Page 1: Comfort Control TAC Installation Manual - LUNOS · Comfort Control TAC Installation Manual. Contents Page: About this manual Read this manual carefully and completely before assembly

Comfort Control TAC Installation Manual

Page 2: Comfort Control TAC Installation Manual - LUNOS · Comfort Control TAC Installation Manual. Contents Page: About this manual Read this manual carefully and completely before assembly

Contents Page:

About this manual

Read this manual carefully and completely before assembly. Always observe the general safety in-

structions and the safety symbols with information in the text.

Hand out this manual to the user (tenants, proprietors, property management etc.) after completing

assembly.

Symbols in this manual

2

About this manual 2 Safety Instructions, Technical data, Disposal 3 Application 4 Dimension drawing 6 Shipping unit 7 Operating range 8 Assembly: Provision electronics box and cable 9 Electrical connection 10 Assembly: CO2 sensor type SCO2 -TAC 21 Final assembly 22 Commissioning 24 Changing the names of outlets 25 USB connection, firmware update and reset key 26 Accessories 27

This symbol warns you against risks of injury. This symbol warns you against risks of injury from electricity.

Page 3: Comfort Control TAC Installation Manual - LUNOS · Comfort Control TAC Installation Manual. Contents Page: About this manual Read this manual carefully and completely before assembly

Safety instructions

Caution! Any assembly work to the ventilation device may only be carried out after disconnecting all poles of the supply voltage. The ventilation device is fitted with protective insulation according to Protection Class II, a protective conductor connection is not required.

Attention! The electric connection may only be made by authorised qualified personnel and according to the applicable version of VDE 0100.

Attention! This device must not be operated by children and persons (filter replacement/cleaning) who are not able to operate the device safely due to their physical, sensory or mental abilities or their inexperience or lack of knowledge. Children should be supervised to ensure that they do not play with the device.

Attention! In the case of installation in connection with heat systems dependent on room air, the ventila-tion units must be separated from the mains voltage via a safety device when deactivated.

Technical data

Supply Voltage: 100-240 VAC; 50-60 Hz Output voltage: 12 VDC SELV Protection Class: IP 22

Disposal

The packaging must be sorted before disposal. If you wish to dispose of the ventilation device, observe the current regulations. The competent municipal authority will provide information.

3

Page 4: Comfort Control TAC Installation Manual - LUNOS · Comfort Control TAC Installation Manual. Contents Page: About this manual Read this manual carefully and completely before assembly

Application

The TAC comfort control serves to provide common triggering for ventilation units of the company LUNOS with different functionality:

Ventilation with heat recovery

Exhaust air

Supply air

The TAC is fitted with a standard humidity/temperature sensor. A CO2 sensor can also be purchased as an optional accessory. Important: The TAC has three inlets and three outlets. If required, you can connect switches or push-buttons directly to the inlets (contact voltage range 100 to 240 VAC) and allocate the outlets via configuration software. When using the universal control 5/UNI-FT in connection with the TAC you can only connect push-buttons to the 5/UNI FT. You can trigger only one ventilation unit type with the same funtion via the outlets. The basic number of possible devices which can be connected per outlet is displayed in the adjacent table. Which and how many devices are to be connected, and in which way, is normally defined by planning and the respective configuration code.

4

Page 5: Comfort Control TAC Installation Manual - LUNOS · Comfort Control TAC Installation Manual. Contents Page: About this manual Read this manual carefully and completely before assembly

Fan type Connection Number of units

e²/e²neo directly to 2 outlets 2 pairs

via 1 x 5/UNI-FT to one outlet 3 pairs with power supply 18 W or 5 pairs with power supply 60 W

ego directly to 2 outlets 2 units

Via 1 x 5/UNI-FT to one outlet 3 units with power supply 18 W or 5 units with power supply 60 W

directly to 1 outlet* 1 unit RA 15-60

via 1 x 5/UNI-FT to one outlet 1 unit with power supply 18 W or 2 units with power supply 60 W

Silvento ec directly to 1 outlet 1 unit

Silvento 30/60 with 1 x 5/ACM to 1 outlet 1 unit

AB 30/60 with 1 x 5/ACM to 1 outlet 1 unit

Connection of several 5/UNI-FT or 5/ACM to one outlet is possible. *when a RA 15-60 is directly connected to 1 outlet, additional RA 15-60 can only be connected via 5/UN-FT to other outlets.

