CDT900 Series Touchscreen Programmable Thermostat
Contents
Application/Features............................................... ................. ................. ........................... 2
Specifications/Ordering Information ..................... ................. ................. ............................. 4Installation ........................................................ .. ................. ...............................................13Wiring ................................................................... ................. ................. ............................ 17Power the Thermostat .................................. ................ ................. ..................................... 34Installer Setup ............................. ................. ................ ...................................................... 47Installer System Test ................. ................. ................ ........................................................ 59
Operation............................. ................. ............... ............................................................... 62Programming .................. ................. ................. .................................................................. 68Troubleshooting ................ ................. ................. ................................................................ 97
1
`
8/13/2019 CDT900 Series Manual
3/102
PRODUCT DATAAPPLICATIONThe CDT900 Series Touchscreen Programmable Thermostat is an effortless, 7-Dayprogrammable thermostat that provides universal system compatibility, precise comfortcontrol and is easy-to-program.The CDT900 Series Thermostats provide temperature control for gas, oil, electric and heatpumps for up to 3 heat, 2 cool systems including dual fuel operation plus dehumidificationcontrol.
CDT900 Series Touchscreen Programmable Thermostat
2
8/13/2019 CDT900 Series Manual
4/102
8/13/2019 CDT900 Series Manual
5/102
8/13/2019 CDT900 Series Manual
6/102
CDT900 Series Touchscreen Programmable Thermostat
Electrical Ratings:
Terminal Voltage (50/60 Hz) Running CurrentW Heating 20 - 30 Vac 02 - 1.0A
W Heating (Powerpile) 750 mV dc 100 mA dc
Y Cooling 20 - 30 Vac .02 - 1.0A
G Fan 20 - 30 Vac 02 - .60A
Temperature Setting Range:Heating: 40F to 90F(4C to 32C).Cooling: 50F to 99F (10C to 37C).
Operating Ambient Temperature:32F to 120F(0C to 49C).
Shipping Temperature:CDT900 Thermostats: -30 F to 150 F(-34.4C to 65.6C).
5
8/13/2019 CDT900 Series Manual
7/102
CDT900 Series Touchscreen Programmable Thermostat
Operating Relative Humidity (Non-condensing):CDT900 Series Thermostats: 5% to 90%.
IRS-1: 5% to 95%.ORS-1: 5% to 95%.
Humidity Setting Range (CDT901 models only):Cooling: 40% to 80% RH.
Humidity Display Range (CDT901 models on ly):0% to 99%.
Cycle Rates (at 50% Load):Heating: Selectable 1 - 12 cycles per hour.Cooling: Selectable 1 - 6 cycles per hour.
Clock Accuracy: +/- 1 minute per month.
Batteries:Two replaceable AA alkaline batteries: Power thermostats when 24 Vac common is not used.Non-replaceable lithium battery with ten-year life under normal use to hold calendar and timesettings. Alkaline batteries keep calendar and time after lithium battery is no longerfunctional.
6
8/13/2019 CDT900 Series Manual
8/102
CDT900 Series Touchscreen Programmable Thermostat
Cool Indication:CDT900 series Touchscreen Thermostats show "Cool On" on the screen when Cool is
activated.
Heat Indication:CDT900 series Touchscreen Thermostats show "Heat On" on the screen when Heat isactivated.
7
8/13/2019 CDT900 Series Manual
9/102
CDT900 Series Touchscreen Programmable Thermostat
ORDERINGINFORMATIONIf you have additional questions, need further information, or would like to comment on ourproducts or services, please write or phone:1. Smart Electric
Attn: Warranty Department12201 NW 107th AveMiami, Fl 33178
2. Call Customer Service at 1-866-591-9898
Auxi liary Heat Indicat ion:CDT900 Touchscreen Thermostats show "Aux Heat On" on the screen when Auxiliary Heatis activated.
Emergency Heat Indication:CDT900 Touchscreen Thermostats show "Heat On" on the screen when Emergency Heat isactivated and the System mode is in the Emer position.
Calibration:CDT900 Touchscreen Thermostats are factory-calibrated and require no field calibration.
Nomenclature:
8
8/13/2019 CDT900 Series Manual
10/102
CDT900 Series Touchscreen Programmable Thermostat
Series System Stages Appl icat ion
CDT900CDT901 3H/2C CDT900 - StandardCDT901-Humidity Sensor
Mounting Means:CDT900 Series Touchscreen Thermostat: Mounts directly on the wall in the living spaceusing mounting screws and anchors provided.Outdoor Sensor: Mounts outside of living space with mounting clip and screws provided.Remote Indoor Sensor: Mounts directly on the wall using mounting screws and anchorsprovided.
Dimensions:CDT900 Series Touchscreen Thermostat: see Fig 1.1. CDT900 Outdoor Sensor Mounting Clip: see Fig 2.2. Cover Plate: see Fig 3.3. CDT900 SeriesRemote Indoor Sensor: see Fig. 4
9
8/13/2019 CDT900 Series Manual
11/102
8/13/2019 CDT900 Series Manual
12/102
CDT900 Series Touchscreen Programmable Thermostat
Fig. 1. Touchscreen Thermostat dimensions in in. (mm).
11
1.17 in.(29.84mm)
5.98 in.(152mm)
4.48in.(114mm)
8/13/2019 CDT900 Series Manual
13/102
CDT900 Series Touchscreen Programmable Thermostat
Fig. 2. Outdoor Sensor Mounting Clip dimensions in in. (mm).
12
1.49 in.(38mm)
0.17in.(4.2mm)
R1.6in.(4mm
)
1.82 in.(46.3mm)
R0.04
in.(1mm)
R0.098in.(2.5m
m)
1.10in.(28.1mm)
0.62in.(16mm
)
1.56 in .(39.7mm)
0.24 in.(6.2mm)
0.44 in .(11.2mm)
R0.098in.(2.5mm)
0.08 in.(2mm)
8/13/2019 CDT900 Series Manual
14/102
CDT900 Series Touchscreen Programmable Thermostat
Fig. 3. Cover Plate dimensions in in. (mm).
13
3.29 in.(83.5mm)
0.85 in .(21.5mm)
3.29in.(83.5mm)
5.35 in.(136mm)
4.13in.(105mm)
8/13/2019 CDT900 Series Manual
15/102
CDT900 Series Touchscreen Programmable Thermostat
INSTALLATIONWhenInstallingthisProduct...1.Read these instructions carefully. Failure to follow the instructions can damage the productor cause a hazardous condition.2.Check the ratings given in the instructions to make sure the product is suitable for yourapplication.3.Installer must be a trained, experienced service technician.4.After completing installation, use these instructions to check out the product operation.
SelectingLocationInstall the thermostat about 5 ft. (1.5m) above the floor in an area with good air circulation ataverage temperature. See Fig. 5.
Do not install the thermostat where it can be affected by:----Drafts or dead spots behind doors and in corners.----Hot or cold air from ducts.----Radiant heat from sun or appliances. Concealed pipes and chimneys.
----Unheated (uncooled) areas such as an outside wall behind the thermostat.
14
8/13/2019 CDT900 Series Manual
16/102
CDT900 Series Touchscreen Programmable Thermostat
Fig. 5. Selecting thermostat location.
15
5FEET
1.5METERS
8/13/2019 CDT900 Series Manual
17/102
CDT900 Series Touchscreen Programmable Thermostat
InstallingWallplate
CAUTIONElectrical Hazard.Can cause electrical shock or equipment damage.Disconnect power before wiring.
The thermostat can be mounted horizontally on the wall1.Position and level the wallplate (for appearance only).2.Use a pencil to mark the mounting holes.3.Remove the wallplate from the wall and, if drywall, drill two holes in the wall, as marked. For
firmer material such as plaster, drill two holes. Gently tap anchors (provided) into the drilledholes until flush with the wall.4.Position the wallplate over the holes, pulling wires through the wiring opening. See Fig. 65.Insert the mounting screws into the holes and tighten.
16
8/13/2019 CDT900 Series Manual
18/102
CDT900 Series Touchscreen Programmable Thermostat
Fig. 6. Mounting wallplate.
17
WALL
WIRES THROUGH
WALL AND WIRE
SLOT
WALL ANCHORS
M0UNTING
HOLES(2)
M0UNTINGSCREWS(2)
8/13/2019 CDT900 Series Manual
19/102
CDT900 Series Touchscreen Programmable Thermostat
WIRING(FIG.9- 21)All wiring must comply with local electrical codes and ordinances.1.Select set of terminal identifications (Table 1) that corresponds with system type(conventional or heat pump in Fig. 7).2.Loosen the screws for the appropriate system type selected; see Table 1. See Table 2 forterminal designation descriptions. Insert wires in the terminal block under the loosenedscrew. See Fig. 8.3.Securely tighten each screw.4.Push excess wire back into the hole.5.Plug the hole with nonflammable insulation to prevent drafts from affecting the thermostat.6.See Fig. 9 through 21 for typical wiring hookups.
Fig. 7. Selecting terminal identifications forsystem type.
18
CONVENTIONAL
HEATPUMP
SCREW
TERMINALS
S1 S2 C R RC E L Y2 Y G
S1 S2 C R RC W W2 Y2 Y G
O/B AUX
8/13/2019 CDT900 Series Manual
20/102
8/13/2019 CDT900 Series Manual
21/102
CDT900 Series Touchscreen Programmable Thermostat
IMPORTANT:Use 18 gauge thermostat wire.
Fig. 8. Inserting wires in terminal block.
20
8/13/2019 CDT900 Series Manual
22/102
CDT900 Series Touchscreen Programmable Thermostat
Table 2. Terminal Designation Descript ions.
Terminal Designation Description
Rc (see Note 1)
Power for cooling--connect to secondary side of cooling
system transformerR (see Note 1) Power for heating--connect to secondary side of heatingsystem transformer
C (see Note 2) Common wire from secondary side of cooling systemtransformerW Heat relayY Compressor contactorG Fan relayY2 Second stage coolingW2 Second stage heat relayO/B (see Note 3) Changeover valve for heat pump systems
AUX Auxiliary heat relay for heat pump systemsE Emergency heat relay for heat pump systems
L (see note 4) Equipment monitor for heat pump systemsS1, S2 Optional outdoor or indoor remote sensor
NOTES:.1.When sed in a single-transformer system, leave metal jumper wire in place between Rc
and R. If used on a two-transformer system, remove metal jumper wire between Rc and R.2.Common wire is optional when thermostat is used with batteries.3. If thermostat is configured for a heat pump system in the Installer Setup, configurechangeover valve for cool (O-factory setting) or heat (B).4.L terminal is an input (system monitor) when the System mode is in the Heat, Off, Cool or
Auto position. L terminal is a 24 Vac output when System mode is Emergency Heat. Mustconnect the 24 Vac Common when using the L terminal. See LCD Indication section for moredetails.
