Upload
others
View
28
Download
1
Embed Size (px)
Citation preview
Photo/isometric drawing
provided by manufacturer
Advanced Smoke Group Limited – RTC Smokeclear Real Time Control Pressure Differential System
Description of Product
This is an assessment of the RTC Smokeclear
Real Time Control Pressure Differential System
manufactured by Advanced Smoke Group
Limited, incorporating the use of Door Position
Sensors (DPS) for close control of precise
closed door design pressures and open door
velocities, applicable to all pressure differential
systems.
The RTC Smokeclear Pressure Differential
System incorporates the use of a Door Position
Sensor (DPS) on each relevant door in the
system to communicate the location and
opening angle of each door in real time. This
information is communicated to the system
control panel. This information is used to
control fan speed to ensure the maintenance
of accurate compartment pressure or door
face velocity.
Key Factors Assessed
Mechanical Resistance & Stability
Safety in case of Fire
Safety in Use
Durability serviceability and identification
Validity
This certificate was first issued on 8th September 2015 and is valid until 8th September 2020
Issue Dated 30th October 2019
Certificate No: EW602
The scope of application for this product, in accordance with this Registered Detail, is considered to include all applications
where a pressure differential system designed, installed and commissioned in accordance with the current edition of BS EN
12101-6 Smoke and heat control systems - Part 6: Specification for pressure differential systems – Kits.
It is considered to be an acceptable solution, in accordance with the applicable volume of the current Approved Document B or
BS 9999 Approved Document B - Fire Safety, BS 9999:2008 Code of practice for fire safety in the design, management and use
of buildings and BS 9991:2011. Fire safety in the design, management and use of residential buildings. Code of practice and as
approved by the relevant Building Control body.
This Registered Detail only covers the applicability of Door Position Sensor technology as a part of Advanced Smoke Group
Limited’s
RTC Smokeclear – Real Time Control Pressure Differential System designed, installed and commissioned in accordance with
BS EN 12101-6 and does not cover the overall pressure differential system design nor the range of scenarios in which a
pressure differential smoke ventilation system is considered to be a suitable solution in order to achieve compliance with
the Building Regulations, but may be applied in such applications after full consideration of the design – see below.
The pressure differential system, of which the Door Position Sensors (DPS) form a part, shall be designed, installed and
commissioned in accordance with the current edition of BS EN 12101-6 Smoke and heat control systems - Part 6: Specification
for pressure differential systems - Kits
It is the responsibility of the Building Control body, in consultation with the Fire Authority, to determine if the use of a pressure
differential system is an acceptable solution as part of any particular application under the Building Regulations, either as part of
a code-compliant design in accordance with Approved Document B, BS 9999, BS 9991 or as part of a performance-based ‘fire
engineered’ solution utilising the approach outlined in BS 7974 Application of fire safety engineering principles to the design of
buildings. Code of practice
This Registered Detail is not intended to indicate the suitability of the RTC Smokeclear – Real Time Control Pressure Differential
System, incorporating Door Position Sensors (DPS) technology, for any particular application under the Building Regulations as
this will need to be determined on a project specific basis.
This Registered Detail confirms that the Advanced Smoke Group Limited’s RTC Smokeclear – Real Time Control Pressure
Differential System and Door Position Sensors (DPS) are suitable for use wherever a BS EN 12101-6 compliant pressure
differential system is considered to be applicable.
The provision of indicating equipment and override controls intended for Fire Service use shall in all cases be in accordance with
the standard specification referenced in ‘Supporting Documentation’ below, but for specific projects it may be considered
necessary to incorporate additional indication equipment and/or override controls, for example manual control points local to
protected lobbies, in addition to the central override control specified in paragraph 2.4 ‘Fire Service Control’ of the standard
specification. In all cases, the incorporation of additional controls must be agreed on a project specific basis with the Building
Control body, Fire Authority and any other Authorities Having Jurisdiction, as applicable.
The precise location(s) for remote monitoring of the system (noted in the “standard specification) and as required by any
relevant standards and specifications shall in all cases be agreed on a project specific basis with the Building Control body, Fire
Authority and any other Authorities Having Jurisdiction, as applicable.
All system cabling shall be in accordance with paragraph 5 ‘Cabling’ of the standard specification and with the current edition of
BS 8519 Selection and installation of fire-resistant power and control cable systems for life safety and fire-fighting applications –
Code of practice.
