Upload
others
View
5
Download
1
Embed Size (px)
Citation preview
٧٤
Capacitance of Transmission Line:
The capacitance between the conductors is the charge per unit of potential difference .
mFV
qC /
……………(25)
Capacitance between parallel conductors is a constant depending on the size and spacing of the conductors .
For the length of transmission line less than 80 Km , the effect of capacitance is usually neglected .
The flow of charge is a current , and this current is called the charging current of the line .
The charging current effects the voltage drop along the line , efficiency , power factor and stability of the power system .
Gauss theorem states that at any instant of time , the total electric flux through any closed surface (A) is equal to the total charge enclosed by that surface .
X +
٧٥
2/2
mcoulombx
qD
………..(26)
Where q - charge on the conductor coulomb /m x - distance , from the conductor to the point
where the electric flux density is computed. D - the electric flux density .
The electric field intensity = mediumtheoftypermittiviThe
densityfluxelectricThe
D
E mVx
q/
2
……….(27)
Where - actual permittivity of material .
0/ r
r - relative permittivity ; 0 - permittivity of free space
mF /
1094
11085.8
912
0
1- coulomb E-force on unit charge
Electric flux lines
q- coulomb/meter on line conductor
equipotential Electric surface flux lines
Electric field between two line conductors
٧٦
equipotential surface
1P
1D
q
2D 2P
Therefore , instantaneous voltage drop between 1P and
2P is :
2
1
12
D
D
dxEv
voltsD
Dqdx
x
qD
D 1
2ln22
2
1
…..(28)
Capacitance of a two wire line :
aq bq ar br
D
٧٧
From eq. ( 28)
voltr
Dqqtoduev
a
aaab ln
2
And voltage due to bq , calculated by :
voltr
Dqv
b
bba ln
2
baab vv 1
ln2
ln2
b
b
b
bab r
Dq
r
Dqv
voltD
rqqtoduev bb
bab ln2
By the principle of superposition the voltage drop from conductor (a) to conductor (b) due to charges on both conductors is the sum of the voltage drop caused by each charge alone .
voltD
rq
r
Dqv b
ba
aab
lnln
2
1
…..(29)
For two-wire line aq = - bq , so that : 2
2
ln2
ln2
ba
a
ba
aab
rr
Dq
rr
Dqv
٧٨
volts
rr
Dq
ba
a
ln
meterFarads
rr
Dv
qC
ba
ab
aab /
ln
If rrr ba ( radius of two conductors are same )
mF
rD
C ab /ln
………(30)
mFandIf r /
1094
1,1,
90
KmF
rD
mF
rD
C ab
/ln36
1
/ln36
10 9
…(31)
٧٩
a abC b a n b
naC nbC
abC - capacitance between conductors (a) and (b) .
naC - capacitance between conductor (a) and neutral .
nbC - capacitance between conductor (b) and neutral .
naC = nbC = nC = 2 abC
rD
rD
C n
ln18
1
ln36
12
KmF
rD
C n /ln
0555.0 ……(32)
Capacitive reactance between one conductor and neutral is :
nc Cf
X2
1
٨٠
r
D
ffrD
X c log106.6
2
10ln186
6
Where , 10log303.2ln
KmDfrf
X c /log106.61
log106.6 66
Capacitive reactance Capacitive reactance at 1 meter spacing spacing factor ( aX ) ( dX )
Potential difference between two conductors of a group of charged conductors :
The voltage drop between the two conductors is the sum of the voltage drops due to each charged conductor . bThe voltage drop abD bcD
between (a) to (b) : a acD c amD bmD cmD
m
٨١
volts
D
Dq
D
Dq
D
rq
r
Dq
v
ma
mbm
ca
cbc
ba
bb
a
aba
ab
ln......
...lnlnln
2
1
....…(33) In similar manner :
volts
D
Dq
D
rq
D
Dq
r
Dq
v
ma
mcm
ca
cc
ba
bcb
a
aca
ac
ln......