21
8/13/2019 CDT900 Series Manual
23/102
CDT900 Series Touchscreen Programmable Thermostat
1.POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2. FACTORY INSTALLED JUMPER.3.OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE
SEPARATE FROM THE THERMOSTAT CABLE
Fig. 9. Typical hookup of conventional single-stage heat and cool system with s ingletransformer(1H/1C conventional).
22
CONVENTIONALS1 S2 C R RC W W2 Y2 Y G
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
3
HEATRELAY
OPTIONAL24VAC
COMMON
CONNECTION
RC 1
2
FANRELAY
8/13/2019 CDT900 Series Manual
24/102
1.POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2.REMOVE FACTORY INSTALLED JUMPER
3.OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE
SEPARATE FROM THE THERMOSTAT CABLE.
Fig. 10. Typical hookup of conventional single-stage heat and cool system with twotransformers (1H/1C conventional).
23
CONVENTIONALS1 S2 C R RC W W2 Y2 Y G
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
3 RC 1
2
FANRELAY
HEATRELAY
R C 1
COMPRESSOR
CONTACTOR
OPTIONAL
24VACCOMMON
CONNECTION
8/13/2019 CDT900 Series Manual
25/102
CDT900 Series Touchscreen Programmable Thermostat
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED
2. FACTORY INSTALLED JUMPER.
3. OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE
SEPARATE FROM THE THERMOSTAT CABLE
Fig. 11. Typical hookup of heat-only system (1 H conventional).
24
CONVENTIONALS1 S2 C R RC W W2 Y2 Y G
OUTDOOR/INDOORTEMPERATURE
SENSOR
3
HEATRELAY
OPTIONAL
24VAC
COMMON
CONNECTION
R C1
2
8/13/2019 CDT900 Series Manual
26/102
CDT900 Series Touchscreen Programmable Thermostat
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED
2. FACTORY INSTALLED JUMPER.
3. OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE
SEPARATE FROM THE THERMOSTAT CABLE
Fig. 12. Typical hookup of heat only system with fan (1H conventional).
25
CONVENTIONALS1 S2 C R RC W W2 Y2 Y G
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
3
HEATRELAY
OPTIONAL24VAC
COMMON
CONNECTION
RC 1
2
FANRELAY
8/13/2019 CDT900 Series Manual
27/102
CDT900 Series Touchscreen Programmable Thermostat
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED2. FACTORY INSTALLED JUMPER.
3. OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE
SEPARATE FROM THE THERMOSTAT CABLE
Fig. 13. Typical hookup of heat only power to open and power to close zone valve(Series 20) system.
26
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
3
R C 1
2
WBR
TR TRSERIES20
MOTOROR
VALVE
CONVENTIONALS1 S2 C R RC W W2 Y2 Y G
8/13/2019 CDT900 Series Manual
28/102
CDT900 Series Touchscreen Programmable Thermostat
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED
2. FACTORY INSTALLED JUMPER.3. OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE
SEPARATE FROM THE THERMOSTAT CABLE
Fig. 14. Typical hookup of heat only system with normally open zone valves.
27
CONVENTIONALS1 S2 C R RC W W2 Y2 Y G
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
3
NORMALLYOPEN
ZONEVALVE
OPTIONAL24VAC
COMMON
CONNECTION
R C1
2
4
8/13/2019 CDT900 Series Manual
29/102
CDT900 Series Touchscreen Programmable Thermostat
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED
2. FACTORY INSTALLED JUMPER.3. OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE
SEPARATE FROM THE THERMOSTAT CABLE
Fig. 15. Typical hookup of cool only system(1C conventional).
28
CONVENTIONALS1 S2 C R RC W W2 Y2 Y G
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
3
COMPRESSOR
CONTACTOR
OPTIONAL
24VAC
COMMON
CONNECTION
RC 1
2
FANRELAY
HEATRELAY
8/13/2019 CDT900 Series Manual
30/102
CDT900 Series Touchscreen Programmable Thermostat
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED2. FACTORY INSTALLED JUMPER.
3. OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE
SEPARATE FROM THE THERMOSTAT CABLE
Fig. 16. Typical hookup of conventional multistage two-stage heating and two-stagcooling in a single-transformer system (2H/2C, 2H/1C or 1H/2C conventional).
29
S1 S2 C R RC W W2 Y2 Y G
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
3
OPTIONAL
24VAC
COMMON
CONNECTIONMUSTCOME
FROMTHE
COOLING
TRANSFORMER
2
FANRELAY
HEATRELAY2
HEATRELAY1 COOLRELAY2
COOLRELAY1
R C 1
CONVENTIONAL
8/13/2019 CDT900 Series Manual
31/102
CDT900 Series Touchscreen Programmable Thermostat
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED
2. FACTORY INSTALLED JUMPER.
3. OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLESEPARATE FROM THE THERMOSTAT CABLE
Fig. 17. Typical hookup of conventional mul tistage two-stage heating and two-stagecooling in a two-transformer system (2H/2C, 2H/1C or1H/2C conventional).
30
CONVENTIONAL S1 S2 C R RC W W2 Y2 Y G
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
3
OPTIONAL
24VAC
COMMONCONNECTION
MUSTCOME
FROMTHE
COOLING
TRANSFORMER
RC 1
2
FANRELAY
HEATRELAY1
HEATRELAY2
COOLRELAY2
COOLRELAY1
R C 1
8/13/2019 CDT900 Series Manual
32/102
CDT900 Series Touchscreen Programmable Thermostat
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED
2. FACTORY INSTALLED JUMPER.
3"O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP4OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE
SEPARATE FROM THE THERMOSTAT CABLE
Fig. 18. Typical hookup of single-stage heat pump with no auxil iary/backup heat (1H/heat pump).
31
HEATPUMP
S1 S2 C R RC W W2 Y2 Y G
S1 S2 C R RC E L Y2 Y GO/B AUX
OUTDOOR/INDOORTEMPERATURE
SENSOR
4
2
R C 1
CHANGEOVER
VALVECOMPRESSOR
RELAY
FANRELAYOPTIONAL24VAC
COMMON
CONNECTION
3
8/13/2019 CDT900 Series Manual
33/102
CDT900 Series Touchscreen Programmable Thermostat
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED
2. FACTORY INSTALLED JUMPER.
3MUST CONNECT THE 24 VAC COMMON WHEN USING L. THE TERMINAL IS SHOWN AS EQUIPMENT MONITOR, CAN ALSO BEUSED AS A 24 VAC OUTPUT. SEE "HEAT PUMP LED" SECTION FOR MORE INFORMATION.
4"O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP
5OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE
SEPARATE FROM THE THERMOSTAT CABLE
Fig. 19. Typical hookup of multistage heat pump with no auxil iary/backup heat2H/2C heat um .
32
HEATPUMP
S1 S2 C R RC W W2 Y2 Y G
S1 S2 C R RC E L Y2 Y GO/B AUX
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
2
R C 1
CHANGEOVER
VALVE
FANRELAYOPTIONAL
24VAC
COMMON
CONNECTION
5
COMPRESSOR2
COMPRESSOR1
4 3
8/13/2019 CDT900 Series Manual
34/102
CDT900 Series Touchscreen Programmable Thermostat
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED
2. FACTORY INSTALLED JUMPER.
3OUTDOORSENSORREQUIREDINSYSTEMWITHFOSSILFUELBACKUPHEATTHATISNOTUSINGANEXTERNALFOSSILFUELKIT4OPTIONALOUTDOORORINDOORREMOTESENSOR.AVAILABLEONSELECTMODELS.WIRESMUSTHAVEACABLESEPARATE FROMTHE
THERMOSTATCABLE
5MUSTCONNECTTHE24VACCOMMONWHENUSINGL.THETERMINALISSHOWNASEQUIPMENTMONITOR,CANALSOBEUSEDAS
A24VACOUTPUT.SEE"HEATPUMPLED"SECTIONFORMOREINFORMATION.
6"O/B"TERMINALSETTOCONTROLASEITHER"O"OR"B"INTHEINSTALLERSETUP.
Fig. 20. Typical hookup of single-stage heat pump with auxiliary/backuheat (2H/1C heat pump). 33
34
HEATPUMP
S1 S2 C R RC W W2 Y2 Y G
S1 S2 C R RC E L Y2 Y GO/B AUX
OUTDOOR/INDOOR
TEMPERATURESENSOR
2
R C 1
CHANGEOVER
VALVE
FANRELAY
OPTIONAL
24VAC
COMMON
CONNECTION
6 5
COMPRESSOR
RELAY
EMERGENCY
HEATRELAYHEAT2RELAY(AUXILIARYHEAT)
EQUIPMENT
MONITOR
8/13/2019 CDT900 Series Manual
35/102
CDT900 Series Touchscreen Programmable Thermostat
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED
2. FACTORY INSTALLED JUMPER.
3OUTDOORSENSORREQUIREDINSYSTEMWITHFOSSILFUELBACKUPHEATTHATISNOTUSINGANEXTERNALFOSSILFUELKIT
4OPTIONALOUTDOORORINDOORREMOTESENSOR.AVAILABLEONSELECTMODELS.WIRESMUSTHAVEACABLESEPARATE FROMTHE
THERMOSTATCABLE
5MUSTCONNECTTHE24VACCOMMONWHENUSINGL.THETERMINALISSHOWNASEQUIPMENTMONITOR,CANALSOBEUSEDAS
A24VACOUTPUT.SEE"HEATPUMPLED"SECTIONFORMOREINFORMATION.
6"O/B"TERMINALSETTOCONTROLASEITHER"O"OR"B"INTHEINSTALLERSETUP.
Fig. 21. Typical hookup of mul tistage heat pump with auxil iary/backup heat (3H/2C heapump).
34
34
HEATPUMP
S1 S2 C R RC W W2 Y2 Y G
S1 S2 C R RC E L Y2 Y GO/B AUX
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
2
R C 1
CHANGEOVER
VALVE
FANRELAY
OPTIONAL
24VAC
COMMON
CONNECTION
6 5
EMERGENCY
HEATRELAYHEAT2RELAY(AUXILIARYHEAT)
EQUIPMENTMONITOR
COMPRESSOR1
COMPRESSOR1
8/13/2019 CDT900 Series Manual
36/102
CDT900 Series Touchscreen Programmable Thermostat
POWERTHETHERMOSTAT
You can choose from three methods to power the thermostatBatteries only (AA alkaline). 24 Vac common wire only. 24 Vac common wire with battery backup (AA alkaline).
