting Alarm TypeThefollowingoperatingprocedureshowsanexampleofchangingthealarm-1type(factorydefault:PVhighlimitalarm)toPVlowlimitalarm.
1.
2.
3.
4.
5.
6.
8
AL menu is displayed.
ALRM menu is displayed.
Show the Operation Display.
Hold down the key for 3 seconds.
Press the Right arrow key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
The parameter AL1 (alarm-1 type) is displayed.
The last digit of the setpoint blinks.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
The alarm-1 type setpoint 02 (PV low limit) is registered.After the setup is completed, press the DISP key once to return to the Operation Display.
To change the alarm type, change the last 2 digits of the 5-digit value.
Stand-by action and excitation are turned on or off by selecting 1 or 0. (See “ Setting Display of Alarm Type.”)
For the latch action, see User ’s Manual.
Symbol Stand-by actionEnergized/De-energizedLatch action
- -No alarm (00)
Alarm Action (De-energized)
PV high limit (01)
PV low limit (02)
PV velocity (29)
Fault diagnosis alarm (30)
FAIL (31)
Alarm Type (Alarm Setpoint) Alarm Action (Energized)
Hysteresis
Alarm setpoint PV
Closed(lit)
Open(unlit)
Alarm setpoint
Hysteresis
PV
Closed(lit)
Open(unlit)
Hysteresis
Alarm setpoint PV
Open(lit)
Closed(unlit)
Alarm setpoint
Hysteresis
PV
Open(lit)
Closed(unlit)
Burnout of PV input, ADC failure, RJC error.
For the factory default, the contact output is turned ON in normal operation, OFF at the time of FAIL. Alarm output: OFF
Note 1: “Open/closed” shows status of relay contact, and “lit/unlit” shows status of EV (event) lamp.
Setting Display of Alarm Type Stand-by Action
Energized (0) / De-energized (1)
Alarm typeWithout (0) or With (1) Stand-by action
Latch action (0/1/2/3/4)See User’s Manual.
PV low limit alarm setpoint
Treatedas normal
ºC
Power-on Time
The alarm output does not turn onin this region even if the PV valuleis below PV low limit alarm setpoint.
Normal Abnormal
The alarm outputturns on.
8
1.
2.
3.
4.
5.
6.
8.
9.
10.
11.
7.
8
8
8
8
Power-on
Quick setting starts
The PV input type parameter (IN) is displayed.Initial value: OFF
OFF blinks.Blinking allows you to change the setting.
K1 is displayed.
K1 has been registered.
The last digit of the upper limit value blinks.
The parameter RH (maximum value of PV input range) has been changed to 500.0.
The setpoint for the parameter RH has been registered.
The PV input unit parameter (UNIT) is displayed.Initial value: C (Degree Celsius)
Select NO with the Down arrow key and press the SET/ENTER key.
Press the SET/ENTER key while YES is displayed to start the Quick setting.
[YES][NO]
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the Up arrow key.
Select NO to return to the Operation Display.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
The upper limit value of the setting range is displayed for the parameter RH (maximum value of PV input range).
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
Finally, EXIT is displayed.Press the SET/ENTER key to swtich to the setting mode.Change NO to YES and press the SET/ENTER key to complete the setup of the basic function.Operation Display appears.The Quick setting function continues in the NO state.
Operation Display
Displays the measured input value (PV).
Follow the same procedure to set RL.