5

Page 6: Comfort Control TAC Installation Manual - LUNOS · Comfort Control TAC Installation Manual. Contents Page: About this manual Read this manual carefully and completely before assembly

Dimension drawing

TAC installed in electronics box (Dimensions in mm)

73 20

155

140

97

67

6

Page 7: Comfort Control TAC Installation Manual - LUNOS · Comfort Control TAC Installation Manual. Contents Page: About this manual Read this manual carefully and completely before assembly

Shipping unit

Please check the supplies for completeness and mint condition

Display of the basic electric connection and the documents required

Electronics box

TAC sub-frame

TAC Top Piece

Top piece and sub-frame are connected via 2 screws

Installation manual

+ Operating manual

+ USB cable

7

Page 8: Comfort Control TAC Installation Manual - LUNOS · Comfort Control TAC Installation Manual. Contents Page: About this manual Read this manual carefully and completely before assembly

8

Operating range

Operating temperature range: 15°C – 40°C Operating humidity range: max. 65% relative humidity, non-condensing Recommended installation location: Living and sleeping areas Do not install in bathrooms, kitchens or damp locations

Page 9: Comfort Control TAC Installation Manual - LUNOS · Comfort Control TAC Installation Manual. Contents Page: About this manual Read this manual carefully and completely before assembly

Assembly: Provision electronics box and cable

Install the electronics box in hori-zontal position at a recommended height of installation of approx. 1.5 m from the ground. Prepare all cables required in the respective cross-section in accordance with the plan. Connect the TAC sub-frame in accordance with the plan and the connection diagrams.

Insert cable

9

Page 10: Comfort Control TAC Installation Manual - LUNOS · Comfort Control TAC Installation Manual. Contents Page: About this manual Read this manual carefully and completely before assembly

Safety instructions

Caution! Installation work must only be carried out when the mains voltage has been completely disconnected. Make sure that all connection lines are disconnected and de-energized before connecting the TAC and the ventila-tion units (separation from mains with at least 3 mm contact opening, e.g. electric fuse). Each circuit connected to the fans must be fitted with residual current protection (e.g. FI switch/RCD switch). Electric connection only by a specialist.

Additional installations and electrical components in the ventilation systems are not admissible. Other connection diagrams available on request.

Electrical Connection

Use the following cables for electrical connections:

Cable to the ventilation units e.g. J-Y(St)Y(2x2x0.8), max. 1.5 mm²

Cable for connection to comfort control TAC: e.g. J-Y(St)Y(2x2x0.8), max. 1.5 mm²

Cable for supply voltage e.g. NYM 3 x 1.5 mm²

10

Page 11: Comfort Control TAC Installation Manual - LUNOS · Comfort Control TAC Installation Manual. Contents Page: About this manual Read this manual carefully and completely before assembly

Outlets for direct connection of fans; connection of fans to the universal control 5/UNI-FT or the additio-nal module 5/ACM

Basic connection 1

12 V + - 0-10 V

0-10 V - + 12 V

+12 V - 0-10 V

A1

A3

A2

E1 E2 E3 = Switch inlets 100-240 VAC 50/60 Hz

11

100-240 VAC 50/60 Hz

L N

Page 12: Comfort Control TAC Installation Manual - LUNOS · Comfort Control TAC Installation Manual. Contents Page: About this manual Read this manual carefully and completely before assembly

Connection TAC

Connection of universal control 5/UNI-FT 2

0

Coding switch: Select program in accordance with the ventilation systems connected, e.g. e²: Programs 3 or 4

grey red black

+ 12V

-

+ 12V

-

0-10V

Voltage supply from mains power supply

If a push-button is not connec-ted, all functions are controlled via the TAC. Important: If a push-button is connected, the same pro-gram as at the TAC must be set at the coding switch!

To the ven-tilation units

red + blue - purple S1 red + blue - purple S2

12

Page 13: Comfort Control TAC Installation Manual - LUNOS · Comfort Control TAC Installation Manual. Contents Page: About this manual Read this manual carefully and completely before assembly

Direct connection e² 3

L N

Unit 1;3;5 Unit 2;4;6 From/To To/From

rd bl pu rd bl pu

+ - 0-10 V + - 0-10 V

13

Page 14: Comfort Control TAC Installation Manual - LUNOS · Comfort Control TAC Installation Manual. Contents Page: About this manual Read this manual carefully and completely before assembly

Direct connection RA 15-60 4

L

N

+ red - blue 0-10 V purple

14

Page 15: Comfort Control TAC Installation Manual - LUNOS · Comfort Control TAC Installation Manual. Contents Page: About this manual Read this manual carefully and completely before assembly

Direct connection Silvento ec 5

L

N

+ - 0-10 V

L2 L1 L N F+ F-

15

Page 16: Comfort Control TAC Installation Manual - LUNOS · Comfort Control TAC Installation Manual. Contents Page: About this manual Read this manual carefully and completely before assembly

Direct connection ego 6

L

N

+ - 0-10 V + - 0-10 V

16

+ - S1 + - S2

Page 17: Comfort Control TAC Installation Manual - LUNOS · Comfort Control TAC Installation Manual. Contents Page: About this manual Read this manual carefully and completely before assembly

Connection Silvento 30/60 with additional module 5/ACM 7

L

N

Lzu L L1 L2

+ 0-10 V -

+ - 0-10 V

L2 L1 L N F+ F-

17

Page 18: Comfort Control TAC Installation Manual - LUNOS · Comfort Control TAC Installation Manual. Contents Page: About this manual Read this manual carefully and completely before assembly

Connection AB 30/60 with additional module 5/ACM 8

L

N

+ - 0-10 V

Lzu L L1 L2

+ 0-10 V -

N L L1

18

Page 19: Comfort Control TAC Installation Manual - LUNOS · Comfort Control TAC Installation Manual. Contents Page: About this manual Read this manual carefully and completely before assembly

9

L

N

E1

5/W

Bridge installation side

19

Connection of a switch e.g. 5/W Observe the configuration code (DCC)! e.g. in connection with all types of the fan type series Silvento.

