CHAPTER 5 - System Protection.pdf

Embed Size (px)

Citation preview

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    1/41

    28/11/2012

    1

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    Earthing System Protection Against Electric Shocks Earth Faults Protection Protection Against Voltage Surges

    2

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    2/41

    28/11/2012

    2

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    Earth : The conductive mass of the Earth, whose e ec r c po en a a any po n s conven ona y taken as zero.

    An earth is defined as a connection to the general mass of earth .

    3

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    (1) Earth electrode

    (2) Earthing conductor

    (3) Protective conductor

    (4) Electrical installation

    (5) Bonding conductor

    (6) Main earthing terminal

    4

    (7) Removable link

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    3/41

    28/11/2012

    3

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    A conductor or other metal is earthed when it s e ec ua y connec e o e genera mass o earth by means of a metal rod or a system of metal water pipes or other conducting object.

    Solidly earthed or Bolted earthed when it is earthed without the intervention of a fuse switch, circuit breaker , resistor, reactor, or solenoid.

    5

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    Earthing is meant by having every item of apparatus an every con uctor s a e prevented from giving rise to earth leakage

    currents . It is carried out by ensuring any metal liable to

    become char e should be earth and ever art of the earthing circuit should be properly installed.

    6

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    4/41

    28/11/2012

    4

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    Other alternatives to earthing that could be

    construction, double insulation and by having an isolation.

    Earthing protects people and equipment from potentially dangerous over voltages and

    in homes, offices, retail outlets and industrial plant.

    7

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    Groundingonnec ng equ pmen an po n s on e ec r ca sys ems

    to the earth or an earth substitute. Purpose is to limit overvoltages between the equipment

    and the earth due to lightning, faults, etc.

    Bonding

    neutral point. Purpose is to limit voltages between equipment and to

    provide a path for ground fault current.

    8

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    5/41

    28/11/2012

    5

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    9

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    Reason (1) Minimise overvoltages

    Lightning strike

    Lightning arrester

    transformerUtility phase conductor

    10

    Service earth rodTransformer earth rod

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    6/41

    28/11/2012

    6

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    Reason (2) Limit voltage potential on equ pmen enc osures

    415V

    Ungroundedmotor frame

    Insulation breakdown

    Groundedmotor frame

    Insulation breakdown

    11

    400V motor

    feeder conductors 240V

    400V motor

    Equipment earthingconductor

    0V

    Earthing surface Earthing surface

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    Reason (3) Provide a low impedance path for au t current

    415V

    Ungrounded

    motor frame

    Insulation

    breakdown

    Grounded

    motor frame

    Insulation

    breakdown

    IF=

    Overcurrentdevices

    Overcurrentdevices

    12

    400V motor

    feeder conductors

    400V motor

    Equipment earthingconductor IF

    IF F

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    7/41

    28/11/2012

    7

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    Designing a safe earthing system means prov ng e eas es an s or es pa or e fault current without exposing a person to electric shock .

    Satisfactory earthing is the most important part of an electrical installation because o eration of all the protective devices depend upon it.

    13

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    The total impedance of the conductor,

    to the earth electrode (earth continuity conductor) measured between the earth electrode and any other part of the installation at supply frequency should not exceed 1.0 .

    . resistance), it is an indication of improper earthing.

    14

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    8/41

    28/11/2012

    8

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    Earth lug terminal rusty Loose wire connection Layers of paint on the electric apparatus Loose connection of earth wire to the plug and

    socket outlet

    Loose connection between conduit and terminal box

    15

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    T = Terre (French word for earth)

    supply connected to earth through an impedancefor isolation.

    N = Neutral (in AC system, the earth point isnormally the neutral point).

    provided by separate conductors).

    C = Combin (neutral and protective functionscombined in a single conductor, PEN).

    16

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    9/41

    28/11/2012

    9

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    TT system (earthed neutral)

    17

    One point at the supply source is connected directly to earth. All exposed andextraneous conductive parts are connected to a separate earth electrode at theinstallation. This electrode may or may not be electrically independent of the sourceelectrode.

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    TNC system

    18

    The neutral conductor is also used as a protective conductor and is referred to as a PEN (Protective Earth and Neutral) conductor.

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    10/41

    28/11/2012

    10

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    TNS system

    19

    The protective conductor and the neutral conductor are separate. Onunderground cable systems where lead sheathed cables exist, the protectiveconductor is generally the lead sheath.

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    TNCS system

    20

    In the TN CS system, the TN C (4 wires) system must never be used downstream of the TN S (5 wires) system, since any accidental interruption in the neutral on theupstream part would lead to an interruption in the protective conductor in thedownstream part and therefore a danger.

