building services safety methods

Embed Size (px)

Citation preview

  • 7/30/2019 building services safety methods

    1/45

    SAFETY MEASURES

  • 7/30/2019 building services safety methods

    2/45

    WHAT IS A STANDARD ?

    A standard is an agreed, repeatable way of doing something.

    It is a published document that contains a technical

    specification or other precise criteria designed to be used

    consistently as a rule, guideline, or definition. Standards help

    to make life simpler and to increase the reliability and the

    effectiveness of many goods and services we use. Standards

    are created by bringing together the experience and expertise

    of all interested parties such as the producers, sellers, buyers,

    users and of a particular material, product, process or service.

  • 7/30/2019 building services safety methods

    3/45

    GENERATION OF ELECTRICITY

    The various sources of electricity are :

    Solar power

    Wind power

    Tidal power

    Thermal energy

    Nuclear energy

    Hydroelectric energy

    Gas turbine

  • 7/30/2019 building services safety methods

    4/45

    Solar energy

    Solar power is the conversion of sunlight into electricity,

    either directly using photovoltaic cells (PV), or indirectly

    using concentrated solar power (CSP). CSP systems use

    lenses or mirrors and tracking systems to focus a large area of

    sunlight into a small beam. Photovoltaic cell converts light

    into electric current using the photoelectric effect.

    Solar power plant

    In North America

  • 7/30/2019 building services safety methods

    5/45

  • 7/30/2019 building services safety methods

    6/45

    SAFETY FEATURES

    All solar electric panels should have durable connectors on

    the module. The connectors should be sturdy, and the

    method of attaching the wire should be simple, yet provide

    a secure connection. Most modules have sealed junction boxes to protect the

    connections. So before buying a solar electric panel, look at

    the junction box and see if it is easy to make the connections. A switch or circuit breaker as part of a combiner box should

    be installed to isolate the PV array during maintenance.

  • 7/30/2019 building services safety methods

    7/45

    circuit breakers are normally installed to isolate each load.

    Fuses are used to protect any current carrying conductor.

    Fuses and cables in the array circuit should be sized to carry

    the maximum current that could be produced by short-term

    "cloud focusing" of the sunlight--up to 1.5 times the short

    circuit current at 1,000 w/m2 irradiance.

    Slow-blow fuses or PV breakers are recommended. Only

    fuses rated for dc current should be used. (Auto-motive

    fuses should not be used.)

    All metal in a solar panel array should be grounded to help

    protect the array against lightning surges, and The

    negative conductor is also grounded .

  • 7/30/2019 building services safety methods

    8/45

    wind power

    Wind turbines convert the kinetic energy in the wind intomechanical power . A generator converts this mechanical

    power into electricity to power homes, businesses, and

    schools.Top 10 countries by nameplate wind power capacity (2010)

    Country Wind power capacity (MW)

    China 44,733

    United States 40,180

    Germany 27,215

    Spain 20,676

    India 13,066

    Italy 5,797

    France 5,660

    United Kingdom 5,204

    Canada 4,008

  • 7/30/2019 building services safety methods

    9/45

  • 7/30/2019 building services safety methods

    10/45

    Safety features

    Dual disc brakes When the turbine control system detects

    any fault condition such as excess wind or a grid power loss,

    the disc braking system activates, shutting the turbine down

    completely until the control system instructs the brakes torelease and the turbine to re-start.

    Aerodynamic stalling Advanced blade designs that shed

    wind in excessive wind conditions in order to protect theturbine from damage.

    Advanced computer control system Each turbine is

  • 7/30/2019 building services safety methods

    11/45

    controlled by an on board computer system and the proprietary

    software application which manages all operational aspects of theturbine such as power output (select units), cut-in, cut-out, fault

    detection and pneumatic braking.