Suitable information shall be provided for the use of Fire Service personnel regarding the coverage and operation of the system,
including system indication and all override controls. It is recommended that the scope of this information be agreed with the
applicable Fire Authority. This information shall be encapsulated and placed in a suitable location, such as a premises information
box or within the Fire Control Centre where one is provided.
The Door Position Sensor (DPS) devices will be clearly marked to indicate that they should not be removed, as they part of an
active fire protection/life safety system (as “standard specification”)
On completion of the installation and commissioning of the pressure differential system, the Building Control body shall be
invited to attend acceptance testing of the system, including at minimum a demonstration of the following:
• That the system is activated by the appropriate fire alarm system input devices;
• That the pressure differentials and air velocities, or the extract volumes, are in accordance with the design specification, as
appropriate for the type of system, for the worst case protected space (e.g. the protected space furthest from the system fans)
and for any other areas, as requested by the Building Control body;
• That, where stand-by fans and drive mechanisms are provided in accordance with clause 11.7 of BS EN 12101-6, upon failure of
the duty fan, the stand-by fan(s) run automatically within a reasonable period of time;
• That, on failure of the primary power supply to the pressure differential system, changeover to the secondary/backup power
supply takes place automatically and the pressure differential system resumes operation within a period of not less than 30
seconds, or within a time period otherwise agreed between the Building Regulations applicant/the person carrying out the work
and the Building Control body, in consultation with the Fire Authority;
• That a simulated fault with the following system components are registered and displayed on the remote indication panel:
A. Door Proximity Sensors
B. Motorised Smoke Dampers
C. The duty fan(s) and, where applicable, the stand-by fan(s)
D. The primary power supply;
• That all system override controls operate as intended and are appropriately labelled as to their function;
• That all doors on means of escape routes can be opened using less than 100N pressure when the system is operating;
• That all components are provided with suitable and agreed signage, including marking to Door Proximity Sensors in
accordance with paragraph 3.5 of the standard specification.
On completion of the installation and commissioning of the pressure differential system, the Building Control body shall be
provided with a Completion/Commissioning Certificate issued by the system installer certifying that the system has been
designed, installed and commissioned in accordance with BS EN 12101-6 and the standard specification. This shall include
documentation indicating that the key system parameters (pressure differentials, air velocities or extract volumes, as appropriate)
have been measured as part of the commissioning process and the performance achieved is within acceptable tolerances of the
design specification.
LABC consider that, the RTC Smokeclear – Real Time Control Pressure Differential System incorporating
Door Position Sensors (DPS), will meet the functional requirements of the Building Regulations (listed
below) if the criteria detailed in this certificate are met;
The Building Regulations 2010 (as amended) England & Wales
Regulation 7 Materials and workmanship
Note: The product is acceptable when installed in accordance with the manufacturer’s
instructions and the specification referenced in ‘Supporting Documentation’ below.
Part B Fire safety
Note: See Conditions of Certificate section
The Building Regulations 2010 (as amended) England
None presently
The Building Regulations 2010 (as amended) Wales
None presently
The Building (Scotland) Regulations 2004 (as amended)
If you would like to discuss a specific use of the product in Scotland it will require an additional
assessment under the Scottish Building Regulations and accordingly you should contact the LABSS
STAS Administrator at www.labss.org
LABC Warranty
The use of the RTC Smokeclear – Real Time Control Pressure Differential System has not been assessed
to meet the requirements of the LABC Warranty Technical Manual. If you would like to discuss a
specific use please make an enquiry to [email protected]
Specification for the installation and control of pressure differential systems using the RTC Smokeclear – Real Time Control
Pressure Differential System (Advanced Smoke Group Limited, July 2015), referenced above as the ‘standard specification’.
BS EN ISO 9001:2008 certificate number 4011084, issued by Quay Audit UK Ltd to Advanced Smoke Group Ltd for the ‘Design,
Manufacture and Installation of Unique Solutions for Air/Smoke Movement and Extraction’.
Advanced Smoke Group Limited
46 Kenilworth Drive
Oadby Industrial Estate
Leicester
LE2 5LG
Tel: 0116 271 6861
Email: [email protected]
Web: www.advancedsmoke.co.uk