88
1 COMFORTMAN - ComfortPoint Diagnostic Manager for Plant Controller User’s Guide en2b0084-ie10r0319-ComfortManUsers March 2019 (Applicable for CPO-PC400 Series and CPO-PC200 Controllers) Release 200

COMFORTMAN - Honeywell Россия

  • Upload
    others

  • View
    17

  • Download
    0

Embed Size (px)

Citation preview

Page 1: COMFORTMAN - Honeywell Россия

COMFORTMAN - ComfortPoint Diagnostic

Manager for Plant Controller

User’s Guideen2b0084-ie10r0319-ComfortManUsers

March 2019

(Applicable for CPO-PC400 Series and CPO-PC200 Controllers)

Release 200

1

Page 2: COMFORTMAN - Honeywell Россия

Document Release Issue Dateen2b0084-ie10r0319-

ComfortManUsers

200 0319 March 2019

Notice

This document contains Honeywell proprietary information. Information contained herein is to be used solely for the purpose submitted, and no part of this document or its contents shall be reproduced, published, or disclosed to a third party without the express permission of Honeywell International Inc.While this information is presented in good faith and believed to be accurate, Honeywell disclaims the implied warranties of merchantability and fitness for a purpose and makes no express warranties except as may be stated in its written agreement with and for its customer.In no event is Honeywell liable to anyone for any direct, special, or consequential damages. The information and specifications in this document are subject to change without notice.Copyright 2019 – Honeywell International Inc.

Honeywell trademarks

ComfortPoint™ Open is a trademark of Honeywell International Inc.

Other trademarks

BACnet® is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).Trademarks that appear in this document are used only to the benefit of the trademark owner, with no intention of trademark infringement.Google Chrome™ is a registered trademark of Google Inc.Safari® is a trademark of Apple Inc., registered in the U.S. and other countries.Microsoft EDGE is a trademark of Microsoft Corporation.Opera is a trademark of Opera Software AS in Norway.

Support and other contacts

For technical assistance, call your nearest Honeywell office.

2 www.honeywell.com/ps/buildingsolutions

Page 3: COMFORTMAN - Honeywell Россия

CONTENTS

1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Intended Audience and Assumed Knowledge. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Definition of Product Related terms/Acronyms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Document References. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

2 Connecting to Controller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Installing the Gserial Driver on Windows 7 Machine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10

Establishing Communication (serial port terminal tool) via USB Serial Port. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11

3 Board Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Viewing the Board Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18

4 Port Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Viewing the Port Configuration Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22

Viewing the Port Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23

Ports Availability. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24

Configuring the BACnet Application Download (Enable/Disable) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24

Configuring the BACnet UDP Port Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25

Viewing the Bus configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27

Viewing the IO Board Details for Panel Bus, CP-IO Bus, and FBA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29

Viewing the Modbus Device Details. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34

Viewing the MSTP Device Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37

Viewing the BACnet Device Info . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38

Viewing the BACnet Network Info . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39

Setting the Router Configurations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40

5 System Resource Usage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43Viewing the System Resource Usage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44

6 A9 Process Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49Viewing the A9 Process Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50

7 Trace Channel Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51Viewing the Trace Channel Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52

8 Application Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55Viewing the Application Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56

Viewing the Admin Info . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57

Viewing the Application Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58

Viewing the Point DB Info . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59

Alarm for Revision 1.14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61

Viewing the IO Comm Info. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .63

Viewing the Data Sharing Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .64

Viewing the Schedule Info . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .66

Viewing the Trend Log Objects Info. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .68

Viewing the Daylight Saving Info . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .69

Setting the Alarm Recipient Details. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .70

Viewing the C-Bus Sharing Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .71

9 Command Shell . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75Viewing the Command Shell. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .76

Using the Commands in Command Shell. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .77

Using the np option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .78

Using the ping option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .80

Using the appdel option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .81

1

Page 4: COMFORTMAN - Honeywell Россия

1 –

10 Board Restart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83Restarting the Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .84

11 Logout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85Logging out from ComfortMan. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .86

2 www.honeywell.com/buildingsolutions

Page 5: COMFORTMAN - Honeywell Россия

1

Introduction

The ComfortPoint Diagnostic Manager (ComfortMan) can be used for collecting internal information from the controller Firmware. It analyzes and displays the diagnostic data obtained from the tasks running within the firmware. Therefore, the ComfortMan itself is implemented as a task to be a part of the firmware. It writes its output to a terminal queue that must be handled by a terminal emulation program. This program is also called ComfortMan.

ComfortMan has different operator privilege levels. This is to ensure that only experienced users have access to the actions that eventually affect the board behavior or information that needs to be interpreted on an advanced level.

Related Topics

Scope

Intended Audience and Assumed Knowledge

Definition of Product Related terms/Acronyms

Document References

3

Page 6: COMFORTMAN - Honeywell Россия

1 – INTRODUCTION

ScopeThis document describes all the functions that are accessible from the Engineering mode. User mode functions are the subset of the Engineering mode functions.

Attention

This document is applicable for the CPO-PC400 series and CPO-PC200 controllers having firmware 3.0.9.0.1 and later versions.

4 www.honeywell.com/buildingsolutions

Page 7: COMFORTMAN - Honeywell Россия

INTENDED AUDIENCE AND ASSUMED KNOWLEDGE

Intended Audience and Assumed Knowledge• This guide is intended for people who use the ComfortMan to manage the CPO-

PC400 series and CPO-PC200 controllers.

• It is assumed that the user is trained and familiar with HVAC concepts and CPO-PC400 series and CPO-PC200 controllers.

5

Page 8: COMFORTMAN - Honeywell Россия

1 – INTRODUCTION

Definition of Product Related terms/AcronymsTerm Definition

BACnet Building Automation Control Network. It is the data communication protocol for Building Automation and Control Networks.

RAM Random Access Memory

VAV Variable Air Volume Controller, which comes under the unitary controller.

MSTP Master Slave Token Passing

FCU Fan Coil Unit, which comes under the unitary controller.

EXPIO Expansion IO Boards for the CPO-PC400/CPO-PC400-W/CPO-PC400-UW/CPO-PC200 controller. The controller gets the IO Point details from these Extension IO Boards.

RACL Recursive Algorithm Control Logic. It is the control program which drives the output points based on the input point’s value. It also transfers the function used in that program.

CPO Manager It is a workstation which is mainly used for monitoring the point status (both physical and pseudo) in the controller.

FTP File Transfer Protocol. It is used to log on to other Internet sites for sending or retrieving files or both.

6 www.honeywell.com/buildingsolutions

Page 9: COMFORTMAN - Honeywell Россия

DOCUMENT REFERENCES

Document ReferencesTitle Product Literature Number Contents

ComfortPoint™ Open PC400 Plant

Controller - Data Sheet

EN0B0076-IE10 Product data for the CPO-PC400

series controllers.

