Upload
ngotuyen
View
229
Download
6
Embed Size (px)
Citation preview
37
CHAPTER 3
EXPERIMENTAL INVESTIGATION
3.1 PROPERTIES OF MATERIALS USED
For designing the concrete mix, preliminary tests as per Bureau of
Indian standards (BIS) were conducted to find out the basic properties of
cement, fine aggregate and coarse aggregate used in this research. pH value of
potable tap water used was 7.54 (greater than 6) conforming to IS: 456-2000.
The test results are shown in Table 3.1.
Table 3.1 Test results of Concrete Ingredients
Material Property Average
Test results
Conducted test as per Indian Standards
BIS Cement Fineness test
(% residue on 90µ sieve) 1.26 IS:4031(part-1) 1996
Normal consistency 36% IS:4031(part-4)- 1988 Initial & Final setting time
125 & 230 Min
IS:4031(part-5)- 1988
Specific gravity 3.10 IS:4031(part-11)- 1988 Fine Aggregate
Fineness Modulus 2.42 IS: 383-1970 Zone confirm to II Specific gravity 2.65 IS: 2386 (Part III)
-1963 Moisture content 2.51% Coarse aggregate
Fineness Modulus 7.46 IS: 383-1970 Specific gravity 2.60 IS: 2386 (Part III)
-1963 Water absorption 1.11%
38
3.2 DESIGN OF REFERENCE CONCRETE MIX
Based on preliminary test results as presented in Table 3.1,
Reference concrete mix was designed as per Indian standard method by IS:
10262-1982. The relevant tables are presented in APPENDIX 1.
3.2.1 Design Stipulations
a) Grade of concrete = M20
b) Characteristic compressive strength
Required at 28 days = 20 MPa
c) Maximum size of aggregate =20mm
(Angular)
d) Degree of workability (Compaction factor) = 0.9
e) Degree of quality control = good
f) Type of exposure = mild
g) Specific gravity of cement ( sc ) = 3.10
h) Specific gravity of coarse aggregate ( Sca ) = 2.60
i) Specific gravity of fine aggregate ( Sfa ) = 2.65
j) Water absorption = 1.11%
k) Free surface of moisture of fine aggregate = 2.51%
l) Fine aggregate confirming zone = II
m) Entrapped air content (E air ) = 2%
(Table A.1.6 )
39
3.2.2 Design of Mix
Target Mean Strength
Target mean strength (ft) = fck + 1.65* S (S- Standard Deviation=4, Table A.1.1) = 20 + (1.65x4)
= 26.60 N/mm2
Water Cement Ratio
a. From graph w/c = 0.50 (Figure A.1.1 )
b. From type of exposure w/c = 0.55 (Table A 1.2)
c. Take least value of w/c = 0.50
Selection of Water and Sand Content
Table 3.2 shows the calculation of Adjustment of values in water
content and sand percentage by referring A 1.5. For 20mm size coarse
aggregate and sand confirming to zone II, Water content per cubic metre of
concrete was 186 kg and sand content as percentage of total aggregate by
absolute volume was 35% as per Table A1.3 and 1.4.
Table 3.2 Adjustment of values in water content and sand percentage
Change in condition Adjustment required in
Water content Sand content Sand zone – II – 0
For increasing compaction factor (0.90-0.80) = 0.1
+3
0
For decrease in water content ratio by (0.5-0.6) = -0.10
0
-2
+3% -2%
40
Required water content = 186 +3%
w = 191.58 kg
Required sand content = 35-2
P = 33%
Required cement content for w/c = 0.5,
= 191.58/0.5
C = 383.16 kg
Weight of Fine Aggregate (FA)
F.A = (1000 (1-Eair ) – w – C/sc) P x Sfa
F.A = (1000 (1-2/100) – 191.58 – (383.16/3.1)) x 33/100 x 2.65
= 581.38 kg/m3
Weight of Coarse Aggregate (CA)
C.A = (1000 (1-Eair ) – w – C/sc) (1 – P) x Sca
C.A = (1000 (1-2/100)– 191.58 – (383.16/3.1)) x (1 – 33/100) x 2.60
= 1158.11 kg/m3
Table 3.3 Water Adjustment for Actual Quantities of Different
Constituents
Quantity of water to be
changed
Water Cement Fine aggregate Coarse aggregate
191.58 383.16 581.38 1158.11 Water
absorption of C.A =1.1%
+12.73
–
– -12.73
Free surface moisture
FA =2.51% – 14.59 – +14.59 –
189.72 383.16 595.97 1145.38
41
The quantities of materials per cubic metre of concrete as presented
in Table 3.3 are summarised as below.
a) Cement = 383.16 kg
b) Fine aggregate = 595.97 kg
c) Coarse aggregate = 1145.38 kg
d) Water = 189.72 litres
Table 3.4 Calculation of Reference Concrete Mix Ratio
Cement Fine aggregate Coarse aggregate Water
383.16 595.97 1145.38 189.72
1 1.55 2.98 0.49
From Table 3.4, Reference Mix Ratio, RMX = 1: 1.55: 2.98: 0.49
3.3 PRELIMINARY INVESTIGATIONS
3.3.1 Optimum Dosage of Superplasticiser
Concrete consumption is 10 billion ton per year, which is
equivalent to 1 ton per every living person and hence judicious use of cement
has distinct economic and environmental effect reported by Nataraja et al
(2005). Another report by ACI 212.4R (1993) stated that superplasticisers are
added to economise the cement by simultaneous reduction of cement and
water content of the reference mix. Hence it is aimed to optimize the dosage
of superplasticiser by reducing cement and water content simultaneously,
keeping water-cement ratio constant, by the addition of superplasticiser to the
reference mix (RMX) at plastic and hardened states. Cement and water
content of the reference mix was reduced at a time simultaneously by 5%,
10%, 15% & 20% at each stage, superplasticiser was added at 0.4%, 0.8%,
42
and 1.2% by weight of cement. At each level of reduction of cement & water
with addition of superplasticiser, workability & strength values were
determined and compared.