...lnlnln
2
1
Capacitance of three – phase line:
a- Equilateral spacing : b
D D By using eq. ( 33) a c 0 D
D
Dq
D
rq
r
Dqv cbaab lnlnln
2
1
D
rq
D
Dq
r
Dqv cbaac lnlnln
2
1
D
rqq
r
Dqvv cbaacab ln)(ln2
2
1
Volts
٨٢
But acb qqq
voltsr
Dq
r
Dq
D
rq
r
Dq
D
rq
r
Dqvv
a
aaa
aaacab
ln2
3
ln2
1lnln
2
1
lnln22
1
32
Phasor diagram of voltages cabcab vandvv , : b
30 abab vv abv
30cos2 anab V
v a 30 n bcv
anV2
3 cav
anab Vv 3 c
303 anab Vv
303 ancaac Vvv
303303 ananacab VVvv
3330cos23 anan VV
anV3
٨٣
voltr
DqV
r
DqV
aan
aan
ln2
ln2
33
neutraltomF
rDV
qC
an
an /
ln
2
1rFor
KmF
rD
rD
C n /ln
0555.0
ln18
1
(as in the case of single-phase lines , eq(32)
b) Unsymmetrical spacing but transposed :
1
31D 12D
2
3 23D
31
23
12
121 lnlnln
2
1
D
Dq
D
rq
r
Dqv cbaab ….(34)
٨٤
12
31
23
232 lnlnln
2
1
D
Dq
D
rq
r
Dqv cbaab
23
12
31
313 lnlnln
2
1
D
Dq
D
rq
r
Dqv cbaab
3321 ababab
ab
vvvv
312312
312312
312312
3
3312312
ln
lnln
6
1
DDD
DDDq
DDD
rq
r
DDDq
v
c
ba
ab
3312312
3312312 lnln
2
1
DDD
rq
r
DDDqv baab
If , 3312312 DDDDeq
eqb
eqaab D
rq
r
Dqv lnln
2
1
Similarly ,
eqc
eqaac D
rq
r
Dqv lnln
2
1
٨٥
As in section (a) :
acbanacab qqqandVvv 3
eqa
eqaan D
rq
r
Dqv lnln2
23
1
eqa
eqaan D
rq
r
Dqv lnln
23
12
2
3
3
ln23
1
r
Dqv eq
aan
volts
r
Dqv eqa
an ln2
mF
r
Dv
qC
eqan
an /
ln
2
KmF
r
D
r
DC
eqeqn /
ln
0555.0
ln18
1
…(35)
٨٦
Effect of earth on the capacitance of a line :
The presence of earth will change the electric flux lines and equipotential surfaces considerably , which in effect will change the effective capacitance between the wires,as shown in fig. below :
equipotential surface
Electric fluxlines
h
D
influence of ground on the electric field picture
٨٧
a b
aq bq conductor
h H Ground
h a b
aq bq Images of conductors
D (a) and (b)
H
hq
h
Hq
D
rq
r
Dqv babaab
2ln
2ln
2
1lnln
2
1
2222 4)2( hDhDHbut
22
22
4
2ln
2
4ln
2
1
lnln2
1
hD
hq
h
hDq
D
rq
r
Dqv
ba
baab
٨٨
hD
hDrq
hDr
hDqv baab 2
4ln
4
2ln
2
1 22
22
ba qqbut
)4(
4ln
2
1222
22
hDr
Dhqv aab
2
22 )4(1ln
2
1
hDr
Dqa
)4(1ln2
2
122 hDr
Dqa
volts
hDr
Dqa
)4(1
1lnln
22
mF
hDrDv
qC
ab
aab /
)4(1
1lnln
22
effect of earth term
٨٩
Charging current due to capacitance :
Single-phase line :
ampvcjcj
vI chg (
/
Where , f 2
c-capacitance between lines (Farads) v- phase voltage (volts)
Three – phase line :
)(/
ampsvcjcj
vI chg
Where , v- voltage to neutral (volts) c-capacitance to neutral (Farads)
Capacitance of bundle conductors
Instead of (r) , put bscD , where :
bscD - is the GMR of a bundle conductor, and can be
calculated as in inductance (page 67) .1- For two – conductor bundle :
)()()( 4 22 22dDdDdDD SSS
bSC
٩٠
2- For three – conductor bundle :
3 29 323 3 )()(2
dDdDddDD SSSbSC
3- For four – conductor bundle :
4 3
4 316 434 4
09.1
2)2()2(2
dD
dDdDdddDD
S
SSSbSC
IF conductor is solid , rDS in above three condition
Capacitance of 3-phase line , bundle conductor with equilateral spacing :
KmF
DD
C
bsc
nb /ln
0555.0
And for unsymmetrical spacing but transposed , the capacitance is :
KmF
D
DC
bsc
eqnb /
ln
0555.0
٩١
EX.1 A 3-phase , 50Hz , 132 KV overhead transmission lines has conductor diameter of 4 cm each , are arranged in a horizontal plane as shown in fig . supplies a balanced load , assume the line is completely transposed . Find the capacitance to neutral per phase per Km.