ComfortPoint™ Open PC400 Plant

Controller - Installation Guide

EN1B0077-IE10 Describes wiring connections between CPO-PC400 series controller and other communication devices.

ComfortPoint™ Open PC400 Plant

Controller - Mounting Guide

MU1B0078-IE10 Describes the mechanical mounting

and basic wiring of the CPO-PC400

series controllers.

ComfortPoint™ Open PC200 Plant

Controller - Data Sheet

EN0B0083-IE10 Product data for the CPO-PC200

controller.

ComfortPoint™ Open PC200 Plant

Controller - Installation Guide

EN1B0085-IE10 Describes wiring connections between CPO-PC200 controller and other communication devices.

ComfortPoint™ Open PC200 Plant

Controller - Mounting Guide

MU1B0086-IE10 Describes the mechanical mounting and basic wiring of the CPO-PC200 controller.

ComfortPoint™ Open MMI - User

Guide

EN2B0080-IE10 User guide for CPO-MMI.

ComfortPoint™ Open MMI - Quick Start Guide

EN2B0087-IE10 Quick start guide for CPO-MMI.

ComfortPoint™ Open MMI - Data

Sheet

EN0B0079-IE10 Product data for the CPO-MMI

device.

ComfortPoint™ Open MMI -

Mounting Guide

MU1B0081-IE10 Describes the mechanical mounting

and basic wiring of the CPO-MMI

device.

7

Page 10: COMFORTMAN - Honeywell Россия

1 – INTRODUCTION

8 www.honeywell.com/buildingsolutions

Page 11: COMFORTMAN - Honeywell Россия

2

Connecting to Controller

If you are using a Windows 7 machine to connect with the controller, make sure that the Gserial driver is installed on the machine to avoid USB port related errors. For more information, see the Installing the Gserial Driver on Windows 7 Machine section on page no. 10.

This section provides information to connect your machine where ComfortMan is installed and the controller.

Related Topics

Installing the Gserial Driver on Windows 7 Machine

Establishing Communication (serial port terminal tool) via USB Serial Port

Attention

9

Page 12: COMFORTMAN - Honeywell Россия

2 – CONNECTING TO CONTROLLER

Installing the Gserial Driver on Windows 7 MachineThis section is only applicable to the users who use Windows 7 machine. It provides the instructions to install the Gserial driver on your machine to avoid the USB port related errors when you connect your machine to the controller.

Prerequisite

A controller must be connected to your machine while installing the Gserial driver.

To install Gserial driver on Windows 7 machine

1. Download the zipped gadgetdriver file from the extranet into your machine

2. Navigate to the downloaded location and unzip the file to extract the gadget driver folder.

3. Navigate to Start > Control Panel > Device Manager.

4. In the Device Manager window, double-click Ports (COM & PLT).

5. Right-click USB Serial Port (COM5) and click Update Driver Software...

6. Click Browse my computer for driver software.

The Browse for driver software in this location window appears.

7. Click Browse and navigate to the gadget driver folder and click OK.

8. Click Next.

Driver installation or update related message appears.

9. Click Close.

10 www.honeywell.com/buildingsolutions

Page 13: COMFORTMAN - Honeywell Россия

ESTABLISHING COMMUNICATION (SERIAL PORT TERMINAL TOOL) VIA USB SERIAL PORT

Establishing Communication (serial port terminal tool) via USB Serial Port

We have used HyperTerminal as the serial port terminal tool to establish the connection. If the HyperTerminal tool is idle for more than 15 minutes, the tool log outs automatically.

Communicate with the controller via a computer through the USB serial port. Use the serial port terminal tool for establishing communication.

To configure the HyperTerminal settings

1. Go to Start > Accessories > HyperTerminal. The Connection Description dialog box appears.

Figure 1 HyperTerminal tool

2. In the Name box, type a name for the session and click OK.

The Connect To dialog box appears.

3. In the Connect using drop-down list, select the port to which the controller is connected via

RS232 cable and click OK.

The Port Settings window appears.

4. Click Restore Defaults.

5. Click OK.

The communication is established successfully and Shell> appears on the command

screen.

Attention

11

Page 14: COMFORTMAN - Honeywell Россия

2 – CONNECTING TO CONTROLLER

Figure 2 Command Shell Display

6. On the Command Shell screen, press Enter twice to see the communication details.

12 www.honeywell.com/buildingsolutions

Page 15: COMFORTMAN - Honeywell Россия

ESTABLISHING COMMUNICATION (SERIAL PORT TERMINAL TOOL) VIA USB SERIAL PORT

Connecting to ComfortMan

The client certificate with PEM format is available to users with an Administrator role. For more information on roles, see the Role-based authorization section of the ComfortPoint Open Network Deployment Guide (EN2B0054 IE10).

After establishing the communication between the HyperTerminal and the controller, execute the cman command. It is mandatory to have a valid client certificate (downloaded from the Web portal) on your device. The client certificate with PEM format must be used for establishing communication. For more information on certificates, see ComfortPoint Open Online User’s Guide.

Best practices:• Always start a new instance of Hyper Terminal connection to establish

communication with a controller.

• Always log out of ComfortMan before closing the Hyper Terminal application.

• Always close the Hyper Terminal application after use.

To connect to ComfortMan

1. Type cman to execute ComfortMan and press Enter.

Note: If you want to view other options, type help.

The Main menu for user mode screen appears. Follow the on-screen instructions.

Figure 3 Main Menu for User Mode

On-screen instructions2. Right-click on the screen and select Send File.

Figure 4 Send File

Attention

13

Page 16: COMFORTMAN - Honeywell Россия

2 – CONNECTING TO CONTROLLER

3. Click Browse and navigate to the folder where you have the client certificates and select

PEM file.

4. In the Protocol list, click Xmodem.

Figure 5 Send File

5. Click Send.

The page prompts you to enter the client certificate password, which you generated using

ComfortPoint Open certificate portal while downloading the client certificate.

Figure 6 License Page

6. Enter the password.

7. Press Y to continue.

The ComfortMan main screen appears.

If a failure occurs when sending the Client Certificate or when accessing the ComfortMan tool, you must close and reopen the Hyper Terminal application to establish a fresh connection.

Attention

Always send the Client Certificate file within 60 seconds after issuing the ‘cman’ command.

Attention

14 www.honeywell.com/buildingsolutions

Page 17: COMFORTMAN - Honeywell Россия

ESTABLISHING COMMUNICATION (SERIAL PORT TERMINAL TOOL) VIA USB SERIAL PORT

Figure 7 ComfortMan Main Screen

The ComfortMan main screen displays nine commands. To execute the commands you must press the relevant command number on your keyboard.

