Download pdf - CDT900 Series Manual

Transcript
  • 8/13/2019 CDT900 Series Manual

    1/102

  • 8/13/2019 CDT900 Series Manual

    2/102

    CDT900 Series Touchscreen Programmable Thermostat

    Contents

    Application/Features............................................... ................. ................. ........................... 2

    Specifications/Ordering Information ..................... ................. ................. ............................. 4Installation ........................................................ .. ................. ...............................................13Wiring ................................................................... ................. ................. ............................ 17Power the Thermostat .................................. ................ ................. ..................................... 34Installer Setup ............................. ................. ................ ...................................................... 47Installer System Test ................. ................. ................ ........................................................ 59

    Operation............................. ................. ............... ............................................................... 62Programming .................. ................. ................. .................................................................. 68Troubleshooting ................ ................. ................. ................................................................ 97

    1

    `

  • 8/13/2019 CDT900 Series Manual

    3/102

    PRODUCT DATAAPPLICATIONThe CDT900 Series Touchscreen Programmable Thermostat is an effortless, 7-Dayprogrammable thermostat that provides universal system compatibility, precise comfortcontrol and is easy-to-program.The CDT900 Series Thermostats provide temperature control for gas, oil, electric and heatpumps for up to 3 heat, 2 cool systems including dual fuel operation plus dehumidificationcontrol.

    CDT900 Series Touchscreen Programmable Thermostat

    2

  • 8/13/2019 CDT900 Series Manual

    4/102

  • 8/13/2019 CDT900 Series Manual

    5/102

  • 8/13/2019 CDT900 Series Manual

    6/102

    CDT900 Series Touchscreen Programmable Thermostat

    Electrical Ratings:

    Terminal Voltage (50/60 Hz) Running CurrentW Heating 20 - 30 Vac 02 - 1.0A

    W Heating (Powerpile) 750 mV dc 100 mA dc

    Y Cooling 20 - 30 Vac .02 - 1.0A

    G Fan 20 - 30 Vac 02 - .60A

    Temperature Setting Range:Heating: 40F to 90F(4C to 32C).Cooling: 50F to 99F (10C to 37C).

    Operating Ambient Temperature:32F to 120F(0C to 49C).

    Shipping Temperature:CDT900 Thermostats: -30 F to 150 F(-34.4C to 65.6C).

    5

  • 8/13/2019 CDT900 Series Manual

    7/102

    CDT900 Series Touchscreen Programmable Thermostat

    Operating Relative Humidity (Non-condensing):CDT900 Series Thermostats: 5% to 90%.

    IRS-1: 5% to 95%.ORS-1: 5% to 95%.

    Humidity Setting Range (CDT901 models only):Cooling: 40% to 80% RH.

    Humidity Display Range (CDT901 models on ly):0% to 99%.

    Cycle Rates (at 50% Load):Heating: Selectable 1 - 12 cycles per hour.Cooling: Selectable 1 - 6 cycles per hour.

    Clock Accuracy: +/- 1 minute per month.

    Batteries:Two replaceable AA alkaline batteries: Power thermostats when 24 Vac common is not used.Non-replaceable lithium battery with ten-year life under normal use to hold calendar and timesettings. Alkaline batteries keep calendar and time after lithium battery is no longerfunctional.

    6

  • 8/13/2019 CDT900 Series Manual

    8/102

    CDT900 Series Touchscreen Programmable Thermostat

    Cool Indication:CDT900 series Touchscreen Thermostats show "Cool On" on the screen when Cool is

    activated.

    Heat Indication:CDT900 series Touchscreen Thermostats show "Heat On" on the screen when Heat isactivated.

    7

  • 8/13/2019 CDT900 Series Manual

    9/102

    CDT900 Series Touchscreen Programmable Thermostat

    ORDERINGINFORMATIONIf you have additional questions, need further information, or would like to comment on ourproducts or services, please write or phone:1. Smart Electric

    Attn: Warranty Department12201 NW 107th AveMiami, Fl 33178

    2. Call Customer Service at 1-866-591-9898

    Auxi liary Heat Indicat ion:CDT900 Touchscreen Thermostats show "Aux Heat On" on the screen when Auxiliary Heatis activated.

    Emergency Heat Indication:CDT900 Touchscreen Thermostats show "Heat On" on the screen when Emergency Heat isactivated and the System mode is in the Emer position.

    Calibration:CDT900 Touchscreen Thermostats are factory-calibrated and require no field calibration.

    Nomenclature:

    8

  • 8/13/2019 CDT900 Series Manual

    10/102

    CDT900 Series Touchscreen Programmable Thermostat

    Series System Stages Appl icat ion

    CDT900CDT901 3H/2C CDT900 - StandardCDT901-Humidity Sensor

    Mounting Means:CDT900 Series Touchscreen Thermostat: Mounts directly on the wall in the living spaceusing mounting screws and anchors provided.Outdoor Sensor: Mounts outside of living space with mounting clip and screws provided.Remote Indoor Sensor: Mounts directly on the wall using mounting screws and anchorsprovided.

    Dimensions:CDT900 Series Touchscreen Thermostat: see Fig 1.1. CDT900 Outdoor Sensor Mounting Clip: see Fig 2.2. Cover Plate: see Fig 3.3. CDT900 SeriesRemote Indoor Sensor: see Fig. 4

    9

  • 8/13/2019 CDT900 Series Manual

    11/102

  • 8/13/2019 CDT900 Series Manual

    12/102

    CDT900 Series Touchscreen Programmable Thermostat

    Fig. 1. Touchscreen Thermostat dimensions in in. (mm).

    11

    1.17 in.(29.84mm)

    5.98 in.(152mm)

    4.48in.(114mm)

  • 8/13/2019 CDT900 Series Manual

    13/102

    CDT900 Series Touchscreen Programmable Thermostat

    Fig. 2. Outdoor Sensor Mounting Clip dimensions in in. (mm).

    12

    1.49 in.(38mm)

    0.17in.(4.2mm)

    R1.6in.(4mm

    )

    1.82 in.(46.3mm)

    R0.04

    in.(1mm)

    R0.098in.(2.5m

    m)

    1.10in.(28.1mm)

    0.62in.(16mm

    )

    1.56 in .(39.7mm)

    0.24 in.(6.2mm)

    0.44 in .(11.2mm)

    R0.098in.(2.5mm)

    0.08 in.(2mm)

  • 8/13/2019 CDT900 Series Manual

    14/102

    CDT900 Series Touchscreen Programmable Thermostat

    Fig. 3. Cover Plate dimensions in in. (mm).

    13

    3.29 in.(83.5mm)

    0.85 in .(21.5mm)

    3.29in.(83.5mm)

    5.35 in.(136mm)

    4.13in.(105mm)

  • 8/13/2019 CDT900 Series Manual

    15/102

    CDT900 Series Touchscreen Programmable Thermostat

    INSTALLATIONWhenInstallingthisProduct...1.Read these instructions carefully. Failure to follow the instructions can damage the productor cause a hazardous condition.2.Check the ratings given in the instructions to make sure the product is suitable for yourapplication.3.Installer must be a trained, experienced service technician.4.After completing installation, use these instructions to check out the product operation.

    SelectingLocationInstall the thermostat about 5 ft. (1.5m) above the floor in an area with good air circulation ataverage temperature. See Fig. 5.

    Do not install the thermostat where it can be affected by:----Drafts or dead spots behind doors and in corners.----Hot or cold air from ducts.----Radiant heat from sun or appliances. Concealed pipes and chimneys.

    ----Unheated (uncooled) areas such as an outside wall behind the thermostat.

    14

  • 8/13/2019 CDT900 Series Manual

    16/102

    CDT900 Series Touchscreen Programmable Thermostat

    Fig. 5. Selecting thermostat location.

    15

    5FEET

    1.5METERS

  • 8/13/2019 CDT900 Series Manual

    17/102

    CDT900 Series Touchscreen Programmable Thermostat

    InstallingWallplate

    CAUTIONElectrical Hazard.Can cause electrical shock or equipment damage.Disconnect power before wiring.

    The thermostat can be mounted horizontally on the wall1.Position and level the wallplate (for appearance only).2.Use a pencil to mark the mounting holes.3.Remove the wallplate from the wall and, if drywall, drill two holes in the wall, as marked. For

    firmer material such as plaster, drill two holes. Gently tap anchors (provided) into the drilledholes until flush with the wall.4.Position the wallplate over the holes, pulling wires through the wiring opening. See Fig. 65.Insert the mounting screws into the holes and tighten.

    16

  • 8/13/2019 CDT900 Series Manual

    18/102

    CDT900 Series Touchscreen Programmable Thermostat

    Fig. 6. Mounting wallplate.

    17

    WALL

    WIRES THROUGH

    WALL AND WIRE

    SLOT

    WALL ANCHORS

    M0UNTING

    HOLES(2)

    M0UNTINGSCREWS(2)

  • 8/13/2019 CDT900 Series Manual

    19/102

    CDT900 Series Touchscreen Programmable Thermostat

    WIRING(FIG.9- 21)All wiring must comply with local electrical codes and ordinances.1.Select set of terminal identifications (Table 1) that corresponds with system type(conventional or heat pump in Fig. 7).2.Loosen the screws for the appropriate system type selected; see Table 1. See Table 2 forterminal designation descriptions. Insert wires in the terminal block under the loosenedscrew. See Fig. 8.3.Securely tighten each screw.4.Push excess wire back into the hole.5.Plug the hole with nonflammable insulation to prevent drafts from affecting the thermostat.6.See Fig. 9 through 21 for typical wiring hookups.

    Fig. 7. Selecting terminal identifications forsystem type.

    18

    CONVENTIONAL

    HEATPUMP

    SCREW

    TERMINALS

    S1 S2 C R RC E L Y2 Y G

    S1 S2 C R RC W W2 Y2 Y G

    O/B AUX

  • 8/13/2019 CDT900 Series Manual

    20/102

  • 8/13/2019 CDT900 Series Manual

    21/102

    CDT900 Series Touchscreen Programmable Thermostat

    IMPORTANT:Use 18 gauge thermostat wire.

    Fig. 8. Inserting wires in terminal block.

    20

  • 8/13/2019 CDT900 Series Manual

    22/102

    CDT900 Series Touchscreen Programmable Thermostat

    Table 2. Terminal Designation Descript ions.

    Terminal Designation Description

    Rc (see Note 1)

    Power for cooling--connect to secondary side of cooling

    system transformerR (see Note 1) Power for heating--connect to secondary side of heatingsystem transformer

    C (see Note 2) Common wire from secondary side of cooling systemtransformerW Heat relayY Compressor contactorG Fan relayY2 Second stage coolingW2 Second stage heat relayO/B (see Note 3) Changeover valve for heat pump systems

    AUX Auxiliary heat relay for heat pump systemsE Emergency heat relay for heat pump systems

    L (see note 4) Equipment monitor for heat pump systemsS1, S2 Optional outdoor or indoor remote sensor

    NOTES:.1.When sed in a single-transformer system, leave metal jumper wire in place between Rc

    and R. If used on a two-transformer system, remove metal jumper wire between Rc and R.2.Common wire is optional when thermostat is used with batteries.3. If thermostat is configured for a heat pump system in the Installer Setup, configurechangeover valve for cool (O-factory setting) or heat (B).4.L terminal is an input (system monitor) when the System mode is in the Heat, Off, Cool or

    Auto position. L terminal is a 24 Vac output when System mode is Emergency Heat. Mustconnect the 24 Vac Common when using the L terminal. See LCD Indication section for moredetails.

