Callout inlet info and LP's (TYP). This slope does not correspond the roadway LP
Crystal
Callout
number suince street names are not legible on key map(TYP)
Crystal
Rectangle
Crystal
Rectangle
Crystal
Rectangle
Crystal
Rectangle
Crystal
Rectangle
Crystal
Callout
curbline
Crystal
Callout
and roadway elevations are CL
Crystal
Callout
Provide CL STA/EL (TYP)
Crystal
Text Box
All spot elevations shall be defined with roadway CL STA and offset is location does not correspond to the typical roadway section. -Supplemental FL stationing may/should be provided where FL profiles are provided (i.e.cul-de-sacs, knuckles, etc) All roadway HP's, LP's, PCR's and other roadway transitions and/or critical points as well as inlets that fall within the intersection grading detail are to be included (STA, EL, OS) and verified that they correspond to the pavement grades identified Define beginning and endings for roadway warping...for example at artificial sump inlets Ensure street names correspond throughout the construction plans. (Example: the roadways called in the intersection details and corresponding locations generally identified in the Key Map do not correspond to the Roadway/Stormsewer plan and profiles
Crystal
Text Box
Provide intersection grading details for ALL intersections depicting the roadway crown transitions to meet the through streets. (STA & EL at EOA or FL at 25' even stationing 1+25, 1+50, ....). applicable LP's and inlets need to be included within these details as well as as through street slopes, PCR's, and FLPI's. Ramp/sidewalk elevations are recommended on these details as well. (The standard midblock or similar ramp needs approx 7.5'+ in length to meet ADA grades. That also does not account for the 2%-5% slope in the tree lawns which only adds to the length. In order to meet ADA, sufficient ramp lengths need to be provided, but where tyeing into a detached sidewalk for example that would limit the ability to lengthen a ramp thus required further evaluation of the top of ramp within the confines and the elevations/slopes of the sidewalk behind the ramp. If, as typically done in residential construction, the sidewalk is poured continuously and based on the typical rise behind the curb, this makes meeting ADA not possible without requiring removal of part of the sidewalk to depress it. The information provided in the plans should allow for proper construction in the beginning and if a general detail is not sufficient to achieve this, and it is necessary that the plans provide the supplemental information. Hence the comment and the discussion at the review of the comments flowing the 1st submittal. This issue/comment has not been addressed in the resubmittal - TYP) Additional curb return information may be provided as an alternative to curb return profiles (i.e. defined spot elevations and slopes with % between elevations based on the FL distance between points) Verify assumptions made regarding drainage flow routing. Consider roadway capacity at curb returns and the impacts of the grade transitions from the typical sections (These details to represent actual pavement grades resulting from typical paving practices. The CL STA/EL are critical to define along with corresponding C&G or EOA to determining the extend and acceptable slopes of transitions to be followed in the field via blue-topping)
Crystal
Ellipse
Crystal
Text Box
?
Crystal
Cloud
Crystal
Callout
transiton to meet through street
Crystal
Cloud
Crystal
Ellipse
Crystal
Ellipse
Crystal
Callout
What kind of transition/tie-in to the ramps here is proposed
Crystal
Callout
As shown, will not meet ADA. Identify sidewalk transitions/landings that will be necessary to make this work.
Crystal
Text Box
)
Crystal
Ellipse
Crystal
Callout
1% min
Crystal
Ellipse
Crystal
Callout
Show raised intersection
Crystal
Cloud
Crystal
Callout
Right crown should be maintained until closer to the intersection
Crystal
Ellipse
Crystal
Callout
maintain 2% crown on through street.
Crystal
Callout
Label inlets, LP's, HP's, PCR's, etc. as such including STA, EL, OS
Crystal
Callout
STA:14+61.19 TFI: 5257.30 STA:16+10.56 TFI:5257.04
Crystal
Callout
STA:15+99.22 TFI: 5255.56 STA:16+10.56 TFI:5255.45
Crystal
Callout
Provide CL, R, L elevations where defining transitions (TYP)
Crystal
Ellipse
Crystal
Callout
Maintain typical crown on through street to maintain drainage. Here would be important to show c-slopes and elev as indicated for through street to demonstrate adequate drainage in VC/detail
Crystal
Callout
Where is LP and how does it correspond to the inletsd
Crystal
Text Box
This detail does not correspond to the profiles shown on Sheet PP05 - Revise
Crystal
Text Box
This detail does not correspond to the profiles shown on Sheet PP02 - Revise
Crystal
Callout
Provide CL elev & Sta (TYP). FL elevations and Stations are to correspond to CL
ccarlow
Callout
Typically don't need through street elevations other than PCR and FLPI's (if there is a cross-pan). Remove.