For example, to view the Board Information. press 1 on your keyboard. The Board Information screen will appear. For more information, see Viewing the Board Information

section on page no. 18.

Other than the commands, the main screen also displays the details of the following information.

• Firmware Version: Displays the controller firmware version details.

• System Up Time: Displays the number of days and time, since you last restarted the

controller.

• Current System Time: Displays the current date and time.

If the telnet interface is idle for more than 1 minute, the interface log outs automatically.

When the HyperTerminal connection is disconnected from the computer or the screen is closed abruptly (by pressing “X “on the window), the ComfortMan screen remains on the last screen until the timeout period is elapsed. When you try to reconnect to ComfortMan screen before timeout elapses, the screen does not respond to any command. You must wait until the timeout period is complete. Therefore, it is recommended to close the ComfortMan screen by pressing 9 from the main screen.

For example, according to the System Up Time, the controller is running for the last 3 days, 16 hours, 28 minutes, and 35 seconds.

Attention

15

Page 18: COMFORTMAN - Honeywell Россия

2 – CONNECTING TO CONTROLLER

16 www.honeywell.com/buildingsolutions

Page 19: COMFORTMAN - Honeywell Россия

3

Board Information

This chapter describes how to view the board information of the controller.

Related Topic

Viewing the Board Information

17

Page 20: COMFORTMAN - Honeywell Россия

3 – BOARD INFORMATION

Viewing the Board InformationBoard information allows you to confirm software versions of the various controller components.

To view the Board information

1. Open ComfortMan.

Figure 8 ComfortMan Main Screen User Mode

2. Press 1 to view the Board Information.

The Board Information screen appears which displays the information about the board

connected to the ComfortMan,

18 www.honeywell.com/buildingsolutions

Page 21: COMFORTMAN - Honeywell Россия

VIEWING THE BOARD INFORMATION

Figure 9 Board Information

NoteThe contents of the Board Information screen are common for both the Engineer mode and the User mode.

3. To return to the main screen, press Q or ESC on the keyboard.

19

Page 22: COMFORTMAN - Honeywell Россия

3 – BOARD INFORMATION

20 www.honeywell.com/buildingsolutions

Page 23: COMFORTMAN - Honeywell Россия

4

Port Overview

Port Overview provides information about the available ports of the controller and helps diagnose the communication port.

Related Topics

Viewing the Port Configuration Overview

Viewing the Port Settings

Viewing the Bus configuration

Viewing the BACnet Device Info

Viewing the BACnet Network Info

Setting the Router Configurations

21

Page 24: COMFORTMAN - Honeywell Россия

4 – PORT OVERVIEW

Viewing the Port Configuration OverviewTo view the Port overview

1. On the ComfortMan main screen, press 2.

The Port Configuration Overview screen appears with the following options.

• Port settings

• Bus Configuration <DSL’s>

• BACnet Device info

• BACnet Network info

• Router ConfigurationFigure 10 Port Configuration Overview

2. To return to the main screen, press Q or ESC on the keyboard.

22 www.honeywell.com/buildingsolutions

Page 25: COMFORTMAN - Honeywell Россия

VIEWING THE PORT SETTINGS

Viewing the Port SettingsTo view the Port settings

1. On the Port Configuration Overview screen, press 1.

The Port Configuration Information screen appears which displays the available port

settings of the controller.

Figure 11 Port Configuration Information (Port settings)

The first three ports are user configurable with the following options:

• MSTP - for communication with the unitary controllers

• CBus - for communication with Excel 5000 controllers during migration

• Modbus

• M-Bus

• Panel

• Field Bus

The fourth port can be configured as either Panel or EXPIO/DIO. The fifth port specifies the

BACnet IP Communication.

The port settings helps to find out if the communication is currently active and with which

baud rate the communication occurs and with which baud rate the communication occurs.

2. Press C to configure the BACnet application download and to configure the Telnet port. For

more information, see Configuring the BACnet Application Download (Enable/Disable)

section on page no. 24 and see Configuring the BACnet UDP Port Number section on page

no. 25.

3. Press P to configure the UDP port number. For more information, see Configuring the

BACnet UDP Port Number section on page no. 25.

23

Page 26: COMFORTMAN - Honeywell Россия

4 – PORT OVERVIEW

Ports Availability• Disabled ports:

- Telnet Port 23

- FTP Port 21

• Enabled ports:

- BACnet Communication - Port 47808

- BACnet MS/TP - Port RS485 (can be disabled via the CPO Online tool)

- HTTPS - Port 443 - The Internet Browser Access and Firmware Downloads can be

performed via this port

- DNS - Port 53

Configuring the BACnet Application Download (Enable/Disable)

AttentionFor redundant pair of controllers, ensure that the BACnetAppBinaryDwnld property remains in the default (Enabled) state.

This section provides the instructions to enable/disable BACnet application download.

By default, the application can be downloaded over BACnet without client certificate. However, the controller can be configured to allow application download only after providing the client certificate password. This makes the application download secure.

The option is enabled state by default. In this state, the CPO Online tool does not prompt for client certificate during the application download.

To configure the BACnet application download

1. On the Port Configuration Overview screen, press 1.

2. Press C to configure the ports.

24 www.honeywell.com/buildingsolutions

Page 27: COMFORTMAN - Honeywell Россия

VIEWING THE PORT SETTINGS

Figure 12 Configure BACnet Application Download

3. Press 5 to disable the application binary download via BACnet.

4. Press Y to confirm your selection.

This sets the BACnetAppBinaryDwnld flag to Disabled.

Additionally, the BACnet Application download flag is set to False in the CPO Online tool

(Controller properties page), thereafter the CPO Online tool prompts for client certificate

during application download.

NoteTo enable the application binary download again, perform the same steps as mentioned above. This sets the BACnetAppBinaryDwnld flag to Enabled.

Configuring the BACnet UDP Port NumberYou can configure the BACnet UDP port number. This isolates the Honeywell network from other networks.

To configure BACnet UDP port number

1. On the Port Configuration Overview screen, press 1.

2. Press P.

25

Page 28: COMFORTMAN - Honeywell Россия

4 – PORT OVERVIEW

Figure 13 Port Number

3. Type the BACnet UDP port number of the controller and press Enter on the keyboard.

The possible values for BACnet UDP port numbers are 47808 (BAC0) to 47823 (BACF).

Figure 14 Port Number

4. Restart the controller for the new port number to take effect.

26 www.honeywell.com/buildingsolutions

Page 29: COMFORTMAN - Honeywell Россия

VIEWING THE BUS CONFIGURATION

Viewing the Bus configurationTo view Bus configuration

1. On the Port Configuration Overview screen, press 2.

The Online Devices Information screen appears.

