bs241it

Embed Size (px)

Citation preview

  • 8/12/2019 bs241it

    1/130

    Installation Test

    Base Transceiver Station Equipment

    ITMN:BTSE BS-241 / 241 II

    A30808-X3247-M357-3-7630

  • 8/12/2019 bs241it

    2/130

    Installation TestBase Transceiver Station Equipment

    2 A30808-X3247-M357-3-7630

    ITMN:BTSE BS-241 / 241 II

    f Important Notice on Product SafetyDANGER - RISK OF ELECTRICAL SHOCK OR DEATH - FOLLOW ALL INSTALLATION INSTRUCTIONS.

    The system complies with the standard EN 60950 / IEC 60950. All equipment connected to the system must

    comply with the applicable safety standards.

    Hazardous voltages are present at the AC power supply lines in this electrical equipment. Some components may

    also have high operating temperatures.

    Failure to observe and follow all installation and safety instructions can result in serious personal injury

    or property damage.

    Therefore, only trained and qualified personnel may install and maintain the system.

    The same text in German:

    Wichtiger Hinweis zur Produktsicherheit

    LEBENSGEFAHR - BEACHTEN SIE ALLE INSTALLATIONSHINWEISE.

    Das System entspricht den Anforderungen der EN 60950 / IEC 60950. Alle an das System angeschlossenen

    Gerte mssen die zutreffenden Sicherheitsbestimmungen erfllen.

    In diesen Anlagen stehen die Netzversorgungsleitungen unter gefhrlicher Spannung. Einige Komponenten

    knnen auch eine hohe Betriebstemperatur aufweisen.

    Nichtbeachtung der Installations- und Sicherheitshinweise kann zu schweren Krperverletzungen oder

    Sachschden fhren.

    Deshalb darf nur geschultes und qualifiziertes Personal das System installieren und warten.

    Caution:

    This equipment has been tested and found to comply with EN 301489. Its class of conformity is defined in tableA30808-X3247-X910-*-7618, which is shipped with each product. This class also corresponds to the limits for a

    Class A digital device, pursuant to part 15 of the FCC Rules.

    These limits are designed to provide reasonable protection against harmful interference when the equipment is

    operated in a commercial environment.

    This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accor-

    dance with the relevant standards referenced in the manual Guide to Documentation, may cause harmful inter-

    ference to radio communications.

    For system installations it is strictly required to choose all installation sites according to national and local require-

    ments concerning construction rules and static load capacities of buildings and roofs.

    For all sites, in particular in residential areas it is mandatory to observe all respectively applicable electromagnetic

    field / force (EMF) limits. Otherwise harmful personal interference is possible.

    Trademarks:

    All designations used in this document can be trademarks, the use of which by third parties for their own purposes

    could violate the rights of their owners.

    Copyright (C) Siemens AG 2005.

    Issued by the Communications Group

    Hofmannstrae 51

    D-81359 Mnchen

    Technical modifications possible.

    Technical specifications and features are binding only insofar asthey are specifically and expressly agreed upon in a written contract.

  • 8/12/2019 bs241it

    3/130

    A30808-X3247-M357-3-7630 3

    Installation TestBase Transceiver Station Equipment

    ITMN:BTSE BS-241 / 241 II

    Reason for Update

    Summary:

    Third Edition for Release BR 8.0

    Details:

    Chapter/Section Reason for Update

    1.4.6 Revised tables.

    Issue HistoryIssue

    Number

    Date of Issue Reason for Update

    1 01/2005 First Edition for New Release BR 8.0

    2 04/2005 More instructions for adjusting of the DIAMCO,

    (F)DUAMCO. Revised tables.

    3 07/2005 Revised tables.

  • 8/12/2019 bs241it

    4/130

  • 8/12/2019 bs241it

    5/130

    A30808-X3247-M357-3-7630 5

    Installation TestBase Transceiver Station Equipment

    ITMN:BTSE BS-241 / 241 II

    This document consists of a total of 130 pages. All pages are issue 3.