ParameterstobesetInput Function
Parameter Symbol Name of Parameter Setting Range
IN PVinputtype
OFF:DisableK1:-270.0to1370.00C/-450.0to2500.00FK2:-270.0to1000.00C/-450.0to2300.00FK3:-200.0to500.00C/-200.0to1000.00FJ:-200.0to1200.00C/-300.0to2300.00FT1:-270.0to400.00C/-450.0to750.00FT2:0.0to400.00C/-200.0to750.00FB:0.0to1800.00C/32to33000FS:0.0to1700.00C/32to31000FR:0.0to1700.00C/32to31000FN:-200.0to1300.00C/-300.0to2400.00FE:-270.0to1000.00C/-450.0to1800.00FL:-200.0to900.00C/-300.0to1600.00FU1:-200.0to400.00C/-300.0to750.00FU2:0.0to400.00C/-200.0to1000.00FW:0.0to2300.00C/32to42000FPL2:0.0to1390.00C/32.0to2500.00FP2040:0.0to1900.00C/32to34000FWRE:0.0to2000.00C/32to36000FJPT1:-200.0to500.00C/-300.0to1000.00FJPT2:-150.00to150.000C/-200.0to300.00FPT1:-200.0to850.00C/-300.0to1560.00FPT2:-200.0to500.00C/-300.0to1000.00FPT3:-150.00to150.000C/-200.0to300.00F0.4-2V:0.400to2.000V1-5V:1.000to5.000V4-20:4.00to20.00mA0-2V:0.000to2.000V0-10V:0.00to10.00V0-20:0.00to20.00mA-1020:-10.00to20.00mV0-100:0.0to100.0mV
UNIT PVinputunit -:Nounit,C:DegreeCelsius-:Nounit,--:Nounit,---:Nounit,F:DegreeFahrenheit
RH MaximumvalueofPVinputrange
Dependsontheinputtype.-Fortemperatureinput-Setthetemperaturerangethatisactuallydisplayed.(RL<RH)-Forvoltage/currentinput-Settherangeofavoltage/currentsignalthatisapplied.Thescaleacrosswhichthevoltage/currentsignalisactuallydisplayedshouldbesetusingthemaximumvalueofinputscale(SH)andminimumvalueofinputscale(SL).(Inputisalways0%whenRL=RH.)
RL MinimumvalueofPVinputrange
SDPPVinputscaledecimalpointposition
0:Nodecimalplace1:Onedecimalplace2:Twodecimalplaces
3:Threedecimalplaces4:Fourdecimalplaces
SH MaximumvalueofPVinputscale
-19999to30000,(SL<SH),|SH-SL|≤30000SL Minimumvalueof
PVinputscale
Note1:SDP,SH,andSLaredisplayedonlyforvoltage/currentinput.Note2:W:W-5%Re/W-26%Re(HoskinsMfg.Co.),ASTME988
IM 05P03D21-11EN page 6/8
Contents1. Monitoring-purposeOperationDisplaysAvailableduringOperation2. SettingAlarmSetpoint3. Troubleshooting
1. Monitoring-purpose Operation Displays Available during Operation
OperationDisplaySwitchingDiagram
8 8
PV Display SELECT Displays (1 to 5)
PresstheDISPkeytoshowSELECTDisplay-1to-5conditionally.FortheregistrationoftheSELECTDisplays,seeUser’sManual.
OperationGuide
UM33ADigital Indicator with AlarmsOperation Guide
This operation guide describes key entries for operating the UM33A.For operations using external contact inputs, see “DI” of “6. Terminal Wiring Diagrams” in “Installation and Wiring.” If you cannot remember how to carry out an operation during setting, press the DISP key once. This brings you to the display (Operation Display) that appears at power-on. The scrolling guide is displayed on PV display in the Parameter Setting Display. This guide can be turned on/off with the Fn key.
Operations
2. Setting Alarm SetpointThefollowingoperatingprocedureshowsanexampleofsettingthealarm-1setpointto180.0.Beforesettingthealarmsetpoint,checkthealarmtype.Tochange thealarmtype,see“3.SettingAlarmType” in “Initialsettings”of thismanual.
1.
2.
3.
4.
5.
6.
8
8
AL menu is displayed.
Display the parameter that need to be changed.
Blinks during the change.
Show the Operation Display.
Hold down the PARA key for 3 seconds.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
The parameter A1 is displayed.A1 to A8 represent the alarm-1 to -8 setpoints.
Each parameter can be changed in the Parameter Setting Displays of alarms using Up/Down arrow keys .
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
The setpoint has been registered.After the setup is completed, press the DISP key once to return to the Operation Display.
