Upload
aerwin-bautista
View
114
Download
2
Embed Size (px)
DESCRIPTION
Nulec - N-Series Automatic Circuit Recloser
Citation preview
Quick Guide to Calculation of Fault Along a LineRolando C. Garrido
Sr. Staff Engr.Research & Development
Introduction
This article aims to guide the Meralco Engineers in calculating the short circuit current when a shunt fault
occurs along a line. Shunt faults include Three-Phase (3Ø) fault, Single Line-to-Ground (SLG) fault,
Double Line-to-Ground (DLG) fault and Line-to-Line (L-L) fault. However, since the maximum fault will
occur either during a 3Ø fault or a SLG fault, depending on the grounding of the system, only these two
types of faults are discussed in this article. Procedure for the calculation is discussed through an actual
example. Data required for the calculation are presented as well as where the values for these data could
be obtained. This guide will particularly help the Engineers connected with Sales Offices in determining
the available fault current at the tapping point of a customer. Application of this guide, however, is for
radial distribution system only.
Data Requirements
1. Source Impedance (Thevenin’s Equivalent Impedance of the bus where the circuit is connected), Zb
a. Positive-Sequence Impedance, Zb1
b. Negative-Sequence Impedance, Zb2 (normally equivalent to the pos.-seq.)
c. Zero-Sequence Impedance, Zb0
The source impedance may be obtained from the “Bus Fault Data Report” being maintained by the
System Planning Office.
2. Type and size of wire of the circuit
Type and size of wire may be obtained from the Single Line Diagram or from the AM/FM system.
3. Circuit configuration (e.g. horizontal X-arm, horizontal Alley-arm, vertical, etc.)
Circuit configuration may be determined through field survey. However, it is normal for our circuit to
have a configuration that varies along the line. In most cases, it is sufficient to assume a single type of
configuration for a particular fault calculation. Together with the size of wire, the line configuration is
necessary to determine the per unit impedance per km of the line which is available from Research &
Development.
4. Location of the fault point (kM away from the bus), L
Distance of the fault point from the substation may be approximated through survey or through a
scaled Single Line Diagram.
Example:
Calculate the Three-Phase (3Ø) and Single Line-to-Ground(SLG) fault along a circuit connected to
the 34.5 kV bus of Sta. Mesa Bank #1. The fault is located 3 kms. away from the bus. The circuit is
utilizing 336.4 MCM ACSR. Assume that the circuit configuration is that of L10 (horizontal).
Solution:
Step 1. Draw the Single Line Diagram of the circuit at the fault point
Step 2. Compute for the required impedances
From the “Bus Fault Data Report” :
@ MVAbase = 100 MVA
KVbase = 34.5 kV
Zb1 = Zb2 = (0.000992 + j0.107236) p.u. = 0.10724 / 89.47 ° p.u.
Zb0 = (0.008190 + j0.227705) p.u. = 0.22785 / 87.94 ° p.u.
Based on the Line Impedance program from R&D, a circuit with 336.4 MCM ACSR wire and a
configuration of L10 has a per unit (p.u.) impedance, per km of the line of:
Z1 = (0.0159752 + j0.0343810) p.u./km
Z0 = (0.0438571 + j0.1229010) p.u./km
At the 3 kM fault point, the total impedance of the line from the bus is
ZL1 = (0.0159752 + j0.0343810) x 3
= (0.0479256 + j0.103143) p.u.
= 0.11373 / 65.08 ° p.u.
ZL0 = (0.0438571 + j0.1229010) x 3
= (0.1315713 + j0.368703) p.u.
= 0.39148 / 70.36 ° p.u.
L10, 336.4 MCM ACSR3Ø, SLG
3 kMZb1, Zb2, Zb0
Step 3. Construct the equivalent sequence networks as seen at the fault point
(+) Sequence Network:
(-) Sequence Network:
(0) Sequence Network:
Note:
In short circuit calculation, Ea1 is always assumed to be
Ea1 = 1.0 / 0 ° p.u.
+
Ea1
-
Zb0 ZL0
+
Ea0’
-
Ia0
Ia1
Zb2 ZL2
Ia2
+
Ea2’
-
Zeq2
Ia2
+
Ea2’
-
Zeq0
Ia0
+
Ea0’
-
Zb1 ZL1
+
Ea1
-
Ia1
+
Ea1’
-
Zeq1
Ia1
+
Ea1’
-
+
Ea1
-
Step 4. Connect the sequence network involve as required for each particular type of fault. Solve
for the sequence currents (positive-, negative- and zero-sequence)
For a Three-Phase (3Ø) fault, only the positive sequence is involved.
If = Ia1
Zeq1 = Zb1 + ZL1
= (0.000992 + j0.107236) + (0.0479256 + j0.103143)
= 0.0489176 + j0.210379 p.u.
= 0.215991 / 76.91 ° p.u.
Base Current, Ib is
Therefore, the 3Ø fault current is
If = 4.62982 x 1.673 = 7.75 kA
Zeq1
Ia1
+
Ea1’
-
For a Single Line-to-Ground (SLG) fault, all the three sequence networks are involved and are
connected in series.
If = Ia1 + Ia2 + Ia0
= 3Ia1 = 3Ia2 = 3Ia0 ( because Ia1 = Ia2 = Ia0 at the fault point )
Normally, however, the fault impedance is assumed to be zero, unless you have a given value.
If = 3Ia1 = 3(0.95735 / -76.85 °)
= 2.87206 / -76.85 ° p.u.
If = 2.87206 x 1.673 = 4.806 kA
For a more detailed study of fault calculation, you may read the references provided below.
3Zf
Zeq1
Zeq2
Zeq0
+
Ea1
-
Ia1
Ia2
Ia0
Zf - Fault Impedance
Reference:
1. Analysis of Faulted Power Systems
Paul M. Anderson
2. Elements of Power System Analysis
William D. Stevenson, Jr.
3. Electrical Transmission and Distribution Reference Book
Westinghouse Electric Corporation