    21

  • 8/13/2019 CDT900 Series Manual

    23/102

    CDT900 Series Touchscreen Programmable Thermostat

    1.POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

    2. FACTORY INSTALLED JUMPER.3.OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE

    SEPARATE FROM THE THERMOSTAT CABLE

    Fig. 9. Typical hookup of conventional single-stage heat and cool system with s ingletransformer(1H/1C conventional).

    22

    CONVENTIONALS1 S2 C R RC W W2 Y2 Y G

    OUTDOOR/INDOOR

    TEMPERATURE

    SENSOR

    3

    HEATRELAY

    OPTIONAL24VAC

    COMMON

    CONNECTION

    RC 1

    2

    FANRELAY

  • 8/13/2019 CDT900 Series Manual

    24/102

    1.POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

    2.REMOVE FACTORY INSTALLED JUMPER

    3.OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE

    SEPARATE FROM THE THERMOSTAT CABLE.

    Fig. 10. Typical hookup of conventional single-stage heat and cool system with twotransformers (1H/1C conventional).

    23

    CONVENTIONALS1 S2 C R RC W W2 Y2 Y G

    OUTDOOR/INDOOR

    TEMPERATURE

    SENSOR

    3 RC 1

    2

    FANRELAY

    HEATRELAY

    R C 1

    COMPRESSOR

    CONTACTOR

    OPTIONAL

    24VACCOMMON

    CONNECTION

  • 8/13/2019 CDT900 Series Manual

    25/102

    CDT900 Series Touchscreen Programmable Thermostat

    1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED

    2. FACTORY INSTALLED JUMPER.

    3. OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE

    SEPARATE FROM THE THERMOSTAT CABLE

    Fig. 11. Typical hookup of heat-only system (1 H conventional).

    24

    CONVENTIONALS1 S2 C R RC W W2 Y2 Y G

    OUTDOOR/INDOORTEMPERATURE

    SENSOR

    3

    HEATRELAY

    OPTIONAL

    24VAC

    COMMON

    CONNECTION

    R C1

    2

  • 8/13/2019 CDT900 Series Manual

    26/102

    CDT900 Series Touchscreen Programmable Thermostat

    1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED

    2. FACTORY INSTALLED JUMPER.

    3. OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE

    SEPARATE FROM THE THERMOSTAT CABLE

    Fig. 12. Typical hookup of heat only system with fan (1H conventional).

    25

    CONVENTIONALS1 S2 C R RC W W2 Y2 Y G

    OUTDOOR/INDOOR

    TEMPERATURE

    SENSOR

    3

    HEATRELAY

    OPTIONAL24VAC

    COMMON

    CONNECTION

    RC 1

    2

    FANRELAY

  • 8/13/2019 CDT900 Series Manual

    27/102

    CDT900 Series Touchscreen Programmable Thermostat

    1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED2. FACTORY INSTALLED JUMPER.

    3. OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE

    SEPARATE FROM THE THERMOSTAT CABLE

    Fig. 13. Typical hookup of heat only power to open and power to close zone valve(Series 20) system.

    26

    OUTDOOR/INDOOR

    TEMPERATURE

    SENSOR

    3

    R C 1

    2

    WBR

    TR TRSERIES20

    MOTOROR

    VALVE

    CONVENTIONALS1 S2 C R RC W W2 Y2 Y G

  • 8/13/2019 CDT900 Series Manual

    28/102

    CDT900 Series Touchscreen Programmable Thermostat

    1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED

    2. FACTORY INSTALLED JUMPER.3. OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE

    SEPARATE FROM THE THERMOSTAT CABLE

    Fig. 14. Typical hookup of heat only system with normally open zone valves.

    27

    CONVENTIONALS1 S2 C R RC W W2 Y2 Y G

    OUTDOOR/INDOOR

    TEMPERATURE

    SENSOR

    3

    NORMALLYOPEN

    ZONEVALVE

    OPTIONAL24VAC

    COMMON

    CONNECTION

    R C1

    2

    4

  • 8/13/2019 CDT900 Series Manual

    29/102

    CDT900 Series Touchscreen Programmable Thermostat

    1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED

    2. FACTORY INSTALLED JUMPER.3. OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE

    SEPARATE FROM THE THERMOSTAT CABLE

    Fig. 15. Typical hookup of cool only system(1C conventional).

    28

    CONVENTIONALS1 S2 C R RC W W2 Y2 Y G

    OUTDOOR/INDOOR

    TEMPERATURE

    SENSOR

    3

    COMPRESSOR

    CONTACTOR

    OPTIONAL

    24VAC

    COMMON

    CONNECTION

    RC 1

    2

    FANRELAY

    HEATRELAY

  • 8/13/2019 CDT900 Series Manual

    30/102

    CDT900 Series Touchscreen Programmable Thermostat

    1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED2. FACTORY INSTALLED JUMPER.

    3. OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE

    SEPARATE FROM THE THERMOSTAT CABLE

    Fig. 16. Typical hookup of conventional multistage two-stage heating and two-stagcooling in a single-transformer system (2H/2C, 2H/1C or 1H/2C conventional).

    29

    S1 S2 C R RC W W2 Y2 Y G

    OUTDOOR/INDOOR

    TEMPERATURE

    SENSOR

    3

    OPTIONAL

    24VAC

    COMMON

    CONNECTIONMUSTCOME

    FROMTHE

    COOLING

    TRANSFORMER

    2

    FANRELAY

    HEATRELAY2

    HEATRELAY1 COOLRELAY2

    COOLRELAY1

    R C 1

    CONVENTIONAL

  • 8/13/2019 CDT900 Series Manual

    31/102

    CDT900 Series Touchscreen Programmable Thermostat

    1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED

    2. FACTORY INSTALLED JUMPER.

    3. OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLESEPARATE FROM THE THERMOSTAT CABLE

    Fig. 17. Typical hookup of conventional mul tistage two-stage heating and two-stagecooling in a two-transformer system (2H/2C, 2H/1C or1H/2C conventional).

    30

    CONVENTIONAL S1 S2 C R RC W W2 Y2 Y G

    OUTDOOR/INDOOR

    TEMPERATURE

    SENSOR

    3

    OPTIONAL

    24VAC

    COMMONCONNECTION

    MUSTCOME

    FROMTHE

    COOLING

    TRANSFORMER

    RC 1

    2

    FANRELAY

    HEATRELAY1

    HEATRELAY2

    COOLRELAY2

    COOLRELAY1

    R C 1

  • 8/13/2019 CDT900 Series Manual

    32/102

    CDT900 Series Touchscreen Programmable Thermostat

    1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED

    2. FACTORY INSTALLED JUMPER.

    3"O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP4OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE

    SEPARATE FROM THE THERMOSTAT CABLE

    Fig. 18. Typical hookup of single-stage heat pump with no auxil iary/backup heat (1H/heat pump).

    31

    HEATPUMP

    S1 S2 C R RC W W2 Y2 Y G

    S1 S2 C R RC E L Y2 Y GO/B AUX

    OUTDOOR/INDOORTEMPERATURE

    SENSOR

    4

    2

    R C 1

    CHANGEOVER

    VALVECOMPRESSOR

    RELAY

    FANRELAYOPTIONAL24VAC

    COMMON

    CONNECTION

    3

  • 8/13/2019 CDT900 Series Manual

    33/102

    CDT900 Series Touchscreen Programmable Thermostat

    1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED

    2. FACTORY INSTALLED JUMPER.

    3MUST CONNECT THE 24 VAC COMMON WHEN USING L. THE TERMINAL IS SHOWN AS EQUIPMENT MONITOR, CAN ALSO BEUSED AS A 24 VAC OUTPUT. SEE "HEAT PUMP LED" SECTION FOR MORE INFORMATION.

    4"O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP

    5OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE

    SEPARATE FROM THE THERMOSTAT CABLE

    Fig. 19. Typical hookup of multistage heat pump with no auxil iary/backup heat2H/2C heat um .

    32

    HEATPUMP

    S1 S2 C R RC W W2 Y2 Y G

    S1 S2 C R RC E L Y2 Y GO/B AUX

    OUTDOOR/INDOOR

    TEMPERATURE

    SENSOR

    2

    R C 1

    CHANGEOVER

    VALVE

    FANRELAYOPTIONAL

    24VAC

    COMMON

    CONNECTION

    5

    COMPRESSOR2

    COMPRESSOR1

    4 3

  • 8/13/2019 CDT900 Series Manual

    34/102

    CDT900 Series Touchscreen Programmable Thermostat

    1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED

    2. FACTORY INSTALLED JUMPER.

    3OUTDOORSENSORREQUIREDINSYSTEMWITHFOSSILFUELBACKUPHEATTHATISNOTUSINGANEXTERNALFOSSILFUELKIT4OPTIONALOUTDOORORINDOORREMOTESENSOR.AVAILABLEONSELECTMODELS.WIRESMUSTHAVEACABLESEPARATE FROMTHE

    THERMOSTATCABLE

    5MUSTCONNECTTHE24VACCOMMONWHENUSINGL.THETERMINALISSHOWNASEQUIPMENTMONITOR,CANALSOBEUSEDAS

    A24VACOUTPUT.SEE"HEATPUMPLED"SECTIONFORMOREINFORMATION.

    6"O/B"TERMINALSETTOCONTROLASEITHER"O"OR"B"INTHEINSTALLERSETUP.

    Fig. 20. Typical hookup of single-stage heat pump with auxiliary/backuheat (2H/1C heat pump). 33

    34

    HEATPUMP

    S1 S2 C R RC W W2 Y2 Y G

    S1 S2 C R RC E L Y2 Y GO/B AUX

    OUTDOOR/INDOOR

    TEMPERATURESENSOR

    2

    R C 1

    CHANGEOVER

    VALVE

    FANRELAY

    OPTIONAL

    24VAC

    COMMON

    CONNECTION

    6 5

    COMPRESSOR

    RELAY

    EMERGENCY

    HEATRELAYHEAT2RELAY(AUXILIARYHEAT)

    EQUIPMENT

    MONITOR

  • 8/13/2019 CDT900 Series Manual

    35/102

    CDT900 Series Touchscreen Programmable Thermostat

    1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED

    2. FACTORY INSTALLED JUMPER.

    3OUTDOORSENSORREQUIREDINSYSTEMWITHFOSSILFUELBACKUPHEATTHATISNOTUSINGANEXTERNALFOSSILFUELKIT

    4OPTIONALOUTDOORORINDOORREMOTESENSOR.AVAILABLEONSELECTMODELS.WIRESMUSTHAVEACABLESEPARATE FROMTHE

    THERMOSTATCABLE

    5MUSTCONNECTTHE24VACCOMMONWHENUSINGL.THETERMINALISSHOWNASEQUIPMENTMONITOR,CANALSOBEUSEDAS

    A24VACOUTPUT.SEE"HEATPUMPLED"SECTIONFORMOREINFORMATION.

    6"O/B"TERMINALSETTOCONTROLASEITHER"O"OR"B"INTHEINSTALLERSETUP.