    Contents

    1 BS-241 / 241 II Installation Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

    1.1.1 Aims of Installation and Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

    1.1.2 Pre-Commissioning and Pre-Acceptance. . . . . . . . . . . . . . . . . . . . . . . . . . . 9

    1.1.3 Optional Measurements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

    1.1.4 Using the ITMN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

    1.1.5 Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

    1.1.6 Closing the Shelter Door. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

    1.2 Visual Inspection of BTSE Mechanics . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

    1.2.1 Shelters of BS-241 / 241 II . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

    1.2.2 Mounting and Installation of BTSE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

    1.2.3 Check of BTSE Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

    1.2.4 Antenna and Feeder Cable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

    1.2.5 Module HW Coding. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

    1.3 Visual Inspection of BTSE Electrics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

    1.3.1 Polarity of DC Input and Tolerance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

    1.3.2 Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

    1.3.3 External Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

    1.3.4 DC Connector for Network Termination (NT). . . . . . . . . . . . . . . . . . . . . . . 24

    1.4 Visual Inspection of BTSE Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

    1.4.1 STAR/LOOP/MULTIDROP/CROSS CONNECT Connection . . . . . . . . . . . 24

    1.4.2 Antenna Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 251.4.3 RF System Cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

    1.4.4 Antenna Combining . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

    1.4.5 Antenna Multicoupling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

    1.4.6 Adjustable Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

    1.5 Preparation for Offline Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

    1.5.1 Recommended Test Equipment and Tools. . . . . . . . . . . . . . . . . . . . . . . . . 48

    1.5.2 Preparation and Presetting of Test Equipment. . . . . . . . . . . . . . . . . . . . . . 50

    1.5.3 BTSE Power ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

    2 Tasklist. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

    3 Procedures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 553.1 SW Download and Activation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57

    3.2 Rack. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60

    3.3 Hardware Related Managed Objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

    3.4 ACDCP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63

    3.5 ACT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65

    3.6 Battery. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66

    3.7 COSA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68

    3.8 CU. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69

    3.9 ECU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71

    3.10 FlexCU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

    3.11 GCU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75

  • 8/12/2019 bs241it

    6/130

    6 A30808-X3247-M357-3-7630

    ITMN:BTSE BS-241 / 241 II Installation TestBase Transceiver Station Equipment

    3.12 FAN. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76

    3.13 DIAMCO. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77

    3.14 DUAMCO / FDUAMCO. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80

    3.15 FICOM. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 843.16 TMA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86

    3.17 Create the Alarm Configuration (ENVABTSE). . . . . . . . . . . . . . . . . . . . . . . 87

    3.18 Set Attributes for BTSE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90

    3.19 BPORT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91

    3.20 XCONNECT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93

    3.21 Set BTSM. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94

    3.22 LAPDLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95

    3.23 CORE Redundancy. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96

    3.24 Check the State of all Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100

    3.25 Replacing of Failed HW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101

    3.26 External Alarm Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1023.27 BTS Backup Files Generation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103

    3.28 Remote Inventory. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104

    3.29 Switch to Phase 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111

    3.30 Setup for Optional RF-Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113

    3.30.1 Measuring Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113

    3.31 Spectrum Analyzer Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115

    3.32 VSWR Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118

    3.33 RFI-Confirmation: Unit ATMN. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118

    4 Tables, Lists and Figures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119

    4.1 Frequency/Channel Conversion Table. . . . . . . . . . . . . . . . . . . . . . . . . . . . 121

    5 Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123

    5.1 Power/Level Conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123

    5.2 Used Expressions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123

    5.3 Module Identification by Inventory Data and Label . . . . . . . . . . . . . . . . . . 124

    6 Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125

    7 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129

  • 8/12/2019 bs241it

    7/130

    A30808-X3247-M357-3-7630 7

    Installation TestBase Transceiver Station Equipment

    ITMN:BTSE BS-241 / 241 II

    Illustrations

    Fig. 1.1 Installation Test Sequence. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