Phase A Phase B Phase C
4m 4m
Solution :
3
CABCABeqm DDDDD
m04.58443
cmrDS 2
KmF
D
DC
S
m
/01.0529.5
0555.0
102
04.5ln
0555.0
ln
0555.0
2
EX.2 A 3-phase , 50Hz , 400 KV overhead transmission lines are arranged in a horizontal plane , each phase has two – strand bundle conductors , the diameter of each strand is 25mm , as shown in the fig. below . Find the capacitance to neutral per phase per Km .
0.3m 25mm
6m 6m Phase A Phase B Phase C
٩٢
Solution :
3CABCABeqm DDDDD
m56.712663
mmrDS 5.12
2
25
dDD SbSC
m0612.03.0105.12 3
KmF
D
DC
bSC
eqnb /0115.0
816.4
0555.0
0612.056.7
ln
0555.0
ln
0555.0
Discussion Questions 1 – Discuss the effect of earth on the capacitance of a line :
2 – Derive in expression for the capacitance to neutral per phase per Km of a single phase overhead transmission line , taking into account the effect of earth .
3 – Derive in expression for the capacitance to neutral per phase per Km of a 3- phase overhead transmission line when conductors are of equilateral spacing .
٩٣
Tutorial Problems
Q1. A 3-phase , 50 Hz , 110 KV , overhead transmission line consists of three solid conductors of 3 cm diameter positioned on the corners of triangle with sides of 2 m , 2.5 m , 3.125 m .
If the conductor of each phase of this line is replaced by three-strand bundle conductor has the same equivalent area of one solid conductor , and the space between the strands of bundle is 0.2 m .
Find the capacitance to neutral per phase per Km for two conditions . Assume the line is transposed.
Q2. A 3-phase , 132 KV , 50 Hz , 100 Km , single circuit bundle conductor transmission line as shown in the figure below . If the diameter of each strand is 1 cm , and the conductors are regularly transposed . Determine , the capacitance to neutral per phase per Km .
6 m
5 m
0.18 m
٩٤
Q3. By using the method of images , prove that the capacitance between conductor and earth , taking into account the effect of earth for 3- phase equilateral spacing (as shown in fig. below) is :
conductor.theofradiustheisr)(and
Where
lnln
2
2
3
31
24
3
42
3
22
1
H
H
HH
H
HH
HH
r
DCan
b
D D
a D c
2H
1H Ground level
3H 4H
a D c
D D
b
٩٥
Performance of Transmission lines
For balance 3-phase system only 1-phase need be considered for analysis .
For purpose of analysis , transmission lines may be classified as :
a- Short line - The length of line is less than 80 Km.b- Medium line - The length of line is between 80 to
250 Km.c- Long line - The length of line is more than 250 Km.
Short Transmission line
The Fig. below , shown the equivalent circuit of a short line .
The effect of shunt capacitance is neglected . The series impedance can be taken a lumped .
rI LI
rV Load
rS VV & - phase voltage (rms value)For short line :
IIII LrS
…………………….(1)
٩٦
rrS IZVV
Eq. (1) can be written in matrix form as :
r
r
S
S
I
VZ
I
V
10
1 …………………(2)
Phasor diagram :
rV - as reference .
- Power angle ( load angle ) , it is the angle between
rS VV & , and is small ( 7to1 for short line ) .
SV IZ IX
s rV IR
III Sr
Phasor diagram per phase , any value taken from it is per phase .
Sr VV ;0
22 )sin()cos( IXVIRVV rrS
٩٧
222 )()()sincos(2 IXIRXRIVVV rrS
Percent voltage regulation of line (V.R) =100
r
ro
V
VV
(at rated current and at a given power factor )
oV - The magnitude of receiving end voltage at no-load.
rV - The magnitude of receiving end voltage at full-load.
With SV - constant .
For short line So VV
100line)short(forV.R
r
rS
V
VV
f
SV
IX o rV a b c IR
s III Sr 90
From phasor diagram :
oaof rS VV
٩٨
is very small ( ocof )
acoaoc rS VV
bcab
tely)(approximasincos XIRI + For lagging P.F.
- For leading P.F.
100
sincos.
rr
rS
V
IXIR
V
VVRV
V.R , depends on I , R ,X and P.F.Condition for zero voltage regulation ( approximately)
0sincos IXIR
V.R becomes zero at leading P.F.
sincos IXIR
X
Rtan
Also from phasor diagram :
IRV
IXV
r
rs
cos
sintan 1
s
٩٩
Medium Transmission line
The effect of shunt capacitance becomes more and more pronounced with the increase in the length of line .For medium length T.L , the shunt capacitance can be considered as lumped , by two type of equivalent circuit :
a) Nominal π circuit .b) Nominal T circuit .