    Fig. 21. Typical hookup of mul tistage heat pump with auxil iary/backup heat (3H/2C heapump).

    34

    34

    HEATPUMP

    S1 S2 C R RC W W2 Y2 Y G

    S1 S2 C R RC E L Y2 Y GO/B AUX

    OUTDOOR/INDOOR

    TEMPERATURE

    SENSOR

    2

    R C 1

    CHANGEOVER

    VALVE

    FANRELAY

    OPTIONAL

    24VAC

    COMMON

    CONNECTION

    6 5

    EMERGENCY

    HEATRELAYHEAT2RELAY(AUXILIARYHEAT)

    EQUIPMENTMONITOR

    COMPRESSOR1

    COMPRESSOR1

  • 8/13/2019 CDT900 Series Manual

    36/102

    CDT900 Series Touchscreen Programmable Thermostat

    POWERTHETHERMOSTAT

    You can choose from three methods to power the thermostatBatteries only (AA alkaline). 24 Vac common wire only. 24 Vac common wire with battery backup (AA alkaline).

    Wiring 24VacCommon Single-Transformer System Connect the common side of the transformer to the C screw

    terminal of the thermostat wallplate. Leave the metal jumper wire in place between Rc andR.

    Two-Transformer System Connect the common side of the cooling transformer to the Cscrew terminal of the thermostat wallplate. Remove the metal jumper wire between Rc andR.

    35

  • 8/13/2019 CDT900 Series Manual

    37/102

    CDT900 Series Touchscreen Programmable Thermostat

    InstallingBatteries1.Install Two AA alkaline batteries on the

    back of the thermostat as marked on thethermostat. See Fig. 22.

    Fig. 22. Installing batteries.

    2.Locate and remove the tab labeled. See

    Fig. 23.

    Fig. 23. Remove tab labeled, Remove,on thermostat back.

    36

    BATTERIES(2)

    REMOVE

    TAB

  • 8/13/2019 CDT900 Series Manual

    38/102

    CDT900 Series Touchscreen Programmable Thermostat

    Mount Thermostat to Wallplate

    1.Align the terminal screw blocks with the pins on the back of the thermostat. Push thethermostat straight onto the wallplate until it snaps into place. See Fig 24.

    Fig. 24. Mount thermostat to wallplate.

    37

    WALLPLATE

    TERMINALSCREWBLOCK

    PINSONBACKOF

    THERMOSAT

  • 8/13/2019 CDT900 Series Manual

    39/102

  • 8/13/2019 CDT900 Series Manual

    40/102

    CDT900 Series Touchscreen Programmable Thermostat

    Fig. 25. Typical locations for ORS-1 Outdoor Sensor.

    39

  • 8/13/2019 CDT900 Series Manual

    41/102

    CDT900 Series Touchscreen Programmable Thermostat

    CAUTIONElectrical Interference (Noise) Hazard.Can cause erratic system operation.Keep wiring at least one foot away from large inductive loads such as motors, linestarters, lighting ballasts and large power distribution panels.Use shielded cable to reduce interference when rerouting is not possible.

    IMPORTANTErratic temperature readings from a sensor can occur as a result of any of thewiring practices described below. Avoid these practices to assure correctoperation. Use shielded cable to reduce interference if rerouting sensor wiring isnot possible.

    40

  • 8/13/2019 CDT900 Series Manual

    42/102

    CDT900 Series Touchscreen Programmable Thermostat

    Be sure wires have a cable separate from the thermostat cable.Do not route temperature sensor wiring with building power wiring, next to controlcontactors or near light dimming circuits, electric motors or welding equipment.

    Avoid poor wiring connections.Avoid intermittent or missing building earth ground.

    CAUTIONElectrical Shock Hazard.

    Can cause electrical shock or equipment damage.Disconnect ower su l before connectin wirin .

    Wiring must comply with applicable codes, ordinances and regulations:1.Wire Outdoor Sensor to S1and S2 terminals on the thermostat. If leadwire provided is notlong enough), you need an extra cable to reach the hole at location.a. Using color-coded, 18-gauge thermostat wire is recommended. For example of generalwiring of sensor, see Fig. 26.b. Pigtail wiring can be used.

    2.Mount Sensor in its mounting clip.3.Plug wiring hole using nonhardening caulk or putty.

    41

  • 8/13/2019 CDT900 Series Manual

    43/102

    CDT900 Series Touchscreen Programmable Thermostat

    1.USE APPROPRIATE MOUNTING MEANS FOR THE TYPE OF STRUCTURE.2.PLUG WIRING HOLE WITH NON-HARDENING CAULK OR PUTTY .

    Fig. 26. Wire Outdoor Sensor to the thermostat.

    42

    12

    WIRINGHOLE

    THROUGH

    STRUCTUREORS-01

  • 8/13/2019 CDT900 Series Manual

    44/102

    CDT900 Series Touchscreen Programmable Thermostat

    LocateandMount RemoteIndoor TemperatureSensor (Optional)1.Choose a location (see Fig. 27) for mounting the sensor on an inside wall about 19.4 ft

    (1.5m) above the floor.2.Be sure wire distance between sensor and thermostat is less than 65.61 ft6m.3.Make sure there is good air circulation at average temperature at the chosen location.

    Avoid the following locations because they can introduce errors in sensormeasurements. See Fig. 27.Hot areas caused by:(a) Concealed pipes or ducts.

    (b) Drafts from fireplaces or other heat sources.(c) Convection or radiant heat from the sun or electrical equipment.Cold areas caused by:(a) Concealed pipes or ducts.(b) Drafts from windows and doors.Unheated areas on the other side of the wall location.Dead air areas:(a) Behind doors, furniture and curtains. (b) In corners and alcoves.4.Mark the area on the wall selected for mounting the Sensor or junction box.5.Run wire cable to a hole at the selected wall location. Pull approximately three inches ofwire through the opening. Color-coded, 18-gauge thermostat wire is recommended.

    43

  • 8/13/2019 CDT900 Series Manual

    45/102

    CDT900 Series Touchscreen Programmable Thermostat

    44

    Fig. 27. Typical location for Indoor Sensor.

    5FEET

    1.5METERS

  • 8/13/2019 CDT900 Series Manual

    46/102

    CDT900 Series Touchscreen Programmable Thermostat

    WireIndoor Sensor

    CAUTIONElectrical Interference (Noise) Hazard. Can cause erratic system operation.Keep wiring at least one foot away from large inductive loads such as motors, linestarters, lighting ballastsand large power distribution panels.

    IMPORTANTErratic temperature readings from a sensor can occur as a result of any of thewiring practices described below. Avoid these practices to assure correctoperation.Be sure wires have a cable separate from the thermostat cable.Do not route temperature sensor wiring with building power wiring, next tocontrol contactors or near light dimming circuits, electric motors or weldingequipment.

    Avoid poor wiring connections.Avoid intermittent or missing building earth ground.

    45

  • 8/13/2019 CDT900 Series Manual

    47/102

    CDT900 Series Touchscreen Programmable Thermostat

    CAUTIONElectrical Shock Hazard.Can cause electrical shock or equipment damage.Disconnect ower su l before connectin wirin .

    Wiring must comply with applicable codes, ordinances and regulations.1.Wire Indoor Sensor to S1 and S2 terminals on the thermostat. For an example of generalwiring of IRS-1, see Fig. 28 to wire one sensor and 29 to wire multiple sensors.2.Push excess wire back into the hole. Plug the holeusing nonhardening caulk, putty or insulation to prevent drafts from affecting performance.

    3.Remove IRS-1 sensor cover.4.Mount IRS-1 to the wall or junction box using the screws and anchors provided.5.Level the IRS-1 for appearance only. Device functions correctly even when not level.6.Install IRS-1 cover.

    46

  • 8/13/2019 CDT900 Series Manual

    48/102

    CDT900 Series Touchscreen Programmable Thermostat

    1. POWER SUPPLY. PROVIDE DISCONNECT MEANS ANDOVERLOAD PROTECTION AS REQUIRED.

    2. IF MORE THAN ONE REMOTE SENSOR IS REQUIRED, REFER TO

    FIGURE 3

    3.. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTA

    CABLE.

    Fig. 28. Wiring a single Indoor Sensor. 47Fig. 29. Wiring Multiple Sensors.

    1SENSORS MUST BE ARRANGED IN THIS CONFIGURATION TO OPERATE

    CORRECTLY.

    2WIRES MUST HAVE A CABLE SEPARATE FROM THERMOSTAT CABLE

    RC 1

    2

    C7189

    3

    S1 S2 C R RC W W2 Y2 Y G

    S1 S2 C R RC

    C7189 C7189

    C7189 C7189

    1

    2

    S1 S2 C R RC

    C7189 C7189 C7189

    C7189 C7189 C7189

    C7189 C7189 C7189

    1

    2

  • 8/13/2019 CDT900 Series Manual

    49/102

    CDT900 Series Touchscreen Programmable Thermostat

    INSTALLERSETUPFollow these steps to enter the InstallerSetup:1.Press and release the System Key.

    2.Press and hold the two blank keys on

    either side of the center blank key forapproximately five seconds until screenchanges.

    48

    AUTO

    AMRoom SCHED

    HOLD

    CLOCK

    SCREEN

    MORE

    SYSTEM

    AUTO

    FAN

    Set To

    TUE

    Running As SCHED

    DONEDONE

    RoomSYSTEM

    HEAT

    OFFCOOL

    TUE

    CANCEL

    Set To

    AM

  • 8/13/2019 CDT900 Series Manual

    50/102

    CDT900 Series Touchscreen Programmable Thermostat

    3.Release the two blank keys when thescreen on the thermostat matches the

    screen below.

    4.See screen below to review how thethermostat keys are used during Installer

    Setup. See Tables 3-5 for the InstallerSetu Numbers and Settin s.

    5.Press the Done key to exit the Installer Setup screen.

    49

    DONE

    DONE

    INSTALLER

    SETUP

    NUMBER

    ADVA NCE TO N EXT

    INSTALLER SETUP

    CURRENT

    SETTING

    CHANGE THE

    CURRENT SETTING

    PRESS TO EXIT

    INSTALLER SETUP

  • 8/13/2019 CDT900 Series Manual

    51/102

    CDT900 Series Touchscreen Programmable Thermostat

    Installer SetupNumber

    Installer SetupName Settings Notes

    0120 Date(Year Upper)

    Select first two digits of current calendar year(2005, etc)

    it cannt be changed

    0130Date

    (Year Lower)Select last two digits of current calendar year(05 for year 2005, etc)

    2001 - 2099 available

    0140 Date (Month)Select number that represents currentcalendar month

    0150 Date (Day)Select number that represents currentcalendar date

    0160 Schedule Options0-nonprogrammable4-7-day programmable

    when it is changed, the schedneed to be reprogrammed)

    0170 System Type Selection

    1-1 heat/1 cool conventional (factory setting)2-single-stage heat pump (no auxiliary heat)3-heat only conventional (no fan) Also for750mV.4-heat only conventional (with fan)5-heat only (power to open and power toclose zone valves or normally-open zonevalves)6-cool only conventional7-2 heat/1 cool heat pump (with auxiliaryheat)

    8-2 heat/2 cool multistage conventional9-2 heat/1 cool multistage conventional10-1 heat/2 cool multistage conventional11-2 heat/2cool heat pump (no auxiliary heat)12-3 heat/2cool heat pump (with auxiliaryheat)

    Available options and defaultsvary by thermostat. Systemselection automaticallymodifies some default settingsand/or hides other InstallerSetup options.