3. TroubleshootingTroubleshootingFlowIftheOperationDisplaydoesnotappearafterturningontheindicator’spower,checktheproceduresinthefollowingflowchart.Ifaproblemappearstobecomplicated,contactoursalesrepresentatives.
RemediesifPowerFailureOccursduringOperations• Instantaneous power failure within 20 ms. Apowerfailureisnotdetected.Normaloperationcontinues.• Power failure for less than about 5 seconds, or for about 5 seconds or more. Affectsthe"settings"and"operationstatus." Fordetails,seeUser'sManual.
NOTEWrite down the settingsofparameters fora repairrequest.
Is the indicatordefective?
Contact us for repair. Problem solved.
No communicationcapability
Completelyinactive?
Yes
Yes
Yes
No
No
No
Keyoperationfailure?
Yes
No
Yes
Check wiring of thepower terminals.
Check the key locksetting.
Displayfailure?
*Yes
No
Turn off power, andthen turn it on again.
I/O signalfailure?
Yes
No
Check the supply voltage.
Check the specifications and polarity
of connected devices .
Check the communication-related parameters.
Check the specificationsof communication
devices.
Check thecommunication wiring.
Communicationfailure?
No Withcommuni-
cation?
Yes
Yes
Normal?Is the
key locked?
Check the specificationsof the indicator.
Yes
NoCorrect?
Correct the error(s).
Cancel the setting.
Check the I/O specificationsof the indicator.
* The LCD (a liquid crystal display) is used for a display portion of this product.
The LCD has a characteristic that the display action becomes late at the low temperature.
Additionally, the luminance and contrast degradation are caused due to aged deterioration.
However, the function is not affected.
n Errors at Power OnTheerrorsshownbelowmayoccurinthefaultdiagnosiswhenthepoweristurnedon.(FordetailsofSetpointdisplayandinput/outputactionwheneacherroroccurs,seeUser’sManual.)
PV display (Operation
Display)
Setpoint display(Operation Display)
Status indicator(Operation Display)
Parameter that displays error details Error description Cause and diagnosis Remedy
Indicationoff Indicationoff — — FaultyMCURAM/MCUROM MCURAM/MCUROMarefailed. Faulty.Contactusforrepair.
ERR
SYS-----
—
— Systemdataerror Systemdataiscorrupted. Faulty.Contactusforrepair.
PAR0004(foruserdefaultvalueerroronly)
Setupparameter(PA.ER)
User(parameter)defaultvalueerror
Userparameteriscorrupted.Initializedtofactorydefaultvalue. Checkandreconfiguretheinitialized
settingparameters.Errorindicationiserasedwhenthepoweristurnedonagain.
PAR0010(forsetupparametererroronly) Setupparametererror Setupparameterdataiscorrupted.
Initializedtouserdefaultvalue.
PAR0020(foroperationparametererroronly) Operationparametererror Operationparameterdataiscorrupted.
Initializedtouserdefaultvalue.
SLOT0001 Setupparameter(OP.ER)Nonrespondinghardwareofextendedfunction(E1-terminalarea)
Inconsistenceofsystemdataandhardwareofextendedfunction.Nonrespondingcommunicationbetweenhardwareofextendedfunction(E1-terminalarea).
Faulty.Contactusforrepair.
Normalindication Normalindication
RightmostdecimalpointonPVdisplayblinks.
Setupparameter(PA.ER)Calibrationvalueerror Initializedtocalibrateddefaultvaluebecause
ofcorruptedfactorydefaultvalue. Faulty.Contactusforrepair.Rightmostdecimalpoint
onSymboldisplayblinks. FaultyFRAM Datawriting(storing)toFRAMisimpossible.
n Errors during OperationTheerrorsshownbelowmayoccurduringoperation.(Forinput/outputactionwheneacherroroccurs,seeUser’sManual.)