Nominal π circuit
csI crI rI
rV
Z
YVIV
ZIVV
YVI
III
rrr
LrS
rr
crrL
2
2
١٠٠
2
YZVZIV rrr
)3.(..............................
21 ZI
YZV rr
rcrcsLcsS IIIIII
rrS IY
VY
V 22
rrrr IY
VY
ZIYZ
V
2221
21
4
2 YZI
ZYYV rr
)4......(....................
21
41
YZI
YZYV rr
Eq. (3) and (4) can be written in the matrix form as :
)5.(....................
21
41
21
r
r
S
S
I
V
YZYZY
ZYZ
I
V
١٠١
Phasor diagram for nominal π circuit
SV
csI crI IZ IX
rV
sI IR
I csI
rI crI
crI and csI are leads the rV and SV by 90
Angles :
- between sV and rV
- between rV and rI
s - between sV and sI
Nominal T circuit
In the nominal T circuit , the total capacitance of each conductor is concentrated at the center of the line , while the series impedance is split into two equal parts.
١٠٢
SV CV rV
)7........(..........4
12
1
221
2
22
)6.......(..........2
1
2
YZZI
YZV
ZYV
YZI
ZIV
ZI
ZIVV
YVYZ
I
YZ
IVI
YVIIII
rr
rrrr
srrS
rr
rrr
crcrs
Eq. (6) and (7) can be written in the matrix form as :
)8.....(..........
21
41
21
r
r
S
S
I
V
YZY
YZZ
YZ
I
V
١٠٣
Phasor diagram for nominal T circuit
2/ZIr 2/ZIS SV
2
XI S
cI CV 2
RI S
rV 2
XI r
sI 2
RI r
cI
rI
cI - Leads the phasor CV by90
Angles : - between sV and rV
- between rV and rI
s - between sV and sI
Long Transmission line
The line parameters are distributed uniformly over entire length . Assumption of lumped circuit analysis tails in the case of long length T.L.
١٠٤
Fig. below , shows distribution parameter line with series impedance (z) per unit length and shunt admittance (y) per unit length .
rI
rV
( Where z and y per unit length )
From Krichhoff 's voltage law :
)()()( xIxzxVxxV
)(
)()(xzI
x
xVxxV
)()()(
lim0
xzIx
xVxxVx
)9........(....................)()(
or xzIdx
xdV
١٠٥
By Krichhoff 's current law :
)()()( xxVxyxIxxI
Where )( xxVxy is the current flowing in the shunt admittance xy of the element .
)(
)()(xxyV
x
xIxxI
)(lim)()(
lim00
xxyVx
xIxxIxx
)10.......(....................)()(
or xyVdx
xdI
Differentiating eq. (9) and (10) with respect to x :
)11.(....................)()(
)()(
2
2
2
2
dx
xdVy
dx
xId
dx
xdIz
dx
xVd
Substituting values of dx
xdV )( and dx
xdI )( from eq.(9)
and (10) into eq.(11) :
)12.....(..........)()()( 2
2
2
xVxVzydx
xVd
١٠٦
)13.........(..........)()()( 2
2
2
xIxIzydx
xId
yzyz orWhere 2
- Propagation constant , it is complex quantity .
j
Kmradshiftphase
KmfactornAttenuatio
/
/Where
Linear differential equation of the type
solutioncompletitshas,
2
2
ykdz
yd
zkzk ebeay
Where a and b are constant to be evaluatedTherefore , solution of eq. (12) is :
)...(..........)( 14xx ebeaxV
Differentiating eq. (14) ,xx ebea
dx
xdV )(
and substituting the result in eq. (9) to give :
xx ebeaxIz )(
١٠٧
xx ez
be
z
axI )(or
xx e
z
zybe
z
zya
)(
/
1
//xxxx ebea
yze
yz
be
yz
a
)15(...............)(
1 xx
c
ebeaZ
Where yzZc / ohm , is called characteristic impedance , and it is complex quantity .
For lossless line cZ is called Surge impedance and
equal to CL / ohm .