    Table 3.installer Setup Menu.

    50

  • 8/13/2019 CDT900 Series Manual

    52/102

    CDT900 Series Touchscreen Programmable Thermostat

    InstallerSetup

    Number

    Installer SetupName

    Settings Notes

    0180 Fan Control in Heating

    0-gas or oil furnace equipment controls fan in

    heating (factory setting)

    1-electric furnace thermostat controls fan in

    heating

    Only shown if conventional

    system is selected. If heat

    pump is chosen, fan defaults

    to electric.

    0190

    Changeover Valve O/B

    Terminal Energized in

    Heating or Cooling

    (Heat Pumps Only)

    0-changeover valve O/B terminal setting

    1-changeover valve O/B terminal is

    energized in heating

    Only shown if heat pump

    system is chosen.

    0200Backup Heat Source

    (Auxiliary Heat)

    0-heat pump backup heat source is electric(factory setting)

    1-heat pump backup heat source is fossil fuel

    Only shown if 2 heat/1 cool or3 heat/2 cool heat pump is

    chosen

    0210External Fuel

    FossilFuel Kit

    0-no external fossil fuel kit is controlling heat

    pump backup heat. This thermostat controls

    the dual fuel. Must install outdoor sensor and

    set Installer Setup Number 0340 to number

    2. 1-external fossil fuel kit is controlling heat

    pump backup heat

    Only shown if fossil fuel is

    chosen as backup heat

    source.

    0220Cycles per hour (cph)

    for 1st Stage

    Compressor

    3-cph recommended for compressors(factory setting)

    1, 2, 4, 5, 6-other cycle rate settings

    0230

    Cycles per hour (cph)

    for 2nd Stage

    Compressor

    3-cph recommended for compressors

    (factory setting)

    1, 2, 4, 5, 6other cycle rate settings

    Only shown if two stages of

    cool are selected.

    Table 3.installer Setup Menu.(CONTINUES)

    51

  • 8/13/2019 CDT900 Series Manual

    53/102

    CDT900 Series Touchscreen Programmable Thermostat

    Table 3.installer Setup Menu. (CONTINUES)

    Installer SetupNumber

    Installer SetupName Settings Notes

    0240Cycles per hour (cph)

    for 1st StageConventional Heat

    1- 1 cph used for steam and gravity3-3 cph used for hot water system and highefficiency (90% or better) furnaces5-5 cph used for standard fossil fuel forcedair (less than80% efficient) systems (factory setting)9-9 cph used for electric furnaces2, 4, 6, 7, 8, 10, 11, 12other cycle ratesettings

    Not shown if system selectionis heat pump. Selection in thisstage changes default cph for2nd stage heat.

    0250

    Cycles per hour (cph)for 2nd Stage Heat

    (Aux Heat for 2H/1CHeat Pumps)

    1-1 cph used for steam and gravity

    3-3 cph for hot water systems and highefficiency (90% or better) furnaces5-5 cph for standard fossil fuel forced air(less than 90% efficient) systems (factorysetting)9-9 cph used for electric furnaces or electricauxiliary heat for heat pump systems2, 4, 6, 7, 8, 10, 11, 12other cycle ratesettings

    Only shown if two stages ofheat are selected.

    0260Cycles per hour (cph)

    for 3rd Stage Heat AuxHeat for 3H/2C Heat

    Pumps)

    1-1 cph used for steam and gravity3-3 cph for hot water systems and highefficiency (90% or better) furnaces

    5-5 cph for standard fossil fuel forced air(less than 90% efficient) systems (factorysetting)9-9 cph used for electric furnaces or electricauxiliary heat for heat pump systems2, 4, 6, 7, 8, 10, 11, 12-other cycle ratesettings

    Only shown if 3H/2C heatpump is selected.

    52

  • 8/13/2019 CDT900 Series Manual

    54/102

    CDT900 Series Touchscreen Programmable Thermostat

    Table 3.installer Setup Menu. (CONTINUES)

    Installer Setup

    Number

    Installer Setup

    NameSettings Notes

    0270Cycles per hour (cph)

    for Emer

    3-3 cph for hot water systems and highefficiency (90% or better) furnaces

    5-5 cph for standard fossil fuel forced air

    (less than 90% efficient or better) systems

    9-9 cph for electric strip heat for heat pumps

    Only shown if 2H/1C or 3H/2C

    heat pump is selected.

    0280 Continuous Backlight0-Backlight function disable

    1-Backlight function enable.

    0300 Changeover0-manual changeover (factory setting)

    1-auto changeover

    0310 Deadband

    Heating and cooling setpoints can be set no

    closer than chosen value:

    2-2F (1.5C)

    3-3F (2C)

    4-4F (2.5C)

    5-5F (3C)

    6-6F (3.5C)

    7-7F (4C)

    8-8F (4.5C)

    9-9F (5C)

    Shown only if automatic

    changeover is selected.

    0320Temperature Indication

    Scale

    0-fahrenheit temperature display (factory

    setting)

    1-celsius temperature display

    when it is changed, the schedneed to be reprogrammed)

    53

  • 8/13/2019 CDT900 Series Manual

    55/102

    CDT900 Series Touchscreen Programmable Thermostat

    Table 3.installer Setup Menu. (CONTINUES)

    Installer Setup

    Number

    Installer Setup

    NameSettings Notes

    0330 Daylight Savings1-daylight savings is on (factory setting).

    0-daylight savings is off.

    Set to 0 in areas that do not

    follow daylight savings.

    0340

    Remote Temperature

    Sensor (Outdoor or

    Indoor)

    0-no remote temperature sensor

    1-outdoor temperature sensor for display

    only.

    2-outdoor temperature sensor for

    control.Outdoor sensor used for Heat Pump

    Lockout settings. (See Heat PumpTemperature Lockout section for more

    details.)

    3-indoor temperature sensor

    Defaults and Options depend

    on System Type selection.

    Indoor Temperature Sensor

    uses an averaging network

    and does not include on-boardsensor.

    0350

    Heat Pump

    Compressor Lockout

    or (Balance Point)

    0-no compressor lockout.

    15F (-9.5C)

    20F (-6.5C)

    25F (-4C)

    30F (-1C)

    35F (1.5C)

    40F (4.5C)

    45F (7C)

    Default depends on other

    selections. Shown if control is

    selected. (See section formore information.)

    54

  • 8/13/2019 CDT900 Series Manual

    56/102

    CDT900 Series Touchscreen Programmable Thermostat

    Table 3.installer Setup Menu. (CONTINUES)

    Installer Setup

    Number

    Installer Setup

    NameSettings Notes

    0360Heat Pump Auxiliary

    Lockout

    0-no auxiliary heat lockout.

    40F (4.5C)

    45F (7C)

    50F (10C)

    55F (13C)

    60F (15.5C)

    Shown if electric is chosen for

    backup heat source and

    outdoor temperature sensor

    for control is selected. (See

    Advanced Features section for

    more information.)

    0380

    Indoor

    Dehumidification

    Control

    0-No indoor dehumidification control.

    1-Dehumidification control activated.

    Available on select odels. If

    dehumidification control isactivated and auto-

    changeover is selected in

    Installer Setup Number 0300,

    the deadband minimum is

    defaulted to 5F (3C) in

    Number 0310.

    0500Furnace Change

    Reminder

    0-furnace filter reminder off

    1-10 run time days

    2-30 run time days3-60 run time days

    4-90 run time days

    5-120 run time days

    6-365 run time days

    Run time based on call for fan.

    55

  • 8/13/2019 CDT900 Series Manual

    57/102

    CDT900 Series Touchscreen Programmable Thermostat

    Installer Setup

    Number

    Installer Setup

    Name

    Settings Notes

    0510Humidifier PadReplacement

    Reminder

    0-humidifier pad replacement reminder off

    1-90 calendar days

    2-180 calendar days

    3-365 calendar days

    0520UV Lamp Replacement

    Reminder0-UV lamp replacement reminder off

    1-365 calendar days

    0530Adaptive Intelligent

    Recovery

    1-Adaptive Intelligent Recovery control isactivated (system starts early so setpoint isreached by start of program period).

    0-Conventional Recovery (system startsrecovery at programmed time)

    0540 Number of Periods2-two periods available (Wake and Sleep)4-four periods available (Wake, Leave,Return and Sleep)

    Not shown if non-programmable isselected. 2 or4 applies to all days of theweek. (when it is changed, thesched need to bereprogrammed)

    0580Minimum Compressor

    Off Time

    5-five-minute compressor off-time setting(factory setting)

    0, 2, 3, 4-other compressor off-time settings

    0600Heat TemperatureRange Stop

    40-90-temperature range (1F increments) ofheating setpoint.

    Shown in 1/2 C.

    0610Cool TemperatureRange Stop

    50-99-temperature range (1F increments) ofcooling setpoint.

    Shown in 1/2 C.

    0640 Clock Format12-12 hour clock (factory setting)

    24-24 hour clock

    Table 3.installer Setup Menu. (CONTINUES)

    56

  • 8/13/2019 CDT900 Series Manual

    58/102

    CDT900 Series Touchscreen Programmable Thermostat

    Table 3.installer Setup Menu. (CONTINUES)

    Installer Setup

    Number

    Installer Setup

    Name

    Settings Notes

    0650Extended Fan OnTime

    Heat

    0-no extended fan operation after call forheat ends

    90- fan operation is extended 90 secondsafter call for heat ends.

    Not shown if fan operation isset to fossil fuel or in Cool OnlySystems

    0660Extended Fan On Time

    Cool

    0.no extended fan operation after call for coolends

    90.fan operation is extended 90 secondsafter call for cool ends.

    Not shown in Heat Only

    Systems.

    0670 Keypad Lockout

    0-unlocked keypad

    1-partially locked keypad

    2-fully locked keypad

    Unlockedall functions are

    available.Partially locked onlytemperature up and downkeys and ability to enter andmodify Installer Setup modeare available.

    Fully locked only ability toenter and modifyInstallerSetup mode are available.

    0680Temperature Control in

    Heat

    1-less aggressive temperature control (couldcause temperature undershoot)

    2-Standard temperature control in heating(factory setting)

    3-more aggressive temperature control(could cause temperature overshoot)

    Applies to recovery ramp anduse of auxiliary heat during

    recovery.Choose 1 if gettingtemperature overshoot.

    Choose 3 if gettingtemperature undershoot.

    57

  • 8/13/2019 CDT900 Series Manual

    59/102

    CDT900 Series Touchscreen Programmable Thermostat

    Installer Setup

    Number

    Installer Setup

    Name

    Settings Notes

    0690

    Temperature Control in

    Cool

    1-less aggressive temperature control (couldcause temperature undershoot)

    2-Standard temperature control in cooling(factory setting)

    3-more aggressive temperature control(could cause temperature overshoot)

    Applies to recovery ramp.

    Choose 1 if gettingtemperature overshoot.

    Choose 3 if gettingtemperature undershoot.