There were 2 water reducers, 4 levels of cement reduction & 3
dosages of water reducers. Thus (2 x 4 x3 =) 24 mixes were made. The
following tests were conducted on the reference mix. Table 3.5 and Table 3.6
show mix details and quantities of materials used.
a) Slump test and Compaction factor test
b) 7 & 28-days compressive strength test
The quantity of materials required for conducting slump test,
compaction factor test and 7, 28-days compressive strength test were
calculated. The materials (cement, fine aggregate, coarse aggregate and water)
were weighed and taken separately. Cement and sand were first mixed, and
then coarse aggregate was added and thoroughly mixed to form a dry mixture.
Water was then added and mixed until a thorough homogenous mixture was
obtained. Slump test and compaction factor test were done simultaneously
and at the same time, three numbers of 150 mm size concrete cubes were cast
as per IS: 516-1959. The concrete cubes were removed from the moulds after
24 hours and placed in water for curing. At the end of 7th & 28th days from
the date of casting, the cubes were taken out and tested for their 7-days & 28-
days compressive strength in a 200 tonne capacity hydraulic compression
testing machine.
43
Table 3.5 Mix Details
Type MIX MIX DETAILS
REF
EREN
CE
MIX
W
ITH
Org
anic
supe
rpla
stic
iser
ORD1 RMX – 5 % W & C+0.4 % OSP
ORD2 RMX – 5 % W & C+0.8 % OSP
ORD3 RMX – 5 % W & C+1.2 % OSP
ORE1 RMX – 10 % W & C+0.4 % OSP
ORE2 RMX – 10 % W & C+0.8 % OSP
ORE3 R MX– 10 % W & C+1.2 % OSP
ORF1 RMX – 15 % W & C+0.4 % OSP
ORF2 RMX – 15 % W & C+0.8 %OSP
ORF3 RMX – 15 % W & C+1.2 % OSP
ORG1 RMX – 20 % W & C+0.4 % OSP
ORG2 RMX– 20 % W & C+0.8 %OSP
ORG3 RMX – 20 % W & C+1.2 % OSP
REF
EREN
CE M
IX
WIT
H
Nap
htha
lene
supe
rpla
stic
iser
NRD1 RMX – 5 % W & C+0.4 % NSP
NRD2 RMX – 5 % W & C+0.8 %NSP
NRD3 RMX – 5 % W & C+1.2 % NSP
NRE1 RMX – 10 % W & C+0.4 % NSP
NRE2 RMX – 10 % W & C+0.8 %NSP
NRE3 R MX– 10 % W & C+1.2 % NSP
NRF1 RMX – 15 % W & C+0.4 % NSP
NRF2 RMX – 15 % W & C+0.8 % NSP
NRF3 RMX – 15 % W & C+1.2 % NSP
NRG1 RMX – 20 % W & C+0.4 % NSP
NRG2 RMX– 20 % W & C+0.8 % NSP
NRG3 RMX – 20 % W & C+1.2 % NSP
44
Table 3.6 Quantity of Materials used per cubic metre of Concrete
without fibres
MIX Grade of cement
Wt cement per cubic metre of concrete
Fa/c Ca/c W/c %
Dosage of SP
RMX 53 383 1.55 2.98 0.49 0
ORD1 53 363 1.64 3.14 0.49 0.4
ORD2 53 363 1.64 3.14 0.49 0.8
ORD3 53 363 1.64 3.14 0.49 1.2
ORE1 53 345 1.72 3.31 0.49 0.4
ORE2 53 345 1.72 3.31 0.49 0.8
ORE3 53 345 1.72 3.31 0.49 1.2
ORF1 53 326 1.82 3.51 0.49 0.4
ORF2 53 326 1.82 3.51 0.49 0.8
ORF3 53 326 1.82 3.51 0.49 1.2
ORG1 53 306 1.94 3.74 0.49 0.4
ORG2 53 306 1.94 3.74 0.49 0.8
ORG3 53 306 1.94 3.74 0.49 1.2
NRD1 53 363 1.64 3.14 0.49 0.4
NRD2 53 363 1.64 3.14 0.49 0.8
NRD3 53 363 1.64 3.14 0.49 1.2
NRE1 53 345 1.72 3.31 0.49 0.4
NRE2 53 345 1.72 3.31 0.49 0.8
NRE3 53 345 1.72 3.31 0.49 1.2
NRF1 53 326 1.82 3.51 0.49 0.4
NRF2 53 326 1.82 3.51 0.49 0.8
NRF3 53 326 1.82 3.51 0.49 1.2
NRG1 53 306 1.94 3.74 0.49 0.4
NRG2 53 306 1.94 3.74 0.49 0.8
NRG3 53 306 1.94 3.74 0.49 1.2
3.3.2 Test Results and Discussion Tests were conducted on each mix to evaluate both workability and strength values.
45
3.3.2.1 Workability Tests
Slump and compaction factor values at various levels of reduction
are furnished in Table 3.7. It is found from slump test results that at 5%
reduction level of cement and water content, organic based superplasticiser
showed high slump values at the dosage level of 0.8 %. While increasing the
reduction level of cement and water content to 10% and 15%, sulphonated
naphthalene based superplasticiser showed higher slump values at the dosage
levels of 0.4 % and 0.8 %. But at 20% reduction level, very low slump values
were obtained at the dosage level of 0.4% and collapse slump was obtained at
higher dosages of 0.8% and 1.2% of both type of superplasticiser.
