Upload
john-arllan-diestro
View
216
Download
0
Embed Size (px)
Citation preview
7/29/2019 C158-EO
1/1
Technical Information Sheet C158-EO
Novaris Pty Ltd ABN: 33 065 427 23272 Browns Road, Kingston, TAS. 7050 TEL: +61 3 6229 7233AUSTRALIA FAX: +61 3 6229 9245
Copyright 2000 Novaris E-mail: [email protected]
COAXIAL SURGE PROTECTORS - HIGH POWER
Lightning strikes to antenna masts, towers and otherstructures induce large voltages into coaxial antennafeeders. The Novaris series of coaxial feeder protectors
provide protection for high power transmitters with largediameter coaxial feeders.
The protectors utilise an in built adjustable spark gap with a
patented optical arc detector. The arc detector provides a
signal via an inexpensive optical fibre to provide amomentary transmitter shutdown.
Thus the traditional problem of RF energy maintaining the
arc is overcome and a closer tolerance spark gap can bemaintained to provide lower spark over voltage for
enhanced protection for solid-state transmitters. Options forall EIA flange type connectors and solid line are available.
Applications
MF Broadcasting
HF Broadcasting
FM Broadcasting
Television
Defence Communications HF Radar
Features & Benefits
100kA surge rating
50kW power capability
50ohm impedance
26dB return loss
< 0.1dB insertion loss
Patented optical arc sensor
Momentary TX shutdown to extinguish arc
Description
Novaris high power coaxial feeder protectors consist of ashort length of solid coaxial feeder fitted with EIA flange
connectors. The feeder section contains a calibrated andadjustable spark gap electrically connected to the cable
outer. The gap is determined by the transmit power level -the gap must not arc under maximum peak power
conditions.
The arc detector is integral with the feeder section. A
photodiode detects the presence of an arc and signals via aninexpensive optical fibre to the transmitter interface
circuitry. The optical fibre eliminates any possibility ofinduction within the building due to differential earthpotentials. The interface circuitry provides a momentary
shutdown signal to the transmitter.
The major benefit of this arrangement is that the gap settingcan be minimised, and hence the sparkover voltage
minimised to provide enhanced protection for thetransmitter. With conventional spark gaps the gap settingmust be wide enough to ensure that the arc is not sustained
by RF energy.
The protector may be installed in pressurised or non-pressurised systems. The arcing chamber is isolated from
the airflow so that possible arcing products do notcontaminate the feeder. Air is bypassed through the hollowinner conductor to isolate the arcing chamber.
This product is protected by patent.
Specifications
Description: Coaxial surge protector with optical arc sensor
Surge Rating: 100kA peak impulse current for 8/20us impulse
Surge Element: Spark gap, gap setting 2mm/10kW
Spark over voltage: 2.6kV for a 2mm gap
Power Rating: > 50kW, limited only by coaxial cable powercapability
Characteristic
Impedance: 50 ohms
Insertion loss: < 0.1dB to 500MHz, < 0.2dB to 1GHz (gap
setting 1mm)
Return loss: > 26dB to 500MHz, > 20dB to 1GHz (gap
setting 1mm)
Arc Sensor: Optical detector utilising photodiode, feedingtransmitter interface electronics to provide
momentary shutdown.
Power Arc sensor 12V DC @ 35mA.Requirements: Power supply included.
Transmission Arc detector signal fed to
medium: transmitter via optical fibre to eliminateinduced transients in building.
Options
Cat No. Connectors
C158-EO 1 5/8 EIA / EIA flange connectorC318-EO 3 1/8 EIA / EIA flange connector