  • D12-RP - POC1220kV Bus CouplerABBREF 615CT Ratio 3000:1IEC - Normal InversePickup = 1.2 (0.3 - 5 xCT Sec)Time Dial = 0.493x = 3.09 s, 5x = 2.1 s, 8x = 1.62 s

    D05-RP - POC1120MVA Transformer FeederABBREF615CT Ratio 600:1IEC - Normal InversePickup = 0.8 (0.3 - 5 xCT Sec)Time Dial = 0.313x = 1.95 s, 5x = 1.33 s, 8x = 1.02 s

    10K.5 1 10 100 1K3 5 30 50 300 500 3K 5K

    Amps X 100 BB-1A (Nom. kV=220, Plot Ref. kV=220)

    10K.5 1 10 100 1K3 5 30 50 300 500 3K 5K

    Amps X 100 BB-1A (Nom. kV=220, Plot Ref. kV=220)

    1K

    .01

    .1

    1

    10

    100

    .03

    .05

    .3

    .5

    3

    5

    30

    50

    300

    500

    Seco

    nds

    1K

    .01

    .1

    1

    10

    100

    .03

    .05

    .3

    .5

    3

    5

    30

    50

    300

    500

    Seconds

    ETAP Star 12.5.0C

    N7733 ZAKHER GRID CASE-1.1

    Project: 220/33/11kV Zakher Grid Location: Zakher Area of Al AinContract: N7733Engineer: JMFilename: C:\ETAP 1250\N7733\N7733.OTI

    Date: 18-01-2016 SN: LARSENTRN2Rev: BaseFault: PhaseCircuit: 120MVA T/F , 220kV B/C