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    11/41

    28/11/2012

    11

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    IT system (isolated neutral)

    21

    No intentional connection is made between the neutral point of the supply sourceand earth. Exposed and extraneous conductive parts of the installation areconnected to an earth electrode.

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    IT system (impedance earthed neutral)

    22

    An impedance Zs (in the order of 1,000 to 2,000 ) is connected permanentlybetween the neutral point of the transformer LV winding and earth

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    12/41

    28/11/2012

    12

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    23

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    Simplest solution to design and install. Used ininstallations supplied directly by the public LV distributionnetwor .

    Does not require continuous monitoring during operation.

    Protection is ensured by special devices , the residualcurrent devices (RCD), which also prevent the risk of firewhen they are set to 500 mA.

    Each insulation fault results in an interruption in thesupp y o power, owever e ou age s m e o efaulty circuit by installing the RCDs in series or in parallel.

    Loads or parts of the installation which, during normaloperation, cause high leakage currents , require specialmeasures to avoid nuisance tripping .

    24

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    13/41

    28/11/2012

    13

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    TNC system

    25

    TNS system

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    Requires the installation of earth electrodes at regularintervals throughout the installation.

    Requires that the initial check on effective tripping for thefirst insulation fault be carried out by calculations during thedesign stage, followed by mandatory measurements toconfirm tripping during commissioning.

    Requires that any modification or extension be designed andcarried out by a qualified electrician.

    May result, in the case of insulation faults, in greater damageto the windings of rotating machines.

    May, on premises with a risk of fire, represent a greaterdanger due to the higher fault currents

    26

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    14/41

    28/11/2012

    14

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    27

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    Solution offering the best continuity of service during operation.

    Indication of the first insulation fault, followed by mandatory location and clearing, ensures systematic prevention of supply outages.

    Generally used in installations supplied by a private MV/LV or LV/LV transformer.

    Requires maintenance personnel for monitoring and operation.

    Requires a high level of insulation in the network (implies breaking up the network if it is very large and the use of circuit separation transformers to supply loads with high leakage currents).

    28

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    15/41

    28/11/2012

    15

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    An electric shock is the pathophysiological effect.

    The degree of danger for the victim is a function of the magnitude of the current , the parts of thebody through which the current passes, and theduration of current flow .

    through a human being from one hand to feet, theperson concerned is likely to be killed, unless thecurrent is interrupted in a relatively short time.

    29

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    30Zones time/current of effects of AC current on human body when passing from left hand to feet

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    16/41

    28/11/2012

    16

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    A direct contact refers to a person coming into con ac w a con uc or w c s ve n normal circumstances.

    31

    Is = Touch current

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    An indirect contact refers to a person coming nto contact w t an expose con uct ve part

    which is not normally alive, but has become

    alive accidentally (due to insulation failure or some other cause).

    32

    Id = Insulation fault current

    Is = Touch current

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    17/41

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    18/41

    28/11/2012

    18

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    The earthing of all exposed conductive parts of

    constitution of an equi potential bonding network.

    Automatic disconnection of the supply of the section of the

    35

    , way that the touch voltage/time safety requirements are respected for any level of touch voltage (Vc).

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    Maximum safe duration (disconnecting time ) of

    Vc (V) 50 < Vc 120 120 < Vc 230 230 < Vc 400 Vc > 400

    SystemTN or IT 0.8 0.4 0.2 0.1

    TT 0.3 0.2 0.07 0.04

    e assume va ues o ouc vo age n seconds) not exceeding 32 A:

    36

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    19/41

    28/11/2012

    19

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    37

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    The impedance of the earth fault loop consists mainly . .

    installation electrodes) in series.

    The magnitude of the earth fault current is generally too small to operate overcurrent relay or fuses, and the use of a residual current operated device is

    .

    Protection by automatic disconnection of the supply used in TT system is by RCDof sensitivity:

    38 A

    n R

    I 50

    RA is the resistance of the earth electrode for the installation

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    20/41

    28/11/2012

    20

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    39

    TNC

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    In all TN systems, any insulation fault to earth .

    High fault current levels allow to use overcurrent

    protection but can give rise to touch voltages exceeding 50% of the phase to neutral voltage at the fault position during the short disconnection

    . The use of CB, fuses, and RCDs may be necessary

    on TNearthed systems.

    40

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    21/41

    28/11/2012

    21

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    41

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    A permanent monitoring of the insulation to earth ,

    and/or flashing lights, etc.) operating in the event of a first earth fault.