Compaction factor test showed that the concrete with naphthalene based
superplasticiser has medium and higher workability at the dosage level of
0.4% and 0.8%. At 20 % reduction level of cement and water content low
workability was obtained at the dosage level of 0.4 %. By overall observation,
it was found that at 15% reduction of cement and water content, concrete had
the highest slump values of 125 mm and 145 mm and compaction factor
values as 0.97 and 0.98 at the dosage level of 0.8% of organic and
naphthalene based superplasticiser respectively.
3.3.2.2 Compressive Strength Test
As the concrete had segregated and collapse slump occurred at 20%
reduction of cement and water content, it was decided to conduct only
strength test on concrete with both types of superplasticisers from 5% to15%
reduction of cement and water content. From the test results shown in Table
3.8, the compressive strength of concrete of reference concrete was found as
27.11 N/mm2 and 37.78 N/mm2 at 7 and 28 days curing respectively. It is
evident from this table that all the concrete mixes had the higher compressive
strength than the reference mix. Hence it is discriminated to choose the
46
concrete mix with low cement content which has higher strength than the
reference mix. Based on the results obtained from workability test and
compressive strength test, optimum dosage of superplasticiser was chosen
from the mix containing minimum dosage of superplasticiser at the level of
maximum reduction of cement and water content. It was found from Tables
3.7 and 3.8 that concrete mix, at the maximum reduction of cement and water
content by 15% with 0.8% dosage of superplasticiser, has higher workability
and compressive strength than reference concrete mix. Hence it was decided
to choose this mix to find optimum dosage of superplasticiser. Based on this
reduction level, the reference mix was revised as 1: 1.83: 3.51: 0.49 with
0.8% superplasticiser and is presented in Table 3.9. The dosage of
superplasticiser at this revised ratio is defind as the optimized dosage of
superplasticiser. Thus dosage of superplasticsier was optimized as 0.8%.
Consequent to the revised mix ratio it was found that about 58 kg of cement
was saved per cubic metre of concrete and hence economical.
Table 3.7 Workability Test Results
Phase Mix
Slump value in mm Compaction factor
Organic based- SP
Naph thalene
based-SP
Organic based- SP
Naph thalene
based- SP 1 REFERRENCE 10 10 0.9 0.9
2
R – 5 % W & C+0.4 % SP 10 15 0.95 0.89
R – 5 % W & C+0.8 % SP 140 85 0.98 0.91
R – 5 % W & C+1.2 % SP (Collapsed) (Collapsed) 1 0.96
R – 10 % W & C+0.4 % SP 40 20 0.92 0.97
R – 10 % W & C+0.8 % SP 80 140 0.93 0.96
R – 10 % W & C+1.2 % SP (Collapsed) (Collapsed) 0.98 0.96
R – 15 % W & C+0.4 % SP 30 25 0.94 0.95
R – 15 % W & C+0.8 % SP 125 145 0.97 0.98
R – 15 % W & C+1.2 % SP (Collapsed) (Collapsed) 0.98 0.94
R – 20 % W & C+0.4 % SP 0 10 0.89 0.911
R – 20 % W & C+0.8 % SP (Collapsed) (Collapsed) 0.93 0.94
R – 20 % W & C+1.2 % SP (Collapsed) (Collapsed) 0.98 0.99
47
Table 3.8 Compressive strength after 7 and 28 days curing
MIX
7 days strength MPa 28 days strength MPa Organic
based- SP Naphthalene
based- SP Organic
based- SP Naphthalene
based-SP Average %imp Average %imp Average %imp Average %imp
REFERRENCE 27.11 - 27.11 - 37.78 - 37.78 - R – 5 % W & C +0.4 % SP 33.48 23.5 35.11 29.5 46.81 23. 9 40.15 6.2 R – 5 % W & C +0.8 % SP 41.33 52.4 36.00 32.8 47.44 25.6 54.52 44.3 R – 5 % W & C +1.2 % SP 42.07 55.1 39.41 45.37 46.44 22.9 47.56 25.88 R – 10 % W &C +0.4 % SP 31.41 15.9 36.44 34.41 38.47 1.8 46.37 22.73 R – 10 % W &C +0.8 % SP 32.2 18.8 33.18 22.4 43.1 14 39.26 3.91 R – 10 % W &C +1.2 % SP 31.11 14.8 40.89 50.8 46.51 23.1 49.33 30.57 R – 15 % W &C +0.4 % SP 37.18 37.1 37.18 37.14 39.7 5.1 43.55 15.2 R – 15 % W &C +0.8 % SP 38.16 40.8 38.52 42.1 40.44 7 40.30 6.67 R – 15 % W &C +1.2 % SP 36.3 33.9 37.78 39.35 44.58 18 42.37 12.14
Table 3.9 Revised Mix ratio at 15 % simultaneous reduction of
cement and water
Cement Fine aggregate Coarse aggregate
Water
383.16 595.97 1145.38 189.72
325.67 595.97 1145.38 161.26
1 1.83 3.5 0.49
Reference Mix ratio RMX = 1: 1.55: 2.98: 0.49
Case A: Revised Mix Ratio OSP = 1: 1.83: 3.51: 0.49 +0.8% SP
Case B: Revised Mix Ratio NSP = 1: 1.83: 3.51: 0.49 +0.8% SP
48
3.4 EXPERIMENTAL PROGRAMME The programme was divided into two cases such as Case A and Case B and Figure 3.1 shows flow chart for experimental programme. Table 3.10 shows the materials used for entire experimental programme.