PV display (Operation
Display)
Setpoint display(Operation Display)
Status indicator(Operation Display)
Parameter that displayserror details Error description Cause and diagnosis Remedy
AD.ERR Normalindication — Setupparameter(AD1.E) AnaloginputterminalADCerror•PVinput AnaloginputterminalADvalueerror Faulty.
Contactusforrepair.
RJC.E(DisplaysRJC.EandPValternately.)
Normalindication — Setupparameter(AD1.E) UniversalinputterminalRJCerror•PVinput UniversalinputterminalRJCerror
Faulty.Contactusforrepair.SettheparameterRJCtoOFFtoeraseerrorindication.
B.OUT Normalindication —
Setupparameter(AD1.E) Analoginputterminalburnouterror•PVinput Analoginputterminalsensorburnout
Checkwiringandsensor.Errorindicationiserasedinnormaloperation.
Setupparameter(PV1.E) PVinputburnouterror BurnoutofanaloginputconnectedtoPV
Checkwiringandsensorofconnectedanaloginputterminals.Errorindicationiserasedinnormaloperation.
OVER-OVER
Normalindication — Setupparameter(PV1.E)PVinputover-scalePVinputunder-scale(PVvaluesoutof-5to105%)
PVinputisoutof-5to105%.Alsooccurswhenthedataoutofrangewhichistheladdercalculationresultisinput.
Checkanaloginputvalueorladderprogram.
Normalindication
0.00000000(DecimalpointontheleftoftheSymboldisplayblinks)
— Setupparameter(OP.ER) Communicationerror(RS-485communication)
FramingparityerrorBufferoverflowInter-charactertime-outChecksumerror(PClinkcommunicationwithchecksum)CRCcheckerror(Modbus/RTU)LRCcheckerror(Modbus/ASCII)
Checkthecommunicationparameters.Recoveryatnormalreceipt.Holddownanykeytostopblinking.
Normalindication Normalindication Rightmostdecimalpointon
Symboldisplayblinks. Setupparameter(PA.ER) FaultyFRAM Writing(storing)datatoFRAMisimpossible. Faulty.Contactusforrepair.
Undefined Undefined — — FaultyMCU/DCU(ROM/RAMerror,corrupted) MCU/DCUiscorrupted. Faulty.Contactusforrepair.
IM 05P03D21-11EN page 7/8
Operation ParametersHolddownthePARAkeyfor3secondstomovefromtheOperationDisplaytotheOp-erationParameterSettingDisplay.PresstheDISPkeyoncetoreturntotheOperationDisplay.
Menu
Hold down PARA keyfor 3 sec.
DISP key
SET/ENTER key PARA key
key key key
key key
Operation Dsipaly
Parameter
Parameter
Parameter
Parameter
Parameter
ParameterEND
Menu
END
Menu END
END
Menu Display and Parameter Setting Display are changed in a circular pattern.
Move to the Setup Parameter Setting Display: Hold down the PARA key and the Left arrow key simultaneously for 3 sec.
Operation for Setting· Toselecttheparametersettingdisplayedastheinitialvalue,presstheDownarrowkeytomovetothenextparameter.
· Tochangeandsettheparametersetting,presstheSET/ENTERkeytostarttheset-pointblinking.Theblinkingstateallowsyoutomakechanges(settingmode).UsetheUp/Down/Left/Rightarrowkeystochangethesetpoint.PresstheSET/ENTERkeytoregisterthesetting.
Notethattherearesomeparameterswhicharenotdisplayeddependingonthemodelandsuffixcodes.
n Alarm Setpoint Setting ParameterMenusymbol: (AL)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
to
(A1toA8)
Alarm-1to-8setpoint
SetadisplayvalueofsetpointofPValarmorvelocityalarm.-19999to30000(Setavaluewithintheinputrange.)Decimalpointpositiondependsontheinputtype
0 Tablebelow EASY
For thealarmsetpointparameter,alarm-1to-8aredisplayedfor thefactorydefault.ThenumberofalarmscanbechangedusingthesetupparameterALNO.(numberofalarms).Tochangethenumberofalarms,seeUser'sManual.Usethefollowingtabletorecordalarmsetpoints.
