Upload
others
View
23
Download
1
Embed Size (px)
Citation preview
Date: 08.09.2021
Tender Document No. P.014715 D 11031 008
Project: CGD Expansion Project
Owner: Indraprastha Gas Ltd.
Sr. No. Description Tender Page No. Clause/ Para/ Section
1PTS - Technical specification
of compacted substation.- PTS P.014715 G11077 E011 Addition Technical specification of compacted substation is added as PTS P.014715 G11077 E011 in the Technical Volume II of II.
CORRIGENDUM #2
COMPOSITE WORKS FOR CONSTRUCTION OF CNG STATIONS IN THE STATE OF DELHI, HARYANA,
RAJASTHAN AND UTTAR PRADESH
(IGL TENDER NO. IGL/ET2/CP/CC16543)
Amendment/Addition/Modification/Deletion
Note:
1. All other terms & conditions of tender document remain unaltered.
2. Bidders are requested to visit IGL website / IGL's tendering website https://petroleum.euniwizarde.com / Tractebel website regularly for further announcement .
Page 1 of 1
PTS – CSSP.014715
G11077E011
INDRAPRASTHA GAS LIMITEDCITY GAS DISTRIBUTION PROJECT IN NCT OF DELHI
& NCR REGION, UP, HARYANA, RAJASTHAN(IGL)
PTS – COMPACT SUB-STATION
P.014715 G11077 E011
0 06.09.2021 Issued for Tender BNH BNH SKH
Rev. Date Description Prepared By Checked By Approved By
PTS – CSSP.014715
G11077E011
Rev-0 CNG Station Electrical Works Page 1 of 1
TABLE OF CONTENTS
1.0 SCOPE ................................................................................................................................ 1
2.0 REFERENCE STANDARDS ................................................................................................... 1
3.0 AMBIENT CONDITIONS ...................................................................................................... 2
4.0 POWER SYSTEM DETAILS .................................................................................................. 2
5.0 METERING CURRENT TRANSFORMER ................................................................................ 2
6.0 PROTECTION CURRENT TRANSFORMER ............................................................................ 2
7.0 CABLE ENTRY (TOP/ BOTTOM) : BOTTOM ...................................................................... 2
8.0 SUPPLY .............................................................................................................................. 3
9.0 SPECIFIC FEATURES .......................................................................................................... 3
10.0 MANDATORY SPARES ......................................................................................................... 5
å å å
PTS – CSSP.014715
G11077E011
Rev-0 CNG Station Electrical Works Page 1 of 4
1.0 SCOPE
Scope of work includes Design, Manufacturing, Supply, Installation, Testing & Commissioning ofCompact Sub-station as per GA, SLD provided in this specification.
2.0 REFERENCE STANDARDS
· IEC 61869 : Instrument transformers
· IEC 60005 : Direct acting indicating analogue electricalmeasuring instruments and their accessories.
· IEC 60186 : Voltage transformers
· IEC 60255 : Electrical relays.· IEC 60288 : PVC-insulated cables for switchgear and
control gear wiring.
· IEC 60417 : Graphical symbols for use on equipment.
· IEC 60439 : Low-voltage switchgear and control gear assemblies.
· IEC 60529 : Degrees of protection provided byenclosures. (IP Code)
· IEC 60688 : Electrical measuring transducers for convertinga.c. electrical quantities to analogue or digitalsignals.
· IEC 60715 : Dimensions of low-voltage switchgear and control gear. Standardized mounting on rails for mechanical support of electrical devices in switchgear and control gear installations
· IEC 60947 : Low-voltage switchgear and control gear.
· IEC 61000-4 : Electromagnetic Compatibility (EMC).
· IEC 61346-1 : Industrial systems, installations and products– Structuring principles and referencedesignations.
· IS 8623 (Part 1) : Low Voltage switchgear and control gearassemblies: Part 1 Requirements for typetested and partially type tested assemblies
· IS 13947 (Part 1) : Low Voltage switchgear and control gearassemblies: (Part 1) General rules
· IS 13118 : Specification for High Voltage AC CircuitBreaker.
· IS 3427 : AC metal enclosed switchgear and controlGear for rated voltages above 1kV & up to& including 52kV.
PTS – CSSP.014715
G11077E011
Rev-0 CNG Station Electrical Works Page 2 of 4
· IS 1180 (Part 1) : Outdoor type oil immersed DistributionTransformers Up to and including2500kVA, 33kV
· IS 13947 (Part 1) : Specification for Low Voltage switchgearand control gear : (Part 4) Contactors andmotor starters, sec 1 Electromechanicalcontactors and motor starters (Superseding
· IS 2959 and IS 8544 (all parts))
· Indian Electricity Rule as amended up to date, any other relevant local law codes & regulations(Latest edition) applicable, shall meet requirement for switchboard & associated material.