    0700 Temperature DisplayOffset

    -3F (-1.5C)

    -2F (-1C)

    -1F (-.5C)

    0F (0. C) (no difference in displayedtemperature and actual room temperature )

    1F (.5C)

    2F (1C

    3F (1.5C)

    0710 Reset Thermostat0-no thermostat reset.

    1-resets all Installer Setup Options to defaultvalues and resets schedule to default setting.

    Only calendar settings andtime are retained.

    Table 3.installer Setup Menu. (CONTINUES)

    58

  • 8/13/2019 CDT900 Series Manual

    60/102

    CDT900 Series Touchscreen Programmable Thermostat

    INSTALLERSYSTEMTESTUse the Installer System Test to test the W1 W2 E AUX Y1 Y2 and L .

    CAUTIONEquipment Damage Hazard.Minimum compressor off time is bypassed during Installer System Test

    Avoid cycling compressor quickly.

    59

    Howto Usethe InstallerSystemTestThe Installer Test is part of the Installer Setup Menu.

    1.Enter the Installer System Test by entering the Installer Setup.2.Note that the test appears at the end of the Installer Setup Numbers.3.See Fig. 30 to review how the thermostat buttons are used during the Installer System Test.See Table 6 for available Installer System Tests.

  • 8/13/2019 CDT900 Series Manual

    61/102

    CDT900 Series Touchscreen Programmable Thermostat

    60

    Fig. 30. Review thermostat buttons used during Installer System Test.

    DONE

    SYSTEM TESTNUMBER

    SYSTEM STAUSNUMBER

    UP ARROW KEY

    ADVANCES TO

    NEXT SYSTEMTEST NUMBER

    UP ARROW

    TURNS THE

    SYSTER ON

    DONE KEY

    EXITS INSTALLE

    SYSTEM TEST

    ARROW ARROW

    TURNS THE

    SYSTER OFF

  • 8/13/2019 CDT900 Series Manual

    62/102

    CDT900 Series Touchscreen Programmable Thermostat

    InstallerSystemTestsTable 4. Installer System Test.

    System Test Number Test Type System Status Number andDescription

    Test 1 Cooling System Test1-Cool stage 1 and stage 2 turn on.

    0-Cool is off.

    Test 2 Fan System Test 1-Fan turns on.

    0-Fan turns off.

    Test 3 Heating System Test

    1-Heat stage 1 and stage 2 (aux

    heat) turn on.

    0-Heat is off.

    Test 4 Emergency Heat Test1-Emergency heat and L turn on.

    0-Emergency heat and L turns off.

    Press the Next button to go to the beginning o f the Installer Setup or p ress the Done button to exit the Installer

    System Test.

    61

  • 8/13/2019 CDT900 Series Manual

    63/102

    CDT900 Series Touchscreen Programmable Thermostat

    OPERATION

    ThermostatKeys Thermostat Display

    62

    AUTO

    AMRoom SCHED

    HOLD

    CLOCK

    SCREEN

    MORE

    SYSTEM

    FAN

    Set To

    TUE

    HEAT

    FAN

    SELECTS

    ON/AUTO/CIRC

    SYSTEM

    SELECTS EM.

    HEAT/OFF/COOL

    AUTO/EMER

    UP ARROW

    RAISES

    TEMPERATURESETTING

    DOWN ARROE

    LOWERS

    TEMPERATURESETTING

    SCHED

    ENTERS

    SCHEDULING

    MODE

    HOLD

    SETS A PERMANENT

    HOLD AND ACTIVITIES

    VACATION HOLD

    CLOCK

    SETS THE TIME

    FORWARD

    OR BACK

    SCREEN

    LOCKS OUT THE

    SCREEN TO ALLOWFOR CLEANING

    Running As SCHED

    MORE

    SHOWS ADDITIONAL

    ACCESSORY ANDMAINTENANCE

    OPTIONS

    AUTO

    AMRoomSCHED

    HOLD

    CLOCK

    SCREEN

    MORE

    SYSTEM

    FAN

    Set To

    TUE

    HEAT

    FAN

    SHOWS FAN

    SETTING

    SYSTEM

    SHOWS

    CURRENT

    SYSTEM

    POSITION

    TUE

    SHOWS

    CURRENT

    DAY OF THE

    WEEK

    INSIDE TEMPERATURE

    SHOWS THE CURRENT

    INSIDE TEMPERATURE

    TIME

    DISPLAY CURRENT

    TIME OF DAY. HOLD

    TIME REMAINING OR

    NUMBER OF VACATION

    DAYS REMAINING

    SET TO

    TEMPERATURE

    SHOWS THE

    CURRENT SET

    TEMPERATURE

    Running As SCHEDRunning As SCHED

    RUNNING AS SCHED

    SHOWS THE

    THERMOSTAT IS

    FOLLOWING THE

    PROGRAMMED

    SCHEDULE

  • 8/13/2019 CDT900 Series Manual

    64/102

    CDT900 Series Touchscreen Programmable Thermostat

    SystemandFanSettingsSystem

    The System key selections vary based on your heating and/or cooling system type.Heat Thermostat controls the heating system.Off Both heating and cooling systems are off.Cool Thermostat controls the cooling system.

    Auto Thermostat automatically changes between heating and cooling operation,depending on indoor temperature.Emer Emergency heat cycles to maintain temperature. Compressor is locked out (usedonly for 2H/1C or 3H/2C heat pump systems) and auxiliary heat turns on as second stage ifneeded.

    FanThe Fan key selections vary based on the heating and/or cooling system type.On Fan runs continuously. Use this setting for improved air circulation or for more efficientcentral air cleaning.

    Auto Fan follows the fan program schedule.

    Circ Fan runs randomly approximately 35% of the time when the equipment norequirement. Use this setting for improved air circulation or for more efficient central aircleaning when you do not want the fan running continuously.

    63

  • 8/13/2019 CDT900 Series Manual

    65/102

    CDT900 Series Touchscreen Programmable Thermostat

    UserSetupFollow these steps to enter the User

    Setup:1Press and release the System key.

    2Press and hold the center blank key for

    approximately five seconds until the screenchanges.

    64

    AUTO

    AMRoom SCHED

    HOLD

    CLOCK

    SCREEN

    MORE

    SYSTEM

    FAN

    Set To

    TUE

    Running As SCHED

    HEAT

    DONE

    RoomSYSTEMHEAT

    OFF

    COOL

    TUE

    CANCEL

    Set To

    AM

  • 8/13/2019 CDT900 Series Manual

    66/102

    CDT900 Series Touchscreen Programmable Thermostat

    3Release the center blank key when thescreen on the thermostat matches the

    screen below.

    4See the screen below to review how thethermostat keys are used during the User

    Setup. See Table 5 for the User Setupnumbers and settings.

    5Press the Done key to exit the User Setup screen.

    65

    DONEDONE

    INSTALLER

    SETUP

    NUMBER

    ADVANCE TO NEXT

    INSTALLER SETUPCURRENT

    SETTING

    CHANGE THE

    CURRENT SETTING

    PRESS TO EXIT

    INSTALLER SETUP

  • 8/13/2019 CDT900 Series Manual

    67/102

    CDT900 Series Touchscreen Programmable Thermostat

    Installer Setup

    Number

    Installer Setup

    Name

    Settings

    0120Date

    (Year Upper)it cannt be changed

    0130Date

    (Year Lower)Select last two digits of current calendar year (05 for year 2005, etc)

    0140 Date (Month) Select number of current calendar month (1-12)0150 Date (Day) Select number of current calendar date (1-31)

    0160 Schedule Options0-Non-programmable4-7-day programmable(factory setting)(when it is changed, the sched need tobe reprogrammed)

    0320Display temperature in

    F or C0-F setting (factory setting)1-C setting

    0330 Daylight savings time1-Daylight function enable0-Daylight function disable

    0500 Furnace air filter

    0-off (factory setting)1-10 fan run time days(about one month)2-30 fan run time days(about three months)3-60 fan run time days(about six months)4-90 fan run time days(about nine months)5-120 fan run time days(about one year)6-365 fan run time days(about three years)

    0510Humidifier pad

    reminder

    0-off1-3 months2-6 months3-12 months

    0520 UV lamp reminder0-off (factory setting)1-1 year

    Table 5. User Setup Settings.

    66

  • 8/13/2019 CDT900 Series Manual

    68/102

    CDT900 Series Touchscreen Programmable Thermostat

    Table 5. User Setup Settings. (CONTINUES)

    Installer SetupNumber

    Installer SetupName Settings

    0540Number of schedule

    periods available2-two (Wake and Sleep)4-four (Wake, Leave, Return, Sleep)factory setting

    0640 Clock format12-12-hour clock(factory setting)24-24-hour clock

    0670 Screen lockout

    0-all keys available; screen is unlocked (factory setting)1screen is partially locked. All key functions locked except Temperature Upand Down keys and Cancel key.2-screen is fully locked

    67

  • 8/13/2019 CDT900 Series Manual

    69/102

    CDT900 Series Touchscreen Programmable Thermostat

    PROGRAMMING

    PreprogrammedEnergy Star SettingsTable 6 shows default program settings. Visit the Energy Star web site atwww.energystar.gov for additional education and resources on programmable thermostats.

    Table 6. Energy Star Default Program Settings.

    Setpoints

    Schedule Period Time

    Heat Cool

    Fan Setting

    Wake 6:00AM 68F (20C) 78F (26C) Auto

    Day 8:00AM 60F (16C) 85F (29C) Auto

    Evening 4:00PM 68F (20C) 78F (26C) Auto

    Sleep 10:00PM 60F (16C) 82F (28C) Auto

    Program HeatingandCooling ScheduleYour thermostat can control up to four different schedule periods per day:Wake-Period when you awaken and want your home at a comfortable temperature.Day

    -

    Period when you are away from home and want an energy-saving temperature.Evening-Period when you return home and want your home back to a comfortabletemperature.Sleep-Period when you are asleep and want an energy-saving temperature.NOTE: Schedule times are in 15-minute

    68

  • 8/13/2019 CDT900 Series Manual

    70/102

    CDT900 Series Touchscreen Programmable Thermostat

    Edit Schedule1.Press Sched key. 2.Press PROG DAY key to review the

    programs to see that the settings arecompatible with your lifestyle.

    69

    CANCEL DONE

    AUTO

    CANCELPERIOD

    AM

    COOL

    EDIT

    WAKE

    DAY

    EVENING

    SLEEP

    FAN

    DAYPROGMON TUEWED THU FRI

    HEAT

    CANCEL DONE

    AUTO

    CANCELPERIOD

    AM

    COOL

    EDIT

    WAKE

    DAY

    EVENING

    SLEEP

    FAN

    DAYPROGMON TUEWED THU FRI

    HEAT

  • 8/13/2019 CDT900 Series Manual

    71/102

    CDT900 Series Touchscreen Programmable Thermostat

    3.Press the edit then you press PROG DAYkey to select the program days

    NOTE:The Fan setting can be programmefor On, Auto, or Circ for each periodselected. See Fan Schedule sectionfor more information.

    6.Another approach to programming is tofirst program all weekdays Mon through Firand Sat and Sun as same programs.

    4.Press Wake key. Once pressed, Wakeflashes to show it is selected. Same as theother sched5.Press Up and Down keys to modify timeand heat and cool temperatures from thisscreen.