Parameter Setpoint Parameter Setpoint
A1 A5
A2 A6
A3 A7
A4 A8
n Alarm Function Setting ParameterMenusymbol: (ALRM)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
to
(AL1toAL8)
Alarm-1to8typeExample:Alarm-1
Stand-byaction
Latch actionEnergized/De-energize
Alarmtype
Seta5-digitvalueinthefollowingorder.[Alarmtype:2digits(seebelow)]+[Without(0)orWith(1)Stand-byac-tion]+[Energized(0)orDe-energized(1)]+[Latchaction(0/1/2/3/4)]Forlatchaction,seeUser'sManual.
AL1,AL3,AL5,AL7:
PVhighlimit(01)WithoutStand-by
action(0)
Ener-gized(0)Latchaction(0)
AL2,AL4,AL6,AL8:PVlowlimit(02)WithoutStand-by
action(0)
Ener-gized(0)
Latchaction(0)
Tablebelow
EASY
Alarmtype:2digits00:Disable01:PVhighlimit02:PVlowlimit29:PVvelocity30:Faultdiagnosis31:FAIL
to
(VT1toVT8)
PVvelocityalarmtimesetpoint1to8 0.01to99.59(minute.second) 1.00
to
(HY1toHY8)
Alarm-1to-8hysteresis
Setadisplayvalueofsetpointofhysteresis.-19999to30000(Setavaluewithintheinputrange.)Decimalpointpositiondependsontheinputtype.Whenthedecimalpointpositionfortheinputtypeissetto"1",theinitialvalueofthehysteresisis"1.0".
10
to
(DYN1toDYN8)
Alarm-1to-8On-delaytimer
AnalarmoutputisONwhenthedelaytimerexpiresafterthealarmsetpointisreached.0.00to99.59(minute.second)
0.00 STD
Forthealarmfunctionsettingparameter,8alarmsaredisplayedforthefactorydefault.Thenumberofalarmscanbechangedby thesetupparameterALNO. (numberofalarms).Tochangethenumberofalarms,seeUser'sManual.Parameter n=1 n=2 n=3 n=4 n=5 n=6 n=7 n=8
ALn
VTn
HYn
DYNn
n:alarmnumber
n PV-related Setting ParameterMenusymbol: (PVS)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(BS)PVinputbias -100.0to100.0%ofPVinputrange
span(EUS)
0.0%ofPVinputrangespan
EASY(FL)PVinputfilter OFF,1to120s OFF
(PEAK)PVpeakvalue
Displayonly(-5.0to105.0%ofPVinputrange(EU))
None
(BOTM)PVbottomvalue None
Setup ParametersHolddownthePARAkeyandLeftarrowkeysimultaneously for3secondstomovefromtheOperationDisplayorOperationParameterSettingDisplayto theSetupPa-rameterSettingDisplay.PresstheDISPkeyoncetoreturntotheOperationDisplay.
Menu
DISP key
SET/ENTER key PARA key
key key key
key key
Operation Dsipaly
Parameter
Parameter
Parameter
Parameter
Parameter
ParameterEND
Menu
END
Menu END
END
Menu Display and Parameter Setting Display are changed in a circular pattern.
Move to the Operation Parameter Setting Display: Hold down the PARA key for 3 sec.
Hold down PARA key and Left arrow key simultaneously for 3 sec.
Operation for Setting· Toselecttheparametersettingdisplayedastheinitialvalue,presstheDownarrowkeytomovetothenextparameter.
· Tochangeandsettheparametersetting,presstheSET/ENTERkeytostarttheset-pointblinking.Theblinkingstateallowsyoutomakechanges(settingmode).UsetheUp/Down/Left/Rightarrowkeystochangethesetpoint.PresstheSET/ENTERkeytoregisterthesetting.