Wiring 24VacCommon Single-Transformer System Connect the common side of the transformer to the C screw
terminal of the thermostat wallplate. Leave the metal jumper wire in place between Rc andR.
Two-Transformer System Connect the common side of the cooling transformer to the Cscrew terminal of the thermostat wallplate. Remove the metal jumper wire between Rc andR.
35
8/13/2019 CDT900 Series Manual
37/102
CDT900 Series Touchscreen Programmable Thermostat
InstallingBatteries1.Install Two AA alkaline batteries on the
back of the thermostat as marked on thethermostat. See Fig. 22.
Fig. 22. Installing batteries.
2.Locate and remove the tab labeled. See
Fig. 23.
Fig. 23. Remove tab labeled, Remove,on thermostat back.
36
BATTERIES(2)
REMOVE
TAB
8/13/2019 CDT900 Series Manual
38/102
CDT900 Series Touchscreen Programmable Thermostat
Mount Thermostat to Wallplate
1.Align the terminal screw blocks with the pins on the back of the thermostat. Push thethermostat straight onto the wallplate until it snaps into place. See Fig 24.
Fig. 24. Mount thermostat to wallplate.
37
WALLPLATE
TERMINALSCREWBLOCK
PINSONBACKOF
THERMOSAT
8/13/2019 CDT900 Series Manual
39/102
8/13/2019 CDT900 Series Manual
40/102
CDT900 Series Touchscreen Programmable Thermostat
Fig. 25. Typical locations for ORS-1 Outdoor Sensor.
39
8/13/2019 CDT900 Series Manual
41/102
CDT900 Series Touchscreen Programmable Thermostat
CAUTIONElectrical Interference (Noise) Hazard.Can cause erratic system operation.Keep wiring at least one foot away from large inductive loads such as motors, linestarters, lighting ballasts and large power distribution panels.Use shielded cable to reduce interference when rerouting is not possible.
IMPORTANTErratic temperature readings from a sensor can occur as a result of any of thewiring practices described below. Avoid these practices to assure correctoperation. Use shielded cable to reduce interference if rerouting sensor wiring isnot possible.
40
8/13/2019 CDT900 Series Manual
42/102
CDT900 Series Touchscreen Programmable Thermostat
Be sure wires have a cable separate from the thermostat cable.Do not route temperature sensor wiring with building power wiring, next to controlcontactors or near light dimming circuits, electric motors or welding equipment.
Avoid poor wiring connections.Avoid intermittent or missing building earth ground.
CAUTIONElectrical Shock Hazard.
Can cause electrical shock or equipment damage.Disconnect ower su l before connectin wirin .
Wiring must comply with applicable codes, ordinances and regulations:1.Wire Outdoor Sensor to S1and S2 terminals on the thermostat. If leadwire provided is notlong enough), you need an extra cable to reach the hole at location.a. Using color-coded, 18-gauge thermostat wire is recommended. For example of generalwiring of sensor, see Fig. 26.b. Pigtail wiring can be used.
2.Mount Sensor in its mounting clip.3.Plug wiring hole using nonhardening caulk or putty.
41
8/13/2019 CDT900 Series Manual
43/102
CDT900 Series Touchscreen Programmable Thermostat
1.USE APPROPRIATE MOUNTING MEANS FOR THE TYPE OF STRUCTURE.2.PLUG WIRING HOLE WITH NON-HARDENING CAULK OR PUTTY .
Fig. 26. Wire Outdoor Sensor to the thermostat.
42
12
WIRINGHOLE
THROUGH
STRUCTUREORS-01
8/13/2019 CDT900 Series Manual
44/102
CDT900 Series Touchscreen Programmable Thermostat
LocateandMount RemoteIndoor TemperatureSensor (Optional)1.Choose a location (see Fig. 27) for mounting the sensor on an inside wall about 19.4 ft
(1.5m) above the floor.2.Be sure wire distance between sensor and thermostat is less than 65.61 ft6m.3.Make sure there is good air circulation at average temperature at the chosen location.
Avoid the following locations because they can introduce errors in sensormeasurements. See Fig. 27.Hot areas caused by:(a) Concealed pipes or ducts.
(b) Drafts from fireplaces or other heat sources.(c) Convection or radiant heat from the sun or electrical equipment.Cold areas caused by:(a) Concealed pipes or ducts.(b) Drafts from windows and doors.Unheated areas on the other side of the wall location.Dead air areas:(a) Behind doors, furniture and curtains. (b) In corners and alcoves.4.Mark the area on the wall selected for mounting the Sensor or junction box.5.Run wire cable to a hole at the selected wall location. Pull approximately three inches ofwire through the opening. Color-coded, 18-gauge thermostat wire is recommended.
43
8/13/2019 CDT900 Series Manual
45/102
CDT900 Series Touchscreen Programmable Thermostat
44
Fig. 27. Typical location for Indoor Sensor.
5FEET
1.5METERS
8/13/2019 CDT900 Series Manual
46/102
CDT900 Series Touchscreen Programmable Thermostat
WireIndoor Sensor
CAUTIONElectrical Interference (Noise) Hazard. Can cause erratic system operation.Keep wiring at least one foot away from large inductive loads such as motors, linestarters, lighting ballastsand large power distribution panels.
IMPORTANTErratic temperature readings from a sensor can occur as a result of any of thewiring practices described below. Avoid these practices to assure correctoperation.Be sure wires have a cable separate from the thermostat cable.Do not route temperature sensor wiring with building power wiring, next tocontrol contactors or near light dimming circuits, electric motors or weldingequipment.
Avoid poor wiring connections.Avoid intermittent or missing building earth ground.
45
8/13/2019 CDT900 Series Manual
47/102
CDT900 Series Touchscreen Programmable Thermostat
CAUTIONElectrical Shock Hazard.Can cause electrical shock or equipment damage.Disconnect ower su l before connectin wirin .
Wiring must comply with applicable codes, ordinances and regulations.1.Wire Indoor Sensor to S1 and S2 terminals on the thermostat. For an example of generalwiring of IRS-1, see Fig. 28 to wire one sensor and 29 to wire multiple sensors.2.Push excess wire back into the hole. Plug the holeusing nonhardening caulk, putty or insulation to prevent drafts from affecting performance.
3.Remove IRS-1 sensor cover.4.Mount IRS-1 to the wall or junction box using the screws and anchors provided.5.Level the IRS-1 for appearance only. Device functions correctly even when not level.6.Install IRS-1 cover.
46
8/13/2019 CDT900 Series Manual
48/102
CDT900 Series Touchscreen Programmable Thermostat
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS ANDOVERLOAD PROTECTION AS REQUIRED.
2. IF MORE THAN ONE REMOTE SENSOR IS REQUIRED, REFER TO
FIGURE 3
3.. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTA
CABLE.
Fig. 28. Wiring a single Indoor Sensor. 47Fig. 29. Wiring Multiple Sensors.
1SENSORS MUST BE ARRANGED IN THIS CONFIGURATION TO OPERATE
CORRECTLY.
2WIRES MUST HAVE A CABLE SEPARATE FROM THERMOSTAT CABLE
RC 1
2
C7189
3
S1 S2 C R RC W W2 Y2 Y G
S1 S2 C R RC
C7189 C7189
C7189 C7189
1
2
S1 S2 C R RC
C7189 C7189 C7189
C7189 C7189 C7189
C7189 C7189 C7189
1
2
8/13/2019 CDT900 Series Manual
49/102
CDT900 Series Touchscreen Programmable Thermostat
INSTALLERSETUPFollow these steps to enter the InstallerSetup:1.Press and release the System Key.
2.Press and hold the two blank keys on
either side of the center blank key forapproximately five seconds until screenchanges.
48
AUTO
AMRoom SCHED
HOLD
CLOCK
SCREEN
MORE
SYSTEM
AUTO
FAN
Set To
TUE
Running As SCHED
DONEDONE
RoomSYSTEM
HEAT
OFFCOOL
TUE
CANCEL
Set To
AM
8/13/2019 CDT900 Series Manual
50/102
CDT900 Series Touchscreen Programmable Thermostat
3.Release the two blank keys when thescreen on the thermostat matches the
screen below.
4.See screen below to review how thethermostat keys are used during Installer
Setup. See Tables 3-5 for the InstallerSetu Numbers and Settin s.
5.Press the Done key to exit the Installer Setup screen.
49
DONE
DONE
INSTALLER
SETUP
NUMBER
ADVA NCE TO N EXT
INSTALLER SETUP
CURRENT
SETTING
CHANGE THE
CURRENT SETTING
PRESS TO EXIT
INSTALLER SETUP
8/13/2019 CDT900 Series Manual
51/102
CDT900 Series Touchscreen Programmable Thermostat
Installer SetupNumber
Installer SetupName Settings Notes
0120 Date(Year Upper)
Select first two digits of current calendar year(2005, etc)
it cannt be changed
0130Date
(Year Lower)Select last two digits of current calendar year(05 for year 2005, etc)
2001 - 2099 available
0140 Date (Month)Select number that represents currentcalendar month
0150 Date (Day)Select number that represents currentcalendar date
0160 Schedule Options0-nonprogrammable4-7-day programmable
when it is changed, the schedneed to be reprogrammed)
0170 System Type Selection
1-1 heat/1 cool conventional (factory setting)2-single-stage heat pump (no auxiliary heat)3-heat only conventional (no fan) Also for750mV.4-heat only conventional (with fan)5-heat only (power to open and power toclose zone valves or normally-open zonevalves)6-cool only conventional7-2 heat/1 cool heat pump (with auxiliaryheat)
8-2 heat/2 cool multistage conventional9-2 heat/1 cool multistage conventional10-1 heat/2 cool multistage conventional11-2 heat/2cool heat pump (no auxiliary heat)12-3 heat/2cool heat pump (with auxiliaryheat)
Available options and defaultsvary by thermostat. Systemselection automaticallymodifies some default settingsand/or hides other InstallerSetup options.
Table 3.installer Setup Menu.
50
8/13/2019 CDT900 Series Manual
52/102
CDT900 Series Touchscreen Programmable Thermostat
InstallerSetup
Number
Installer SetupName
Settings Notes
0180 Fan Control in Heating
0-gas or oil furnace equipment controls fan in
heating (factory setting)
1-electric furnace thermostat controls fan in
heating
Only shown if conventional
system is selected. If heat
pump is chosen, fan defaults
to electric.