Table 3.10 Materials Used
Sl No DETAILS QUANTITY
1 Types of Superplasticiser 2
2 Dosage of Superplasticiser 0.8% ( optimized )
3 Types of Fibres 3
4 Volume of Fibre 0%, 0.2%, 0.4%, 0.6%, 0.8% & 1.0%
5 No. of Mixes Proposed 1 x 2 x 1 x 3x 6 = 36 Mixes
CASE A The performance of organic based superplasticiser was evaluated with fibres for mix ratio OSP based on the following phase of tests. PHASE I WORKABILITY TESTS
a) Slump Test
b) Compaction Factor Test
PHASE II STRENGTH TESTS (Before and After Thermoshock)
a) 7 & 28 Days Compressive Strength Test
b) 7 & 28 Days Split Tension Test
c) 28 Days Flexural Strength Test (Third point loading)
d) 28 Days Pull-out Test
e) 28 Days Impact Test
49
PHASE III DURABILITY TESTS (Before and After Thermoshock)
a) 28 Days Water Permeability Test
b) 28 Days Chloride Penetration Test
CASE B
The performance of Naphthalene based superplasticiser was
evaluated with Fibres for mix ratio NSP based on the following phases of
tests.
PHASE I WORKABILITY TESTS
a) Slump Test
b) Compaction Factor Test
PHASE II STRENGTH TESTS (Before and After Thermoshock)
a) 7 & 28 Days Compressive Strength Test
b) 7 & 28 Days Split Tension Test
c) 28 Days Flexural Strength Test (Third point loading)
d) 28 Days Pull-out Test
e) 28 Days Impact Test
PHASE III DURABILITY TEST (Before and After Thermoshock)
a) 28 Days Water Permeability Test
b) 28 Days Chloride Penetration Test
50
FLOW CHART FOR EXPERIMENTAL PROGRAMME
Figure 3.1 Flow Chart for Experimental Programme
OSP=RMX- (15% Water & Cement) + SP Organic Based
RMX-M20 Grade
AR Glass
Polyester
0.2 to 1% (OS1-OS5)
0.2 to 1%
(OG1-OG5)
0.2 to 1%
(OP1- OP5)
NSP=RMX- (15% Water & Cement) + SP Naphthalene Based
AR Glass
Polyester
Steel
0.2 to 1% (NS1- NS5)
0.2 to 1%
(NG1-NG5)
0.2 to 1%
(NP1-NP5)
Workability Test
Strength Test- Before & After Thermoshock Durability Test
Before & After Thermoshock
TEST
[1] Slump Test [2] Compaction Factor Test
[1]7 & 28 Days Compressive Strength Test on Cube and Cylinder specimen [2]7 & 28 Days Split Tension Test [3] 28 Days Flexural Strength Test [4] 28 Days Pull-Out Test [5] 28 Days Impact Test
1] 28 Day Water Permeability Test [2] Chloride Permeability Test.
Case A Case B
Fibres
Fibres
Steel
51
3.4.1 Mix and Specimen Preparation
All the ingredients were first mixed in dry condition in the concrete
mixer machine for one minute. Then, 75 percent of calculated amount of
water was added to the dry mix and mixed thoroughly for one minute. At this
stage, remaining 25 percentage of water mixed with superplasticiser was
poured into the mixer and mixed for one minute. Later, required quantities of
fibres were sprinkled over the concrete mix and mixer machine was allowed
to rotate for four minutes to get a uniform mix. The total mixing time was 7
minutes. Thus concrete mix was prepared.
To prepare specimen for various mixes, the quantity of materials
required and specimen details are presented in Tables 3.11, 3.12 and 3.13 for
various experimental works. The prepared concrete mix was poured in
moulds (after applying oil inside the mould) in three layers and each layer
was tamped 25 times by 16 mm diameter and 600mm long tamping rods and
then it was vibrated using table vibrater for 1minitue. The same procedure
was adopted for specimen preparation throughout this research work.
52
3.11 Details of Mix Proportioning
CASE Type MIX PROPORTIONS
Reference Mix RMX 1:1.55:2.89:0.49
Case A
Organic superplasticiser OSP RMX+0.8%Organic Based
SP O
rgan
ic b
ased
Sup
erpl
astic
iser
Stee
l fib
re OS1 OSP+0.2%SF
OS2 OSP+0.4%SF OS3 OSP+0.6%SF OS4 OSP+0.8%SF OS5 OSP+1%SF
AR
Gla
ss
Fibr
e OG1 OSP+0.2% ARGF OG2 OSP+0.4%ARGF OG3 OSP+0.6% ARGF OG4 OSP+0.8% ARGF OG5 OSP+1%ARGF
Poly
este
r Fib
re
OP1 OSP+0.2% PF OP2 OSP+0.4% PF OP3 OSP+0.6% PF OP4 OSP+0.8% PF OP5 OSP+1% PF
Case B
Naphthalene superplasticiser NSP
RMX+0.8% Naphthalene Based SP
Nap
htha
lene
bas
ed S
uper
plas
ticis
er w
ith
Stee
l fib
re NS1 NSP+0.2%SF
NS2 NSP+0.4%SF NS3 NSP+0.6%SF NS4 NSP+0.8%SF NS5 NSP+1%SF
AR
Gla
ss
Fibr
e
NG1 NSP+0.2% ARGF NG2 NSP+0.4% ARGF NG3 NSP+0.6% ARGF NG4 NSP+0.8%ARGF NG5 NSP+1% ARGF
Poly
este
r Fib
re
NP1 NSP+0.2% PF NP2 NSP+0.4% PF NP3 NSP+0.6 %PF NP4 NSP+0.8 % PF NP5 NSP+1% PF
53
Table 3.12 Quantity of Materials used per cubic metre of Concrete
MIX Grade of cement
Wt of cement per
cubic metre of concrete
Fa/c Ca/c W/c %