NotethattherearesomeparameterswhicharenotdisplayeddependingontheModelandSuffixcodes.
n Function Setting ParameterMenusymbol: (CTL)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(SMP)Inputsamplingperiod 50:50ms,100:100ms,200:200ms 50 STD
n PV Input Setting ParameterMenusymbol: (PV)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(IN)PVinputtype
OFF:DisableK1:-270.0to1370.00C/-450.0to2500.00FK2:-270.0to1000.00C/-450.0to2300.00FK3:-200.0to500.00C/-200.0to1000.00FJ:-200.0to1200.00C/-300.0to2300.00FT1:-270.0to400.00C/-450.0to750.00FT2:0.0to400.00C/-200.0to750.00FB:0.0to1800.00C/32to33000FS:0.0to1700.00C/32to31000FR:0.0to1700.00C/32to31000FN:-200.0to1300.00C/-300.0to2400.00FE:-270.0to1000.00C/-450.0to1800.00FL:-200.0to900.00C/-300.0to1600.00FU1:-200.0to400.00C/-300.0to750.00FU2:0.0to400.00C/-200.0to1000.00FW:0.0to2300.00C/32to42000FPL2:0.0to1390.00C/32.0to2500.00FP2040:0.0to1900.00C/32to34000FWRE:0.0to2000.00C/32to36000FJPT1:-200.0to500.00C/-300.0to1000.00FJPT2:-150.0to150.00C/-200.0to300.00FPT1:-200.0to850.00C/-300.0to1560.00FPT2:-200.0to500.00C/-300.0to1000.00FPT3:-150.00to150.000C/-200.0to300.00F0.4-2V:0.400to2.000V1-5V:1.000to5.000V4-20:4.00to20.00mA0-2V:0.000to2.000V0-10V:0.00to10.00V0-20:0.00to20.00mA-1020:-10.00to20.00mV0-100:0.0to100.0mV
OFF EASY
(UNIT)PVinputunit
-:Nounit,C:DegreeCelsius-:Nounit,--:Nounit,---:Nounit,F:DegreeFahrenheit
C EASY
(RH)MaximumvalueofPVinputrange
Dependsontheinputtype.-Fortemperatureinput-Setthetemperaturerangethatisactuallydisplayed.(RL<RH)-Forvoltage/currentinput-Settherangeofavoltage/currentsignalthatisapplied.Thescaleacrosswhichthevoltage/currentsignalisactuallydisplayedshouldbesetusingthemaximumvalueofinputscale(SH)andminimumvalueofinputscale(SL).(Inputisalways0%whenRL=RH.)
Dependsonthe
inputtypeEASY
(RL)MinimumvalueofPVinputrange
(SDP)PVinputscaledecimalpointposition
0:Nodecimalplace1:Onedecimalplace2:Twodecimalplaces3:Threedecimalplaces4:Fourdecimalplaces
Dependsonthe
inputtypeEASY
(SH)MaximumvalueofPVinputscale
-19999to30000,(SL<SH),|SH-SL|≤30000
Dependsonthe
inputtypeEASY
(SL)MinimumvalueofPVinputscale
(BSL)PVinputburnoutaction
OFF:DisableUP:UpscaleDOWN:Downscale
Dependsonthe
inputtypeSTD
W:W-5%Re/W-26%Re(HoskinsMfg.Co.).ASTME988WRE:W97Re3-W75Re25
nInput Range Setting ParameterMenusymbol: (MPV)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(P.UNI)DisplayPVinputunit
-:NounitC:DegreeCelsius-:Nounit--:Nounit---:NounitF:DegreeFahrenheit
SameasPVinputunit
STD
(P.DP)DisplayPVinputdecimalpointposition
0:Nodecimalplace1:Onedecimalplace2:Twodecimalplaces3:Threedecimalplaces4:Fourdecimalplaces
1
(P.RH)MaximumvalueofdisplayPVinputrange
-19999to30000,(P.RL<P.RH),|P.RH-P.RL|≤30000
Dependsonthe
inputtype
(P.RL)MinimumvalueofdisplayPVinputrange
nOutput Setting ParameterMenusymbol: (OUT)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(RTS)RetransmissionoutputtypeofRET
OFF:DisablePV1:PVLPS:15VDClooppowersupply
PV1 EASY
(RTH)
MaximumvalueofretransmissionoutputscaleofRET
WhenRTS=PV1RTL+1digitto30000-19999toRTH-1digitDecimalpointposition:When
RTS=PV1,decimalpointpositionissameasthatofPVinput.