For Over Head Transmission Line , 600400cZ
, and for underground cable 6040cZ
For eq. (14) and (15) , at x = 0 :
rr IxIVxV )(;)(
)(1
bacZcZ
b
cZ
arI
barV
١٠٨
2;
2cZrIrV
bcZrIrVa
xecZrIrVxecZrIrV
xV
22)(
xecZrIxerVxecZrIxerV
2222
)(16.........22 rIcZ
xexerV
xexe
xec
Zr
Ir
VxecZ
rI
rV
cZ
xI 22
1)(
)(17......22
1
rI
cZ
xexer
Vxexe
cZ
In term of hyperbolic functions , eq. (16) and (17) are:
rrc
rcr
IxVxZ
xI
IxZVxxV
)(cosh)(sinh1
)(
)(sinh)(cosh)(
……(18)
To obtain sending end values of voltage and current , we set (x) equal to (l) in eq. (18) :
١٠٩
rrc
S
rcrS
IlVlZ
I
IlZVlV
)(cosh)(sinh1
)(sinh)(cosh
……(19)
Eq. (19) can be written in matrix form :
The equivalent circuit of along line :
rI rI
rV rV
Nominal circuit Equivalent circuit
( approximately ) ( Exactly )
)20.....(..........coshsinh
1
sinhcosh
r
r
c
c
S
S
I
V
llZ
lZl
I
V
١١٠
Nominal circuit is approximate equivalent circuit , generally used for medium length T.L.
The results from nominal circuit are approximate , but the results from equivalent circuit are exact as by the long line equations .
For equivalent circuit :
ZI
ZYVV rrS
21
Compare this equation with equation (19) :
lZZ C sinh)1
lzy
llzlyz
sinhsinh/
)21(........................................sinh
l
lZZ
Where, Z = z l - Total series impedance of the line .
lZY cosh2
1)2
lZ
l
Z
lY
C
sinh
1cosh1cosh2/
l
lll
ZC
sinh
1cosh
2tanhWhere,
2tanh
1
١١١
)22.......(....................2/
2/tanh
22
l
lYY
Where Y = y l - Total shunt admittance of the line . Similar , an equivalent T circuit can be found for T.L.
Transmission efficiency : ( TL )
The ratio of receiving end power to the sending power of transmission line .
)23.....(100cos
cos)(efficiencyonTransmissi
SSS
rrTL IV
IV
Generalized Constants
In any four terminal network , the input voltage and input current can be expressed in term of output voltage and output current . T.L. is a 4-terminal network as shown :
sI rI
A B sV rV
C D 2 – port , 4 terminals network
The network should be : 1- Passive ; 2- Linear ; 3- Bilateral This condition is fully met in T.L.
١١٢
Therefore , equations ( 2,5,8,20 ) can be written in general form as :
)................. 24(
r
r
S
S
I
V
DC
BA
I
V
rrs IBVAV
rrs IDVCI ………………….(25)
The following points may be kept in mind :
1- Constants A,B,C, and D are all Phasors
DACCBBAA
;;; 2- AD
for all symmetrical line .
3- A
- Dimensionless .
B
- Ohms .
C
- Siemens ( mhos ) .
D
- Dimensionless .
4- 1 CBDA
The values of the generalized constants depend upon the particular method adopted for solving a T.L. , as shown in below table .
١١٣
Comparison of ( A,B,C,D ) constant for T.Ls :
A B C D
Short line 1
Z 0 A
Length <80Km(66Kv) ,Capacitance can be ignored , Parameters can be taken as lumped
21
ZY
Z
41
ZYY
A
Mediumline
T2
1ZY
41
ZYZ
Y A
Length 80-250Km ,Capacitance - is line to neutral per Km , Parameters can be taken as lumped ,Z- Total series
impedance of line ,Y – Total shunt admittance of line .
Long line lcosh lZc sinhl
Zc
sinh1
A
Length >250Km ,
ylYzlZ
Y
Z
y
zZ
ZYzlyll
zy
c
;
z–series impedance
per unit length .
= propagation constant . = j = Attenuation constant . = Phase constant ( rad. / unit length )
cZ = Characteristic impedance , for lossless line it is referred to as the surge impedance .
١١٤
Also , can be determined receiving end condition in term of sending end conditions :
)26(...............
S
S
r
r
I
V
AC
BD
I
V
Summary for long line :
ADlZ
C
lZBlA
Y
Z
y
zZ
ZYzlyllzyl
ylYzlZzy
c
c
c
;)(sinh1
)(sinh;)(cosh
;;
rcrS IlZVlV )(sinh)(cosh
rrc
S IlVlZ
I )(cosh)(sinh1
)sin()sinh()cos()cosh()cosh()(cosh bajbajbal )sin()cosh()cos()sinh()sinh()(sinh bajbajbal
)..........!4
)(
!2
)(1()(cosh
42
ll
l
Or
}..........