0190
Changeover Valve O/B
Terminal Energized in
Heating or Cooling
(Heat Pumps Only)
0-changeover valve O/B terminal setting
1-changeover valve O/B terminal is
energized in heating
Only shown if heat pump
system is chosen.
0200Backup Heat Source
(Auxiliary Heat)
0-heat pump backup heat source is electric(factory setting)
1-heat pump backup heat source is fossil fuel
Only shown if 2 heat/1 cool or3 heat/2 cool heat pump is
chosen
0210External Fuel
FossilFuel Kit
0-no external fossil fuel kit is controlling heat
pump backup heat. This thermostat controls
the dual fuel. Must install outdoor sensor and
set Installer Setup Number 0340 to number
2. 1-external fossil fuel kit is controlling heat
pump backup heat
Only shown if fossil fuel is
chosen as backup heat
source.
0220Cycles per hour (cph)
for 1st Stage
Compressor
3-cph recommended for compressors(factory setting)
1, 2, 4, 5, 6-other cycle rate settings
0230
Cycles per hour (cph)
for 2nd Stage
Compressor
3-cph recommended for compressors
(factory setting)
1, 2, 4, 5, 6other cycle rate settings
Only shown if two stages of
cool are selected.
Table 3.installer Setup Menu.(CONTINUES)
51
8/13/2019 CDT900 Series Manual
53/102
CDT900 Series Touchscreen Programmable Thermostat
Table 3.installer Setup Menu. (CONTINUES)
Installer SetupNumber
Installer SetupName Settings Notes
0240Cycles per hour (cph)
for 1st StageConventional Heat
1- 1 cph used for steam and gravity3-3 cph used for hot water system and highefficiency (90% or better) furnaces5-5 cph used for standard fossil fuel forcedair (less than80% efficient) systems (factory setting)9-9 cph used for electric furnaces2, 4, 6, 7, 8, 10, 11, 12other cycle ratesettings
Not shown if system selectionis heat pump. Selection in thisstage changes default cph for2nd stage heat.
0250
Cycles per hour (cph)for 2nd Stage Heat
(Aux Heat for 2H/1CHeat Pumps)
1-1 cph used for steam and gravity
3-3 cph for hot water systems and highefficiency (90% or better) furnaces5-5 cph for standard fossil fuel forced air(less than 90% efficient) systems (factorysetting)9-9 cph used for electric furnaces or electricauxiliary heat for heat pump systems2, 4, 6, 7, 8, 10, 11, 12other cycle ratesettings
Only shown if two stages ofheat are selected.
0260Cycles per hour (cph)
for 3rd Stage Heat AuxHeat for 3H/2C Heat
Pumps)
1-1 cph used for steam and gravity3-3 cph for hot water systems and highefficiency (90% or better) furnaces
5-5 cph for standard fossil fuel forced air(less than 90% efficient) systems (factorysetting)9-9 cph used for electric furnaces or electricauxiliary heat for heat pump systems2, 4, 6, 7, 8, 10, 11, 12-other cycle ratesettings
Only shown if 3H/2C heatpump is selected.
52
8/13/2019 CDT900 Series Manual
54/102
CDT900 Series Touchscreen Programmable Thermostat
Table 3.installer Setup Menu. (CONTINUES)
Installer Setup
Number
Installer Setup
NameSettings Notes
0270Cycles per hour (cph)
for Emer
3-3 cph for hot water systems and highefficiency (90% or better) furnaces
5-5 cph for standard fossil fuel forced air
(less than 90% efficient or better) systems
9-9 cph for electric strip heat for heat pumps
Only shown if 2H/1C or 3H/2C
heat pump is selected.
0280 Continuous Backlight0-Backlight function disable
1-Backlight function enable.
0300 Changeover0-manual changeover (factory setting)
1-auto changeover
0310 Deadband
Heating and cooling setpoints can be set no
closer than chosen value:
2-2F (1.5C)
3-3F (2C)
4-4F (2.5C)
5-5F (3C)
6-6F (3.5C)
7-7F (4C)
8-8F (4.5C)
9-9F (5C)
Shown only if automatic
changeover is selected.
0320Temperature Indication
Scale
0-fahrenheit temperature display (factory
setting)
1-celsius temperature display
when it is changed, the schedneed to be reprogrammed)
53
8/13/2019 CDT900 Series Manual
55/102
CDT900 Series Touchscreen Programmable Thermostat
Table 3.installer Setup Menu. (CONTINUES)
Installer Setup
Number
Installer Setup
NameSettings Notes
0330 Daylight Savings1-daylight savings is on (factory setting).
0-daylight savings is off.
Set to 0 in areas that do not
follow daylight savings.
0340
Remote Temperature
Sensor (Outdoor or
Indoor)
0-no remote temperature sensor
1-outdoor temperature sensor for display
only.
2-outdoor temperature sensor for
control.Outdoor sensor used for Heat Pump
Lockout settings. (See Heat PumpTemperature Lockout section for more
details.)
3-indoor temperature sensor
Defaults and Options depend
on System Type selection.
Indoor Temperature Sensor
uses an averaging network
and does not include on-boardsensor.
0350
Heat Pump
Compressor Lockout
or (Balance Point)
0-no compressor lockout.
15F (-9.5C)
20F (-6.5C)
25F (-4C)
30F (-1C)
35F (1.5C)
40F (4.5C)
45F (7C)
Default depends on other
selections. Shown if control is
selected. (See section formore information.)
54
8/13/2019 CDT900 Series Manual
56/102
CDT900 Series Touchscreen Programmable Thermostat
Table 3.installer Setup Menu. (CONTINUES)
Installer Setup
Number
Installer Setup
NameSettings Notes
0360Heat Pump Auxiliary
Lockout
0-no auxiliary heat lockout.
40F (4.5C)
45F (7C)
50F (10C)
55F (13C)
60F (15.5C)
Shown if electric is chosen for
backup heat source and
outdoor temperature sensor
for control is selected. (See
Advanced Features section for
more information.)
0380
Indoor
Dehumidification
Control
0-No indoor dehumidification control.
1-Dehumidification control activated.
Available on select odels. If
dehumidification control isactivated and auto-
changeover is selected in
Installer Setup Number 0300,
the deadband minimum is
defaulted to 5F (3C) in
Number 0310.
0500Furnace Change
Reminder
0-furnace filter reminder off
1-10 run time days
2-30 run time days3-60 run time days
4-90 run time days
5-120 run time days
6-365 run time days
Run time based on call for fan.
55
8/13/2019 CDT900 Series Manual
57/102
CDT900 Series Touchscreen Programmable Thermostat
Installer Setup
Number
Installer Setup
Name
Settings Notes
0510Humidifier PadReplacement
Reminder
0-humidifier pad replacement reminder off
1-90 calendar days
2-180 calendar days
3-365 calendar days
0520UV Lamp Replacement
Reminder0-UV lamp replacement reminder off
1-365 calendar days
0530Adaptive Intelligent
Recovery
1-Adaptive Intelligent Recovery control isactivated (system starts early so setpoint isreached by start of program period).
0-Conventional Recovery (system startsrecovery at programmed time)
0540 Number of Periods2-two periods available (Wake and Sleep)4-four periods available (Wake, Leave,Return and Sleep)
Not shown if non-programmable isselected. 2 or4 applies to all days of theweek. (when it is changed, thesched need to bereprogrammed)
0580Minimum Compressor
Off Time
5-five-minute compressor off-time setting(factory setting)
0, 2, 3, 4-other compressor off-time settings
0600Heat TemperatureRange Stop
40-90-temperature range (1F increments) ofheating setpoint.
Shown in 1/2 C.
0610Cool TemperatureRange Stop
50-99-temperature range (1F increments) ofcooling setpoint.
Shown in 1/2 C.
0640 Clock Format12-12 hour clock (factory setting)
24-24 hour clock
Table 3.installer Setup Menu. (CONTINUES)
56
8/13/2019 CDT900 Series Manual
58/102
CDT900 Series Touchscreen Programmable Thermostat
Table 3.installer Setup Menu. (CONTINUES)
Installer Setup
Number
Installer Setup
Name
Settings Notes
0650Extended Fan OnTime
Heat
0-no extended fan operation after call forheat ends
90- fan operation is extended 90 secondsafter call for heat ends.
Not shown if fan operation isset to fossil fuel or in Cool OnlySystems
0660Extended Fan On Time
Cool
0.no extended fan operation after call for coolends
90.fan operation is extended 90 secondsafter call for cool ends.
Not shown in Heat Only
Systems.
0670 Keypad Lockout
0-unlocked keypad
1-partially locked keypad
2-fully locked keypad
Unlockedall functions are
available.Partially locked onlytemperature up and downkeys and ability to enter andmodify Installer Setup modeare available.
Fully locked only ability toenter and modifyInstallerSetup mode are available.
0680Temperature Control in
Heat
1-less aggressive temperature control (couldcause temperature undershoot)
2-Standard temperature control in heating(factory setting)
3-more aggressive temperature control(could cause temperature overshoot)
Applies to recovery ramp anduse of auxiliary heat during
recovery.Choose 1 if gettingtemperature overshoot.
Choose 3 if gettingtemperature undershoot.
57
8/13/2019 CDT900 Series Manual
59/102
CDT900 Series Touchscreen Programmable Thermostat
Installer Setup
Number
Installer Setup
Name
Settings Notes
0690
Temperature Control in
Cool
1-less aggressive temperature control (couldcause temperature undershoot)
2-Standard temperature control in cooling(factory setting)
3-more aggressive temperature control(could cause temperature overshoot)
Applies to recovery ramp.
Choose 1 if gettingtemperature overshoot.
Choose 3 if gettingtemperature undershoot.
0700 Temperature DisplayOffset
-3F (-1.5C)
-2F (-1C)
-1F (-.5C)
0F (0. C) (no difference in displayedtemperature and actual room temperature )
1F (.5C)
2F (1C
3F (1.5C)
0710 Reset Thermostat0-no thermostat reset.
1-resets all Installer Setup Options to defaultvalues and resets schedule to default setting.
Only calendar settings andtime are retained.
Table 3.installer Setup Menu. (CONTINUES)
58
8/13/2019 CDT900 Series Manual
60/102
CDT900 Series Touchscreen Programmable Thermostat
INSTALLERSYSTEMTESTUse the Installer System Test to test the W1 W2 E AUX Y1 Y2 and L .