3.0 AMBIENT CONDITIONS
Max/Min. Region Temperature - 50°C / 5°C
Max/Min. Design Temperature - 55°C / 0°C
Max/Min Region Relative Humidity - 100% / 5%
Altitude above MSL- : Less than 1000 MTS
Atmosphere- : Tropicalized to withstand the site condition,
dust & Vapor
Location- : Indoor
4.0 POWER SYSTEM DETAILS
Voltage with ±% 11kV & 415 V ± 20%Frequency with ±% 50 Hz ± 5%No. of phase & wire 3P + 1NFault level 35kA for 1 sec
5.0 METERING CURRENT TRANSFORMER
VA : As per SLD
Accuracy class : As per SLD (Class 1.0)
6.0 PROTECTION CURRENT TRANSFORMER
VA : As per SLD
Protection class : As per SLD (Class 5P10)
7.0 CABLE ENTRY (TOP/ BOTTOM) : BOTTOM
PTS – CSSP.014715
G11077E011
Rev-0 CNG Station Electrical Works Page 3 of 4
8.0 SUPPLY
Please refer SOR.
The requirement of CSS may be change or vary as per actual site condition.
Obtaining electrical inspector NOC shall be in scope of contractor.
i) It is not the intent to specify completely herein all details of the equipment. Nevertheless, theequipment shall be complete and operative in all aspects and shall conform to highest standard ofengineering, design and workmanship.
ii) Any material or accessory which may not have been specifically mentioned but which is necessaryor usual for satisfactory and trouble-free operation and maintenance of the equipment shall befurnished without any extra charge.
iii) The Contractor shall supply all brand-new equipment and accessories as specified herein with suchmodification and alteration as agreed upon in writing after mutual discussion.
9.0 SPECIFIC FEATURES
Sl. No. System Parameters Design/ Feature
A. MV Parameters
RMU make Siemens, ABB, Schneider, Power Tech,
MV Switchgear 630A, 3 Way RMU
MV Voltage 11kV
MV System 3 phase 3 wire
VCB make Siemens, ABB, L&T
B. Transformer Parameters
Make CGL, VOLTAMP, POWER STAR, GE, ABB,Transformers & Rectifiers India Ltd,
Rating (kVA) 3 Star, As per SOR
Primary Voltage 11kV 50Hz
Secondary Voltage 433V
Type Oil type
Winding material Copper
Vector group Dyn11
Tap changer Off-Circuit
C. LV Parameters
LV System 3 Phase 4 Wire
LV Voltage 433V, 50Hz
D. Wiring MV/LV
Wire type PVC insulated Cu wire multistranded, flexible
PTS – CSSP.014715
G11077E011
Rev-0 CNG Station Electrical Works Page 4 of 4
Insulation grade 1.1kV
Control circuit AC/DC 1.5 Sq.mm (Grey/ Black)
CT circuit 2.5 Sq.mm (Red, Yellow, Blue, Black)
Earthing Wire 2.5 Sq.mm. Green
Circuit identification Printed ferrules at terminations
E. Enclosure
Installation of CSS Outdoor (Weatherproof enclosure) with Twin Canopy
Mounting of CSS On foundation
Lifting arrangement Shall be provided
Transformer compartment access Hinged door
LV Compartment access Hinged door
MV Compartment access Hinged door
Recommended clearance around enclosure 150mm on operational faces
600mm On Non operational faces
Material for enclosure GI Sheet Steel, 2mm thick for Outdoor
CRCA Sheet Steel, 2/1.6mm thick for LV
Base frame ISMC 100x50x5mm
IP protection for Transformercompartment
IP 23
IP protection for MV & LV compartment IP 54
Type of ventilation for Transformercompartment
Natural
Paint Powder coated
Paint material Pure Polyster based Powder
Paint finish Structure finish
Paint shade Enclosure – RAL 7035, Top ring – Blue
Paint thickness Minm. 80 micron
Interconnection between RMU &Transformer
Cable
Interconnection between Transformer toBreaker
Aluminum Busbar
Earth Bus for Enclosure Aluminum Busbar
Neutral Earth Bus Cu. Busbar
MV/LV Cable Entry Bottom through Gland Plate
F. Final Testing Overall dimension, BOQ, Functional Test, Physicaloperation of equipment, Insulation resistance, HV test,IR after HV.
PTS – CSSP.014715
G11077E011
Rev-0 CNG Station Electrical Works Page 5 of 4
10.0 MANDATORY SPARES
As per Manufacture standard.
å å å
PTS – CSSP.014715
G11077E011
Rev-0 CNG Station Electrical Works Page 2 of 4
PTS – CSSP.014715
G11077E011
Rev-0 CNG Station Electrical Works Page 3 of 4
CSS indicative layout for illustration purpose only.
PTS – CSSP.014715
G11077E011
Rev-0 CNG Station Electrical Works Page 4 of 4