ccarlow
Callout
transition to meet through street
ccarlow
Cloud
ccarlow
Ellipse
ccarlow
Ellipse
ccarlow
Ellipse
ccarlow
Ellipse
ccarlow
Arrow
ccarlow
Ellipse
ccarlow
Line
ccarlow
Line
ccarlow
Line
ccarlow
Line
ccarlow
Line
ccarlow
Line
ccarlow
Line
ccarlow
Line
ccarlow
Line
ccarlow
Line
ccarlow
Line
ccarlow
Line
ccarlow
Callout
EL
ccarlow
Callout
STA/EL
ccarlow
Callout
identify CL LP
ccarlow
Callout
slopes between elev (TYP)
Page 2: Callout inlet info and LP's (TYP). This slope does not correspond … · 2015-06-25 · Callout inlet info and LP's (TYP). This slope does not correspond the roadway LP. number suince
Crystal
Cloud
Crystal
Callout
shorten transition
Crystal
Cloud
Crystal
Callout
Revise.. Reduce 2% transition length (L). Only a 1% change needed in which case 25' is plenty of distance
Crystal
Rectangle
Crystal
Rectangle
Crystal
Rectangle
Crystal
Rectangle
Crystal
Ellipse
Crystal
Callout
revise ramp & sidewalk configuration. Per previous comments, coordinate with DE on ramps.
Crystal
Ellipse
Crystal
Callout
show as continous
Crystal
Cloud
Crystal
Callout
Revise. Through street. Maintain 2% crown until Fairfax transition. Eliminate cross pan on through street
Crystal
Callout
Revise slopes (TYP)
ccarlow
Cloud
Page 3: Callout inlet info and LP's (TYP). This slope does not correspond … · 2015-06-25 · Callout inlet info and LP's (TYP). This slope does not correspond the roadway LP. number suince
ccarlow
Callout
HP STA/EL/OS
ccarlow
Callout
STA XX+XX EL XX.XX
ccarlow
Ellipse
ccarlow
Ellipse
ccarlow
Callout
Revise. Use FL, not EOA to be consistant w/in detail. If these are EOA, the % shown are incorrect.
ccarlow
Callout
ROW? Clean up
ccarlow
PolyLine
ccarlow
Callout
FL Slope % (TYP)
ccarlow
Arrow
ccarlow
Callout
provide through street grade (TYP
ccarlow
Callout
number suince street names are not legible on key map(TYP)
ccarlow
Cloud
ccarlow
Callout
Show transition from typical 2% crown to proposed
ccarlow
Callout
warping was to only occur from CL, not whole roadway. Maintain 2% min on R until transition to through street
ccarlow
Ellipse
ccarlow
Callout
why don't this points correspond to beginning of ramp wing?
ccarlow
Ellipse
ccarlow
Text Box
See 145th Ave & Forest St Comments
ccarlow
Callout
(TYP) - Provide STA/EL for all points (OS if not typ section) Provide corresponding CL STA/EL define crown grade breaks (Blue-topped in construction)
ccarlow
Ellipse
ccarlow
Ellipse
ccarlow
Rectangle
ccarlow
Callout
maintain typical 2% crown on through street
ccarlow
Rectangle
ccarlow
Callout
Intersection crown transition not provide results in grade break at PCR and ~3% grade change in roadway over ~20'. Grade warping should not exceed 1.5% in ~25'. R
ccarlow
Ellipse
ccarlow
Ellipse
ccarlow
Ellipse
ccarlow
Callout
Does not correspond to roadway plans and profiles
ccarlow
Ellipse
ccarlow
Callout
Does not correspond to roadway plans and profiles
ccarlow
Arrow
ccarlow
Text Box
1.05%
ccarlow
Ellipse
ccarlow
Callout
%does not correspond to P&P's
ccarlow
Callout
Hudson Way
ccarlow
Ellipse
ccarlow
Ellipse
ccarlow
Arrow
ccarlow
Text Box
2.62%
ccarlow
Callout
Show pavement grade transition to meet through street
ccarlow
Ellipse
ccarlow
Callout
2%
ccarlow
Text Box
~0.5%
ccarlow
Callout
STA/EL
ccarlow
Callout
CL EL
ccarlow
Text Box
PCR?/STA
ccarlow
Text Box
PCR?