CAUTIONEquipment Damage Hazard.Minimum compressor off time is bypassed during Installer System Test
Avoid cycling compressor quickly.
59
Howto Usethe InstallerSystemTestThe Installer Test is part of the Installer Setup Menu.
1.Enter the Installer System Test by entering the Installer Setup.2.Note that the test appears at the end of the Installer Setup Numbers.3.See Fig. 30 to review how the thermostat buttons are used during the Installer System Test.See Table 6 for available Installer System Tests.
8/13/2019 CDT900 Series Manual
61/102
CDT900 Series Touchscreen Programmable Thermostat
60
Fig. 30. Review thermostat buttons used during Installer System Test.
DONE
SYSTEM TESTNUMBER
SYSTEM STAUSNUMBER
UP ARROW KEY
ADVANCES TO
NEXT SYSTEMTEST NUMBER
UP ARROW
TURNS THE
SYSTER ON
DONE KEY
EXITS INSTALLE
SYSTEM TEST
ARROW ARROW
TURNS THE
SYSTER OFF
8/13/2019 CDT900 Series Manual
62/102
CDT900 Series Touchscreen Programmable Thermostat
InstallerSystemTestsTable 4. Installer System Test.
System Test Number Test Type System Status Number andDescription
Test 1 Cooling System Test1-Cool stage 1 and stage 2 turn on.
0-Cool is off.
Test 2 Fan System Test 1-Fan turns on.
0-Fan turns off.
Test 3 Heating System Test
1-Heat stage 1 and stage 2 (aux
heat) turn on.
0-Heat is off.
Test 4 Emergency Heat Test1-Emergency heat and L turn on.
0-Emergency heat and L turns off.
Press the Next button to go to the beginning o f the Installer Setup or p ress the Done button to exit the Installer
System Test.
61
8/13/2019 CDT900 Series Manual
63/102
CDT900 Series Touchscreen Programmable Thermostat
OPERATION
ThermostatKeys Thermostat Display
62
AUTO
AMRoom SCHED
HOLD
CLOCK
SCREEN
MORE
SYSTEM
FAN
Set To
TUE
HEAT
FAN
SELECTS
ON/AUTO/CIRC
SYSTEM
SELECTS EM.
HEAT/OFF/COOL
AUTO/EMER
UP ARROW
RAISES
TEMPERATURESETTING
DOWN ARROE
LOWERS
TEMPERATURESETTING
SCHED
ENTERS
SCHEDULING
MODE
HOLD
SETS A PERMANENT
HOLD AND ACTIVITIES
VACATION HOLD
CLOCK
SETS THE TIME
FORWARD
OR BACK
SCREEN
LOCKS OUT THE
SCREEN TO ALLOWFOR CLEANING
Running As SCHED
MORE
SHOWS ADDITIONAL
ACCESSORY ANDMAINTENANCE
OPTIONS
AUTO
AMRoomSCHED
HOLD
CLOCK
SCREEN
MORE
SYSTEM
FAN
Set To
TUE
HEAT
FAN
SHOWS FAN
SETTING
SYSTEM
SHOWS
CURRENT
SYSTEM
POSITION
TUE
SHOWS
CURRENT
DAY OF THE
WEEK
INSIDE TEMPERATURE
SHOWS THE CURRENT
INSIDE TEMPERATURE
TIME
DISPLAY CURRENT
TIME OF DAY. HOLD
TIME REMAINING OR
NUMBER OF VACATION
DAYS REMAINING
SET TO
TEMPERATURE
SHOWS THE
CURRENT SET
TEMPERATURE
Running As SCHEDRunning As SCHED
RUNNING AS SCHED
SHOWS THE
THERMOSTAT IS
FOLLOWING THE
PROGRAMMED
SCHEDULE
8/13/2019 CDT900 Series Manual
64/102
CDT900 Series Touchscreen Programmable Thermostat
SystemandFanSettingsSystem
The System key selections vary based on your heating and/or cooling system type.Heat Thermostat controls the heating system.Off Both heating and cooling systems are off.Cool Thermostat controls the cooling system.
Auto Thermostat automatically changes between heating and cooling operation,depending on indoor temperature.Emer Emergency heat cycles to maintain temperature. Compressor is locked out (usedonly for 2H/1C or 3H/2C heat pump systems) and auxiliary heat turns on as second stage ifneeded.
FanThe Fan key selections vary based on the heating and/or cooling system type.On Fan runs continuously. Use this setting for improved air circulation or for more efficientcentral air cleaning.
Auto Fan follows the fan program schedule.
Circ Fan runs randomly approximately 35% of the time when the equipment norequirement. Use this setting for improved air circulation or for more efficient central aircleaning when you do not want the fan running continuously.
63
8/13/2019 CDT900 Series Manual
65/102
CDT900 Series Touchscreen Programmable Thermostat
UserSetupFollow these steps to enter the User
Setup:1Press and release the System key.
2Press and hold the center blank key for
approximately five seconds until the screenchanges.
64
AUTO
AMRoom SCHED
HOLD
CLOCK
SCREEN
MORE
SYSTEM
FAN
Set To
TUE
Running As SCHED
HEAT
DONE
RoomSYSTEMHEAT
OFF
COOL
TUE
CANCEL
Set To
AM
8/13/2019 CDT900 Series Manual
66/102
CDT900 Series Touchscreen Programmable Thermostat
3Release the center blank key when thescreen on the thermostat matches the
screen below.
4See the screen below to review how thethermostat keys are used during the User
Setup. See Table 5 for the User Setupnumbers and settings.
5Press the Done key to exit the User Setup screen.
65
DONEDONE
INSTALLER
SETUP
NUMBER
ADVANCE TO NEXT
INSTALLER SETUPCURRENT
SETTING
CHANGE THE
CURRENT SETTING
PRESS TO EXIT
INSTALLER SETUP
8/13/2019 CDT900 Series Manual
67/102
CDT900 Series Touchscreen Programmable Thermostat
Installer Setup
Number
Installer Setup
Name
Settings
0120Date
(Year Upper)it cannt be changed
0130Date
(Year Lower)Select last two digits of current calendar year (05 for year 2005, etc)
0140 Date (Month) Select number of current calendar month (1-12)0150 Date (Day) Select number of current calendar date (1-31)
0160 Schedule Options0-Non-programmable4-7-day programmable(factory setting)(when it is changed, the sched need tobe reprogrammed)
0320Display temperature in
F or C0-F setting (factory setting)1-C setting
0330 Daylight savings time1-Daylight function enable0-Daylight function disable
0500 Furnace air filter
0-off (factory setting)1-10 fan run time days(about one month)2-30 fan run time days(about three months)3-60 fan run time days(about six months)4-90 fan run time days(about nine months)5-120 fan run time days(about one year)6-365 fan run time days(about three years)
0510Humidifier pad
reminder
0-off1-3 months2-6 months3-12 months
0520 UV lamp reminder0-off (factory setting)1-1 year
Table 5. User Setup Settings.
66
8/13/2019 CDT900 Series Manual
68/102
CDT900 Series Touchscreen Programmable Thermostat
Table 5. User Setup Settings. (CONTINUES)
Installer SetupNumber
Installer SetupName Settings
0540Number of schedule
periods available2-two (Wake and Sleep)4-four (Wake, Leave, Return, Sleep)factory setting
0640 Clock format12-12-hour clock(factory setting)24-24-hour clock
0670 Screen lockout
0-all keys available; screen is unlocked (factory setting)1screen is partially locked. All key functions locked except Temperature Upand Down keys and Cancel key.2-screen is fully locked
67
8/13/2019 CDT900 Series Manual
69/102
CDT900 Series Touchscreen Programmable Thermostat
PROGRAMMING
PreprogrammedEnergy Star SettingsTable 6 shows default program settings. Visit the Energy Star web site atwww.energystar.gov for additional education and resources on programmable thermostats.
Table 6. Energy Star Default Program Settings.
Setpoints
Schedule Period Time
Heat Cool
Fan Setting
Wake 6:00AM 68F (20C) 78F (26C) Auto
Day 8:00AM 60F (16C) 85F (29C) Auto
Evening 4:00PM 68F (20C) 78F (26C) Auto
Sleep 10:00PM 60F (16C) 82F (28C) Auto
Program HeatingandCooling ScheduleYour thermostat can control up to four different schedule periods per day:Wake-Period when you awaken and want your home at a comfortable temperature.Day
-
Period when you are away from home and want an energy-saving temperature.Evening-Period when you return home and want your home back to a comfortabletemperature.Sleep-Period when you are asleep and want an energy-saving temperature.NOTE: Schedule times are in 15-minute
68
8/13/2019 CDT900 Series Manual
70/102
CDT900 Series Touchscreen Programmable Thermostat
Edit Schedule1.Press Sched key. 2.Press PROG DAY key to review the
programs to see that the settings arecompatible with your lifestyle.
69
CANCEL DONE
AUTO
CANCELPERIOD
AM
COOL
EDIT
WAKE
DAY
EVENING
SLEEP
FAN
DAYPROGMON TUEWED THU FRI
HEAT
CANCEL DONE
AUTO
CANCELPERIOD
AM
COOL
EDIT
WAKE
DAY
EVENING
SLEEP
FAN
DAYPROGMON TUEWED THU FRI
HEAT
8/13/2019 CDT900 Series Manual
71/102
CDT900 Series Touchscreen Programmable Thermostat
3.Press the edit then you press PROG DAYkey to select the program days
NOTE:The Fan setting can be programmefor On, Auto, or Circ for each periodselected. See Fan Schedule sectionfor more information.
6.Another approach to programming is tofirst program all weekdays Mon through Firand Sat and Sun as same programs.
4.Press Wake key. Once pressed, Wakeflashes to show it is selected. Same as theother sched5.Press Up and Down keys to modify timeand heat and cool temperatures from thisscreen.
70
CANCEL DONE
WAKE
DAY
EVENING
SLEEP
DAYPROGMON TUEWED THU FRI
CANCEL DONE
AUTO
CANCELPERIOD
AM
COOL
EDIT
WAKE
DAY
EVENING
SLEEP
FAN
DAYPROGMON TUEWED THU FRI
HEAT
8/13/2019 CDT900 Series Manual
72/102
CDT900 Series Touchscreen Programmable Thermostat
.
7. To exit schedule without saving changes,press Cancel key any time.
CancelaSchedulePeriod1.Press Sched key.