    70

    CANCEL DONE

    WAKE

    DAY

    EVENING

    SLEEP

    DAYPROGMON TUEWED THU FRI

    CANCEL DONE

    AUTO

    CANCELPERIOD

    AM

    COOL

    EDIT

    WAKE

    DAY

    EVENING

    SLEEP

    FAN

    DAYPROGMON TUEWED THU FRI

    HEAT

  • 8/13/2019 CDT900 Series Manual

    72/102

    CDT900 Series Touchscreen Programmable Thermostat

    .

    7. To exit schedule without saving changes,press Cancel key any time.

    CancelaSchedulePeriod1.Press Sched key.

    2.Press Edit key.3.Select the Day(s) of the week desired.4.Press schedule period you want to cancel(Wake, Leave, Return or Sleep). Onceselected, the period flashes.5.Press Cancel Period key.

    NOTE: To set a Program Schedule for theremaining days of the week, repeatsteps 1-9. Example: If Mon Fri waselected first, go back and repeatsteps 1-6 for Sat and Sun.

    6.The time, temperature(s) and fan settingdisappear. The bar above the selected periodis removed, indicating the scheduled period

    was cancelled.NOTE: To reinstate a schedule period, pressarrow keys to set desired time andtemperatures.

    71

    CANCEL DONE

    AUTO

    CANCEL

    PERIOD

    AM

    COOL

    WAKE

    DAY

    EVENING

    SLEEP

    FAN

    DAYPROGMON TUEWED THU FRI

    HEAT

  • 8/13/2019 CDT900 Series Manual

    73/102

    CDT900 Series Touchscreen Programmable Thermostat

    7. Press Done key.

    OnFan runs continuously (programmablefor all schedule periods).

    Circ

    Fan runs randomly for approximately35% of schedule period when norequirement from equipments(programmable for all schedule periods).

    Fan SchedulePress Fan key while in the Scheduling

    Screen to program the System Fan. Choicavailable from the Scheduling Screen:

    Auto (default position)Fan runs withequipment. Programmable for all scheduleperiods (Wake, Leave, Return and Sleep).

    72

    CANCEL DONE

    AUTO

    CANCELPERIOD

    WAKE

    DAY

    EVENING

    SLEEP

    FAN

    DAYPROGMON TUEWED THU FRI

    COOLHEAT

    CANCEL DONE

    AUTO

    CANCELPERIOD

    AM

    COOL

    WAKE

    DAY

    EVENING

    SLEEP

    FAN

    DAYPROGMON TUEWED THU FRI

    HEAT

  • 8/13/2019 CDT900 Series Manual

    74/102

    CDT900 Series Touchscreen Programmable Thermostat

    anua verr e o an c e u eUse Fan key to change fan work statesby manual.

    Auto-fan is automatically following the Fanschedule(choices are Auto, On or Circulate).On-Fan runs randomly for approximately35% of schedule period when norequirement from equipments.Circ-Fan circulates randomly forapproximately 35% of time.

    When the program reaches to nextschedule, the fan will run as the setting inthe period.

    Operate CDT900 SeriesTouchscreen

    Set Time1.Press Clock.2.Use arrows to set current

    73

    CANCEL DONE

    AM

  • 8/13/2019 CDT900 Series Manual

    75/102

    CDT900 Series Touchscreen Programmable Thermostat

    4. Press Done key.

    IMPORTANTThe current day of the week shouldalready be set correctly. If not, seeInstaller Setup to set the day.

    Set TemperatureOverridesThe thermostat has three temperature

    override options: Override TemperatureUntil, Permanent Override and VacationHold.

    Override Until (TEMPORARY Override)

    Holds temperature temporarily until the nextscheduled period time or until the time theuser sets.

    1. Press Up or Down arrow next to thetemperature you want to adjust. HoldTemperature Until time appears on thescreen. The Hold Temperature Until timedefaults to the start time of the nextscheduled period.

    2. Press Up or Down arrow next to the Timekey to set desired time for the thermostat toresume

    3. Press the Cancel or Sched key to cancelOverrideTemperature Untiland resumeschedule.

    74

    CANCEL

    AUTO

    PM

    Override Until

    Room

    SCHED

    HOLD

    CLOCK

    SCREEN

    SYSTEM

    HEAT

    FAN

    Set To

    TUE

  • 8/13/2019 CDT900 Series Manual

    76/102

    75

    CDT900 Series Touchscreen Programmable Thermostat

    VACATION HOLD

    Changes temperature setting for a designated number of days.

    1

    Press the Up and Down arrow keys to set the desired temperature while away on vacation.Notice that Hold Temperature Until time is shown on the screen. (This is the time the Vacation

    Hold override expires after the number of days ends.)

    2Press Hold key twice. Screen shows Hold Temperature Until one day.3Press Up and Down arrow keys to change the number of Days you desire thermostatto override the schedule.NOTE: Days Up and Down arrows appear for approximately seven seconds. Pressing

    ust below Hold Temperature Until on the screen allows the Days Up and Down arrowsto reappear.

    4. To cancel the Vacation Hold overrideearly, press the Cancel key.NOTE:When the number of days of

    Vacation Hold expires, the screenshows Following Schedule to

    indicate that Vacation Hold hasended.

    CANCEL

    AUTO

    Override UntilRoom SCHED

    CLOCK

    SCREEN

    SYSTEM

    HEAT

    FAN

    Set To

    TUE

    DAYS

  • 8/13/2019 CDT900 Series Manual

    77/102

    CDT900 Series Touchscreen Programmable Thermostat

    CleanThermostat Screen

    The thermostat has a touch screen interaction. Follow these steps to clean the screenwithout making thermostat changes:1.Press the Screen key. Thermostat locks out all touch keys for 30 seconds to allow forcleaning.

    76

    CLEAN SCREEN

  • 8/13/2019 CDT900 Series Manual

    78/102

    CDT900 Series Touchscreen Programmable Thermostat

    2.Use damp cloth slightly moistened withwater or house- hold glass cleaner to cleanthe screen.3.Repeat the above steps, as necessary.IMPORTANT

    Do not spray any type of liquiddirectly on the thermostat itself. Ifusing household glass cleaner,spray cleaner on cloth. Then usea cloth to clean the thermostat

    screen.4.Press the Done key to return to theHome Screen and normal operation.

    ReplaceBatteries1.When the Battery indicator is flashing,

    replace the batteries promptly with twofresh AA alkaline batteries

    2.Remove thermostat from the wallplate bpulling straight out.

    3.Remove the old batteries and insert twofresh AA alkaline batteries, as marked on thethermostat.

    77

  • 8/13/2019 CDT900 Series Manual

    79/102

    CDT900 Series Touchscreen Programmable Thermostat

    4.Align the screw blocks with the pins on theback of the thermostat.

    5.Push the thermostat straight onto the

    wallplate until it snaps into place.

    78

    BATTERIES(2)

    WALLPLATE

    TERMINALSCREWBLOCK

    PINSONBACKOF

    THERMOSAT

  • 8/13/2019 CDT900 Series Manual

    80/102

    CDT900 Series Touchscreen Programmable Thermostat

    BatteryTips1.Replace the batteries as soon as Battflashes in the display. The Battery indicator

    flashes in the display one month before thebatteries run down completely.2.Always use fresh AA alkaline batteries.Non-alkaline batteries do not last as longand can leak, causing thermostat damage.3.Although the thermostat has a LowBattery indicator, replace the batteriesonce a year to prevent the thermostat andheating/cooling system from shutting downdue to lack of battery power.

    ScreenLocks

    Partially Locked ScreenWhen partially locked, the screen indicatesScreen Locked for 5 to 7 seconds whenever the

    user attempts to press a key that is locked.Pressing a locked key, while Screen Locked isshown, flashes ScreenLocked on thescreen.In this mode, all keys are locked except theTemperature Up and Down arrow keys:User can change temperature up or down

    but cannot change schedule settings.Temporary temperature change lasts untilnext scheduled period and that time showson screen.To cancel temperature override and beginfollowing schedule, press Cancel key.To unlock screen, see Installer Setup section.

    Fully Locked ScreenIn this mode, all keys are locked and notfunctional. To unlock screen, see InstallerSetup section. The screen continuouslydisplays Screen Locked.

    79

    AUTO

    Room SCHED

    HOLD

    CLOCK

    SCREEN

    SYSTEM

    HEAT

    FAN

    Set To

    TUE SCREEN LOCKED

    Running As SCHED

    MORE

  • 8/13/2019 CDT900 Series Manual

    81/102

    CDT900 Series Touchscreen Programmable Thermostat

    Outdoor TemperatureIf an outdoor temperature sensor is installed,

    the thermostat displays the outsidetemperature in the lower right corner of theHome Screen.

    If thermostat is set to Auto ChangeoverSystem mode, press the More key until theoutside temperature is shown on the screen.

    80

    CANCEL DONE

    Outside

    AUTO

    Room SCHED

    HOLD

    CLOCK

    SCREEN

    SYSTEM

    HEAT

    FAN

    Set To

    TUE

    AM

    Running As SCHED

    MORE

    AM

    Outside

  • 8/13/2019 CDT900 Series Manual

    82/102

    CDT900 Series Touchscreen Programmable Thermostat

    RemoteIndoor TemperatureIf a remote indoor temperature sensor isinstalled, the thermostat displays the inside

    temperature on the screen from the remotesensor(s).The thermostat internaltemperature sensor is not used.

    ONE REMOTE INDOOR SENSOR INSTALLED(OPTIONAL)

    If one remote indoor temperature sensor is

    used, the screen showing the Insidetemperature reading shows the temperatureat the indoor remote sensor location. Thethermostat internal temperature sensor isnot used.

    MULTIPLE REMOTE INDOOR SENSORSINSTALLED (OPTIONAL)

    If more than one remote indoor sensor isused, the screen showing Inside temperaturreading shows the average of all the remoteindoor sensors. The thermostat internaltemperature sensor is not used.

    81

    AUTO

    Room SCHED

    HOLD

    CLOCK

    SCREEN

    SYSTEM

    HEAT

    FAN

    Set To

    TUE

    AM

    Heat On

    Running As SCHED

    MORE

    AM

  • 8/13/2019 CDT900 Series Manual

    83/102

    CDT900 Series Touchscreen Programmable Thermostat

    Indoor Air QualityRemindersFilter Change Reminder

    The filter change reminder must be turnedon from the Installer Setup. Once expired,the screen flashes, ChangeFilterand a Reset key appears. Press theReset key to reset the change reminder.

    NOTE: The days are counted as fan runtime, so anytime the fan is running, thereminder is counting that time against thenumber of days selected.

    The remaining run time days can be viewedby pressing the More key; the remainingdays can be edited using the More key or

    from the Installer Setup. To view or reset thereminder before it expires, follow thesesteps using the More key:

    1.Press the More key until the filter reminderappears on the screen. This is the number offan run-time days remaining on the filterreminder.

    82

    DONE

    MORE

    DAYS

    FILTER

    EDIT

    CANCEL

    RESET

    AUTO

    Override Until

    Room

    SCHED

    HOLD

    CLOCK

    SCREEN

    SYSTEM

    HEAT

    FAN

    Set To

    TUERENEW FILTER

    Running A s SCHED

    MORE

    PM

    RESET

  • 8/13/2019 CDT900 Series Manual

    84/102

    CDT900 Series Touchscreen Programmable Thermostat

    2.Press the Edit key.3.Use the Up and Down keys to changethe number of run-time days.