    Fig. 1.2 Used Symbols. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

    Fig. 1.3 ESD Symbol. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

    Fig. 1.4 CE Symbol / UL Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

    Fig. 1.5 Closing the Shelter Door: Handle Positions. . . . . . . . . . . . . . . . . . . . . . 15

    Fig. 1.6 Example for BS-241 (Front View) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

    Fig. 1.7 DC Panel (Example) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

    Fig. 1.8 Star/Loop/Multidrop/Cross Connect Configuration . . . . . . . . . . . . . . . . 25

    Fig. 1.9 TMA (Example) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

    Fig. 1.10 RF System Cabling CU - DUAMCO (Example) . . . . . . . . . . . . . . . . . . . 28

    Fig. 1.11 RF System Cabling CU - FICOM and DIAMCO - CU (Example). . . . . . 29

    Fig. 1.12 FDUAMCO in 2:2/4:2 Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

    Fig. 1.13 FDUAMCO / COAMCO in 8:2 Configuration . . . . . . . . . . . . . . . . . . . . . 31

    Fig. 1.14 FICOM Modules for 8 Carriers in 1-Cell Configuration . . . . . . . . . . . . . 32

    Fig. 1.15 FICOM Modules in 2-Cell Configuration . . . . . . . . . . . . . . . . . . . . . . . . 33

    Fig. 1.16 DIAMCO Antenna Connection and DIP Switches. . . . . . . . . . . . . . . . . 34

    Fig. 1.17 View of DIP Switch (Factory Setting) . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

    Fig. 1.18 (F)DUAMCO DIP Switch and Antenna Connection (Example). . . . . . . 36

    Fig. 1.19 COBA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

    Fig. 1.20 Switch Settings of Port 1 and Port 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

    Fig. 1.21 External Clock Synchronization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

    Fig. 1.22 COBA4P12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

    Fig. 1.23 External Clock Synchronization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

    Fig. 1.24 COSA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

    Fig. 1.25 Switch Settings of Port 1 to Port 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

    Fig. 1.26 DIP Switches for Battery Type, Battery Capacities and Slot-ID. . . . . . . 45

    Fig. 1.27 Battery Type DIP Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

    Fig. 1.28 Battery Capacity DIP Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

    Fig. 1.29 DCBCTRL Slot-ID DIP Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

    Fig. 3.1 Setting the SBS Equipment Position. . . . . . . . . . . . . . . . . . . . . . . . . . 105

    Fig. 3.2 Editing Nob-RIU Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106

    Fig. 3.3 Measurement Setup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113

    Fig. 3.4 Example 1: Test Adapter TADL (S30861-U2003-X-1). . . . . . . . . . . . . 113

    Fig. 3.5 Example 2: Test Adapter TADlight (S30861-U688-X) with Integrated Ex-

    tension Adapter TADADPT (S30861-U2170-x) . . . . . . . . . . . . . . . . . . 114

    Fig. 3.6 Spectrum Analyzer HP8594A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115

    Fig. 5.1 Labels and Inventory Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124

  • 8/12/2019 bs241it

    8/130

    8 A30808-X3247-M357-3-7630

    ITMN:BTSE BS-241 / 241 II Installation TestBase Transceiver Station Equipment

    Tables

    Tab. 1.1 Shelter Numbering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

    Tab. 1.2 Module HW Code Key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

    Tab. 1.3 DC Breakers for BS-241 Base Shelter. . . . . . . . . . . . . . . . . . . . . . . . . . 21

    Tab. 1.4 DC Breakers for BS-241 Extension Shelter . . . . . . . . . . . . . . . . . . . . . . 21

    Tab. 1.5 DC Breakers for BS-241 Service1 Shelter . . . . . . . . . . . . . . . . . . . . . . . 22

    Tab. 1.6 DC Breakers for BS-241 Service2 Shelter . . . . . . . . . . . . . . . . . . . . . . . 22

    Tab. 1.7 DC Breakers for BS-241 II Base Shelter. . . . . . . . . . . . . . . . . . . . . . . . . 22

    Tab. 1.8 DC Breakers for BS-241 II Extension Shelter . . . . . . . . . . . . . . . . . . . . . 22