2.Press Edit key.3.Select the Day(s) of the week desired.4.Press schedule period you want to cancel(Wake, Leave, Return or Sleep). Onceselected, the period flashes.5.Press Cancel Period key.
NOTE: To set a Program Schedule for theremaining days of the week, repeatsteps 1-9. Example: If Mon Fri waselected first, go back and repeatsteps 1-6 for Sat and Sun.
6.The time, temperature(s) and fan settingdisappear. The bar above the selected periodis removed, indicating the scheduled period
was cancelled.NOTE: To reinstate a schedule period, pressarrow keys to set desired time andtemperatures.
71
CANCEL DONE
AUTO
CANCEL
PERIOD
AM
COOL
WAKE
DAY
EVENING
SLEEP
FAN
DAYPROGMON TUEWED THU FRI
HEAT
8/13/2019 CDT900 Series Manual
73/102
CDT900 Series Touchscreen Programmable Thermostat
7. Press Done key.
OnFan runs continuously (programmablefor all schedule periods).
Circ
Fan runs randomly for approximately35% of schedule period when norequirement from equipments(programmable for all schedule periods).
Fan SchedulePress Fan key while in the Scheduling
Screen to program the System Fan. Choicavailable from the Scheduling Screen:
Auto (default position)Fan runs withequipment. Programmable for all scheduleperiods (Wake, Leave, Return and Sleep).
72
CANCEL DONE
AUTO
CANCELPERIOD
WAKE
DAY
EVENING
SLEEP
FAN
DAYPROGMON TUEWED THU FRI
COOLHEAT
CANCEL DONE
AUTO
CANCELPERIOD
AM
COOL
WAKE
DAY
EVENING
SLEEP
FAN
DAYPROGMON TUEWED THU FRI
HEAT
8/13/2019 CDT900 Series Manual
74/102
CDT900 Series Touchscreen Programmable Thermostat
anua verr e o an c e u eUse Fan key to change fan work statesby manual.
Auto-fan is automatically following the Fanschedule(choices are Auto, On or Circulate).On-Fan runs randomly for approximately35% of schedule period when norequirement from equipments.Circ-Fan circulates randomly forapproximately 35% of time.
When the program reaches to nextschedule, the fan will run as the setting inthe period.
Operate CDT900 SeriesTouchscreen
Set Time1.Press Clock.2.Use arrows to set current
73
CANCEL DONE
AM
8/13/2019 CDT900 Series Manual
75/102
CDT900 Series Touchscreen Programmable Thermostat
4. Press Done key.
IMPORTANTThe current day of the week shouldalready be set correctly. If not, seeInstaller Setup to set the day.
Set TemperatureOverridesThe thermostat has three temperature
override options: Override TemperatureUntil, Permanent Override and VacationHold.
Override Until (TEMPORARY Override)
Holds temperature temporarily until the nextscheduled period time or until the time theuser sets.
1. Press Up or Down arrow next to thetemperature you want to adjust. HoldTemperature Until time appears on thescreen. The Hold Temperature Until timedefaults to the start time of the nextscheduled period.
2. Press Up or Down arrow next to the Timekey to set desired time for the thermostat toresume
3. Press the Cancel or Sched key to cancelOverrideTemperature Untiland resumeschedule.
74
CANCEL
AUTO
PM
Override Until
Room
SCHED
HOLD
CLOCK
SCREEN
SYSTEM
HEAT
FAN
Set To
TUE
8/13/2019 CDT900 Series Manual
76/102
75
CDT900 Series Touchscreen Programmable Thermostat
VACATION HOLD
Changes temperature setting for a designated number of days.
1
Press the Up and Down arrow keys to set the desired temperature while away on vacation.Notice that Hold Temperature Until time is shown on the screen. (This is the time the Vacation
Hold override expires after the number of days ends.)
2Press Hold key twice. Screen shows Hold Temperature Until one day.3Press Up and Down arrow keys to change the number of Days you desire thermostatto override the schedule.NOTE: Days Up and Down arrows appear for approximately seven seconds. Pressing
ust below Hold Temperature Until on the screen allows the Days Up and Down arrowsto reappear.
4. To cancel the Vacation Hold overrideearly, press the Cancel key.NOTE:When the number of days of
Vacation Hold expires, the screenshows Following Schedule to
indicate that Vacation Hold hasended.
CANCEL
AUTO
Override UntilRoom SCHED
CLOCK
SCREEN
SYSTEM
HEAT
FAN
Set To
TUE
DAYS
8/13/2019 CDT900 Series Manual
77/102
CDT900 Series Touchscreen Programmable Thermostat
CleanThermostat Screen
The thermostat has a touch screen interaction. Follow these steps to clean the screenwithout making thermostat changes:1.Press the Screen key. Thermostat locks out all touch keys for 30 seconds to allow forcleaning.
76
CLEAN SCREEN
8/13/2019 CDT900 Series Manual
78/102
CDT900 Series Touchscreen Programmable Thermostat
2.Use damp cloth slightly moistened withwater or house- hold glass cleaner to cleanthe screen.3.Repeat the above steps, as necessary.IMPORTANT
Do not spray any type of liquiddirectly on the thermostat itself. Ifusing household glass cleaner,spray cleaner on cloth. Then usea cloth to clean the thermostat
screen.4.Press the Done key to return to theHome Screen and normal operation.
ReplaceBatteries1.When the Battery indicator is flashing,
replace the batteries promptly with twofresh AA alkaline batteries
2.Remove thermostat from the wallplate bpulling straight out.
3.Remove the old batteries and insert twofresh AA alkaline batteries, as marked on thethermostat.
77
8/13/2019 CDT900 Series Manual
79/102
CDT900 Series Touchscreen Programmable Thermostat
4.Align the screw blocks with the pins on theback of the thermostat.
5.Push the thermostat straight onto the
wallplate until it snaps into place.
78
BATTERIES(2)
WALLPLATE
TERMINALSCREWBLOCK
PINSONBACKOF
THERMOSAT
8/13/2019 CDT900 Series Manual
80/102
CDT900 Series Touchscreen Programmable Thermostat
BatteryTips1.Replace the batteries as soon as Battflashes in the display. The Battery indicator
flashes in the display one month before thebatteries run down completely.2.Always use fresh AA alkaline batteries.Non-alkaline batteries do not last as longand can leak, causing thermostat damage.3.Although the thermostat has a LowBattery indicator, replace the batteriesonce a year to prevent the thermostat andheating/cooling system from shutting downdue to lack of battery power.
ScreenLocks
Partially Locked ScreenWhen partially locked, the screen indicatesScreen Locked for 5 to 7 seconds whenever the
user attempts to press a key that is locked.Pressing a locked key, while Screen Locked isshown, flashes ScreenLocked on thescreen.In this mode, all keys are locked except theTemperature Up and Down arrow keys:User can change temperature up or down
but cannot change schedule settings.Temporary temperature change lasts untilnext scheduled period and that time showson screen.To cancel temperature override and beginfollowing schedule, press Cancel key.To unlock screen, see Installer Setup section.
Fully Locked ScreenIn this mode, all keys are locked and notfunctional. To unlock screen, see InstallerSetup section. The screen continuouslydisplays Screen Locked.
79
AUTO
Room SCHED
HOLD
CLOCK
SCREEN
SYSTEM
HEAT
FAN
Set To
TUE SCREEN LOCKED
Running As SCHED
MORE
8/13/2019 CDT900 Series Manual
81/102
CDT900 Series Touchscreen Programmable Thermostat
Outdoor TemperatureIf an outdoor temperature sensor is installed,
the thermostat displays the outsidetemperature in the lower right corner of theHome Screen.
If thermostat is set to Auto ChangeoverSystem mode, press the More key until theoutside temperature is shown on the screen.
80
CANCEL DONE
Outside
AUTO
Room SCHED
HOLD
CLOCK
SCREEN
SYSTEM
HEAT
FAN
Set To
TUE
AM
Running As SCHED
MORE
AM
Outside
8/13/2019 CDT900 Series Manual
82/102
CDT900 Series Touchscreen Programmable Thermostat
RemoteIndoor TemperatureIf a remote indoor temperature sensor isinstalled, the thermostat displays the inside
temperature on the screen from the remotesensor(s).The thermostat internaltemperature sensor is not used.
ONE REMOTE INDOOR SENSOR INSTALLED(OPTIONAL)
If one remote indoor temperature sensor is
used, the screen showing the Insidetemperature reading shows the temperatureat the indoor remote sensor location. Thethermostat internal temperature sensor isnot used.
MULTIPLE REMOTE INDOOR SENSORSINSTALLED (OPTIONAL)
If more than one remote indoor sensor isused, the screen showing Inside temperaturreading shows the average of all the remoteindoor sensors. The thermostat internaltemperature sensor is not used.
81
AUTO
Room SCHED
HOLD
CLOCK
SCREEN
SYSTEM
HEAT
FAN
Set To
TUE
AM
Heat On
Running As SCHED
MORE
AM
8/13/2019 CDT900 Series Manual
83/102
CDT900 Series Touchscreen Programmable Thermostat
Indoor Air QualityRemindersFilter Change Reminder
The filter change reminder must be turnedon from the Installer Setup. Once expired,the screen flashes, ChangeFilterand a Reset key appears. Press theReset key to reset the change reminder.
NOTE: The days are counted as fan runtime, so anytime the fan is running, thereminder is counting that time against thenumber of days selected.
The remaining run time days can be viewedby pressing the More key; the remainingdays can be edited using the More key or
from the Installer Setup. To view or reset thereminder before it expires, follow thesesteps using the More key:
1.Press the More key until the filter reminderappears on the screen. This is the number offan run-time days remaining on the filterreminder.
82
DONE
MORE
DAYS
FILTER
EDIT
CANCEL
RESET
AUTO
Override Until
Room
SCHED
HOLD
CLOCK
SCREEN
SYSTEM
HEAT
FAN
Set To
TUERENEW FILTER
Running A s SCHED
MORE
PM
RESET
8/13/2019 CDT900 Series Manual
84/102
CDT900 Series Touchscreen Programmable Thermostat
2.Press the Edit key.3.Use the Up and Down keys to changethe number of run-time days.
4.Press the Done key to go back to the
viewing screen.
83
DONE
MORE
DAYS
FILTER
EDIT
CANCEL
RESET
CANCEL DONE
MORE
RESET
FILTER
EDITDAYS
8/13/2019 CDT900 Series Manual
85/102
CDT900 Series Touchscreen Programmable Thermostat
5.Press the Reset key to activate the newnumber of days selected in the previousscreen.