Dosage of SP
% Vol of Fibre
Aspect Ratio-Fibre
Density of
Fibre t/m3 *
RMX 53 383 1.55 2.98 0.49 0 0 0 0 OSP 53 325.5 1.83 3.51 0.49 0.8 0 0 0 OS1 53 325.5 1.83 3.51 0.49 0.8 0.2 80 7.76 OS2 53 325.5 1.83 3.51 0.49 0.8 0.4 80 7.76 OS3 53 325.5 1.83 3.51 0.49 0.8 0.6 80 7.76 OS4 53 325.5 1.83 3.51 0.49 0.8 0.8 80 7.76 OS5 53 325.5 1.83 3.51 0.49 0.8 1 80 7.76 OG1 53 325.5 1.83 3.51 0.49 0.8 0.2 860 2.6 OG2 53 325.5 1.83 3.51 0.49 0.8 0.4 860 2.6 OG3 53 325.5 1.83 3.51 0.49 0.8 0.6 860 2.6 OG4 53 325.5 1.83 3.51 0.49 0.8 0.8 860 2.6 OG5 53 325.5 1.83 3.51 0.49 0.8 1 860 2.6 OP1 53 325.5 1.83 3.51 0.49 0.8 0.2 267 1.33 OP2 53 325.5 1.83 3.51 0.49 0.8 0.4 267 1.33 OP3 53 325.5 1.83 3.51 0.49 0.8 0.6 267 1.33 OP4 53 325.5 1.83 3.51 0.49 0.8 0.8 267 1.33 OP5 53 325.5 1.83 3.51 0.49 0.8 1 267 1.33 NSP 53 325.5 1.83 3.51 0.49 0.8 0 0 0 NS1 53 325.5 1.83 3.51 0.49 0.8 0.2 80 7.76 NS2 53 325.5 1.83 3.51 0.49 0.8 0.4 80 7.76 NS3 53 325.5 1.83 3.51 0.49 0.8 0.6 80 7.76 NS4 53 325.5 1.83 3.51 0.49 0.8 0.8 80 7.76 NS5 53 325.5 1.83 3.51 0.49 0.8 1 80 7.76 NG1 53 325.5 1.83 3.51 0.49 0.8 0.2 860 2.6 NG2 53 325.5 1.83 3.51 0.49 0.8 0.4 860 2.6 NG3 53 325.5 1.83 3.51 0.49 0.8 0.6 860 2.6 NG4 53 325.5 1.83 3.51 0.49 0.8 0.8 860 2.6 NG5 53 325.5 1.83 3.51 0.49 0.8 1 860 2.6 NP1 53 325.5 1.83 3.51 0.49 0.8 0.2 267 1.33 NP2 53 325.5 1.83 3.51 0.49 0.8 0.4 267 1.33 NP3 53 325.5 1.83 3.51 0.49 0.8 0.6 267 1.33 NP4 53 325.5 1.83 3.51 0.49 0.8 0.8 267 1.33 NP5 53 325.5 1.83 3.51 0.49 0.8 1 267 1.33
* 1 t/m3 = 9.81 kN/m 3
54
Table 3.13 Specimen Details
Test Thermo Shock period
Type of specimen
Dimension of specimen
mm
No of specimen
Compressive Strength Test after 7&28 days curing
1 &2 hrs Cube 150x150 33 x 4 x 3=396
2 hrs Cylinder 150x300 33 x 3 x 3=297
Split Tension Test after 7&28 days curing
2 hrs Cylinder 150x300 33 x 3 x 3=297
Flexural Strength Test after 28 days curing
2 hrs Beams 500x 100x100 33 x 2 x 3=198
Pull-Out Test after 28 days curing
- Cube 150x150 33 x 1 x 3=99
Impact Test after 28 days curing
2 hrs Disc 150 Dia with 62.5 thick 33 x 2 x 3=198
Water Permeability Test after 28 days curing 2 hrs Cube 150x150 33 x 2 x 3=198
Rapid Chloride Permeability Test after 28 days curing
2 hrs Disc 95 Dia with 50mm thick 33 x 2 x 3=198
Total 1881
3.5 EXPERIMENTAL WORK
The experimental works conducted includes workability test,
strength test and durability test as described in section 3.4.
3.5.1 Workability Tests
Workability tests are conducted for concrete at fresh state. At this
stage, concrete should have good workability. At construction place, good
workable concrete will have no segregation while handling, no loss of
homogeneity while placing, easiness for compacting and finishing.
Workability of concrete is obtained by conducting slump and compaction
factor tests.
55
3.5.1.1 Slump Test
The test procedure was used as given in IS: 1199-1959. Slump test
was conducted using a standard slump cone of bottom diameter 200 mm top
diameter 100 mm and of height 300 mm. Concrete mix was prepared and
filled in slump cone as described in section 3.4.1. After filling the concrete,
slump cone was then gently and vertically raised. The concrete settles under
its own weight and vertical distance from its original level to new level after
subsidence was measured. This difference in height is known as slump. From
this test, slump value was measured for all the mixes.
3.5.1.2 Compaction Factor Test
The test procedures were used as given in IS: 1199-1959. The
value of compaction factor was found by using a standard compaction factor
apparatus, which consists of an upper hopper, lower hopper & bottom
cylinder. Concrete mix was prepared and filled in upper hopper. Then trap
door at the bottom of the upper hopper was opened to allow the concrete to
fall into lower hopper. After the concrete comes to rest , trap door of lower
hopper was opened to allow concrete to fall into the cylinder. The weight of
the concrete in cylinder was determined and this is known as Weight of
partially compacted concrete. The cylinder is refilled with concrete from the
same sample in layers and tamped for full compaction. Then the weight of the
refilled concrete in cylinder was determined and this is known as Weight of
fully compacted concrete. From this test, compaction factor was measured for
all the mixes from equation 3.1.