    Tab. 1.9 DC Breakers for BS-241 II Service1 Shelter. . . . . . . . . . . . . . . . . . . . . . 23

    Tab. 1.10 DC Breakers for BS-241II Service2 Shelter. . . . . . . . . . . . . . . . . . . . . . 23

    Tab. 1.11 Settings for ENVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

    Tab. 1.12 RF Cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

    Tab. 1.13 Switch Settings for DIAMCO/(F)DUAMCO . . . . . . . . . . . . . . . . . . . . . . . 34

    Tab. 1.14 Cascading of Multicouplers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

    Tab. 1.15 Adjustable Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

    Tab. 1.16 Boot Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

    Tab. 1.17 Software Images SWI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

    Tab. 1.18 Battery Type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

    Tab. 1.19 Slot-ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

    Tab. 3.1 Hardware Related Managed Objects. . . . . . . . . . . . . . . . . . . . . . . . . . . 61

    Tab. 5.1 Power Conversion Table. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123

  • 8/12/2019 bs241it

    9/130

    A30808-X3247-M357-3-7630 9

    Installation TestBase Transceiver Station Equipment

    ITMN:BTSE BS-241 / 241 II

    1 BS-241 / 241 II Installation Test

    1.1 Introduction

    1.1.1 Aims of Installation and Commissioning

    Installation and commissioning is based on extensive, high quality final factory tests. In

    the factory, each module is tested during its production process; all RF parameters such

    as the power and modulation spectrum are measured in the complete BTSE rack in cus-

    tomer configuration.

    The Final Factory Tests comply with the tests and measurements required by GSM

    specifications.

    The installation test can therefore concentrate on functional tests of the delivered HW.

    The installation and commissioning of a network element followed by unit acceptance is

    proof of:

    It is assumed that:

    The subdivision of tests in the steps

    final factory test

    installation/commissioning (HW-test)

    network integration (data base test)

    allows a quick, economical, and reliable commissioning procedure.

    This is according to the requirements for modern communication systems regarding

    self-tests, and a quick and economic commissioning procedure. As the function test is

    based on self-test routines, a high degree of reliability is achieved.

    1.1.2 Pre-Commissioning and Pre-Acceptance

    The BTSE may also be delivered partly or completely pre-commissioned and pre-

    accepted.

    If the BTSE is pre-commissioned and pre-accepted, some procedures that usually are

    performed on site (see Chapter 2 "Tasklist") have alreadybeen performed in the factory.

    In this case, these particular procedures need not be performed again during the

    installation test phase.

    It depends on the contract to what extent the BTSE is pre-commissioned and pre-

    accepted.

    A correct and complete delivery according to the network planning and the

    customer order.

    A correct mechanical and electrical installation according to the installation

    documents.

    The functional ability of the supplied HW

    (correct functioning of the NEs at an interface in relation to other network

    elements).

  • 8/12/2019 bs241it

    10/130

    10 A30808-X3247-M357-3-7630

    ITMN:BTSE BS-241 / 241 II Installation TestBase Transceiver Station Equipment

    All set parameters are listed in the Pre-Commissioning Paper. All executed tests and

    their results are documented in the Final Factory Test Protocol. Both documents are

    delivered together with the site-specific documentation.

    Consult these documents to find out which procedures of the Tasklistcan be left out.

    1.1.3 Optional Measurements

    Radio Frequency (RF) -measurements and Bit Error Rate Test (BERT) can be per-

    formed by means of a spectrum analyzer or other test equipment and may be used as

    an option for locating suspected faults.

    They need not be done in every BTSE as regular measurements.

    1.1.4 Using the ITMN

    1.1.4.1 Required Knowledge

    Only trained personnel should carry out the installation and installation tests.

    The SIEMENS training centre offers the necessary courses.

    1.1.4.2 Test Equipment

    The test equipment and tools required for the tests are described in the corresponding

    chapters.