6.Press the Done key to return to the Home
Screen.
84
DONE
DAYS
FILTER
CANCEL
8/13/2019 CDT900 Series Manual
86/102
CDT900 Series Touchscreen Programmable Thermostat
Humidif ier Pad ReminderThe Humidifier Pad change reminder must bturned on from the Installer Setup. Onceexpired, the screen flashes,ChangeHumidifier Pad and a Reset key appears.Press the Reset key to reset the changereminder.The remaining calendar days can be viewedby pressing the More key. The remainingdays can be edited using the More key orfrom the Installer Setup. To view or reset thereminder before it expires, follow these steps
using the More key:1.Press the More key until the Humidifier Pachange reminder appears on the screen. Thiis the number of calendar days remaining onthe Humidifier Pad reminder.2.Press the Edit key.3.Use the Up and Down keys to change thenumber of calendar days.4.Press the Done key to go back to the
viewing screen.5.Press the Reset key to activate the newnumber of days selected in the previousscreen.6.Press the Done key to return to the HomeScreen.
UV Lamp ReminderThe UV Lamp change reminder must beturned on from the Installer Setup. Onceexpired, the screen flashes, Change UVLamp and a Reset key appears. Press theReset key to reset the change reminder.1.Press the More key until the UV Lampchange reminder appears on the screen. Thisis the number of calendar days remaining onthe UV Lamp reminder.2.Press the Edit key.
3.Use the Up and Down keys to change thenumber of calendar days.4.Press the Done key to go back to the viewingscreen.5.Press the Reset key to activate the newnumber of days selected in the previous screen6.Press the Done key to return to the Home
Screen.
85
CDT900 S i T h P bl Th
8/13/2019 CDT900 Series Manual
87/102
CDT900 Series Touchscreen Programmable Thermostat
TemperatureRecoveryThe thermostat feature, Adaptive Intelligent
Recovery, eliminates all guesswork whensetting the thermostat schedule.Simply set the program schedule to the timethat the comfort temperature is desired. Thethermostat then turns on the heating orcooling at just the right time to have the homereach the scheduled temperature at the
scheduled time.For example get up at 6:00 AM and want thetemperature to be 70F. Set the Wake periodfor 6:00 AM and 70F. The thermostat thenturns on the heat before 6:00 AM to raise thetemperature to 70F by 6:00 AM.The thermostat alerts that the heating orcooling system is coming on before a
scheduled time by showing Recovery on thescreen.
NOTE:It takes about a week for thethermostat to adjust to local weather, theschedule, the construction of the home and
the heating and/or cooling system. Each dayit adjusts the next days recovery start timeaccordingly.
86
Set To
MORE
SCREEN
RoomHEATPM
SYSTEM
TUE
CLOCK
HOLD
SCHED
FAN
AUTO
Recovery
CDT900 S i T h P bl Th t t
8/13/2019 CDT900 Series Manual
88/102
CDT900 Series Touchscreen Programmable Thermostat
MinimumOff-TimerThe Thermostat has built-in compressor
protection (minimum- off timer) that preventsthe compressor from restarting too early aftea shutdown.The minimum-off timer is activated after thecompressor turns off.If there is a call during the minimum-off timer,the thermostat shows Waitin the display.
When the minimum-off timer expires, CoolOn or Heat Ona appears solidly in the displayand the compressor and fan turn on.
aHeatPumpsonly.
87
SYSTEM
SCREENSet To
SCHED
HOLD
CLOCK
RoomPM
Running As SCHED
COOL
WED
WaitAUTO
FAN
MORE
CDT900 S i T h P bl Th t t
8/13/2019 CDT900 Series Manual
89/102
CDT900 Series Touchscreen Programmable Thermostat
Inside Humidity LevelSelect models can sense the humidity level
in the home. The humidity level in the homeis shown in the lower right corner of theHome Screen.
If thermostat is set to Auto ChangeoverSystem mode, press the More key until thehumidity level is shown on the screen.
88
.
Set To
Room
COOL
SYSTEM
MORE
SCREEN
PM
TIME
HOLD
SCHED
THU
Humidity
FAN
AUTO
Running As SCHED
CANCEL DONE
Humidity
CDT900 S i T h P bl Th t t
8/13/2019 CDT900 Series Manual
90/102
CDT900 Series Touchscreen Programmable Thermostat
Control Dehumidi fication Setting (SelectModels)
Select models read the inside humidity level anallow for a dehumidification setting:1.Press the More key until the inside humiditypercent and dehumidification setpoint areshown.
2.Use Up and Down arrow keys, located tothe right of the dehumidifier setpoint, to setdesired humidity level dehumidification inthe summer.3.Press Done key.
Dehumidification DroopControlThe dehumidification control attempts to
control to the user's humidity setpoint byturning on the air conditioner. In extremelyhigh humidity conditions, the thermostatkeeps the air conditioner running(energizing Y and G) for up to 3F belowthe temperature setpoint. It does this whiletrying to achieve the desired humiditysetpoint and balancing that with the
temperature setpoint. The thermostatcontrols up to 3 F below the temperaturesetting until either the humidity is satisfiedor conditions change.
89
CANCEL DONE
Humidity
DEHUMIDIFICATION
CDT900 S i T h P bl Th t t
8/13/2019 CDT900 Series Manual
91/102
CDT900 Series Touchscreen Programmable Thermostat
SpecialHeatPumpOperationeat ump n cat on equ res
24Vac CommonConnection)E5 indication is located in the screen of thethermostat. It is only visible whenlighted.When the L terminal is wired to anequipment monitor,This is operational in theHeat, Off, Cool or Auto positions. See Fig.32.
HeatPumpEmergencyHeatLCDIndication(Requires 24Vac
CommonConnection)The thermostat uses E5 indicator that lightswhen the thermostat is in the Emergency Heatmode. The E5 is located in the LCD screenof the thermostat. It is visible only when on.When the thermostat is in the Emer systemmode, the L terminal is continuously energized
and the E5is show.
HeatPumpTemperatureLockoutsDual Fuel Heat Pump and Outdoor
Temperature SensorIn this operation, there is no external fossil fuel
kit (dual fuel kit) installed; the thermostat controlthis function.
90
AUTO
AM
SCHED
HOLD
CLOCK
SCREEN
MORE
SYSTEM
HEAT
FAN
Set To
MON
CDT900 Series Touchscreen Programmable Thermostat
8/13/2019 CDT900 Series Manual
92/102
CDT900 Series Touchscreen Programmable Thermostat
Fig. 32. L terminal switch to R (power)side of system transformer.
1.Choose correct heat pump application inInstaller Setup Number 0170.2.Choose Fossil Fuel Option as thebackup heat source in Installer SetupNumber 0200.3.Choose No External Fossil Fuel Ki tOption is control- ling back up heat inInstaller Setup Number 0210.4.Choose Outdoor Temperature Sensorfor Heat PumpTemperature Lockouts
Option in Installer Setup Num- ber 0340.5.Choose appropriate Balance PointTemperature in Installer Setup Number0350.OPERATION IN HEAT MODE ABOVE BALANCEPOINT (OUTDOOR TEMPERATURE)
When the outdoor temperature is abovethe selected Balance Point Temperature(ISU 0350), only the compressor operatesand the fan (G terminal) energizes whenthe thermostat calls for heat. See Fig. 33.
BALANCEPOINT
OUTDOOR
TEMPE
RATURE
COMPRESSOR ONLY
FOSSIL FUEL ONLY
Fig. 33. Dual Fuel Heat Pump Operation inHeat mode with
OPERATION IN HEAT MODE BELOW BALANCEPOINT (OUTDOOR TEMPERATURE)
When the outdoor temperature is below thselected Balance Point Temperature (ISU0350), only the Fossil Fuel (auxiliary heat)
operates and the fan (G terminal) does notenergize when the thermostat calls for hea
91
CDT900 Series Touchscreen Programmable Thermostat
8/13/2019 CDT900 Series Manual
93/102
CDT900 Series Touchscreen Programmable Thermostat
OPERATION IN EMERGENCY HEAT MODE
The balance point (outside) temperature is
not used in the Emergency heat mode. Whthe thermostat is moved to the EmergencyHeat position, the compressor is locked out.The first stage of heat is whatever isconnected to the E terminal. The secondstage of heat is what is connected to the Auterminal. Often there is only one source of
non-compressor heat and the E terminal isjumped to the Aux. terminal.
Heat Pump with Electric Auxiliary
(Backup) Heat and OutdoorTemperature Sensor1.Choose correct heat pump application inInstaller Setup Number 0170.2.Choose Electric asAuxil iary (Backup)Heat Source in Installer Setup Number0200.
3.Choose Outdoor Temperature Sensorfor Control Option in Installer SetupNumber 0340.4.Choose Compressor LockoutTemperature inInstaller Setup Number0350.5.ChooseAuxi liary Lockout Temperaturein Installer Setup Number 0360.
NOTE: There is a 5F deadband between thCompressor and Auxiliary Heat Lockout
92
CDT900 Series Touchscreen Programmable Thermostat
8/13/2019 CDT900 Series Manual
94/102
CDT900 Series Touchscreen Programmable Thermostat
Operation in Heat ModeWhen the outdoor temperature is below the
Compressor Lockout Temperature, only theAuxiliary Heat operates.When the outdoor temperature is above the
Auxiliary Lockout Temperature, only theCompressor operates. See Fig. 34.
AUXILIARY LOCKOUT
TEMPERATURE
COMPRESSOR
LOCKOUT
TEMPERATURE
OUTDOOR
TEMPERA
TURE
BOTH
OMPRESSORANDAUXILIARYHEAT
AUXILIARYONLY
COMPRESSOR
Fig. 34. Heat Pump Operation with LockoutTemperatures Set.
When the outdoor temperature is between thetwo temperatures, both the Compressor and
Auxiliary Heat operate.
Operation in Emergency Heat ModeOnce the thermostat is placed into the
Emergency Heat mode, the compressor andauxiliary lockout features are turned off. Inthe Emergency heat mode, the compressoris locked out. The first stage of heat iswhatever is connected to the E terminal.The second stage of heat is connected tothe Aux. terminal. Usually the emergencyand auxiliary heat sources are electric strip
heat in these cases.
Operating SequenceThe thermostat energizes specificterminal(s), depending on the demand forheating, cooling or fan. The thermostatscreen shows the time, inside temperature,system and fan selections. Additional
indicators are shown when the heating,cooling or fan is energized. See Tables 9 - 11for specification information.