Figure 15 Bus Configuration Info - Online Device Information

• The number of devices configured in each port.

• The type of devices connected.

• The device status.

Legend gives details about the status of the device based on the character displayed on the

corresponding position.

The Bus Configuration display varies according to the login mode.

• I - Displays the IO Board details.

The User mode provides the following options.

• M - Displays the refresh time of the MTSP device status. This property can be modified.

• P - Displays the FBA IO board details.

• S - Displays the time delay before sending the request to the next Modbus device. The

default time is 0 and indicates that there is not time delay. This value can be configured.

• T - Displays the panel bus task details.

• Q or Esc key - Allows you to return to the Port Configuration Overview menu.

2. To set the MSTP refresh time, press M.

The User mode provides the option to type the refresh time.

27

Page 30: COMFORTMAN - Honeywell Россия

4 – PORT OVERVIEW

Figure 16 MSTP Refresh Time

3. Type the refresh time in seconds and press Enter.

The current MSTP refresh time and the new refresh time are displayed.

NoteIf the MSTP unitary controllers are online, it displays “V” in the corresponding channel with respect to the MAC ID. However, if the controllers are offline it continues to display “-”.

Figure 17 MSTP Status

28 www.honeywell.com/buildingsolutions

Page 31: COMFORTMAN - Honeywell Россия

VIEWING THE BUS CONFIGURATION

4. To return to the Port Configuration Overview screen, press Q or Esc key.

The User mode provides the following options.

• I – Displays the IO Board details,

• S- Displays the time delay before sending the request to the next Modbus device. The

default time is 0 and indicates that there is not time delay. This value can be configured.

• Q or Esc key – Allows you to return to the Port Configuration Overview menu.

Viewing the IO Board Details for Panel Bus, CP-IO Bus, and FBA

To view the IO Board details

1. On the Port Configuration Overview screen, press 2. The Online Devices Information screen appears.

2. Press I. The diagnostic manager asks for the board number you want to view.

Figure 18 IO Board Detail Display Option

The display is same for all the login modes. You can select the board number, from the display corresponding to the IO-BUS.

Options applicable for all modules• B – Indicates that the configured IO Board is currently online, but it is running in the

Bootloader mode.

• D – Indicates that the configured IO Board is deactivated.

29

Page 32: COMFORTMAN - Honeywell Россия

4 – PORT OVERVIEW

Options only applicable for Panel Bus• U – Indicates that the Panel Bus module is a universal input module IO Board.

• V – Indicates that the Panel Bus module is a universal output module IO Board.

• W – Indicates that the Panel Bus module is a binary input module Board.

• X – Indicates that the Panel Bus module is a binary output module Board.

• Y – Indicates that the Panel Bus module is a modulating analog output module Board.

• Z – Indicates that the Panel Bus module is a mixed IO module Board.

• O - Indicate the module is offline.

Options only applicable for CP-IO/DIO Bus• E – Indicates the CP-IO module is online.

• O - Indicates the CP-IO module is offline.

• F - Indicates the DIO module is online.

• N - Indicates the DIO module is offline.

Options only applicable for FBA• U– Indicates the module is undiscovered.

• E- Indicates the module is online.

• O- Indicates the DIO module is offline.

To view the IO board details• On the IO Board Detail Display Option screen, press I, followed by enter the port/channel

number and board number as shown in IO Board Detail Display to see the configured IO details

as shown in Board Detail Display for the Online IO Board.

The Board Detail Display for the Online IO Board screen appears with the following information.

- The selected IO Board's firmware version.

- The channel numbers in which the points are configured.

- The points Instance Number.

- Sensor type of the configured points.

- 4 Point Curve Characteristic ID.

- The Physical Value of the points.

- Offset value for the Analog Input Points.

Note

• Referring to the IO Board Detail Display Option figure, the values after pressing I -

• Panel Bus - 1, 0 or 1, 5

• CP-IO Bus - 4, 0

• FBA - 3, 1

30 www.honeywell.com/buildingsolutions

Page 33: COMFORTMAN - Honeywell Россия

VIEWING THE BUS CONFIGURATION

NoteThe Points value displayed in the CPO Manager (client side) are logical values.

• AI, BI, AO, and BO points are configured in the IO Board.

• The Physical value is displayed as no sensor if the Analog Point sensor corresponding to

that input point is configured but not connected.

• You can see the IO communication statistics of an IO Board by pressing S on the Board

Detail Display for the Online IO Board. The option S is available at of the page and to

reach the end of the page press Space bar.

Figure 19 IO Board Detail Display

31

Page 34: COMFORTMAN - Honeywell Россия

4 – PORT OVERVIEW

Figure 20 Board Detail Display for the Online IO Board

Figure 21 IO Communication Statistics Display for the Online IO Board

• Above figure displays the IO Communication statistics of the Board 0.

• Communication Statistics helps to identify what and how many the IO communications occur between the controller and IO Board.

32 www.honeywell.com/buildingsolutions

Page 35: COMFORTMAN - Honeywell Россия

VIEWING THE BUS CONFIGURATION

• As Board 0 is configured and not connected, there is only a version request command from the controller. The IO Communication statistics information page displays the details.

Figure 22 IO Board Display for the Offline Board

Figure 23 IO Communication Statistics Display for the Offline Board

33

Page 36: COMFORTMAN - Honeywell Россия

4 – PORT OVERVIEW

Viewing the Modbus Device Details

To view the Modbus device details

1. On the ComfortMan main screen, press 1.The Port Configuration Overview screen appears.

2. Press 2.The Bus Configuration screen appears.

3. Press I.

4. To see the point details, type the port number and the board number in the diagnostic

manager window. This display is same for all the login modes.

5. If the Modbus Configured Port Number is pressed, then the Modbus Board details are

displayed for the selected board number.

6. The board number can be selected by looking at the display corresponding to the Modbus

BUS. Figure 24 Modbus Device Details Display

The following options are provided.

• M - Indicates that the configured Modbus board is currently online and the board is

communicating properly with the zone controller.

• O - Indicates that the configured Modbus board is currently offline and the board is not

communicating properly with the zone controller.

• D - Indicates that the configured Modbus board is deactivated by an Engineer.

34 www.honeywell.com/buildingsolutions

Page 37: COMFORTMAN - Honeywell Россия

VIEWING THE BUS CONFIGURATION

Figure 25 Modbus Device Points Details

• The selected Modbus Board's Configuration - ASCII or RTU.

- Device ID of that Modbus Device

- Channel Numbers in which the points are configured.