    1.1.4.3 Procedure in the Event of Faults after Commissioning

    If faults occur in on-line operation they should be localized and cleared in accordance

    with the instructions in the Maintenance Manual (MMN:BTSE BS-241 / 241 II).

    1.1.4.4 Procedure in the Event of Faults not Described in the UMN

    First the specialist in the installation team should try to clear the fault. If the installationtechnician is not qualified to eliminate serious faults, a fault report must be filled out, pro-viding the following information in detail:

    description of the test step attempted

    description of the system response

    description of any system activities taking place at the same time, e.g. work done by

    other testers during modification of hardware or software

    The fault report must be sent to the Technical Assistance Center (TAC).

    1.1.4.5 Dealing with Defective Modules

    If a module proves to be defective, it should be sent in appropriate packaging to the re-pair centre with the following information:

    Name and code of the site

    Name and code number of the module

    Description of the fault

    i It is important, however, not to change the order of the remaining procedures.

    http://bs241mt.pdf/http://bs241mt.pdf/
  • 8/12/2019 bs241it

    11/130

    A30808-X3247-M357-3-7630 11

    Installation TestBase Transceiver Station Equipment

    ITMN:BTSE BS-241 / 241 II

    1.1.4.6 Installation Test Sequence

    Fig. 1.1 Installation Test Sequence

    Visual Checkof BTS-Mechanics

    Visual Check

    of BTS-Electrics

    Visual Checkof Boards

    Preparation for

    FunctionTests

    Execution ofFunction Tests

    VISUAL

    CONTROL

    O

    FFLINE

    ONLINE

    S T A R T

    E N D

    Preparation /Executionof Online Tests

  • 8/12/2019 bs241it

    12/130

    12 A30808-X3247-M357-3-7630

    ITMN:BTSE BS-241 / 241 II Installation TestBase Transceiver Station Equipment

    1.1.4.7 Symbols Used

    The following symbols are used throughout this manual:

    Fig. 1.2 Used Symbols

    1.1.5 Safety Instructions

    1.1.5.1 Electrostatically Sensitive Components

    General

    All modules are to be handled with extreme care as each one contains many electrostat-

    ically sensitive devices (ESD).

    All modules which contain ESD are marked with the ESD symbol on the faceplate or in-

    side.

    Reference to another procedure step

    Symbol Meaning

    ESD (Electrostatic Sensitive Device) precautions to be taken

    Note; important information

    Warning; the notes given here are to be followed with care.

    b

    h

    Use the LMT to enter commands

    Reference to another chapter

    Reference to another procedure. Return after finishing.i

    Non-observance can lead to personal injury or property damage.

    i

    !

  • 8/12/2019 bs241it

    13/130

    A30808-X3247-M357-3-7630 13

    Installation TestBase Transceiver Station Equipment

    ITMN:BTSE BS-241 / 241 II

    Fig. 1.3 ESD Symbol

    To avoid destruction or damage comply with following rules.

    Rules for Handling

    The following safety instructions are to be noticed:

    Personnel should avoid wearing synthetic clothing and shoes with plastic soles, as

    these encourage the build-up of electrostatic charge.

    Before handling modules, personnel should be discharged of electrostatic charging.

    For this reason personnel should always put on a grounded wrist strap before chang-

    ing a module.

    ESDs should not be brought in contact with electrostatically charged or chargeable

    objects.

    ESDs should only come in contact with high valued discharging material ("gentle"

    discharging), i.e. should not be made subject to "harsh" discharging with, for exam-

    ple, a metal plate.

    ESDs should be set down on grounded surfaces only (flexible bases with a ground-

    ing connection for servicing purposes)

    ESDs should not be brought into the vicinity of strong DC electrical fields, e.g. cath-

    ode ray tubes/monitors (safety distance at least 10 cm/~4 inches). All tools and test equipment should be discharged of electrostatic charging before

    handling modules.

    ESDs should only be transported in appropriate packing. A grounded wrist strap

    must be put on before removing ESDs.

    Modules should only be touched by their edges. Components or printed circuits

    should not be touched.