  • 7/30/2019 building services safety methods

    12/45

    Tidal power

    It can be extracted from Moon-gravity-powered tides by

    locating a water turbine in a tidal current, or by building

    impoundment pond dams that admit-or-release water through

    a turbine. The turbine can turn an electrical generator, or a gascompressor, that can then store energy until needed.

    In order for this to work well, you need large increases in tides.

    An increase of at least 16 feet between low tide to high tide isneeded.

  • 7/30/2019 building services safety methods

    13/45

  • 7/30/2019 building services safety methods

    14/45

    Thermal power

    . Water is heated, turns into steam and spins a steam turbinewhich drives an electrical generator which then generates

    electricity.

  • 7/30/2019 building services safety methods

    15/45

  • 7/30/2019 building services safety methods

    16/45

    on.

  • 7/30/2019 building services safety methods

    17/45

    Safety features

    Mechanical safety valve/system

    Process alarm operator action.

    Safety instrumented control system.

    Burner management system.

    Mitigation devices.

    Turbine protection.

    Interlock and protection devices.

  • 7/30/2019 building services safety methods

    18/45

    NUCLEAR POWERThis energy is made by fusion or fission .

    It is produced in the reactor of a nuclear power station.The energy turns water into steam, which drives a turbine that powers a generator

    . Nuclear power produces lots of energy and can be made to power major cities.

    This energy, unlike other sources, produces lots of radioactive waste. If that waste

    gets released, it could cause devastation to a large area. In addition, it warms itswaste water, so some fish, such as trout, cannot live in warm water.

  • 7/30/2019 building services safety methods

    19/45

    Safety Objectives

    Nuclear power plants are designed with two principal safety objectives in mind:

    1. To contain fission products to prevent offsite health effects.

    2. To ensure that heat generated by the reactor, including heat generated by the

    decay of fission products after reactor shutdown, is removed.

    The defence-in-depth approach ensures that any release of hazardous amounts of

    radioactive materials will be extremely unlikely.

    This approach uses three barriers to prevent the release of fission products from thereactor core to the environment. These consist of:

    1. Fuel rods (fuel pellet and fuel cladding)

    2. Reactor vessel and primary coolant system

    3. Containment

    The first barrier designed to prevent an inadvertent release of radioactive material

    from the reactor core is the nuclear fuel rod itself.

    During normal operations, about 99 percent of all fission products remain trapped

    within the fuel's structure very near the point at which they were generated by

    fission.

  • 7/30/2019 building services safety methods

    20/45

    The first barrier designed to prevent an inadvertent release of radioactive

    material from the reactor core is the nuclear fuel rod itself.

    During normal operations, about 99 percent of all fission products remain

    trapped within the fuel's structure very near the point at which they weregenerated by fission.

  • 7/30/2019 building services safety methods

    21/45

    Hydroelectric power

    Hydroelectric energy is produced when water falls from a high place to a low

    place.

    A hydroelectric power station contains a turbine driven by falling water from a

    dam.

    The turbine drives the generator.

    This form of energy produces little pollution; in addition, it does not ruin the

    water. The water still can be used for other purposes.

    Hydroelectric power does not cost any more than fossil fuels.

    Another advantage is that there are a lot of lakes or rivers where a dam can be

    built to produce energy.

    Another disadvantage is that when a dam is built, a huge area is flooded to make

    a lake, so the water displaces the people and animals living there.

  • 7/30/2019 building services safety methods

    22/45

  • 7/30/2019 building services safety methods

    23/45

    SUBSTATION

    A substation is a part of an electrical generation, transmission, and distribution

    system. Substations transform voltage from high to low, or the reverse, or perform

    any of several other important functions. Electric power may flow through several

    substations between generating plant and consumer, and its voltage may change in

    several steps.

    Substations may be owned and operated by a transmission or generation electrical

    utility, or may be owned by a large industrial or commercial customer.