- The points Instance Number

- Point Type of the configured points - Coil, DI, IR and HR

- Data Type of that point - Bool, UINT16, INT16, UINT32, INT32, FLOAT

- Message Type - Read Only, Read and Write, Write Only options

- The Physical Value of the points at that time.

- Offset value for the IR and HR Points.

NoteThe points value displayed in the CPO Manager (client side) are logical values.

7. Press S on the Modbus board detail display page.

The diagnostic communication of that Modbus board is displayed.

35

Page 38: COMFORTMAN - Honeywell Россия

4 – PORT OVERVIEW

Figure 26 Modbus Device Statistics

36 www.honeywell.com/buildingsolutions

Page 39: COMFORTMAN - Honeywell Россия

VIEWING THE BUS CONFIGURATION

Viewing the MSTP Device Details

To view the MSTP device details

1. On the Bus Configuration screen, press I.

2. If the MSTP Configured Port Number is pressed, then the channel statistics is displayed.

Figure 27 MSTP Device Details Display

Figure 28 MSTP Channel Statistics

37

Page 40: COMFORTMAN - Honeywell Россия

4 – PORT OVERVIEW

Viewing the BACnet Device InfoBACnet Device info, helps you identify the devices which are online on each of the controller port. When the controller points are shared with some other devices, then this menu can be used for finding out, if the controller is able to identify the devices that are online and not online.

To view the BACnet device info

1. On the Port Configuration Overview screen, press 3.The BACnet device info screen appears.

Figure 29 BACnet Device Info

• DevcieInst: Is the Instance of the device, which is able to reach the controller number configured in the studio.

• Port: Refers to the controller port 0- MSTP1, 1-MSTP2, 2-MSTP3, and 4- BACnet IP.

• Source Addr: Is the Physical address of the online device. For IP devices, it is the IP address; for MSTP devices, it is the MAC address (set with Hex switch).

• Destin Addr: Is used if the device is seen through the BACnet router.

• APDUMax: Is the maximum size of BACnet Packet that device can support.

• Snet: Refers to the BACnet network the device belongs to. It is useful if the device is seen through the BACnet router.

• Seg: Provides information on whether the device supports segmentation or not

• VendorId: Helps to identify the vendor device.

38 www.honeywell.com/buildingsolutions

Page 41: COMFORTMAN - Honeywell Россия

VIEWING THE BACNET NETWORK INFO

Viewing the BACnet Network InfoBACnet Network info allows you to see all the BACnet Network details. This menu is useful in identifying the routers for each of the BACnet networks. If the third-party routers are also used in a project, then this helps in identifying the duplicate network, not used by the two routers.

To view the BACnet network info

1. On the Port Configuration Overview screen, press 4.The Reachable BACnet Network Details screen appears.

Figure 30 BACnet Network Info

- S.No: Refers to the serial number.

- Port No: Refers to the controller port from which this network can be reached.

- N/W/ No: Refers to the BACnet network number.

- Status: Refers to the current Status of the network.

- Router Address: Refers to the Router IP address for which this BACnet network is

connected.

- (B)-Bind/(U) UnBind Routed I-Ams:

B: The controller accepts the routed “I-Ams” messages.

U: The controller does not accept the routed “I-Ams” messages.

NoteThe default option is U. This controls the load on the controller by blocking the routed “I-Ams” messages.

Use option B to accept the routed “I-Ams” when the points of a device connected under a router are shared directly with the controller.

39

Page 42: COMFORTMAN - Honeywell Россия

4 – PORT OVERVIEW

Setting the Router ConfigurationsUse this feature to optimize and control network traffic in order to improve the system performance in large sites.

To set the Router Configurations

1. On the Port Configuration Overview screen, press 5.

The BACnet Routing Control Flags screen appears which displays the router configuration

details.

Figure 31 Router Configuration Screen

All the MSTP channel settings options are in F state by default. It is advised that you do not change the default MSTP channel settings. Consult with Honeywell Technical Assistance Center (TAC) before you change the default settings.

2. Use the arrow keys to move across options and press T to set the value to true or press F to

set the value to false.

3. Press R to reset the flags to the default (F: False) state.

Attention

40 www.honeywell.com/buildingsolutions

Page 43: COMFORTMAN - Honeywell Россия

SETTING THE ROUTER CONFIGURATIONS

Settings Action

Show MSTP devices with instance less than 128

Press T under the required channel to discover fresh devices from the IP channel (out from factory) during installation or commissioning phase.

The devices coming from the factory have the Device instance number from 1 to 127. By default, the controller does not allow the unitary devices with instance number less than 128 to be discovered. However, for commissioning purpose, you can set this flag to T (True) state. This makes the controller discover the devices having instance number less than128. After commissioning, it is recommended to set the flag to F (False) state.

Route other channel broadcast messages (Single flag common to all channels)

Press T to enable message transfer between MSTP channels.

Typically, the value is set to T to allow message transfer from third party MSTP controllers connected to a third party controller in the IP network. This setting is applicable to all channels.

Initiate proxy discovery Press T to enable the controller to act as a proxy for all unitary controllers in the MSTP network.

Typically, the value is set to T if MSTP device response time is less than the desired time. When the value is set to T, the controller sends unicast “I-Am” on behalf of all the unitary controllers that are connected to its channel.

Block unconfirmed private messages

Press T to restrict unconfirmed BACnet private messages from IP network entering to MSTP network.

Block broadcast queries from unitary network

Press T to restrict BACnet broadcast queries such as “Who-Is” or “Who-Has” from MSTP to IP network. However, enabling this filter does not restrict broadcast “I-Am” from unitary controllers in MSTP network to the IP network.

The main purpose of this filter is to restrict unwanted messages created in the IP network as a result of the BACnet broadcast queries from unitary controllers, which creates heavy network load and hence MSTP devices are shown offline.

Block broadcast discovery from IP network

Press T to restrict unconfirmed broadcast messages (I-Ams) from the IP network to MSTP channel.

NOTE:

After setting this parameter to T state, all “I-Am” messages from IP devices are blocked from entering the MSTP network. Eventually, this does not allow the devices on the MSTP network to report alarms, if any. However, you can still configure the IP devices in order to receive alarms from unitary controllers. See the Setting the Alarm Recipient Details section on page no. 70 section.

Block local unconfirmed messages

Press T to restrict the local broadcast messages from MSTP channel to IP network and other MSTP channels.

Typically, the value is set to T if the network traffic has not improved after setting the “Block broadcast discovery from IP network” option to T state.

Enable sending Unicast I-Ams (Single flag common to all channels)

Press T to deliver the “I-Ams” response only to the device or workstation that initiated the “Who-is” message.

41

Page 44: COMFORTMAN - Honeywell Россия

4 – PORT OVERVIEW

Disable routing functionality

Press T to disable the routing functionality of the controller.