93
CDT900 Series Touchscreen Programmable Thermostat
8/13/2019 CDT900 Series Manual
95/102
CDT900 Series Touchscreen Programmable Thermostat
Table 9. Sequence of Operation for Conventional Systems.
System Setting Fan Setting Call for Action Energize Terminals Screen MessageOff Auto None None None
Cool Auto None None None
Cool or Auto Auto Stage 1 Cooling Y, G Cool On
Cool or Auto Auto Stage 1 and Stage 2
Cooling
Y, Y2b, G Cool On
Heat Auto None None None
Heat or Auto Auto Stage 1 Heating W, Ga Heat On
Heat or Auto Auto Stage 1 and Stage 2
Heating
W, W2c, Ga Heat On
aG energizes only if Installer Setup number 0180 is set to Electric.bIf Installer Setup System type is set to two stages of cooling.cIf Installer Setup System type is set to two stages of heating.
Table 10. Sequence of Operation for Power Open and Power Closed Valves or NormalOpen Valves.
System Setting Fan Setting Call for Action Energize Terminals Screen MessageOff Auto None None None
Heat N/A None Y None
Heat N/A Heat W Heat On
94
CDT900 Series Touchscreen Programmable Thermostat
8/13/2019 CDT900 Series Manual
96/102
CDT900 Series Touchscreen Programmable Thermostat
Table 11. Sequence of Operation for Heat Pump Systems.
System Setting Fan Setting Call for Action Energize Terminals Screen Message
Off Auto None O/Ba NoneCool Auto None O/Ba None
Cool or Auto Auto Stage 1 Cooling Y, G, O/Ba
Cool On
Cool or Auto AutoStage 1 and Stage 2
CoolingY, Y2
d, G, O/B
a Cool On
Heat Auto None O/Ba
None
Heat or Auto Auto Stage 1 Heating Y, G, O/Ba
Heat On
Heat or Auto AutoStage 1 and Stage 2
Heating
Y, AUXc
, G, O/Ba
Aux Heat On
Heat or Auto AutoStage 1, 2 and 3
Heating
Y, Y2d, AUXe
, G,
O/Ba
Aux Heat On
Em. Heat Auto None Lb
, O/Ba
None
Em. Heat Auto Stage 1 Heating E, G, Lb, O/Ba
Heat On
Em. Heat AutoStage 1 and Stage 2
HeatingE, AUX, G, L
b, O/B
a Aux. Heat On
aConfigure O/B in Installer Setup. Based on last piece of equipment called (cooling = O or
heating = B).bRed LED is on. See LED Indication section for more details.cIf Installer Setup System Type is set to 2Heat/1Cool Heat Pump with Auxiliary Heat.dIf Installer Setup System Type is set to 3Heat/2Cool Heat Pump with Auxiliary Heat.eThis terminal does not energize if Installer Setup System type is set to 2 Heat/2 Cool HeatPump with no Auxiliary Heat 95
CDT900 Series Touchscreen Programmable ThermostatCDT900 Series Touchscreen Programmable Thermostat
8/13/2019 CDT900 Series Manual
97/102
CDT900 Series Touchscreen Programmable ThermostatCDT900 Series Touchscreen Programmable Thermostat
Outdoor TemperatureSensorOperation
When installed with Thermostat Installer SetupNumber 0340 set to 1 or 2, the outsidetemperature can be displayed on thethermostat. See Fig. 35.
Fig. 35. Outside temperature reading onCDT900 Series Thermostat.
The Outdoor Sensor converts outdoorambient temperature to a resistance thatthe thermostat can interpret.The sensor has a negative temperaturecoefficient (NTC), which means thatresistance decreases as the temperatureincreases.
CheckoutWith an accurate thermometer (1F[0.5C]) measure the temperature at thesensor location, allowing time for thethermometer to stabilize before reading.
CalibrationThe Outdoor Sensor is calibrated at thefactory and cannot be recalibrated in thefield.
96
TUE
SYSTEM
HEAT
SCREEN
MORE
Set To
SCHED
HOLD
CLOCK
Room
Running As SCHED
FAN
AUTO
AM
Outside
CDT900 Series Touchscreen Programmable Thermostat
8/13/2019 CDT900 Series Manual
98/102
CDT900 Series Touchscreen Programmable Thermostat
emote n oor emperatureSensorOperation
When installed with Thermostat InstallerSetup Number 0340 set to 3, the remoteinside temperature is displayed on theThermostat Home Screen as InsideTemperature. The thermostat internaltemperature sensor is not used. See Fig.36.
Fig. 36. Inside temperature reading onTCD900 Series Thermostat.
The Wall Mount Temperature Sensor convertsroom temperature to a resistance that thethermostat can interpret.The sensor has a negative temperaturecoefficient (NTC), which means that resistancedecreases as the temperature increases.
The sensor can be used to provide one remotesensor input (see Fig. 28) or as a temperatureaveraging network with multiple Sensorsconnected, as shown in Fig. 29.
CheckoutFor best results, allow Wall Mount TemperatureSensor to absorb the air moving through theroom for a minimum of twenty minutes beforetaking a resistance measurement.With an accurate thermometer (1F [0.5C])measure the temperature at the sensor location
allowing time for the thermometer to stabilizebefore reading.
CalibrationThe Wall Mount Temperature Sensor iscalibrated at the factory and cannot berecalibrated in the field. 97
AUTO
Room SCHED
HOLD
CLOCK
SCREEN
SYSTEM
HEAT
FAN
Set To
TUE
AM
Heat On
Running As SCHED
MORE
AM
CDT900 Series Touchscreen Programmable Thermostat
8/13/2019 CDT900 Series Manual
99/102
CDT900 Series Touchscreen Programmable Thermostat
TROUBLESHOOTING(TABLE14)Table 14. Troubleshooting.
Symptom Possible Cause Action
Display does not come on. Thermostat is not being powered.
Check for 24 Vac between C and Rc.
Check that AA batteries are installed
correctly and are good.
The upper or lower temperature limits
were reached.
Check temperature setpoints.
Check Installer Setup Numbers 0600 and
0610; modify as needed.Temperature settings do not change.
The keypad is fully locked.Check Installer Setup Number 0670 to
change keypad locked options.
Thermostat minimum off-time isactivated.
Wait up to five minutes for the system torespond.
System selection is not set to Heat or
Cool.Set system Selection to correct position.
Heating or cooling does not come on.
System type Selection is incorrect.
Check Installer Setup Number 0170 and
make sure correct System type is
chosen.
Thermostat is calling for Heat (Heat on)
or Cool (Cool on) but no heating orcooling is running.
Heating or cooling equipment is notoperating.
Check wiring.
Check Installer Setup Number 0170 and
make sure correct system type ischosen.
Verify operation of equipment in System
Test mode.
98
CDT900 Series Touchscreen Programmable Thermostat
8/13/2019 CDT900 Series Manual
100/102
CDT900 Series Touchscreen Programmable Thermostat
Table 14. Troubleshooting. (CONTINUES)Symptom Possible Cause Action
Heating equipment failure.
Check for 24 Vac at the equipment on
the secondary side of the transformerbetween power and common. If voltageis not present, check the heating
equipment to find the cause of theproblem.
Check for 24 Vac between the heatterminal (W) and transformer common. If
24 Vac is present, the thermostat isfunctional. Check the heating equipment
to find the cause of the problem.
Heat does not turn on (Heat On is solid in
the display).
Loose or broken wire connection
between thermostat and heating
equipment.
Check for 24 Vac between the heat
terminal (W) and transformer common. Ifvoltage is not present, check wire
connection (loose or broken) betweenthe thermostat and the heating
equipment.
Cooling does not turn on (Cool
On is solid in the display)
Cooling equipment failure.
Check for 24 Vac at the equipment onthe secondary side of the transformer
between power and common. If voltageis not present, check the cooling
equipment to find the cause of theproblem.
Check for 24 Vac between the coolterminal (Y) and transformer common. If
24 Vac is present, the thermostat isfunctional. Check the cooling equipment
to find the cause of the problem.
99
CDT900 Series Touchscreen Programmable Thermostat
8/13/2019 CDT900 Series Manual
101/102
CDT900 Series Touchscreen Programmable Thermostat
Table 14. Troubleshoot ing. (CONTINUES)Symptom Possible Cause Action
Cooling does not turn on (Cool
On is solid in the display).
Loose or broken wire connection
between thermostat and cooling
equipment.
Check for 24 Vac between the cool
terminal (Y) and transformer common. Ifvoltage is not present, check the wire
connection (loose or broken) between
the thermostat and the cooling
equipment.
Fan does not turn on in a call for heat
(electric furnace).
Fan Control in Heating is set to Gas or
Oil Furnace (Setting 0180).
Set Fan Control in Heating to Electric
Furnace(Setting 0180).
Heat pump puts out cool air in the heat
mode and warm air in the cool mode.
Changeover Valve (Installer Setup
Number 0190) is not configured to match
the changeover required by the installedheat pump.
Set Changeover Valve (Installer Setup
Number 0190) to match the changeover
required by the installed heat pump.
The heating equipment is not a heat
pump but the System Type (Installer
Setup Number 0170) is set to Heat
Pump.
Set System Type (Installer Setup
Number 0170) to match the installed
heating and/or cooling equipment.Both the heating and cooling equipment
are running at the same time.
Heating and cooling wires are shorted
together.
Separate the shorted heating and cooling
wires.
Heating equipment is running in the cool
mode.
Heating equipment is not a heat pump
but System Type (Installer Setup
Number 0170) is set to Heat Pump.
Set System Type (Installer Setup
Number 0170) to match the installed
heating and/or cooling equipment.
Heating equipment does not turn off and
heat temperature setting is set below
room temperature (Heat On is not in the
display).
Heating equipment is not a heat pump
but System Type (Installer Setup
Number 0170) is set to Heat Pump.
Set System Type (Installer Setup
Number 0170) to match the installed
heating and/or cooling equipment.
100
CDT900 Series Touchscreen Programmable Thermostat
8/13/2019 CDT900 Series Manual
102/102
CDT900 Series Touchscreen Programmable Thermostat
Table 14. Troubleshoot ing. (CONTINUES)Symptom Possible Cause Action
Cannot set the system setting to Heat.
System Type (Installer Setup Number
0170) is set to Cool Only.
Set System Type (Installer Setup
Number 0170) to match the installedheating and/or cooling equipment.
Cannot set the system setting to Cool.
System Type (Installer Setup Number
0170) is set to Heat Only or Heat Only
with Fan.
Set System Type (Installer Setup
N