    A substation may include transformers to change voltage levels between high

    transmission voltages and lower distribution voltages, or at the interconnection of two

    different transmission voltages. The word substation comes from the days before the

    distribution system became a grid

  • 7/30/2019 building services safety methods

    24/45

    Elements of a substation

    A:Primary power lines' side B:Secondary power lines' side1.Primary power lines 2.Ground wire 3.Overhead lines 4.Transformer for

    measurement of electric voltage 5.Disconnect switch 6.Circuit breaker 7.Current

    transformer 8.Lightning arrester 9.Main transformer 10.Control building

    11.Security fence 12.Secondary power lines

  • 7/30/2019 building services safety methods

    25/45

    MATERIALS USED IN A SUB-STATION

    Poles are generally constructed with IRON(galvanized), CAST IRON ,CEMENT.

    SILICA GEL GRATER is connected to conservated tank or transformed tank

    where oil is stored.

    The oil stored in tanks releases moisture , this creates short circuit to prevent

    this

    SILICA GEL GRATER is used.

    Lightning arresters (LAS) are provided to avoid short circuit from lightning andthunders.

    Oil sacred breakers

    Vaccum type breakers

    Relays

  • 7/30/2019 building services safety methods

    26/45

    SAFETY MEASURES

    Sprinkler system is provided

    Sand buckets are used

    Fire stations should be constructed if the substation capacity is high.

    A gap of 20ft is provided between the machines.

    Alarm panels are provided.

  • 7/30/2019 building services safety methods

    27/45

    SUBSTATION SAFETY FEATURES

    The installation should be carried out in accordance with approved drawings.

    Phase-to-phase and phase to earth clearances are provided as required.

    All equipment's are efficiently earthed and properly connected to the required

    number of earth electrodes.The required ground clearance to live terminals should be provided.

    Suitable fencing should be provided with gate with lockable arrangements.

    The required number of caution boards, fire fighting equipment's, operating rods,

    rubber mats, should be kept in sub station.

    In case of indoor sub station, sufficient ventilation and draining arrangements

    should be made.All cable trenches should be provided with non-inflammable covers.

    Free accessibility should be provided for all equipments for normal operation.

  • 7/30/2019 building services safety methods

    28/45

  • 7/30/2019 building services safety methods

    29/45

    All name plates should be fixed and the equipment's should be fully painted.

    All construction materials and temporary connections should be removed.

    Oil-level, bus bar tightness, transformer tap position, should be in order.

    Earth pipe troughs and cover slabs are provided for earth electrodes/ earth pits and

    the neutral and LA earth pits should be marked for easy identification.Earth electrodes should be of GI pipes CI pipes or copper plates. For earth

    connections, brass bolts and nuts with lead washers are provided in the pipe/plates

    Earth pipe troughs and oil sumps/pits are free from rubbish and dirt and stone jelly

    and the earth connections should be visible and easily accessible.

    HT and LT panels are switch gears are all vermin and damp proof and all unused

    openings or holds should be blocked properly.

    h h b b h ld h h d

  • 7/30/2019 building services safety methods

    30/45

    The earth busbars should have tight connections and corrosionfree joint surfaces.Operating handle of protective device should be provided at anaccessible height from ground.Adequate headroom should be available in the transformerroom for easy topping up of oil, maintenance etc.Safety devices, horizontal and vertical barriers, busbarcovers/shrouds, automatic safety shutters/doors interlock,

    handle interlock should be safe and reliable in operation of allpanels and cubicles.Clearances in the front, rear and the sides of the main HV, MVand sub switch boards should be adequate.

    The switches should operate freely.Insulators should be free from cracks, should be clean.In transformers, there should not be any oil leak.

  • 7/30/2019 building services safety methods

    31/45

    Connections to bushing in transformers for tightness and good contact.

    Bushings should be free from cracks and should be clean.

    Accessories of transformers like breathers, vent pipe, Buchholz relay should be in

    order.

    Connections to gas relay in transformers should be in order.

    Oil and winding temperature should be set for specific requirements in transformers.