Typically, the value is set to T if a controller does not have any MSTP devices connected under its channels or during maintenance activities where the MSTP device(s) needs to be excluded from the network.

Settings Action

42 www.honeywell.com/buildingsolutions

Page 45: COMFORTMAN - Honeywell Россия

5

System Resource Usage

This chapter describes the system resource usage option of ComfortMan.

Related Topic

Viewing the System Resource Usage

43

Page 46: COMFORTMAN - Honeywell Россия

5 – SYSTEM RESOURCE USAGE

Viewing the System Resource UsageTo view system resource usage

1. On the ComfortMan main screen, press 3. The System Resource Usage Monitor screen appears with the following details.

• Task Usage Monitor

• System Message Queue/Pool Monitor

• Ethernet Statistics

• Memory Usage Monitor

Figure 32 System Resource Usage Monitor

2. Press 1 to monitor the usage task.

The Task Usage monitor screen appears. It displays the Task ID, Task Name, Status, and

Priority of all the tasks.

44 www.honeywell.com/buildingsolutions

Page 47: COMFORTMAN - Honeywell Россия

VIEWING THE SYSTEM RESOURCE USAGE

Figure 33 Task Usage Monitor

3. Press Q to exit the Task Monitor Usage screen.

4. On the System Resource Usage Monitor screen, press 2.

The System Message (Q) Monitor screen appears. It displays the maximum limit size of

message queues and used message queues.

Figure 34 System Message (Q) Monitor

45

Page 48: COMFORTMAN - Honeywell Россия

5 – SYSTEM RESOURCE USAGE

5. On the System Resource Usage Monitor screen, press 3.

The Ethernet Statistics screen appears. It lists out the following information.

• The number of bytes transmitted and received.

• The number of packets dropped during communication.

• The number of errors during communication.

• The number of packets transmitted and received.

Figure 35 Ethernet Statistics

6. On the System Resource Usage Monitor screen, press 4.

The Memory Usage Monitor screen appears. It displays the current status of memory

usage in the system.

46 www.honeywell.com/buildingsolutions

Page 49: COMFORTMAN - Honeywell Россия

VIEWING THE SYSTEM RESOURCE USAGE

Figure 36 Memory Usage Monitor

47

Page 50: COMFORTMAN - Honeywell Россия

5 – SYSTEM RESOURCE USAGE

48 www.honeywell.com/buildingsolutions

Page 51: COMFORTMAN - Honeywell Россия

6

A9 Process Monitor

This chapter describes managing the A9 process monitor option.

A9 process monitor helps you to manage and monitor A9 Linux’s memory, process, files, and kernel logs.

Related Topic

Viewing the A9 Process Monitor

49

Page 52: COMFORTMAN - Honeywell Россия

6 – A9 PROCESS MONITOR

Viewing the A9 Process MonitorTo view the A9 process monitor

1. On ComfortMan Main Menu press 4.

The A9 Process Monitor User Mode screen appears.

Figure 37 A9 Process Monitor

2. Press 1 to view the total running time of Linux. It is similar to Linux uptime detail.

3. Press 2 to view the processor activity of your Linux box and tasks managed by the kernel in

real time.

4. Press 3 to view the information about currently running processes including its PIDs.

5. Press 4 to view available free memory status.

6. Press 5 to view a long listing of the available folder.

7. Press 6 to view the file contents details.

8. Press 7 to delete the files created by the user.

9. Press 8 to modify the system log file.

10.Press 9 to display the kernel log.

11.Press A to reboot the controller.

12.Press Q to go back to the previous screen.

50 www.honeywell.com/buildingsolutions

Page 53: COMFORTMAN - Honeywell Россия

7

Trace Channel Monitor

This chapter describes managing the trace channel monitor option of the ComfortMan.

Related Topics

Viewing the Trace Channel Monitor

51

Page 54: COMFORTMAN - Honeywell Россия

7 – TRACE CHANNEL MONITOR

Viewing the Trace Channel MonitorTo view Trace Channel Monitor

1. On the ComforMan main screen, press 5.

The Trace Channel Monitor screen appears.

Figure 38 Trace Channel Monitor

2. Press 1 to view the Enable/ Disable Task Trace Channel Output screen.

You can use the Trace Channel option for the following:

• To view the logs for a particular, some, or all the Tasks.

• To view the log information for some, or all the RACL Blocks.

52 www.honeywell.com/buildingsolutions

Page 55: COMFORTMAN - Honeywell Россия

VIEWING THE TRACE CHANNEL MONITOR

Figure 39 Enable/ Disable Task Trace Channel Output

53

Page 56: COMFORTMAN - Honeywell Россия

7 – TRACE CHANNEL MONITOR

54 www.honeywell.com/buildingsolutions

Page 57: COMFORTMAN - Honeywell Россия

8

Application Information

This chapter describes managing the application information option of ComfortMan.

Related Topics

Viewing the Application Information

Viewing the Admin Info

Viewing the Application Summary

Viewing the Point DB Info

Viewing the IO Comm Info

Viewing the Data Sharing Information

Viewing the Schedule Info

Viewing the Trend Log Objects Info

Viewing the Daylight Saving Info

Setting the Alarm Recipient Details

Viewing the C-Bus Sharing Information

55

Page 58: COMFORTMAN - Honeywell Россия

8 – APPLICATION INFORMATION

Viewing the Application InformationTo view the controller application information

1. On the ComforMan main screen, press 6.

The Application Information page appears with the following options.

• Admin Info

• Application Summary

• Point DB Info

• IO Comm Info

• Data Sharing Info

• Schedule Info

• Trend Log Objects Info

• Daylight Saving Info

• Alarm Recipient Details

• C-Bus Shr Info

• Quit

Figure 40 Application Information Screen

56 www.honeywell.com/buildingsolutions

Page 59: COMFORTMAN - Honeywell Россия

VIEWING THE ADMIN INFO

Viewing the Admin InfoTo view Admin Info

1. On the Application Information screen, press 1.

The Controller Device Information screen appears with the following information:

• Controller Name

• Controller Location

• BIP Window Size

• BIP APDU:Alarm

• Backup/Restore

• BIP Max Segment

• Backup/Restore

• Application OS Version

• RACL Binary Version

• Max No of Client Devs

• Time Region (UTC Offset)

• MSTP PARAMETER 

• Max MSTP Masters

• MSTP MAX Info

NoteUnicode strings are not supported in ComfortMan.

Figure 41 Admin Info

2. Press Q to go back to the previous screen.

57

Page 60: COMFORTMAN - Honeywell Россия

8 – APPLICATION INFORMATION

Viewing the Application SummaryTo view the Application Summary

1. On the Application Information screen, press 2.

The Application Summary screen appears.