!5
)(
!3
)(){()(sinh
53
ll
ll
١١٥
:)Series( Cascade Two transmission Lines in
1SI 1rI 2SI 2rI
A1 B1 A2 B2 1SV 1rV 12SV 2rV
C1 D1 C2 D2
222111 22and11 rrSrrS IBVAVIBVAV
222111 22and11 rrSrrS IDVCIIDVCI
2
2
2
2
1
1
1
1
D2C2
B2A2and
D1C1
B1A1
r
r
S
S
r
r
S
S
I
V
I
V
I
V
I
V
2121 and SrSr IIVV
2
2
1
1
D2C2
B2A2
D1C1
B1A1
r
r
S
S
I
V
I
V
2
2
1
1
D1D2B2C1C2D1C1A2
B1D2A1B2B1C2A1A2
r
r
S
S
I
V
I
V
2
2
oo
oo
1
1
DC
BA
r
r
S
S
I
V
I
V
…………………….(27)
١١٦
:Two transmission Lines in Parallel
SI 1SI 1rI rI
A1 B1 SV rV
C1 D1
2SI 2rI
A2 B2 SV rV
C2 D2
21 SSS VVV ; 21 rrr VVV
21 SSS III ; 21 rrr III
)28(.....22and11 21 rrSrrS IBVAVIBVAV )29(.....22and11 2211 rrSrrS IDVCIIDVCI
From eq.(28) :
21 2211 rrrr IBVAIBVA
)21(2
1)(2
12)21(
1
11
12
BBIIB
IBIIB
IBIBAAV
rr
rrr
rrr
١١٧
)30..(..........21
)21(21 BB
AAVIBI rr
r
Put eq.(30) in eq.(28)
21
)21(211
BB
AAVIBBVAV rr
rS
rIBB
BBVr
BB
AABA
21
21
21
)21(11
rS IBB
BBVr
BB
BABAV
21
21
21
1221
21,Further SSS III Substituting values of 1SI and 2SI from eq. (29)
21 2211 rrrrS IDVCIDVCI )(2121 11 rrrr IIDIDVCC
r
rrr ID
BB
AAVIBDDVCC 2
21
)21(2)21(21
rrS IBB
BDDBV
BB
DDAACCI
21
2121
21
)21)(21(21
r
r
oo
oo
S
S
I
V
DC
BA
I
V
………………(31)
١١٨
Experimental Determination of Generalized Constants ( A , B , C , D ) :
1- Open circuit test : 0SI
0rI
A B
000
0
0SSS
S
S ZZI
V
0SV
C D 0rV
)0( 000 rrS IVAV
)0( 000 rrS IVCI
)32.(..........0
00
C
A
I
VZ
S
SS
2- Short circuit test : SSI
rI
SSSSSSSS
SS ZZI
V
SSV
A B 0rV
C D
)0( rrSS VIBV
)0( rrSS VIDI
)33.(..........D
B
I
VZ
SS
SSSS
١١٩
From eq. (32) and (33) :
)34.(..........1
0CDCD
CBDA
D
B
C
AZZ SSS
)35.(........../1
/ 2
0
0 ADACD
CA
ZZ
Z
SSS
S
)36(..........0
0
SSS
S
ZZ
ZA
)37(..........and CBDADA
From equations (34 , 36 and 37 ) can be
determined the constants ),,,( DCBA
.
١٢٠
.L.Power Flow and Power Circle Diagram of T
: er Circle Diagram Receiving End pow
rrs IBVAV
rrs IDVCI
………………….(38)
DACCBBAA
;;;
SSrr VVVV
;0
From eq.(38) :
B
VA
B
V
B
VAVI rSrS
r
The conjugate of rI
is :
B
VA
B
VI rS
r
The complex power at the receiving end ( The volt-amperes delivered to the load ) is given by :
rrrrr QjPIVS
١٢١
B
VA
B
VVQjP rrS
rr
2
……………..(39)
)(cos)(cos
2
B
VA
B
VVP rrS
r
)(sin)(sin
2
B
VA
B
VVQ rrS
r
…………………(40)
Where rP - Real power at receiving end .
rQ - Reactive power at receiving end .
j reactive
power axis rrr QjPS
(Var)
B
AVr2
B
VV rS
real power axis 0 (Watt)
١٢٢
rrrrr IVSS
rr QjP
rrrrrr IVjIV sincos
Var
rr IV K O r Watt
L
B
AVr2
B
VV rS
n d f (x , y)
rrrrr IVS OK
OLcos rrrr IVP
LKsin rrrr IVQ
١٢٣
Coordinates of the center of a receiving end circle :
WattrVB
A....)(x )(cos2Horizontal
VarrVB
A....)(y )(sin2Vertical
………………(41)
)..(circleendreceivingaofRadius (nk) VAB
rVSV
Units of Circle :
1- If voltages are phase to neutral in volts , P and Q ( and coordinates x , y ) are in Watts and Vars per phase.