WhenRTS=PV,decimalpointpositionissameasthatofPVinputscale.
100%ofPVinputrange
STD(RTL)
MinimumvalueofretransmissionoutputscaleofRET
0%ofPVinputrange
(RET.A)RETcurrentoutputrange
4-20:4to20mA0-20:0to20mA20-4:20to4mA20-0:20to0mA
4-20
n RS-485 Communication Setting Parameter (E1-terminal Area)Menusymbol: (R485)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(PSL)Protocolselection
PCL:PClinkcommunicationPCLSM:PClinkcommunication(withchecksum)LADR:LaddercommunicationMBASC:Modbus(ASCII)MBRTU:Modbus(RTU)
MBRTU
EASY
(BPS)Baudrate
600:600bps1200:1200bps2400:2400bps4800:4800bps9600:9600bps19200:19.2kbps38400:38.4kbps
19200
(PRI)Parity
NONE:NoneEVEN:EvenODD:Odd
EVEN
(STP)Stopbit 1:1bit,2:2bits 1
(DLN)Datalength 7:7bits,8:8bits 8
(ADR)Address 1to99 1
OperationGuide
UM33ADigital Indicator with AlarmsOperation Guide
This operation guide describes the functions of parameters briefly. The parameter symbols listed are in the order shown on the display in each group of menu symbols. In addition, each parameter table has a “User Setting” column, where you can record your setpoints when setting them in the indicator. The scrolling guide is displayed on PV display in the Parameter Setting Display. This guide can be turned on/off with the Fn key.
Yokogawa Electric Corporation
Parameters
IM 05P03D21-11EN page 8/8
KeyActionSettingParameterMenusymbol: (KEY)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(Fn)Userfunctionkey-nactionsetting
OFF:DisableLTUP:LCDbrightnessUPLTDN:LCDbrightnessDOWNBRI:AdjustLCDbrightnessLCD:LCDbacklightON/OFFswitchLAT:Latchrelease(ACK)AL:AlarmsetpointsettingRST:PVpeakandbottomvalues
reset
RST EASY
DisplayFunctionSettingParameterMenusymbol: (DISP)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(PCMD)ActivecolorPVdisplayswitch
0:Fixedinwhite1:Fixedinred2:Linktoalarm1(AlarmOFF:white,
AlarmON:red)3:Linktoalarm1(AlarmOFF:red,
AlarmON:white)4:Linktoalarm1or2(AlarmOFF:
white,AlarmON:red)5:Linktoalarm1or2(AlarmOFF:
red,AlarmON:white)6:PVlimit(Withinrange:white,Out
ofrange:red)7:PVlimit(Withinrange:red,Outof
range:white)10:LinktoDI(ON:red,OFF:white)
0
EASY
(PCH)PVcolorchangehighlimit
SetadisplayvaluewheninPVlimitorSPdeviation.-19999to30000(Setavaluewithintheinputrange.)Decimalpointpositiondependsontheinputtype.
0
(PCL)PVcolorchangelowlimit 0
(GUID)GuidedisplayON/OFF OFF:Non-display,ON:Display ON
STD
(ECO)Economymode
OFF:Disable1:EconomymodeON(AllindicationsexceptPVdisplayOFF)2:EconomymodeON(AllindicationsOFF)3:Brightness10%(wholeindication)
OFF
(BRI)Brightness (Dark)1to5(Bright) 3 EASY
(MLSD)LeastsignificantdigitalmaskofPVdisplay
OFF:WithleastsignificantdigitON:Withoutleastsignificantdigit OFF STD
SELECTDisplaySettingParameterMenusymbol: (CSEL)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
to
(CS1toCS5)
SELECTDisplay-1to-5registration
Registertheoperationparameter(excepttheOperaitonMode)thatisfrequentlymodifiedtodisplayitintheOperationDisplay.OFF,2301to5000Forthesettingrange,seeUser'sManual.