Figure 42 Application Summary

58 www.honeywell.com/buildingsolutions

Page 61: COMFORTMAN - Honeywell Россия

VIEWING THE POINT DB INFO

Viewing the Point DB InfoTo view the Point DB Info

1. On the Application Information screen, press 3.

The Zone Point Database Information screen appears.

Figure 43 Zone Point Database Info

2. On the Zone Point Database Information screen, press 1.

The Zone Point Database Information displays the notification class details of the

controller.

The controller supports 3 notification classes - Urgent, High, and Low, and also the custom

notification class. The following details of Notification Classes are displayed.

• Notification Class Number

• Notification Class Object Name

• Notification Class Object Id

59

Page 62: COMFORTMAN - Honeywell Россия

8 – APPLICATION INFORMATION

Figure 44 Notification Class Info

By selecting a Notification Class, the following details will be displayed.

• Priority

• Acknowledge Required Status

• Recipient List Details

Figure 45 Notification Class Details without Recipient

60 www.honeywell.com/buildingsolutions

Page 63: COMFORTMAN - Honeywell Россия

VIEWING THE POINT DB INFO

Figure 46 Notification Class Details with Recipient

Recipient List detail for that corresponding Notification Class Object will have the following

properties

• Recipient's Device Instance

• Process Identifier

• Valid days

• Transaction Enabled Status

• Confirmed /Un Confirmed Notification Flag

• Duration for which the Notification is enabled for that recipient

Alarm for Revision 1.14This option provides support for the controller to enable or disable Change of Reliability (COR) for faults to clients as per BACnet Revision 1.14 and 1.12 respectively.

This option set to Disabled will disable COR reporting as per BACnet Revision 1.12 to support faults reporting to EBI.

This option set Enabled will enable COR reporting as per BACnet Revision 1.14 to support faults reporting to third-party BACnet supervisors / frontends.

NoteController needs to be restarted after the selection to apply the settings.

61

Page 64: COMFORTMAN - Honeywell Россия

8 – APPLICATION INFORMATION

Figure 47 Alarm for Revision 1.14

62 www.honeywell.com/buildingsolutions

Page 65: COMFORTMAN - Honeywell Россия

VIEWING THE IO COMM INFO

Viewing the IO Comm InfoTo view IO Comm Info

1. On the Application Information screen, press 4.

The IO 4 PNT Characteristics Information screen appears. This information is configured

from the configuration tool for the Analog Input and Output Points.

Figure 48 IO Four Point Characteristics Information

2. If more 4 PNT characteristics are configured, then press the Space bar to go to the next

page to view other 4PNT characteristics.

3. The Characteristic ID is mentioned for each point in the IO Board details page. You can

identify the voltage value reference for the IO Point by mapping the Characteristic ID in this

page with the one identified from the IO Board details page.

63

Page 66: COMFORTMAN - Honeywell Россия

8 – APPLICATION INFORMATION

Viewing the Data Sharing InformationTo view the Data Sharing Information

1. On the Application Information screen, press 5.

The Point Sharing Summary screen appears which displays the status of each of the data

sharing entry done to/from the device. It is useful when sharing from any of the controllers

does not work.

Figure 49 Data Sharing Information

The data sharing summary table displays the following:

• The number of devices that this device is sharing as source, destination, third party

source, and third-party destination.

• The number of shares this device is having as source, destination, third party source, and

third party destination.

• The number of errors in each of the source, destination, third party source, and third

party destination shares.

The data sharing view has four options

• D- Device List - Press D to view the list of shared devices. Press S to know the share point

details of a particular shared device.

• S/R - Stop/Resume Polling - Press S to stop the polling of the third party points. Press R

to resume.

When you perform the data sharing between two controllers (a controller as the source controller and any ComfortPoint Open family of controllers or a third-party device as the destination controller), the point sharing count indicates two entries in the Share Entries window. The datapoint writes the value in the destination controller at two different priorities. This window helps you to determine the values written at different priorities in the destination controller.

The following figure shows two entries of the point sharing.

64 www.honeywell.com/buildingsolutions

Page 67: COMFORTMAN - Honeywell Россия

VIEWING THE DATA SHARING INFORMATION

Figure 50 Data Sharing Information

Figure 51 Data Sharing Information

NoteThe code 7FFC0000 indicates:

The point in the destination controller is not updated with the source controller's point since the value is not changed in the source controller point. This is expected behavior and not an error code.

65

Page 68: COMFORTMAN - Honeywell Россия

8 – APPLICATION INFORMATION

Viewing the Schedule InfoTo view Schedule Info

1. On the Application Information screen, press 7.

The Point Schedule Details screen appears which helps you to find out the next time of

change and the next change of value, in the Schedule.

Figure 52 Schedule Info

2. Press T to see the schedule details and next time of value.

66 www.honeywell.com/buildingsolutions

Page 69: COMFORTMAN - Honeywell Россия

VIEWING THE SCHEDULE INFO

Figure 53 Schedule Info

In this example, the 10:0 -> 35 0 represents:

- 10:00-Time (in hh:mm 24hrs format) the schedule is set.

- 35: New value which is updated.

- 0: Present value.

- Present value refers to priority array value at 15th priority

3. Press D to set the delay time (min: 1 sec, max: 30 sec). Any changes to the existing schedule

will be calculated only after the specified delay time.

67

Page 70: COMFORTMAN - Honeywell Россия

8 – APPLICATION INFORMATION

Viewing the Trend Log Objects InfoThe Trend Log Info screen is a useful menu in the concept of Trending. It is used for identifying how many Trend Log Objects are configured for this controller and the property of each and every Trend Log Objects.

To view Trend Log Objects Info

1. On the Application Information screen, press 8.

The Trend Log Objects Details screen appears with the following information.

• ObjectID – Trend LogObject Instance ID.

• Obj Ref – Object Instance ID of the Point configured in Trend.

• Total Record Count from the time, trend log object is created.

• Current Record Count from the time, the controller is restarted/Online.

• StopWhenFull – Flag to indicate whether overwrite is allowed after the buffer reaches

full.

• LogEnableFlag

• Start Time.

• Stop Time.Figure 54 Trend Log Object Details

68 www.honeywell.com/buildingsolutions

Page 71: COMFORTMAN - Honeywell Россия

VIEWING THE DAYLIGHT SAVING INFO

Viewing the Daylight Saving InfoTo view the Daylight Saving Info

1. On the Application Information screen, press B.

The Time Zone Regions screen appears which displays the time zone region being set for

the controller with the following options:

• D – User Choice – It displays the DLS Offset change data and time for the next 22 entries

• N – Next Change – Gives the information about Next DLS Change for the given Time

Zone.Figure 55 Viewing Daylight Saving Info

69

Page 72: COMFORTMAN - Honeywell Россия

8 – APPLICATION INFORMATION

Setting the Alarm Recipient DetailsThis section allows you to enable the MSTP device alarms to be sent to BACnet IP clients in spite of enabling the “Block broadcast discovery from IP network” filter. See the Setting the Router Configurations section on page no. 40.