    In case of cable cellars, adequate arrangements to pump out water that has entered

    due to seepage or other reasons.

    All incoming and outgoing circuits of HV and MV panels should be clearly labeled for

    identifications.

    No cable should be damaged.

    There should be adequate clearance around the equipment installed.

    Cable terminations should be proper.

  • 7/30/2019 building services safety methods

    32/45

    LIST OF STANDARDS

    IS NO: 8270(PART 1: 1976)

    1885 (PART 16/SEC3) 1967

    (PART 17): 1979

    TITLE: Guide for preparation

    of diagrams, chartsand tables for electrotechnology: part 1

    definitions andclassifications.

    Electro technicalvocabulary: lighting,section 3 lamps and

    auxiliary apparatus. Switch gear and

    control gear.

    (PART 32) 1993 El t i l bl

  • 7/30/2019 building services safety methods

    33/45

    (PART 32): 1993

    (PART 78): 1993

    12032

    (PART 6 ): 1987

    (PART 7 ): 1987

    (2) 7752 (PART 1);1975

    Electrical cables

    Generation,transmission anddistribution of electricity-General

    Graphical symbols fordiagrams in the field ofelectro technology.

    Protection andconversion of electrical

    energy. Switchgear , control

    gear and protectivedevices.

    Guide for improvementof power factor inconsumer installation:Part 1 low and mediumsupply voltages.

  • 7/30/2019 building services safety methods

    34/45

    3) 5216

    (PART 1):1982

    (PART 2): 1982

    (4) 10118 (PART 2): 1982

    (5) 1646 :1997

    Recommendations onsafety procedures andpractices in electrical work.

    General

    Life saving techniques

    Code of practice forselection, installation andmaintenance of switchgearand control gear: Part 2selection.

    Code of practice for firesafety buildings(general):Electrical installations

  • 7/30/2019 building services safety methods

    35/45

    (6) 732:1989

    1255:1983

    (7)13947:1993

    (8)2148:1981

    (9)5578:1985

    Code of practice forelectrical wiringinstallations.

    Code of practice forinstallation andmaintenance of power

    cables (up to and including33 kV rating)

    Specification for lowvoltage switch gear andcontrol gear.

    Specification for flame

    proof enclosures ofelectrical apparatus.

    Guide for marking ofinsulated conductors.

  • 7/30/2019 building services safety methods

    36/45

    (10) 1777:1978

    2206

    (part 1):1984

    (part 2):1976 3287:1965

    3528:1966

    4012:1967

    4013:1967

    Industrial luminaire withmetal reflectors (1 R)

    Flame proof electriclighting fittings.

    Well glass and bulk headtypes(1R)

    Fittings using glass tubes.

    Industrial lighting fittingswith plastic reflectors.

    Water proof electriclighting fittings

    Specification for watertightelectric lighting fittings.

    Dust-tight electric lightingfittings

  • 7/30/2019 building services safety methods

    37/45

    5077:1969 10322 (par 5/sec 5): 1987

    (11) 8828:1996

    13947

    (part 1):1993

    (Part 2 ):1993

    (Part 3) : 1993

    Decorative lighting out fits. Luminaires: part 5 particular

    requirements, section 5 floodlights.

    Electrical accessories-circuitbreakers for over current

    protection for household andsimilar installations

    Specification for low voltageswitch gear and control gear.

    General rules

    Circuit breakers

    Switches, disconnectors,

    swich disconnectors and fusecombination units

  • 7/30/2019 building services safety methods

    38/45

    (part 4/sec 1): 1993

    (part 5/ sec 1):1993

    (12) 3961

    (part 1): 1967

    (part 2): 1967

    (part 3): 1968

    Contactors and motor-starters sec 1 electro-technical contactors andmotor starters

    Control circuit devices andswitching elements, sec 1

    electro-technical controlcircuit devices.

    Recommended currentratings for cables

    Paper insulated ledsheathed cables.