ccarlow
Text Box
PCR?/STA
ccarlow
Arrow
ccarlow
Arrow
ccarlow
Arrow
ccarlow
Arrow
ccarlow
Text Box
%
ccarlow
Text Box
%
ccarlow
Text Box
%
ccarlow
Text Box
%
ccarlow
Callout
Provide FL slopes or FL profile, either one, but must provide (TYP)
Crystal
Rectangle
Page 4: Callout inlet info and LP's (TYP). This slope does not correspond … · 2015-06-25 · Callout inlet info and LP's (TYP). This slope does not correspond the roadway LP. number suince
Crystal
Rectangle
Crystal
Rectangle
Crystal
Rectangle
Crystal
Ellipse
Crystal
Callout
Why? Maintain typical 2% crown on through street. (TYP)
Crystal
Callout
2.12%
Crystal
Arrow
Crystal
Callout
1.92%
Crystal
Ellipse
Crystal
Callout
provide grading transition to meet through street. W. side 4% change in ~25' as shown. Should be more like 1%-1.5% change per every 25'
Crystal
Callout
Example: Hudson (FL+2")-(1.92%*20)=59.34 To ramp pan lip at 58.47 (6% x-slope in pan at ramps) Diff over 6' is 14% slope in front of ramp. By transitioning crown to meet through street at more reasonable rate and adjusting R & L FL to correspond, slopes like this can be greatly minimized where there are small to modest roadway grades on through streets.
Crystal
Callout
4.1% grade in ramp due to FL grade. Not going to be able to meet ADA grades on ramp
Crystal
Cloud
Crystal
Arrow
Crystal
Callout
Why is this warping affecting the R side of the roadway and why are the slopes the opposite direction than the through street? Maintain the R side of the 2% crown to the intersection CL profile clearly does not correspond to either the R nor L FL profiles. Provide the CL profile and demonstrate that it meets City criteria. (TYP)
Crystal
Ellipse
Crystal
Callout
provide through street flow arrows with associated slopes (TYP)
Crystal
Cloud
Crystal
Callout
FL LP STA 22+98.3 (L)
Crystal
Callout
Why? Does not make sense. Revise. Maintain 2% crown until intersection and/or sump transition
Crystal
Callout
~PVC (L) at 5246.79? Revise. Does not coorespond
Crystal
Callout
1.68%
Crystal
Callout
48.38
Crystal
Callout
47.83
Crystal
Callout
48.86
Crystal
Callout
47.31
Crystal
Callout
47.01
Crystal
Callout
46.81
Crystal
Callout
46.79
Crystal
Text Box
46.60
Crystal
Text Box
46.45
Crystal
Text Box
46.65
Crystal
Text Box
47.10
Crystal
Callout
2.2%
Crystal
Callout
2.08%
Crystal
Callout
1.2%
Crystal
Callout
0.8%
Crystal
Callout
0.08%
Crystal
Callout
Elevations &slopes based on calc'd CL using x-slopes and elevations provided in detail. There are some discrepancies.
Crystal
Cloud
Crystal
Callout
maintain CL and intersection transition. Do not warp L side for R side inlet sump (TYP)
Page 5: Callout inlet info and LP's (TYP). This slope does not correspond … · 2015-06-25 · Callout inlet info and LP's (TYP). This slope does not correspond the roadway LP. number suince
Crystal
Ellipse
Crystal
Callout
Standard Detail 500-22 (for raised intersections) requires a 3.33% (+/- 0.25%) change in grade between the ramps and the connecting street. This required change in grade is not provided here.
Crystal
Callout
Where is the transition to typical crown. Define.
Crystal
Callout
2% max (TYP - per detail)
Crystal
Rectangle
Crystal
Rectangle
Crystal
Rectangle
Crystal
Rectangle
Crystal
Callout
what is the TC elev difference? Clarify
Crystal
Callout
Detail does not correspond to raised intersection details
Crystal
Callout
Why is there extra concrete on these raised intersections. Revise details to correspond to Detail 500-22 for raised intersection ramps. (TYP) Curb height transition mostly within curb return. (TYP)
Crystal
Rectangle
Crystal
Rectangle
Crystal
Rectangle
Crystal
Callout
Show inlets and inlet TFI and FL at throat elevations. (TYP) per detail, inlet openings are to be only 4", not std. Type R 6". Account for this in the drainage report (TYP)
Crystal
Callout
if
Crystal
Callout
Show roadway stationing on each approach (TYP)
Crystal
Callout
Show.label inlets TYP)
Crystal
Callout
Show.label inlets TYP)
Crystal
Text Box
This detail does not correspond to plan and profile grades
Crystal
Text Box
Provide detailed grading/intersection plans for the intersection of 144th & Fairfax and for the intersection of 144th and Holly (interim and final)
ccarlow
Callout
Per city standards the grade break is supposed to be 3.33% +/- 0.25% This does not meet standards.
ccarlow
Callout
Pavement markings are missing from this leg of the intersection.
ccarlow
Callout
Pavement markings are missing from this leg of the intersection.
