Fault level at any given point of the Electric Power Supply Network is the maximum current that would flow in case of a short circuit fault at that point.

The circuit breaker should be capable of Breaking & Making current as per their ratings & should also have Rated short time capacity. So, for proper selection of circuit breaker & other switchgear components, Knowledge of current during normal & abnormal conditions is necessary.

Page 3: Fault Level Calculation

The design of machines, bus bars, isolators, circuit breaker etc. is based on the consideration of Normal & Short Circuit Currents.

The Protective Relaying Schemes can be selected only after ascertaining the fault levels and normal currents at various locations. Fault calculations are also necessary for System Design, stability considerations, selection of Layout etc.

Page 4: Fault Level Calculation

Purpose of Fault Level Calculations:- a) For selecting short circuit protective

devices of adequate short circuit Breaking capacity.

b) For selecting circuit breakers and

switches of Adequate short circuit Making capacity.

c) for selecting Bus Bars, cable and switchgear, designed to withstand thermal and mechanical stresses because of short circuit.

Page 5: Fault Level Calculation

Types of Short Circuits:-

1) L-E (Single Line to Earth)

2) L-L ( Line to Line)

3) L-L-E ( Line to Line to Earth)

4) L-L-L ( Three Phase)

Page 6: Fault Level Calculation

In Fault Calculations, many assumptions are made for simplifying the calculations.

Resistances are neglected when their values are negligible as compared to the Reactance.

Capacitance is neglected. Machine reactance are assumed to be constants.

Saturation effects are neglected.

Page 7: Fault Level Calculation

Generated voltages are assumed to be constant. Contribution of Shunt capacitor banks are neglected.

Impedences of BusBar, Switchgear, C.Ts are neglected.

Transformer tap is in the main position.

Short circuit current waveform is a pure Sine wave.

Page 8: Fault Level Calculation

Resistance of short transmission line are neglected.

Fault calculations are always done assuming Three Phase bolted short circuit fault.

Page 9: Fault Level Calculation

Procedure for Fault Level Calculation.

Fault calculations begin with drawing Single line or One line diagram of the given network with Ratings of all the transformers & Generators in the network.

Suitable Base MVA is chosen. For ex. 100 MVA.

Per Unit reactance (impedence) is calculated for every Transformer & Generator in the given network by using-

Page 10: Fault Level Calculation

Formula P.u reactance = [(% impedence)/100] x [Base MVA/Actual MVA]

Then redraw the network putting the P.u reactance values.

Calculate the Equivalent reactance for the for the network as seen from the source to the fault point.

Page 11: Fault Level Calculation

Then, Calculate Fault MVA using formula-

Fault MVA= Base MVA/ Eq. Impedence

Calculate Fault Current using formula= Fault Current =

Fault MVA / (1.732x Phase to Phase Voltage at the fault point)

Page 12: Fault Level Calculation
Page 13: Fault Level Calculation
Page 14: Fault Level Calculation
Page 15: Fault Level Calculation
Page 16: Fault Level Calculation
Page 17: Fault Level Calculation
Page 18: Fault Level Calculation
Page 19: Fault Level Calculation
Page 20: Fault Level Calculation
Page 21: Fault Level Calculation
Page 22: Fault Level Calculation
Page 23: Fault Level Calculation
Page 24: Fault Level Calculation
Page 25: Fault Level Calculation
Page 26: Fault Level Calculation
Page 27: Fault Level Calculation
Page 28: Fault Level Calculation
Page 29: Fault Level Calculation
Page 30: Fault Level Calculation
Page 31: Fault Level Calculation
Page 32: Fault Level Calculation

Current Limiting Reactors:-

Current Limiting Reactors ( Series Reactors) are inserted in series with the line, to limit the current flow in the event of a short Circuit & thereby, bring down the fault level. The current Limiting Reactors are also called Series Reactors.

A current Limiting Reactor is an inductive coil having a large inductive reactance (wL) and is used for limiting short-circuit currents to be interrupted by circuit breaker.

Page 33: Fault Level Calculation
Page 34: Fault Level Calculation

If X is the reactance of a circuit , E is the voltage then by neglecting the resistance , the short circuit current is given by Isc= E / X.

Therefore, by increasing the series reactance of the system, the short circuit current can be decreased.

The short circuit current depends upon the generating capacity, voltage at the fault point and the total reactance between the generator and the fault point.

Page 35: Fault Level Calculation

The circuit breaker should have enough breaking current capacity such that the fault current are less than the breaking current capacity. IF the fault currents are beyond the capacity of the circuit breaker, the circuit breaker may not interrupt the fault current.

Then the fault current should be limited by some means so that the existing circuit breaker can be used safely.

Page 36: Fault Level Calculation

Also when the system is extended by adding more generating stations, the Fault current to be interrupted by the same circuit breaker will be greater than before.

In these cases, the circuit breaker should

be replaced by another of higher breaking current capacity or the fault current can be limited by the means of REACTORS.

The current limiting reactors are useful in limiting short circuit current so that the circuit breaker can interrupt them.

Page 37: Fault Level Calculation

1) Reactors limit the Short Circuit Current.

2) Reactors are used in the systems when extensions are made and the circuit breaker breaking current capacities become inadequate.

3) Reactors are employed in Large Systems so as to limit the short circuit MVA to match with the breaking current capacity of the circuit breaker.

Page 38: Fault Level Calculation

Location of Series Reactor:-

Generator Reactors- Reactors are inserted between the

generator and the generator bus. The high reactance is provided to safeguard the generators in case of dead three phase short circuits at its terminals.

When new generators are installed , generator reactors can be added to the old generators.

Page 39: Fault Level Calculation

GENERATOR REACTOR:-

Page 40: Fault Level Calculation

Feeder Reactors- The reactors in this case are connected

in series with the feeders. The advantage is that the voltage of the bus does not drop substantially in the event of fault on the feeder.

The Busbar Reactor-

The busbar reactor is placed between two sections of busbar.

Page 41: Fault Level Calculation

BUSBAR REACTOR-

Page 42: Fault Level Calculation

FEEDER REACTORS-

Page 43: Fault Level Calculation

QUESTIONS:-1) Why Fault Calculation is required?2) What is meant by Breaking Current

capacity & Making Current Capacity of Circuit Breaker?

3) What is the formula for Calculating Fault MVA?

4) What is the Formula for Calculating Fault Current?

5) What should be used to decrease Fault Level at any point?