    PVC insulated and PVCsheathed heavy dutycables.

    Rubber insulated cables

  • 7/30/2019 building services safety methods

    39/45

    (13) 2086:1993

    13703 (part 1): 1993

    (14) 2672:1996

    4347:1967

    6665:1972

    8030:1976

    Specification for carriersand basis used in re wireable type electrical fusesfor voltages up to 650V

    LV fuses for voltages notexceeding 1000V ac or

    1500 dc : part 1 generalrequirements

    Code of practice for librarylighting

    Code for practice forhospital lighting.

    Code of practice forindustrial lighting

    Specification for luminairesfor hospitals

  • 7/30/2019 building services safety methods

    40/45

    (15) 732:1989

    (16) 4648 : 1968

    (17) 900: 1992

    (18) 2412 : 19975

    (19) 2667 : 1988

    3419 : 1989

    9537

    Code of practice for electricalwiring installations (3 R)

    Guide for electrical layout inresidential buildings.

    Code of practice forinstallation and maintenance

    of induction motors.(2 R) Link clips for electrical wiring(1 R)

    Fittings for rigid steel conduitsfor electrical wiring (1 R)

    Fittings for rigid non metallicconduits (2 R)

    Conduits for electricalinstallations

  • 7/30/2019 building services safety methods

    41/45

    (part 1) : 1980 (part 2) : 1981

    (part 3) : 1983

    14772 : 2000

    (20) 1913 (part 1) : 1978

    (21) 1258 : 1987

    (22) 148 : 1978

    General requirements Rigid steel conduits

    Rigid plain conduits ofinsulating materials

    Specification for accessoriesfor house hold and similar

    fixed electrical installations General and safety

    requirements for luminaires :part 1 tubular florescentlamps (2 R)

    Bayonet lamp holders (3 R)

    Tungsten filament general

    service electrical lamps (3 R)

  • 7/30/2019 building services safety methods

    42/45

    1534 (part 1) : 1977

    1569 : 1976

    2215 : 1983

    2418

    (part 1) : 1977

    Ballasts for florescentlamps : part 1 for switchstart circuits (2 R)

    Capacitors for usingtubular florescent highpressure mercury and low

    pressure sodium vapourdischarge lamp circuit. (1R)

    Specification for startersfor florescent lamps (3 R)

    Specification for tubular

    florescent lamps forgeneral lighting service

    Requirements and tests (1R)

  • 7/30/2019 building services safety methods

    43/45

    (part 2) : 1977

    (part 3) : 1977

    (part 4) : 1977

    3323 : 1980

    3324 : 1982

    9900

    (part 1) : 1981

    Standard lamp data sheets (1R)

    Dimensions of G5 and G13ic-pin caps (1 R)

    Go and no-go gauges for G5and G13 ic-pins caps (1 R)

    Bi-pin lamp holders for tubularflorescent lamps (1 R)

    Holders for starters for tubularflorescent lamps (1 R)

    Basic environmental testingprocedures for electronic andelectrical Items

    General

  • 7/30/2019 building services safety methods

    44/45

    (part 2) : 1981 (part 3) : 1981

    (part 4) : 1981

    (23) 374:1979

    (24) 3043 : 1987

    (25) 8623 (part 1): 1993

    (26) 10028 (part 2) : 1981

    Cold test Dry heat test

    Damp test (steady state)

    Electric ceiling type fans andregulators (3 R)

    Code of practice for earthing

    Specification for low voltageswitch gear and control gearassembles. Part 1requirements for type testedand partially type testedassemblies (1 R)

    Code of practice for selection,

    installation, maintenance oftransformers : part 2installation

  • 7/30/2019 building services safety methods

    45/45

    11353 : 1985

    (27) 309 : 1989

    Guide for uniform

    system of marking

    and identification ofconductors and

    apparatus terminals

    Code of practice for

    protection ofbuildings and allied

    structures against

    lighting (2 R)