Page 6: Callout inlet info and LP's (TYP). This slope does not correspond … · 2015-06-25 · Callout inlet info and LP's (TYP). This slope does not correspond the roadway LP. number suince
ccarlow
Text Box
Crystal
Text Box
Elevations are to be provide at all flowline transitions. Supplemental elevations should also be provided to further demonstrate grading. All elevations are to be definitively tied down (STA/OS). Supplemental FL stationing may be provided as well The round-about and approach lane pavement is to be straight graded from inner to outter curb and gutter. Provide a typical x-section of the round-about. (A cross section is necessary for construction to identify jointing, depths, reinforcement. The truck apron associated mountable C&G should generally reflect depths and reinforcement...this is not just a median it is a round-about island and is to be design to handle the potential traffic loading of larger vehicles and trailers, Further the engineer was to coordinate with the City on the design. Neither have been done. ) Provide a separate exhibit showing turning templates in, out and through the roundabout (all legs) for a WB-50 (Not provided with CD re- submittal) Identify/define LP's, HP's, grade breaks, etc. Turn off sight triangles in details for plan clarity (TYP)
Crystal
Callout
Provide FL profiles (TYP)
Crystal
Callout
Provide jointing and slope info (TYP)
Crystal
Callout
Identify all sidewalk transitions necessary to achieve ADA/City grades on ramps. Account for 6" curb and tree lawn grades (TYP for all detached sidewalks)
Crystal
Callout
Provide round-about x-section. Define truck apron, monolithic pours, raised median cover, landscaped area, etc. Provide dimensions and minimum/maximum slopes, heights, expansion joints, sawcuts, tooled joint spacing, etc.
Crystal
Ellipse
Crystal
Callout
No grad breaks. Srate grade from meding lip to outer C&G
Crystal
Ellipse
Crystal
Callout
Maintain min pavement grades.
Crystal
Callout
adjust grades/island in circle to maintain slope away from island (circle x-slope). Cut across flows often result in pavement failures and ice issues
Crystal
Ellipse
Crystal
Text Box
Crystal
Line
Crystal
Line
Crystal
Callout
Should be draining away from island and therefore spill C&G
Crystal
Line
Crystal
Line
Crystal
Ellipse
Crystal
Callout
These elevations result in and inadequate slope & drainage. Evaluate x-slopes throughout and revise.
Crystal
Ellipse
Crystal
Ellipse
Crystal
Ellipse
Crystal
Ellipse
Crystal
Callout
maintain 6' (TYP). See previous comments
Crystal
Ellipse
Crystal
Length Measurement
6 ft
Crystal
Length Measurement
6 ft
Crystal
Callout
extend ramps to proper length given min/max slopes and tree lawn grades (TYP)
Crystal
Length Measurement
6 ft
Crystal
Length Measurement
6 ft
Crystal
Ellipse
Crystal
Callout
provide top of ramp elevations and define sidewalk lowering behind ramps to meet ADA
Crystal
Length Measurement
6 ft
Crystal
Length Measurement
6 ft
Crystal
Callout
provide truncated domes (ADA requirements do not just apply to ramps.
Crystal
Callout
maintain slopes across splitter island refuges. 2% max. Consider ice and water holding and include prevention of said issues in design. (TYP)
Crystal
Rectangle
Crystal
Callout
not a median. Design should be appropriate for truck apron/vehicle loading or round-about may need to be enlarged.
Crystal
Callout
What are these areas? What about jointing, expansion, reinforcement, depth, etc. The typical median design is not sufficient for this application.
Crystal
Callout
6' min tree lawn (TYP)
Crystal
Callout
Provide PCR STA/EL/OS at all curb returns. (TYP)
Crystal
Callout
Provide jointing and slope info
Crystal
Callout
sloped apron or mountable curb? What is this (show on x-section)
Crystal
Text Box
Elevations are at ___ unless specified otherwise. (TYP)
ccarlow
Callout
Line across travel lane is supposed to be dotted (2 ft skip with 4 ft gap)