Weight of partially compacted concrete Compacting Factor = (3.1)
Weight of fully compacted concrete
56
3.5.2 Strength Tests
Tests were conducted on hardened concrete to find out
Compressive strength, Split tensile strength, Flexural strength, Pull-out test
and Impact strength as per the procedure given below and the results are
presented in chapter 4.
3.5.2.1 Compressive Strength Test
The test procedures were used as given in IS: 516-1979. Steel
moulds of size 150 x 150x 150 mm were used for casting the specimens.
Concrete mix was prepared and specimens were prepared as per section 3.4.1.
Specimens were allowed for curing in a curing tank for a period of 7days &
28 days. After the curing period the specimens were removed from the
curing tank and the surfaces were wiped. The dimensions of the specimens
and the weight of the specimens were noted down with accuracy. Area of the
specimen (A) was calculated from its dimensions. Weight of all the specimens
were in between 8.4 to 8.8 kg. A 200 tonne hydraulic compression testing
machine was used. Then specimen was placed in such a manner that the load
is applied to opposite side of cubes as caste. The load was applied at the rate
of 140 kg/cm2/minute till the cube breaks. Maximum load (W) is recorded at
the time of concrete failure. Same procedure was adopted for all the mixes
and compressive stress was calculated from equation 3.2.
Compressive Stress = AW (3.2)
3.5.2.2 Split Tension Test
The split tension test is a method of determining the tensile strength
of concrete. In its most common form, a cylinder is compressed along two
57
opposite generators until it splits across the diametrical plane connecting the
loading strips. The test procedures were used as given in IS: 516-1979. Steel
moulds of diameter 150mm and of height 300 mm were used for casting the
specimens. Concrete mix and specimens were prepared as per section 3.4.1.
Specimens were allowed for curing in a curing tank for a period of 7days &
28 days. The dimensions of the specimens and the weight of the specimens
were noted down with accuracy. Weight of all the specimens were in between
13.2 to 13.6 kg. Then specimen was placed horizontally between the loading
surface of the 200 tonne hydraulic compression testing machine and the load
was applied till the specimen splitted into two halves. The ultimate load at the
time of failure was noted. Same procedure was adopted for all the mixes and
split tensile stress was calculated from equation 3.3. Figure 3.2 shows set up
for split tensile test.
Figure 3.2 Split Tensile Test Set Up
Split Tensile Strength = DL
P2
(3.3)
Where, P is the load on the cylinder L is the length of the cylinder D is the diameter of the cylinder
P
Poisson’s Effect
Concrete Cylinder
58
3.5.2.3 Flexural Strength Test
The test procedures were used as given in IS: 516-1979. Steel
moulds of size 500 x100 x 100 mm were used for casting the specimens.
Concrete mix and specimens were prepared as per section 3.4.1. Specimens
were allowed to cure in a curing tank for a period of 28 days. The dimensions
of the specimens and the weight of the specimens were noted down with
accuracy. Weight of all the specimens were in between 12.5 to 12.8 kg The
testing machine was provided with two rollers of 38mm diameter on which
the specimens were placed and the rollers were spaced such that the distance
between two rollers was 400 mm as shown in Figure 3.3. The load was
applied through two similar rollers mounted at the third points of the
supporting span, at a distance of 133.3 mm centre to centre. The load was
divided equally between the two loading rollers and the rollers were mounted
in such a manner that the transverse load was applied along the longitudinal
axis and without subjecting specimen to any torsion stresses.
The load was applied with out shock and increasing continuously at
a rate such the extreme fibre stress increase at approximately 0.7kg/sqcm/ min
that is at a rate of loading 180 kg/min. The load was applied until the
specimen failed and maximum failure load applied was recorded. Same
procedure was adopted for all the mixes.
Figure 3.3 Flexural Strength Test Set Up
w
133.3 133.3 133.3 50 50 Dimensions are in mm
59
After the failure of this specimen, the position of fracture was
noted. If ‘a’ is the distance between line of fracture and the nearer support and
if it is greater than 133mm (that is, middle third of the span), the Flexural
Stress (FS) or modulus of rupture of the specimen was calculated from
equation 3.4
Flexural Stress = 2BDWL (3.4)
Where, W is the load applied L is the length of the beam B is the breadth of the beam and D is the depth of the beam. 3.5.2.4 Pull-Out Test
The test procedures were used as per in IS: 2770-1967. Steel moulds of size 150 x 150x 150 mm were used for casting the specimens. Concrete mix and specimens were prepared as per section 3.4.1. A single reinforcing bar was embedded vertically along a central axis in each prepared specimen as shown in Figure 3.4. The diameter of the bar used was 16mm. The bar should be free from grease, paint or other coatings which would affect the bond between reinforcing bar and concrete. The bar was projected down such that the clear distance between the rod and the bottom face of the cube was about 10 mm and was projected upward from the top face with a convenient distance necessary to provide sufficient length of bar to extend through the bearing blocks and the support of the testing machine and to provide an adequate length to be gripped for application of load. Then, the specimen was mounted on a universal testing machine in such a manner that the bar is pulled axially from the cube. The load was applied to the reinforcing bar at a rate not greater than 2250 kg/mm. The loading was continued until the enclosing concrete fails and the corresponding load was
60
noted. Same procedure was adopted for all the mixes and bond stress was calculated from equation 3.5.