    During a phase to earth fault , the current passing through the electrode resistance RnA is the vector sum

    .

    The use of CB, fuses, and RCDs may be necessary on ITearthed systems

    42

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    22/41

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    23/41

    28/11/2012

    23

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    For regular houses 40A / 63A, single phase or

    capacity, ELCB's sensitivity is not exceeding 100mA .

    For heater water , it should posses separate additional ELCB (other than no. 1 above) with

    . For load which higher than 100A, 3 phases , ELCB's sensitivity must not exceed 100mA .

    45

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    To load fault

    Circuit Breaker Tri coil

    Current Transformer

    earth

    46

    3wire 3phase suppl y

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    24/41

    28/11/2012

    24

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    During normal operation the current from supply L flows through N1, to the load and then flow through N2 before returning to N.

    and the current through them is also the same the resulting flux in the iron core is zero.

    However, if there is a leakage from the load to the ground, a certain amount of current will flow to the ground.

    As such current through N1 and N2 will not be the same resulting in some magnetic flux setting up in the core.

    The fault sensing winding will trip the tripping device if

    the leakage current falls within 10 to 100 milliampere. A test circuit consisting of a push button and a test resistor is normally included in the ELCB as shown. Its function is to create an unbalance current in the N1 and N2 windings, and the current flow through the test resistor is great enough for the fault sensing winding to trip the circuit breaker.

    47

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    There are two main reasons why RCDs are used: To provide additional and a higher level of protection than

    that given by direct earthing, against electric shock and alsoagainst fire risk caused by earth leakage currents. Wherefuses and miniature circuit breakers (MCBs) are the only

    means of earth fault protection, it is possible for earth faultcurrents to flow undetected and cause fire risk (or touchvoltage problems).

    The use of an RCD will prevent the flow of a sustained

    greatly reducing shock and fire risk. All live conductors inthe protected circuits should be disconnected in the eventof earth leakage current flowing .

    48

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    25/41

    28/11/2012

    25

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    Terms associated with RCDs: RCCB:

    Residual Current Circuit Breaker used in distribution boards to protect individual or groups of circuits

    RCBO:Residual Circuit Breaker with overcurrent protection. This is a combined MCB/RCD and provides overload, short circuit and earth fault protection in one unit

    Socket outlet with combined RCD

    PRCD:This is a portable RCD unit with an inbuilt plug top and socket outlet

    49

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    Single Phase RCD

    LOAD

    Neutral

    Phase

    Detection Coil

    50

    Relay

    Test Button

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    26/41

    28/11/2012

    26

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    Three Phase RCD

    EarthedMetalwork

    L1

    L3

    L2

    Test Resistor

    LOAD

    Test Button

    51

    Amplifier

    Magnetic Core

    Trip Relay

    u rDetection Coil

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    Regulation D22 (Basic Earthing Requirements)

    States that earth leakage protection may be provided by means of fuses or excess current circuit breakers if the earth fault current

    available to operate the protective device and so make the faultycircuit dead exceeds:1. 3 times the current rating of any semi enclosed fuse or any

    cartridge fuse having a fusing factor exceeding 1.5 , used to protect the circuit, or

    2. 2.4 times the rating of any cartridge fuse having a fusingfactor not exceeding 1.5 , used to protect the circuit, or

    3. 1.5 times the tripping current of any excess current circuitbreaker used to protect the circuit.

    52

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    27/41

    28/11/2012

    27

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    A single phase 240 V, 15 kW 50Hz motor circuit o eratin at 0.8 ower factor la in is rotected b a cartridge fuse having blowing current of 110 A. A fault occurs in the circuit causes a current of 220 amperes to flow through the earth continuity path. As a result of poor contact due to a lock nut and bush connecting a steel conduit to a metal box, the resistance of this conduit connection alone is 1.35 . State:a) whether the fuse will ruptureb) the amount of heat produced at the metal boxc) the degree of risk, if any, of a fire developing

    53

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    Yes. The rating current:

    Fusing factor:

    AV

    I r 125.78

    8.0240=

    =

    41.1125.78

    110==

    A

    AF

    F

    D22, the protection is by a cartridge having a fusing factor

    not exceeding 1.5. Then the maximum current in the fault is 2.4 x 78.125 A = 187.5 A.

    I2R = (220) 2 x 1.35 Ohms = 65.34 kW. High Risk

    54

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    28/41

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    29/41

    28/11/2012

    29

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    57

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    Atmospheric voltage surges Operating voltage surges Transient overvoltage at industrial frequency Voltage surges caused by electrostatic

    discharge

    58

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    30/41

    28/11/2012

    30

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    Lightning risk. Between 2,000 and 5,000 storms are .

    are accompanied by lightning which constitutes a serious risk for both people and equipment.