To set Alarm Recipient details

1. On the Application Information screen, press B.

The following screen appears.

2. Press C to provide the IP address of BACnet IP clients.

3. Follow the instructions provided on the screen to enter the IP addresses. A maximum of 3

alarm recipient BACnet IP clients (EBI point server or BACnet workstation) is allowed.

This allows the ‘I-Am’ messages from BACnet IP clients whose IP addresses are provided.

NoteUse option D to delete the IP address from the list and Q to exit the screen and return to the previous screen.

Figure 56 Viewing Alarm Recipient Details

70 www.honeywell.com/buildingsolutions

Page 73: COMFORTMAN - Honeywell Россия

VIEWING THE C-BUS SHARING INFORMATION

Viewing the C-Bus Sharing InformationTo view the C-Bus sharing information

1. On the Application Information screen, press D.

The C Bus Share Entries screen appears.

Figure 57 C-Bus Sharing Information

The C-Bus data sharing summary table displays the following:

• No. Of Devices: The number of devices which is being shared with this device as source, destination, global source, and global destination.

• No. Of Shares: The number of shares this device is having as source, destination, global source, and global destination.

2. Press D to view the list of shared devices.

The Shared Device List screen appears.

71

Page 74: COMFORTMAN - Honeywell Россия

8 – APPLICATION INFORMATION

Figure 58 C-Bus Sharing Information

3. Press S to know the share point details of a particular shared device.

Figure 59 C-Bus Sharing Information

4. Enter the device number of the device whose sharing details are required.

The sharing details of the selected device are displayed.

72 www.honeywell.com/buildingsolutions

Page 75: COMFORTMAN - Honeywell Россия

VIEWING THE C-BUS SHARING INFORMATION

Figure 60 C-Bus Sharing Information

5. Press Space bar for the next page and press Q to return to the main screen.

73

Page 76: COMFORTMAN - Honeywell Россия

8 – APPLICATION INFORMATION

74 www.honeywell.com/buildingsolutions

Page 77: COMFORTMAN - Honeywell Россия

9

Command Shell

This chapter describes the command shell option of ComfortMan.

Related Topics

Viewing the Command Shell

Using the Commands in Command Shell

Using the np option

Using the ping option

Using the appdel option

75

Page 78: COMFORTMAN - Honeywell Россия

9 – COMMAND SHELL

Viewing the Command ShellYou can perform low-level commands in the controller using the Command Shell.

To view the Command Shell Display

1. Open the ComforMan main screen, press 7.

The Command shell screen appears.

Figure 61 Command Shell Prompt

CautionThe command Shell must be used only by an Expert user. Using the commands without expertise, might destroy the firmware and prevent the controller from working.

76 www.honeywell.com/buildingsolutions

Page 79: COMFORTMAN - Honeywell Россия

USING THE COMMANDS IN COMMAND SHELL

Using the Commands in Command ShellTo view the available commands

• On the Command Shell screen, type help or press ? on the keyboard. The command shell options vary depends on the mode you logged in.

• When you press ? on the keyboard or type help in the command prompt, it initially displays the controller Firmware version and then lists the possible options in that mode.

• The Engineering mode option and user mode options are given in the below figures.

Figure 62 Command Prompt Shell Options in Engineering Mode

77

Page 80: COMFORTMAN - Honeywell Россия

9 – COMMAND SHELL

Using the np optionThe np option is related to the Network Parameter Configuration.

To view the np option

1. In the Command Shell screen, type np? or np help.

2. Enter display or modify or release or exit to view respective options.

Figure 63 np Command in the Command Shell

• Display option provides the current basic network parameters like MAC address, IP address, Network Mask, and Gateway. Use the other options only in case you want to change requirements.

• Modify option allows modifying any or all the basic network parameters. Here the user can make use of DHCP option as well wherein the controller will join the IP Network without pre-configured IP Address. After saving the changes, the controller restarts and gets adopted based on the changes made. For example, if you have modified the IP address, then after restart you have to again connect using the modified IP Address.

Note: For a factory controller, the IP-Address Mode (DHCP/manual) is shown as Invalid. Please enter manual to configure the IP address manually.

• Release option allows you to release the IP address of the controller which is assigned by the DHCP server.

• Renew option allows you to renew the controller IP address.

• Exit option allows you to exit the basic network parameter menu.

78 www.honeywell.com/buildingsolutions

Page 81: COMFORTMAN - Honeywell Россия

USING THE NP OPTION

Figure 64 Display and Modification of basic Network Parameters

79

Page 82: COMFORTMAN - Honeywell Россия

9 – COMMAND SHELL

Using the ping optionYou can use the ping option to ping the controller IP address.

To use the ping option

1. On the Command Shell screen, type ping and followed by IP of the controller.

80 www.honeywell.com/buildingsolutions

Page 83: COMFORTMAN - Honeywell Россия

USING THE APPDEL OPTION

Using the appdel optionYou can use appdel option to delete the application present in the controller.

To use the appdel option

1. On the Command Shell screen, type appdel.

81

Page 84: COMFORTMAN - Honeywell Россия

9 – COMMAND SHELL

82 www.honeywell.com/buildingsolutions

Page 85: COMFORTMAN - Honeywell Россия

10

Board Restart

This chapter describes how to restart the board.

Related Topic

Restarting the Controller

83

Page 86: COMFORTMAN - Honeywell Россия

10 – BOARD RESTART

Restarting the ControllerTo remotely restart the controller

1. On the ComfortMan Main screen, press 8.

The System Restart page appears.

2. Press Y, to restart the controller.

The Telnet connection also closes simultaneously. After the controller becomes Online

again, you can start the ComfortMan.

Figure 65 System Restart

84 www.honeywell.com/buildingsolutions

Page 87: COMFORTMAN - Honeywell Россия

11

Logout

This section describes how to log out from ComfortMan.

Relate Topic

Logging out from ComfortMan

85

Page 88: COMFORTMAN - Honeywell Россия

11 – LOGOUT

Logging out from ComfortManYou must follow the procedure to log out from ComfortMan.

To log out from ComfortMan

1. On the ComfortMan main screen, press 9.

If you are on any other screen, you must navigate back to ComfortMan main screen to logout.

86 www.honeywell.com/buildingsolutions