2- If voltages are line-to-line in volts , the Watts and Vars on the diagram are total three-phase quantities .
3- If voltages are in Kilovolts from line-to-line , the coordinates given by above equation are total in MW , MVar for three-phase .
From circle diagram , maximum power is delivered if :
or
0
١٢٤
)(cos
2
.)(max B
VA
B
VVP rrS
r
df.)(max rP
( For maximum power , the load must draw a large leading current . )
If rV - constant , and SV -Variable , the following receiving-end power circles are obtained :
Q (Var) K3 Load line a K2 K1
b O P(Watt)
r
n
(x , y) 1SV 2SV 3SV
١٢٥
EX. (1) : A 3–phase , 50Hz . medium transmission line , the load at the receiving end is 75MVA at 0.8 power factor lagging with 132KV between lines . If at the sending end , the voltage is
9.65.165 KV , and the power is 68.44 MW at 0.7791 power factor lagging , find the total resistance , inductance and capacitance per phase of line .
Solution : We can be use nominal T circuit method :
SI
2/Z
2/Z
rI
CI
SV
Y
CV
rV
KVphaseVr 21.763
132/
KVVr
021.76
KVphaseVS
9.65.95
3
5.165/
KVj 5.119.94
AIr
9.361.3288.0cos1.328
101323
1075 1
3
6
Aj 9.1965.262
779.0cos5.306779.0105.1653
1044.68 1
3
6
SI
A9.315.306 Aj 46.1623.260
١٢٦
rrC IZ
VV
2
Volt9.361.3282
10021.76 3
Z
SCS IZ
VV
2
9.315.3062
9.361.3282
10021.76108.66.95 33
Z
Z
)4.1623.2609.1965.262(2
1021.7610)5.119.94( 33 jjZ
j
6328
6.31141.666.342
jZ
jZ
Therefore , the resistance per phase of line is = 28 ,
and the reactance per phase of line is = 63
Hf
X L 2.0502
63
2lineofphaseperinductancethe
C
rS
C
C
V
II
V
IY
9.361.3281.666.3410021.76
)9.1965.262()4.1623.260(3
jj
mho9010468.35.86297
35.8657.34 4
١٢٧
CX
Y1
FXf
C
X
C
C
2.11025.0502
1
2
1
1025.0104
1
4
44
EX. (2) A 3-phase , 50 Hz transmission line 160 Km long . delivers a load of 90 MW at 0.85 power factor lagging . The line voltage at the receiving end is 230 KV . The generalized circuit constants for the line are as follows :
01.9000503.0;47.772.85;3.09785.0 CBDA
Calculate :1- The sending end voltage , current , and power factor .2- Efficiency of transmission .
Solution :
Receiving end voltage / phase KVVr 8.1323
230)(
Receiving end current , AI r 4.2828.0102303
10903
6
KVVr
08.132
AI r
9.364.2828.0cos4.282 1
Sending end voltage per phase :
rrs IBVAV
9.364.28247.772.851008.1323.09785.0 3
57.4048.24060103.0130 3
١٢٨
373.156486.182766.680998.129 jj 97.163286.148274 j
KV28.6171.149 Sending end current :
rrs IDVCI
9.364.2823.09785.00108.13201.9000503.0 3
6.3632.27601.98.66 74.16483.22146.1097.65 jj 28.1548.287 j
A19.2854.326
47.3419.2828.6 S
Power factor of sending end = lagging824.047.34coscos S
Sending end power = SSS IV cos3
MW47.120824.054.326171.1493
100powerendSending
powerendReceivingontransmissiofEfficiency
%7410047.120
90
١٢٩
Discussion Questions
1- Draw the phasor diagram of a nominal -circuit of transmission line .
2- Prove that the voltage regulation (V.R) for short line is :
rV
IXIR sincosV.R
Where , I –load current , rV and cos are the receiving end voltage and power factor , R and X are resistance and reactance of line .
3- Prove that the voltage regulation (V.R) for short transmission line , unity power factor is :
rV
IRV.R
Where , I –load current , rV - receiving end voltage , R-resistance of line .
4- State the advantage of bundle conductor lines over single conductor lines .
5- What is the effect of unsymmetrical spacing of conductor in a 3-phase transmission line .
Tutorial Problems
Q1. A 3-phase , 132 KV , 50 Hz transmission line , 200 Km long has constants per phase per Km as follows : resistance = 0.26 Ω , inductive
reactance = j0.38 Ω , shunt susceptance = j 61075.2 mho.The power received is 1.8 MW at 0.8 power factor lagging , calculate : 1) The sending end power . 2) The percentage regulation.