    4.Press the Done key to go back to the

    viewing screen.

    83

    DONE

    MORE

    DAYS

    FILTER

    EDIT

    CANCEL

    RESET

    CANCEL DONE

    MORE

    RESET

    FILTER

    EDITDAYS

  • 8/13/2019 CDT900 Series Manual

    85/102

    CDT900 Series Touchscreen Programmable Thermostat

    5.Press the Reset key to activate the newnumber of days selected in the previousscreen.

    6.Press the Done key to return to the Home

    Screen.

    84

    DONE

    DAYS

    FILTER

    CANCEL

  • 8/13/2019 CDT900 Series Manual

    86/102

    CDT900 Series Touchscreen Programmable Thermostat

    Humidif ier Pad ReminderThe Humidifier Pad change reminder must bturned on from the Installer Setup. Onceexpired, the screen flashes,ChangeHumidifier Pad and a Reset key appears.Press the Reset key to reset the changereminder.The remaining calendar days can be viewedby pressing the More key. The remainingdays can be edited using the More key orfrom the Installer Setup. To view or reset thereminder before it expires, follow these steps

    using the More key:1.Press the More key until the Humidifier Pachange reminder appears on the screen. Thiis the number of calendar days remaining onthe Humidifier Pad reminder.2.Press the Edit key.3.Use the Up and Down keys to change thenumber of calendar days.4.Press the Done key to go back to the

    viewing screen.5.Press the Reset key to activate the newnumber of days selected in the previousscreen.6.Press the Done key to return to the HomeScreen.

    UV Lamp ReminderThe UV Lamp change reminder must beturned on from the Installer Setup. Onceexpired, the screen flashes, Change UVLamp and a Reset key appears. Press theReset key to reset the change reminder.1.Press the More key until the UV Lampchange reminder appears on the screen. Thisis the number of calendar days remaining onthe UV Lamp reminder.2.Press the Edit key.

    3.Use the Up and Down keys to change thenumber of calendar days.4.Press the Done key to go back to the viewingscreen.5.Press the Reset key to activate the newnumber of days selected in the previous screen6.Press the Done key to return to the Home

    Screen.

    85

    CDT900 S i T h P bl Th

  • 8/13/2019 CDT900 Series Manual

    87/102

    CDT900 Series Touchscreen Programmable Thermostat

    TemperatureRecoveryThe thermostat feature, Adaptive Intelligent

    Recovery, eliminates all guesswork whensetting the thermostat schedule.Simply set the program schedule to the timethat the comfort temperature is desired. Thethermostat then turns on the heating orcooling at just the right time to have the homereach the scheduled temperature at the

    scheduled time.For example get up at 6:00 AM and want thetemperature to be 70F. Set the Wake periodfor 6:00 AM and 70F. The thermostat thenturns on the heat before 6:00 AM to raise thetemperature to 70F by 6:00 AM.The thermostat alerts that the heating orcooling system is coming on before a

    scheduled time by showing Recovery on thescreen.

    NOTE:It takes about a week for thethermostat to adjust to local weather, theschedule, the construction of the home and

    the heating and/or cooling system. Each dayit adjusts the next days recovery start timeaccordingly.

    86

    Set To

    MORE

    SCREEN

    RoomHEATPM

    SYSTEM

    TUE

    CLOCK

    HOLD

    SCHED

    FAN

    AUTO

    Recovery

    CDT900 S i T h P bl Th t t

  • 8/13/2019 CDT900 Series Manual

    88/102

    CDT900 Series Touchscreen Programmable Thermostat

    MinimumOff-TimerThe Thermostat has built-in compressor

    protection (minimum- off timer) that preventsthe compressor from restarting too early aftea shutdown.The minimum-off timer is activated after thecompressor turns off.If there is a call during the minimum-off timer,the thermostat shows Waitin the display.

    When the minimum-off timer expires, CoolOn or Heat Ona appears solidly in the displayand the compressor and fan turn on.

    aHeatPumpsonly.

    87

    SYSTEM

    SCREENSet To

    SCHED

    HOLD

    CLOCK

    RoomPM

    Running As SCHED

    COOL

    WED

    WaitAUTO

    FAN

    MORE

    CDT900 S i T h P bl Th t t

  • 8/13/2019 CDT900 Series Manual

    89/102

    CDT900 Series Touchscreen Programmable Thermostat

    Inside Humidity LevelSelect models can sense the humidity level

    in the home. The humidity level in the homeis shown in the lower right corner of theHome Screen.

    If thermostat is set to Auto ChangeoverSystem mode, press the More key until thehumidity level is shown on the screen.

    88

    .

    Set To

    Room

    COOL

    SYSTEM

    MORE

    SCREEN

    PM

    TIME

    HOLD

    SCHED

    THU

    Humidity

    FAN

    AUTO

    Running As SCHED

    CANCEL DONE

    Humidity

    CDT900 S i T h P bl Th t t

  • 8/13/2019 CDT900 Series Manual

    90/102

    CDT900 Series Touchscreen Programmable Thermostat

    Control Dehumidi fication Setting (SelectModels)

    Select models read the inside humidity level anallow for a dehumidification setting:1.Press the More key until the inside humiditypercent and dehumidification setpoint areshown.

    2.Use Up and Down arrow keys, located tothe right of the dehumidifier setpoint, to setdesired humidity level dehumidification inthe summer.3.Press Done key.

    Dehumidification DroopControlThe dehumidification control attempts to

    control to the user's humidity setpoint byturning on the air conditioner. In extremelyhigh humidity conditions, the thermostatkeeps the air conditioner running(energizing Y and G) for up to 3F belowthe temperature setpoint. It does this whiletrying to achieve the desired humiditysetpoint and balancing that with the

    temperature setpoint. The thermostatcontrols up to 3 F below the temperaturesetting until either the humidity is satisfiedor conditions change.

    89

    CANCEL DONE

    Humidity

    DEHUMIDIFICATION

    CDT900 S i T h P bl Th t t

  • 8/13/2019 CDT900 Series Manual

    91/102

    CDT900 Series Touchscreen Programmable Thermostat

    SpecialHeatPumpOperationeat ump n cat on equ res

    24Vac CommonConnection)E5 indication is located in the screen of thethermostat. It is only visible whenlighted.When the L terminal is wired to anequipment monitor,This is operational in theHeat, Off, Cool or Auto positions. See Fig.32.

    HeatPumpEmergencyHeatLCDIndication(Requires 24Vac

    CommonConnection)The thermostat uses E5 indicator that lightswhen the thermostat is in the Emergency Heatmode. The E5 is located in the LCD screenof the thermostat. It is visible only when on.When the thermostat is in the Emer systemmode, the L terminal is continuously energized

    and the E5is show.

    HeatPumpTemperatureLockoutsDual Fuel Heat Pump and Outdoor

    Temperature SensorIn this operation, there is no external fossil fuel

    kit (dual fuel kit) installed; the thermostat controlthis function.

    90

    AUTO

    AM

    SCHED

    HOLD

    CLOCK

    SCREEN

    MORE

    SYSTEM

    HEAT

    FAN

    Set To

    MON

    CDT900 Series Touchscreen Programmable Thermostat

  • 8/13/2019 CDT900 Series Manual

    92/102

    CDT900 Series Touchscreen Programmable Thermostat

    Fig. 32. L terminal switch to R (power)side of system transformer.

    1.Choose correct heat pump application inInstaller Setup Number 0170.2.Choose Fossil Fuel Option as thebackup heat source in Installer SetupNumber 0200.3.Choose No External Fossil Fuel Ki tOption is control- ling back up heat inInstaller Setup Number 0210.4.Choose Outdoor Temperature Sensorfor Heat PumpTemperature Lockouts

    Option in Installer Setup Num- ber 0340.5.Choose appropriate Balance PointTemperature in Installer Setup Number0350.OPERATION IN HEAT MODE ABOVE BALANCEPOINT (OUTDOOR TEMPERATURE)

    When the outdoor temperature is abovethe selected Balance Point Temperature(ISU 0350), only the compressor operatesand the fan (G terminal) energizes whenthe thermostat calls for heat. See Fig. 33.

    BALANCEPOINT

    OUTDOOR

    TEMPE

    RATURE

    COMPRESSOR ONLY

    FOSSIL FUEL ONLY

    Fig. 33. Dual Fuel Heat Pump Operation inHeat mode with

    OPERATION IN HEAT MODE BELOW BALANCEPOINT (OUTDOOR TEMPERATURE)

    When the outdoor temperature is below thselected Balance Point Temperature (ISU0350), only the Fossil Fuel (auxiliary heat)

    operates and the fan (G terminal) does notenergize when the thermostat calls for hea

    91

    CDT900 Series Touchscreen Programmable Thermostat

  • 8/13/2019 CDT900 Series Manual

    93/102

    CDT900 Series Touchscreen Programmable Thermostat

    OPERATION IN EMERGENCY HEAT MODE

    The balance point (outside) temperature is

    not used in the Emergency heat mode. Whthe thermostat is moved to the EmergencyHeat position, the compressor is locked out.The first stage of heat is whatever isconnected to the E terminal. The secondstage of heat is what is connected to the Auterminal. Often there is only one source of

    non-compressor heat and the E terminal isjumped to the Aux. terminal.

    Heat Pump with Electric Auxiliary

    (Backup) Heat and OutdoorTemperature Sensor1.Choose correct heat pump application inInstaller Setup Number 0170.2.Choose Electric asAuxil iary (Backup)Heat Source in Installer Setup Number0200.

    3.Choose Outdoor Temperature Sensorfor Control Option in Installer SetupNumber 0340.4.Choose Compressor LockoutTemperature inInstaller Setup Number0350.5.ChooseAuxi liary Lockout Temperaturein Installer Setup Number 0360.

    NOTE: There is a 5F deadband between thCompressor and Auxiliary Heat Lockout

    92

    CDT900 Series Touchscreen Programmable Thermostat

  • 8/13/2019 CDT900 Series Manual

    94/102

    CDT900 Series Touchscreen Programmable Thermostat

    Operation in Heat ModeWhen the outdoor temperature is below the

    Compressor Lockout Temperature, only theAuxiliary Heat operates.When the outdoor temperature is above the

    Auxiliary Lockout Temperature, only theCompressor operates. See Fig. 34.

    AUXILIARY LOCKOUT

    TEMPERATURE

    COMPRESSOR

    LOCKOUT

    TEMPERATURE

    OUTDOOR

    TEMPERA

    TURE

    BOTH

    OMPRESSORANDAUXILIARYHEAT

    AUXILIARYONLY

    COMPRESSOR

    Fig. 34. Heat Pump Operation with LockoutTemperatures Set.

    When the outdoor temperature is between thetwo temperatures, both the Compressor and

    Auxiliary Heat operate.

    Operation in Emergency Heat ModeOnce the thermostat is placed into the

    Emergency Heat mode, the compressor andauxiliary lockout features are turned off. Inthe Emergency heat mode, the compressoris locked out. The first stage of heat iswhatever is connected to the E terminal.The second stage of heat is connected tothe Aux. terminal. Usually the emergencyand auxiliary heat sources are electric strip

    heat in these cases.

    Operating SequenceThe thermostat energizes specificterminal(s), depending on the demand forheating, cooling or fan. The thermostatscreen shows the time, inside temperature,system and fan selections. Additional

    indicators are shown when the heating,cooling or fan is energized. See Tables 9 - 11for specification information.

