Busbar Clearance

Embed Size (px)

Citation preview

Appendices

EXCEL POWER SWITCHGEAR CHENNAI-32 BUSBAR CLEARANCE FOR 11KVSL

No ITEM REQUIREMENT

01C Spacing between the Bus bars i.e. live part to live part spacing(PHASE TO PHASE)120 (mm)

Minimum

02Spacing between the Bus bars and earth (i.e) live part to earth spacing(PHASE TO EARTH)120 (mm)

Minimum

BUSBAR CLEARANCE FOR 11KV WITH BBTM HEAT SHRINKABLE SLEEVESL

No ITEM REQUIREMENT

01C Spacing between the Bus bars i.e. live part to live part spacing(PHASE TO PHASE)65 (mm)

Minimum

02Spacing between the Bus bars and earth (i.e) live part to earth spacing(PHASE TO EARTH)75 (mm)

Minimum

BUSBAR CLEARANCE FOR 33KV

SL

No ITEM REQUIREMENT

01C Spacing between the Bus bars i.e. live part to live part spacing(PHASE TO PHASE)320 (mm)

Minimum

02Spacing between the Bus bars and earth (i.e) live part to earth spacing(PHASE TO EARTH)320 (mm)

Minimum

BUSBAR CLEARANCE FOR 33KV WITH BBTM HEAT SHRINKABLE SLEEVESL

No ITEM REQUIREMENT

01C Spacing between the Bus bars i.e. live part to live part spacing(PHASE TO PHASE)200 (mm)

Minimum

02Spacing between the Bus bars and earth (i.e) live part to earth spacing(PHASE TO EARTH)285 (mm)

Minimum

Ref: IEC 71-2