Bond stress =dLP
(3.5)
Where P is the load applied
L is the length of the steel bar embedded in the cube
d is the diameter of the steel bar
F ib r eC o n c r e te C u b e
P
Figure 3.4 Pull-Out Test Set Up
3.5.2.5 Impact Strength Test
The test procedures were used as per ACI committee report
544.2R-89. Concrete structures are subjected to short duration (dynamic)
loads. Such loads originate from sources such as impact from missiles and
projectiles wind gusts, earthquakes and machine vibrations reported by
Gopalarathinam (1986). The dynamic response to impact is complex and is
dependent on many factors such as velocity of striker, contact area, size of the
target structure, material behaviour of the striker on the structure etc. It is
necessary to estimate the maximum dynamic energy absorption capacity
which a structure would sustain if it were involved in a collision with another
body or subjected to explosive loads. The review of literature indicates that
61
there were four different methods available to test the impact resistance of
cementitious and hybrid reinforced cementitious materials namely, explosive
test, projectile impact test, drop weight impact test and Charpy impact test.
Drop weight impact test method also known as repeated impact test was the
simplest among all the four methods and was devised by Schrader.
Figure 3.5 Section Through Test Equipment for Impact Strength
In drop weight method the number of blows necessary to cause
prescribed level of distress in the specimen is counted and this gives the
quantitative estimate of energy absorbed by the specimen at the distressed
level. Concrete test specimen is a cylindrical disc having 150mm diameter
and 62.5 mm thickness as shown in Figure 3.5. The specimen was coated on
the bottom with a thin layer of grease and placed at the base plate. Elastomer
pads were placed between specimen to restrict movement of the specimen
during testing. A drop hammer was used to apply the impact load. The
weight of the hammer was 45N. The number of blows required by the
dropping hammer through a height of 457mm to cause the first visible crack
and to cause ultimate failure were recorded. Each blow represents 20.2 Nm of
energy absorbed by the specimen. The first crack was based on visual
observation. Painting the surface of the test specimen facilitated the
Dimensions are in mm
62
identification of this crack. Ultimate failure is defined in terms of number of
blows required to open the crack in the specimen into three or more fractured
pieces and butting against the legs of base plate. Same procedure was adopted
for all the mixes and Energy absorption capacity was calculated from
equation 3.6.
Energy absorption capacity= Load x distance x No. of blows required for cracking/failure (3.6) Where Load = 45 N Distance = 457 mm 3.5.2.6 Reserve Strength
It is defind as strength or energy stored or absorbed beyond first
crack strength upto ultimate failure of concrete. It is assumed that concrete
undergoes elastic deformation upto first crack and concrete undergoes
inelastic response beyond first crack. The measure of reserve capacity gives
ability of concrete to resist inelastic deformation. This is the post cracking
strength of concrete. Percentage of reserve strength is calculated from
equation 3.7.
Percentage of reserve strength = 100xEA
EAEA
Icrack
IcrackUlt
(3.7)
Where EAUlt - Energy absorption at ultimate failure EAI crack - Energy absorption at first crack
3.5.3 Durability Tests
Nowadays durability of concrete is a subject of major concern in many countries. It is a wrong notion that strong concrete is always a durable concrete. Strong concrete may be structurally strong enough to withstand the external load. But such structure may fail by environmental effects. For
63
example, while it is structurally possible to build a jetty pier in marine conditions with 20 MPa concrete, environmental condition or exposure may lead this structure to a disastrous consequences. Durable concrete will retain its original form, quality and serviceability when exposed to its environment. Hence it is necessary to conduct durability tests on concrete. Under this study, water permeability and chloride penetration test was conducted on concrete. Recent revision of IS: 456-2000 gives more emphasis on durability of concrete apart from strength.
3.5.3.1 Permeability Testing of Concrete
Water permeability test procedures were carried out as per the standard IS: 3085-1965. Though much research has been performed to identify, investigate, and understand the mechanical traits of fibre–reinforced concrete, relatively little research has concentrated on the transport properties of this material. Material transport properties, especially permeability, affect the durability and integrity of a structure. Permeability of concrete is due to internal movement of water or other fluids, transporting aggressive agents through the pore structure of the concrete. High permeability, due to porosity or cracking, provides an ingress for water, chlorides and other corrosive agents. If such agents reach reinforcing bars within the structure, the bars get corroded. Hence the study of water permeability of concrete is very important.
To conduct the permeability test cubes of side size 150mm were
cast and water cured for 28 days. After 28 days of curing, specimens were
placed properly in the six cell permeability apparatus. Figure 3.5 shows
section of permeability cell. A Rubber sheet of 8mm thick and 150 x 150mm
size with a central hole of 100 x 100mm was taken. This rubber sheet was
then placed on the top & bottom surface of the cube in the permeability cell.
Cover plate was then tightened properly. The rubber sheet acts as a washer
and prevents the leakage of water through the annular space between
64
specimen and cell. Suitable arrangements were made for supplying
compressed air at 10 kg/cm2 to the cell by a compressor with an adequate
supply of cleaned de-aired water for constant supply of pressurized water.
Collecting jar was placed under the concrete specimen to collect the
discharged water from the concrete. The test was conducted continuously for
100hrs. After 100hrs cubes were then taken out from the cell for finding the
coefficient of permeability. There are two common methods for the
evaluation of co-efficient of permeability of concrete and they are steady flow
method and depth of penetration method. During the test if there is
permeability of water, the coefficient of permeability can be calculated using
the steady flow method and if there is no permeability of water, the
coefficient of permeability can be calculated using depth of penetration
method. In this method cubes are splitted and depth of penetration is
measured in the specimen.
Figure 3.6 Enlarged Section of Permeability Cell
While conducting the test, it was monitored for the permeability
of water through the specimen. It was found that there was no permeability of
65
water through the concrete. Hence co-efficient of permeability (K) was found
by depth of Penetration method from equation 3.8. In this method, cubes were
splitted and depth of penetration was measured in the specimen at different
locations and average depth of penetration was obtained. The method was
developed by Valenta referred in Neville (1981), equivalent to that used in
Darcy’s Law.