    93

    CDT900 Series Touchscreen Programmable Thermostat

  • 8/13/2019 CDT900 Series Manual

    95/102

    CDT900 Series Touchscreen Programmable Thermostat

    Table 9. Sequence of Operation for Conventional Systems.

    System Setting Fan Setting Call for Action Energize Terminals Screen MessageOff Auto None None None

    Cool Auto None None None

    Cool or Auto Auto Stage 1 Cooling Y, G Cool On

    Cool or Auto Auto Stage 1 and Stage 2

    Cooling

    Y, Y2b, G Cool On

    Heat Auto None None None

    Heat or Auto Auto Stage 1 Heating W, Ga Heat On

    Heat or Auto Auto Stage 1 and Stage 2

    Heating

    W, W2c, Ga Heat On

    aG energizes only if Installer Setup number 0180 is set to Electric.bIf Installer Setup System type is set to two stages of cooling.cIf Installer Setup System type is set to two stages of heating.

    Table 10. Sequence of Operation for Power Open and Power Closed Valves or NormalOpen Valves.

    System Setting Fan Setting Call for Action Energize Terminals Screen MessageOff Auto None None None

    Heat N/A None Y None

    Heat N/A Heat W Heat On

    94

    CDT900 Series Touchscreen Programmable Thermostat

  • 8/13/2019 CDT900 Series Manual

    96/102

    CDT900 Series Touchscreen Programmable Thermostat

    Table 11. Sequence of Operation for Heat Pump Systems.

    System Setting Fan Setting Call for Action Energize Terminals Screen Message

    Off Auto None O/Ba NoneCool Auto None O/Ba None

    Cool or Auto Auto Stage 1 Cooling Y, G, O/Ba

    Cool On

    Cool or Auto AutoStage 1 and Stage 2

    CoolingY, Y2

    d, G, O/B

    a Cool On

    Heat Auto None O/Ba

    None

    Heat or Auto Auto Stage 1 Heating Y, G, O/Ba

    Heat On

    Heat or Auto AutoStage 1 and Stage 2

    Heating

    Y, AUXc

    , G, O/Ba

    Aux Heat On

    Heat or Auto AutoStage 1, 2 and 3

    Heating

    Y, Y2d, AUXe

    , G,

    O/Ba

    Aux Heat On

    Em. Heat Auto None Lb

    , O/Ba

    None

    Em. Heat Auto Stage 1 Heating E, G, Lb, O/Ba

    Heat On

    Em. Heat AutoStage 1 and Stage 2

    HeatingE, AUX, G, L

    b, O/B

    a Aux. Heat On

    aConfigure O/B in Installer Setup. Based on last piece of equipment called (cooling = O or

    heating = B).bRed LED is on. See LED Indication section for more details.cIf Installer Setup System Type is set to 2Heat/1Cool Heat Pump with Auxiliary Heat.dIf Installer Setup System Type is set to 3Heat/2Cool Heat Pump with Auxiliary Heat.eThis terminal does not energize if Installer Setup System type is set to 2 Heat/2 Cool HeatPump with no Auxiliary Heat 95

    CDT900 Series Touchscreen Programmable ThermostatCDT900 Series Touchscreen Programmable Thermostat

  • 8/13/2019 CDT900 Series Manual

    97/102

    CDT900 Series Touchscreen Programmable ThermostatCDT900 Series Touchscreen Programmable Thermostat

    Outdoor TemperatureSensorOperation

    When installed with Thermostat Installer SetupNumber 0340 set to 1 or 2, the outsidetemperature can be displayed on thethermostat. See Fig. 35.

    Fig. 35. Outside temperature reading onCDT900 Series Thermostat.

    The Outdoor Sensor converts outdoorambient temperature to a resistance thatthe thermostat can interpret.The sensor has a negative temperaturecoefficient (NTC), which means thatresistance decreases as the temperatureincreases.

    CheckoutWith an accurate thermometer (1F[0.5C]) measure the temperature at thesensor location, allowing time for thethermometer to stabilize before reading.

    CalibrationThe Outdoor Sensor is calibrated at thefactory and cannot be recalibrated in thefield.

    96

    TUE

    SYSTEM

    HEAT

    SCREEN

    MORE

    Set To

    SCHED

    HOLD

    CLOCK

    Room

    Running As SCHED

    FAN

    AUTO

    AM

    Outside

    CDT900 Series Touchscreen Programmable Thermostat

  • 8/13/2019 CDT900 Series Manual

    98/102

    CDT900 Series Touchscreen Programmable Thermostat

    emote n oor emperatureSensorOperation

    When installed with Thermostat InstallerSetup Number 0340 set to 3, the remoteinside temperature is displayed on theThermostat Home Screen as InsideTemperature. The thermostat internaltemperature sensor is not used. See Fig.36.

    Fig. 36. Inside temperature reading onTCD900 Series Thermostat.

    The Wall Mount Temperature Sensor convertsroom temperature to a resistance that thethermostat can interpret.The sensor has a negative temperaturecoefficient (NTC), which means that resistancedecreases as the temperature increases.

    The sensor can be used to provide one remotesensor input (see Fig. 28) or as a temperatureaveraging network with multiple Sensorsconnected, as shown in Fig. 29.

    CheckoutFor best results, allow Wall Mount TemperatureSensor to absorb the air moving through theroom for a minimum of twenty minutes beforetaking a resistance measurement.With an accurate thermometer (1F [0.5C])measure the temperature at the sensor location

    allowing time for the thermometer to stabilizebefore reading.

    CalibrationThe Wall Mount Temperature Sensor iscalibrated at the factory and cannot berecalibrated in the field. 97

    AUTO

    Room SCHED

    HOLD

    CLOCK

    SCREEN

    SYSTEM

    HEAT

    FAN

    Set To

    TUE

    AM

    Heat On

    Running As SCHED

    MORE

    AM

    CDT900 Series Touchscreen Programmable Thermostat

  • 8/13/2019 CDT900 Series Manual

    99/102

    CDT900 Series Touchscreen Programmable Thermostat

    TROUBLESHOOTING(TABLE14)Table 14. Troubleshooting.

    Symptom Possible Cause Action

    Display does not come on. Thermostat is not being powered.

    Check for 24 Vac between C and Rc.

    Check that AA batteries are installed

    correctly and are good.

    The upper or lower temperature limits

    were reached.

    Check temperature setpoints.

    Check Installer Setup Numbers 0600 and

    0610; modify as needed.Temperature settings do not change.

    The keypad is fully locked.Check Installer Setup Number 0670 to

    change keypad locked options.

    Thermostat minimum off-time isactivated.

    Wait up to five minutes for the system torespond.

    System selection is not set to Heat or

    Cool.Set system Selection to correct position.

    Heating or cooling does not come on.

    System type Selection is incorrect.

    Check Installer Setup Number 0170 and

    make sure correct System type is

    chosen.

    Thermostat is calling for Heat (Heat on)

    or Cool (Cool on) but no heating orcooling is running.

    Heating or cooling equipment is notoperating.

    Check wiring.

    Check Installer Setup Number 0170 and

    make sure correct system type ischosen.

    Verify operation of equipment in System

    Test mode.

    98

    CDT900 Series Touchscreen Programmable Thermostat

  • 8/13/2019 CDT900 Series Manual

    100/102

    CDT900 Series Touchscreen Programmable Thermostat

    Table 14. Troubleshooting. (CONTINUES)Symptom Possible Cause Action

    Heating equipment failure.

    Check for 24 Vac at the equipment on

    the secondary side of the transformerbetween power and common. If voltageis not present, check the heating

    equipment to find the cause of theproblem.

    Check for 24 Vac between the heatterminal (W) and transformer common. If

    24 Vac is present, the thermostat isfunctional. Check the heating equipment

    to find the cause of the problem.

    Heat does not turn on (Heat On is solid in

    the display).

    Loose or broken wire connection

    between thermostat and heating

    equipment.

    Check for 24 Vac between the heat

    terminal (W) and transformer common. Ifvoltage is not present, check wire

    connection (loose or broken) betweenthe thermostat and the heating

    equipment.

    Cooling does not turn on (Cool

    On is solid in the display)

    Cooling equipment failure.

    Check for 24 Vac at the equipment onthe secondary side of the transformer

    between power and common. If voltageis not present, check the cooling

    equipment to find the cause of theproblem.

    Check for 24 Vac between the coolterminal (Y) and transformer common. If

    24 Vac is present, the thermostat isfunctional. Check the cooling equipment

    to find the cause of the problem.

    99

    CDT900 Series Touchscreen Programmable Thermostat

  • 8/13/2019 CDT900 Series Manual

    101/102

    CDT900 Series Touchscreen Programmable Thermostat

    Table 14. Troubleshoot ing. (CONTINUES)Symptom Possible Cause Action

    Cooling does not turn on (Cool

    On is solid in the display).

    Loose or broken wire connection

    between thermostat and cooling

    equipment.

    Check for 24 Vac between the cool

    terminal (Y) and transformer common. Ifvoltage is not present, check the wire

    connection (loose or broken) between

    the thermostat and the cooling

    equipment.

    Fan does not turn on in a call for heat

    (electric furnace).

    Fan Control in Heating is set to Gas or

    Oil Furnace (Setting 0180).

    Set Fan Control in Heating to Electric

    Furnace(Setting 0180).

    Heat pump puts out cool air in the heat

    mode and warm air in the cool mode.

    Changeover Valve (Installer Setup

    Number 0190) is not configured to match

    the changeover required by the installedheat pump.

    Set Changeover Valve (Installer Setup

    Number 0190) to match the changeover

    required by the installed heat pump.

    The heating equipment is not a heat

    pump but the System Type (Installer

    Setup Number 0170) is set to Heat

    Pump.

    Set System Type (Installer Setup

    Number 0170) to match the installed

    heating and/or cooling equipment.Both the heating and cooling equipment

    are running at the same time.

    Heating and cooling wires are shorted

    together.

    Separate the shorted heating and cooling

    wires.

    Heating equipment is running in the cool

    mode.

    Heating equipment is not a heat pump

    but System Type (Installer Setup

    Number 0170) is set to Heat Pump.

    Set System Type (Installer Setup

    Number 0170) to match the installed

    heating and/or cooling equipment.

    Heating equipment does not turn off and

    heat temperature setting is set below

    room temperature (Heat On is not in the

    display).

    Heating equipment is not a heat pump

    but System Type (Installer Setup

    Number 0170) is set to Heat Pump.

    Set System Type (Installer Setup

    Number 0170) to match the installed

    heating and/or cooling equipment.

    100

    CDT900 Series Touchscreen Programmable Thermostat

  • 8/13/2019 CDT900 Series Manual

    102/102

    CDT900 Series Touchscreen Programmable Thermostat

    Table 14. Troubleshoot ing. (CONTINUES)Symptom Possible Cause Action

    Cannot set the system setting to Heat.

    System Type (Installer Setup Number

    0170) is set to Cool Only.

    Set System Type (Installer Setup

    Number 0170) to match the installedheating and/or cooling equipment.

    Cannot set the system setting to Cool.

    System Type (Installer Setup Number

    0170) is set to Heat Only or Heat Only

    with Fan.

    Set System Type (Installer Setup

    N