Note: When connecting a switch you can only switch one fan stage or ON/OFF!

Page 20: Comfort Control TAC Installation Manual - LUNOS · Comfort Control TAC Installation Manual. Contents Page: About this manual Read this manual carefully and completely before assembly

E1

L

N

10

20

Connection of a push-button e.g. 5/WT Observe configuration code (DCC)! e.g. in connection with all types of the fan type series Silvento.

Note: When connecting a push-button you can switch several fan stages in series.

e.g. single rocker button 5/WT

Page 21: Comfort Control TAC Installation Manual - LUNOS · Comfort Control TAC Installation Manual. Contents Page: About this manual Read this manual carefully and completely before assembly

Assembly: CO2 sensor type SCO2 -TAC

21

Push the CO2 sensor with its two socket terminal strips onto the pin strips of the control board, as illustrated.

CO2 sensor Socket terminal strip

Pin strip

Control board

Page 22: Comfort Control TAC Installation Manual - LUNOS · Comfort Control TAC Installation Manual. Contents Page: About this manual Read this manual carefully and completely before assembly

Final assembly

Mount the TAC sub-frame into the electronics box using the screws enclosed.

22

Page 23: Comfort Control TAC Installation Manual - LUNOS · Comfort Control TAC Installation Manual. Contents Page: About this manual Read this manual carefully and completely before assembly

23

Connect the top piece and sub-frame to the connector positioned on a flat ribbon cable. Place the top piece on the sub-frame and connect these from un-derneath using the screws provided.

Connector with flat ribbon cable

Page 24: Comfort Control TAC Installation Manual - LUNOS · Comfort Control TAC Installation Manual. Contents Page: About this manual Read this manual carefully and completely before assembly

Commissioning

Apply the mains voltage. After the mains voltage has been connected, the display changes from the circuit diagram to the language selection. After the system language has been selected the display changes to the enter field of the configuration code. Enter the configuration code DCC (refer to plan) or generate the configuration code for your ventilation system with the aid of the planning tool (www.lunos.de) and confirm via “OK“ (press button for approx. 2 seconds). Check operation of the ventilation units connected in accordance with the plan. By pressing the button ““ (press for ca. 3 seconds) you cancel the operation without saving.

24

Page 25: Comfort Control TAC Installation Manual - LUNOS · Comfort Control TAC Installation Manual. Contents Page: About this manual Read this manual carefully and completely before assembly

Changing the names of outlets

Via the configuration code you are provided with the standard term ‚Outlet 1‘, ‚Outlet 2‘ and ‚Outlet 3‘ for the fans connected to the respective outlet. If required, you can adjust this term to your specific needs and give names of the respective rooms to the outlets. This adjustment is easy to do via ‚intuitive‘ operati-on of the TAC: Via the permanently displayed start screen (refer to the title page of this manual), you access the screen for the outlet to be changed via the key „V“ (‚Outlet 1‘, ‚Outlet 2‘ or ‚Outlet 3‘). Here you will find a line ‚Room Allocation‘ which you can access via the keys “V“ and “Λ“ and can activate via “OK“. You will then see a screen in which you can change the preset names. You can delete these via “Delete‘ and can then select one or several names from those offered via “V“ and “Λ“ and confirm your decision via “OK“. You can also number rooms with the same name e.g. Bathroom 1, Bathroom 2 etc. You can leave this screen and return to the start screen by actuating the key ““ several times.

25

Page 26: Comfort Control TAC Installation Manual - LUNOS · Comfort Control TAC Installation Manual. Contents Page: About this manual Read this manual carefully and completely before assembly

26

USB connection, firmware update and reset key

A USB connection and a reset key are located on the underside of the TAC. The USB connec-tion is used for communication with the PC. To update the firmware you need to download the Update file (www.lunos.de). Connect the TAC and PC with the USB cable. Instructions for executing the update are included in each Update file. The reset button serves to enable a restart of the TAC in case of error.

USB connection

Reset key

Page 27: Comfort Control TAC Installation Manual - LUNOS · Comfort Control TAC Installation Manual. Contents Page: About this manual Read this manual carefully and completely before assembly

Accessories

Universal Control 5/UNI-FT Order No.: 040 089 Additional module 5/ACM Order No.: 039 990 One-rocker switch 5/W Order No.: 036 641 One-rocker push-button 5/WT Order No.: 040 010 Two-rocker push-button 5/W2T Order No.: 040 011 CO2 Sensor SCO2-TAC Order No.: 040 000

27

Page 28: Comfort Control TAC Installation Manual - LUNOS · Comfort Control TAC Installation Manual. Contents Page: About this manual Read this manual carefully and completely before assembly

E1

81

01

.16 LUNOS Germany

LUNOS Lüftungstechnik GmbH Phone +49 30 362 001-0 für Raumluftsysteme Fax +49 30 362 001-89 Wilhelmstr. 31 [email protected] 13593 Berlin ∙ Germany www.lunos.de

Notes