K = TH2
PD 2
(3.8)
Where K = Co-efficient of permeability in m/s D = Depth of penetration in cm
P = Porosity of concrete measured as a fraction T = Time in sec H = Pressure head=100m
3.5.3.2 Porosity Calculation
The mix ratio of reference concrete is 1:1.55:2.98:0.49. Neville
and Brooks (2008) have dealt in detail the derivation of the formula to find
the porosity of concrete. Porosity of concrete (p) was calculated using the
formula 3.9.
ca
cw
cA
S1
cA
S1317.0
cah17.0
cw
pco
ca
f
fa
(3.9)
Where w/c- Water- Cement ratio h- Degree of hydration a- Volume of entrapped air S- Specific gravity of cement 3.10 Sfa - Specific gravity of fine aggregate 2.65 Sca - Specific gravity of coarse aggregate 2.60
66
Ac, Af, Aco - Proportions of cement, fine aggregate and coarse aggregate in the reference mix ratio RMX. Air content of the concrete is calculated from equation 3.10. The
percentage of air content to total volume is 2% (from section 3.2)
02.0a
cw
SA
SA
SA
ava
ca
co
fa
fc
(3.10)
Here, denominator represents the total volume of concrete For w/c=0.49, Degree of hydration h=68%
The volume of air “a” was given by
a = 0.052
Porosity (p) of the concrete was therefore from equation 3.9
ca
cw
cA
S1
cA
S1317.0
cah17.0
cw
pco
ca
f
fa
Thus Porosity of concrete p = 0.149
3.5.3.3 Rapid Chloride Penetration Test
Corrosion of reinforcement in reinforced concrete structures is one of the most hazardous durability problems. One of the principal sources of this problem is the ingress of chloride ions into porous concrete. Movement of ions in a porous medium under a concentration gradient is called diffusion. It
02.0a49.015.158.033.0
a
052 .049. 06 .2
98.265. 255. 1317. 0
052.0)68.0 (X17. 049. 0p
67
is often necessary to ascertain the impermeability of concrete to chloride ions as a quality control measure and also for assessment of improvements effected in properties of new concrete. Measurements of chloride diffusion co-efficient requires a long time for establishment of steady state conditions. Therefore a direct current (DC) potential is usually applied to accelerate migration of ions.
Rapid chloride penetration test (RCPT) was performed as per ASTM C 1202 to determine the electrical conductance of the Fibrous concrete at the age of 28 days curing. The test method consists of monitoring the amount of electrical current passed through 50mm thick slices of 95 mm diameter of cylindrical specimens for duration of six hours.
The RCPT apparatus consists of two reservoirs as shown in Figure 3.7. The specimen was fixed between two reservoirs using an epoxy bonding agent to make the test setup leak proof. One reservoir was filled with 0.3N Sodium Hydroxide solution and the other reservoir with 3 % Sodium Chloride solution. A DC of 60V was applied across the specimen using two copper des and the current across the specimen was recorded at 30 minutes intervals for duration of six hours. The total charge passed in coulombs during this period was calculated from equation 3.11 given in ASTM C 1202.
Figure 3.7 Chloride Penetration Test Set Up
68
Q = 900 ( I0 + 2 I30 + 2 I60 +………+ 2 I330 + 2 I360 ) (3.11)
Where,
Q = Charge passed (coulombs)
I0 = Current immediately after voltage was applied
It = Current at ‘t’ minutes after voltage was applied
The higher amount of electric charge passed in the test represents
the higher penetrability of the concrete to chloride ions. The concrete quality
(degree of chloride ion penetrability) can be assessed based on the limits as
given in ASTM C 1202 and it is presented in Table 3.14.
Table 3.14 Chloride ion penetrability based on charge passed
Charge Passed (Coulombs) Chloride ion penetrability >4000 High
2000-4000 Moderate 1000-2000 Low 100-1000 Very Low
<100 Negligible
3.5.4 Testing of Concrete After Thermoshock
Generally concrete is incombustible and has good fire resistance
properties. When concrete is subjected to continuous exposure to elevated
temperature under fire and sudden cooling by water, it leads to thermoshock.
Thermo shock which may significantly influence the dehydration of the
hydrated calcium silicate, the release of chemically bound water, thermal
incompatibility between the aggregates & cement paste and these are the main
detrimental factors under heating. During exposure to heat, aggregate expands
and cement matrix shrinks due to loss of moisture and drying shrinkage type
69
stresses will be created. If it exceeds drying shrinkage capacity of concrete,
micro cracks are developed at interfacial transition zone and propagate. Such
micro cracks lead to decrease its strength and durability of concrete. Hence
experimental study of concrete before and after thermoshock is made under
strength as well as durability aspects.
The residual strength is the strength of heated and subsequently
cooled concrete specimen. That is strength of concrete after thermoshock is
referred as residual strength (TRS). The residual strength of concrete after
subjected to elevated temperature is generally less than its RMX strength. The
percentage variation in residual strength is calculated from equation 3.12
Percentage variation Residual strength with RMX =
100x
RMXRMXTRS (3.12)
3.5.4.1 Testing Procedure
The specimens were placed inside the hot air oven and were heated
to a temperature of 200o C and the temperature was sustained for two hours.
After two hours, the specimens were taken out and were immediately
quenched in water to simulate the thermo shock effect. The cooling was done
for about half an hour. The specimens were then tested for its residual
strength. Percentage change in strength was calculated by comparing the
strength of specimens without thermo shock.
Cube and cylinder specimens were used to test for compressive
strength. Thermoshock test was conducted after 1 hr and 2 hr exposure to
heat. Similarly test was conducted after 2hrs exposure to heat in case of
cylinder specimens. Thermoshock test was performed for specimen under
split tension test, flexure test, impact test, water permeability test and chloride
penetration test after 2 hrs exposure to heat.