OFF STD
UsethefollowingtabletorecordSELECTDsipalysettingvalue.
Parameter n=1 n=2 n=3 n=4 n=5
CSn
KeyLockSettingParameterMenusymbol: (KLOC)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(COM.W)Communicationwriteenable/disable OFF:Enable,ON:Disable OFF
STD
(DATA)Frontpanelparameterdata(,)keylock
OFF:Unlock,ON:Lock(AvailableforOperationDisplayonly.) OFF
DIFunctionResistrationParameterMenusymbol: (DI.SL)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(RST)PVpeakandbottomvaluesreset
SetanIrelaynumberofcontactinput.Set“OFF”todisablethefunction.
StandardterminalsDI1:5025,DI2:5026
5025
STD(LAT)
Latchrelease(ACK) 5026
(LCD)LCDbacklightON/OFFswitch OFF
(PVRW)PVred/whiteswitch OFF
AL1-AL4FunctionRegistrationParameterMenusymbol: (ALM)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(AL1.S)AL1functionselection
SetanIrelaynumber.Fortheitemsotherthanbelow,seeUser'sManual.Ex.)Setthenumber4353forAL1.Stousethealarm1.Set“OFF”todisablethefunction.
Nofunction:OFFAlarm1:4353Alarm2:4354Alarm3:4355Alarm4:4357Alarm5:4358Alarm6:4359Alarm7:4361Alarm8:4362
FAIL(NormallyON)output:4256
4353
STD
(AL2.S)AL2functionselection 4354
(AL3.S)AL3functionselection 4355
(AL4.S)AL4functionselection 4357
DOSettingParameter(E1-terminalArea)Menusymbol: (DO)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(DO1.S)DO11functionselection
SameasAL1.SSet“OFF”todisablethefunction
4358
STD
(DO2.S)DO12functionselection 4359
(DO3.S)DO13functionselection 4361
(DO4.S)DO14functionselection 4362
(DO5.S)DO15functionselection 4256
SystemSettingParameterMenusymbol: (SYS)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(R.TM)Restarttimer 0to10s. 0 STD
(FREQ)Powerfrequency AUTO,60:60Hz,50:50Hz AUTO
EASY
(QSM)Quicksettingmode OFF:Disable
ON:Enable ON
(LANG)Guidedisplaylanguage
ENG:EnglishFRA:FrenchGER:GermanSPA:Spanish
Depe-ndsonthemodelandsuffixcodes
(PASS)Passwordsetting
0(Nopassword)to65535Setting“0”means“withoutpasswordprotection.”
0
ErrorandVersionConfirmationParameter(fordisplayonly)Menusymbol: (VER)
Parameter symbol Name of Parameter Status record Display
level
(PA.ER)Parametererrorstatus
EASY
(OP.ER)Optionerrorstatus
(AD1.E)A/Dconvertererrorstatus1
(PV1.E)PVinputerrorstatus
(MCU)MCUversion
(DCU)DCUversion
(ECU1)ECU-1version(E1-terminalarea)
(PARA)Parameterversion
(H.VER)Productversion
(SER1)Serialnumber1
(SER2)Serialnumber2
ParameterDisplayLevelParameterMenusymbol: (LVL)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(LEVL)Parameterdisplaylevel
EASY:EasysettingmodeSTD:StandardsettingmodePRO:Professionalsettingmode
STD EASY
*ForProfessionalsettingmode,seeUser’sManual.
Trademarks Our product names or brand names mentioned in this manual are the trademarks or registered trademarks of Yokogawa Electric Corporation. Adobe, Acrobat, and Postscript are either registered trademarks or trademarks of Adobe Systems Incorporated. We do not use the TM or ® mark to indicate these trademarks or registered trademarks in this manual. All other product names mentioned in this manual are trademarks or registered trademarks of their respective companies.