Q2. A 3-phase load of 5 MW at a power factor of 0.9 lagging is to be transmitted over a distance of 100 Km with a receiving end voltage of 66 KV , 50 Hz . Each conductor has a resistance 0f 0.8 Ω /Km and radius of 26.1mm , the conductors have an equilateral spacing of 2 m
١٣٠
. Find the sending end voltage , current and power factor , by using :1) Nominal circuit method . 2) Nominal T circuit method .
Q3, A 3-phase transmission line , 10 Km long consists of three solid copper conductors are arranged at corner of an equilateral triangle of 0.5 m side . Load conditions at receiving end are 5 MW at 0.8 power factor lagging , 11 KV , 50 Hz . The efficiency of transmission is
90.9% and the resistivity of copper is 6107774.1 Ω cm . Calculate :
i) The sending end voltage and power factor .ii) The voltage regulation of the transmission line.
Q4. A 3-phase , 50 Hz , 100 Km long overhead transmission line has the following line constants :
Resistance per phase per Km = 0.153 Ω Inductance per phase per Km = 1.21 mH Capacitance per phase per Km = 0.00958 F
The line supplies a load of 20 MW at 0.9 power factor lagging at a line voltage of 132 KV . Calculate :
1- Sending end voltage and current .2- The voltage regulation of line .3- Efficiency of transmission .
Q5. A 3-phase , 50 Hz , 100 Km transmission line has conductors composed of 12 strands of Aluminum wound around a core of 7steel strands . Each of the aluminum and steel strands has a diameter of 0.28 cm . The resistivity and T constant for the
aluminum are given by 61085.2 Ω m at C20 , and 228respectively . The steel strands carry no current due to the skin effect . If the line conductors are placed at corners of an equilateral triangle of 2 m a side . Determine :
1- The conductor resistance per Km of the line at C402- The line inductance and capacitance . 3- The voltage and current at the sending end , if the receiving end
voltage is 132 KV .
Mechanical Design of Overhead System
: Type of line supports
The supports for an overhead line ( O.H.L) must be capable of carrying the load due to the conductors and insulators ( including the ice and wind loads on the conductors ) .The supports are of the following types :
: Poles -1 a - Wooden poles . b - Reinforced concrete poles . c – Steel pipes poles .
Poles used for high voltage (H.V) distribution and for low voltage (L.V) transmission line up to 33 KV.There are separate types of poles designed for single circuit and double circuit lines , figures below illustrate the various types of poles : FigSingle circuit pole double circuit pole
: Steel Towers -2Steel towers are extremely useful for long distance transmission lines running across open country where long spans are a decided advantage . There are separate types of towers designed for single circuit and double circuit lines , figures below illustrate the types of tower which are used for 66KV and 132 KV :Fig
Single circuit tower Double circuit tower
Figures below illustrate the types of tower which are used for voltage levels above 220 KV :Fig
:and Tension , Sag , Length Calculation of
A. Line Supported at equal levels :
Fig
d- Maximum Sag at mid span , in metres . S- length of section OP.W- Weight/unit length of conductor.l - Span ( distance between supports A and B ).L- Actual length of conductor between A and B
( AOB).
0T - Ultimate strength ( horizontal tension in the section OP at point O in Kg .
- Angle between the horizontal axis at point P with the tangent line at point P .
yX TT , - Horizontal and vertical components of tension in the section OP at point P .
BA TT , - Tension at the supporting points A and B.
dS dy
X
y
T
T
dx
dytan
dx
The part OP (S) under equilibrium :
SWT
TT
y
X
0
)1......(..........tan0T
SW
T
T
dx
dy
X
y
And for the infinitesimal part dS
222 dydxdS 22
1
dx
dy
dx
dS
2
0
1
T
SW
2
0
1
T
SW
dx
dS
2
0
1
T
SW
dSdx
2
0
0
0
1
TSW
TW
dSW
T
dx
Integrating both sides :
Asinh
0
10
T
SW
W
TX
Where , A – Constant of integration .
At X = 0 ( i.e. at point 0 ) , S = 0
0 A
0
10 sinhT
SW
W
TX
)2........(..........sinh
0
0
T
SW
W
TS
Length (L) of the conductor :
2;
2At
LS
lX
0
0
0
0
2sinh
2
2sinh
2
T
lW
W
TL
T
lW
W
TL
:followsasdrepresentebecan2
sinh0
T
lW
........!5
2!3
222sinh
5
0
3
000 T
lW
T
lW
T
lW
T
lW
.etc!52
Ignorting5
0
T
lW
!3
22
23
00
0
T
lW
T
lW
W
TL
6321!3
)3....(....................
241
20
22
T
lWlL