    Strokes of lightning hit the ground at a rate of 30 to 100 strokes per second.

    Lightning affects transformers, electricity meters, household appliances, and all electrical and electronic installations in the residential sector and in industry.

    59

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    Lightning discharge values given by the IEC g tn ng protect on comm ttee:

    Beyond peak

    probability P%

    Current peak,

    I (kA)

    Gradient,

    S (kA/ s)

    Total duration

    (s)

    Number of

    discharges n

    95 7 9.1 0.001 1

    50 33 24 0.01 2

    60

    5 85 65 1.1 6

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    31/41

    28/11/2012

    31

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    A sudden change in the established operating con ons n an e ec r ca ne wor causes transient phenomena to occur.

    These are generally high frequency or damped oscillation voltage surge waves.

    61

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    The opening of protection devices (fuse, circuit breaker), and the opening or closing of control devices (relays, contactors, etc.).

    Inductive circuits due to motors starting and stopping, or the opening of transformers such as MV/LV substations.

    Capacitive circuits due to the connection of .

    All devices that contain a coil, a capacitor or a transformer at the power supply inlet: relays, contactors, television sets, printers, computers, electric ovens, filters, etc.

    62

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    32/41

    28/11/2012

    32

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    These overvoltages have the same frequency as the network (50, 60 or 400 Hz).

    63

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    Phase/frame or phase/earth insulating faults on a ,

    or by the breakdown of the neutral conductor . When this happens, single phase devices will be supplied in 400 V instead of 230 V.

    A cable breakdown. For example, a medium voltage cable which falls on a low voltage line.

    The arcing of a high or medium voltage protective spark gap causing a rise in earth potential during the action of the protection devices.

    64

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    33/41

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    34/41

    28/11/2012

    34

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    The purpose of primary protection devices is to

    lightning . They catch and run the lightning current into the

    ground . The principle is based on a protection area determined by a structure which is higher than the rest.

    There are three types of primary protection: Lightning conductors Overhead earth wires The meshed cage or Faraday cage

    67

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    The lightning conductor is a ape e o p ace on top of the building . It is

    earthed by one or more conductors (often copper strips).

    68

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    35/41

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    36/41

    28/11/2012

    36

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    These handle the effects of atmospheric , opera ng or n us r a requency vo age surges.

    They can be classified according to the way they are connected in an installation: serial or

    arallel rotection.

    71

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    This is connected in series to the power supply w res o t e system to e protecte .

    72

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    37/41

    28/11/2012

    37

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    Transformers

    certain harmonics disappear by coupling. This protection is not very effective .

    Filters Based on components such as resistors, inductance

    coils and capacitors they are suitable for voltage surges

    cause y n ustr a an operat on stur ance corresponding to a clearly defined frequency band . This protection device is not suitable for atmospheric disturbance .

    73

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    Wave absorbers They are essentially made up of air inductance coils

    which limit the voltage surges, and surge arresters

    which absorb the currents . They are extremely suitable for protecting sensitive electronic and computing equipment.

    74

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    38/41

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    39/41

    28/11/2012

    39

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    Main characteristics

    correspond to the network voltage at the installation terminals.

    When there is no voltage surge , a leakage current should not go through the protection device which is on standby .

    When a voltage surge above the allowable voltage

    , protection device abruptly conducts the voltage surge current to the earth by limiting the voltage to the desired protection level, Vp.

    77

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    When the voltage surge disappears, the protection

    without a holding current. This is the ideal U/I characteristic curve : The protection device response time (t r) must be as short

    as possible to protect the installation as quickly as possible.

    e pro ec on ev ce mus ave e capac y o e a e to conduct the energy caused by the foreseeable voltage surge on the site to be protected.

    The surge arrester protection device must be able to withstand the rated current , In.

    78

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    40/41

    28/11/2012

    40

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    (1) Voltage limiters They are used in MV LV

    substations at thetransformer output, inIT earthing scheme.

    surges to the earth,especially industrialfrequency surges.

    79

    BEX 42803/ BEF 33203/ BEE 4213 Utilisation of Electrical Energy

    (2) LV surge arresters

    Low voltage surge arresters come in the form of modules to be installed inside LV switchboard .

    They ensure secondary protection of nearby elements but have a small flow capacity.

    ome a e even u n o oa s a oug ey cannot protect against strong voltage surges.

    80

  • 7/28/2019 CHAPTER 5 - System Protection.pdf

    41/41