    1.1.5.2 System Voltages

    All the system units require a power supply of 230 V AC (207 V AC in case of BS-241U),

    which are converted to -48 V DC (positive pole grounded).Some parts are supplied with the line voltage directly and are to be handled with safety

    tools with extreme care. Only trained personnel should carry out those jobs.

    Care must be taken because some parts produce a high operating temperature.

    This warning must appear in the original German text:

    Alle Systemeinheiten bentigen eine Wechselspannung von 230 V AC (207 V AC bei

    BS-241U), die in eine Gleichspannung von -48 V DC (positiver Pol an Masse)

    umgesetzt wird.

    Einige Teile fhren Netzspannung und sind mit besonderer Sorgfalt zu behandeln. Nur

    ausgebildetes Personal darf entsprechende Arbeiten bernehmen.

    Weiterhin ist zu beachten, da sich einige Bauteile stark erhitzen.

  • 8/12/2019 bs241it

    14/130

    14 A30808-X3247-M357-3-7630

    ITMN:BTSE BS-241 / 241 II Installation TestBase Transceiver Station Equipment

    1.1.5.3 Changing Breakers

    Breakers may only be changed by operator. Only authorized breakers as given in the

    manual may be used. Breakers are to be changed as described in this manual.

    1.1.5.4 Grounding of Modules / Shelters

    All modules must be plugged in correctly to ground them before power is switched on.

    Ground connections between Shelters must be plugged in correctly.

    1.1.5.5 Handling Moist Modules

    After storage in an humid environment, modules with condensation moisture must be

    dried before they are used. This is important because otherwise the modules may be

    damaged or destroyed.

    1.1.5.6 CE and UL Declaration of Conformity

    Fig. 1.4 CE Symbol / UL Symbol

    The CE and UL declaration of conformity for the product will be fulfilled if the setup and

    cabling is undertaken in accordance with the specification in the manual and the docu-

    mentation listed there, such as mounting instructions, cable lists, etc. Where necessary,

    account should be taken of project-specific documentation.

    Deviations from the specifications or independent changes during setup, such as use of

    cable types with lower screening values, for example, can lead to the CE requirements

    being violated. In such cases, the CE declaration of conformity is invalidated and the re-

    sponsibility passes to the person who has caused the deviations.

  • 8/12/2019 bs241it

    15/130

    A30808-X3247-M357-3-7630 15

    Installation TestBase Transceiver Station Equipment

    ITMN:BTSE BS-241 / 241 II

    1.1.6 Closing the Shelter Door

    The final step after performing any work at the BTSE is closing the shelter door.

    Fig. 1.5 Closing the Shelter Door: Handle Positions

    iImportant Note:

    In order to make sure that the Door Openalarm is really deactivated after closing the

    shelter door, please do the following:

    Close the door, turn the door handle in the clockwise direction and pass over the nor-

    mal locking position (vertical to the ground), until you feel that it can not be turned any

    further. Then bring back the handle to the normal locking position (vertical to the

    ground) and press it into the handle latch. The Door Openalarm goes off.

    1

    2

    LOCKIN

    GP

    OSITION

    DOOR OPEN

    3

  • 8/12/2019 bs241it

    16/130

    16 A30808-X3247-M357-3-7630

    ITMN:BTSE BS-241 / 241 II Installation TestBase Transceiver Station Equipment

    1.2 Visual Inspection of BTSE Mechanics

    A visual inspection for all delivered Shelters has to be executed to secure that these

    Shelters are not damaged and the quantity and location of the modules is correct.

    1.2.1 Shelters of BS-241 / 241 II

    A BS-241 / 241 II consists of one Base Shelter, 1-2 Extension Shelters and 1- 5 Service

    Shelters. The numbering of the Shelters is shown in the table below.

    For setting the correct rack number, please refer to the Hardware Manual (see HW:BT-SE Modules, ACTP Switch Settings).

    Shelter numbering Type of Shelter

    0 Base Shelter

    1, 2 Extension Shelter

    3 Service 1 Shelter (BS-241) with AC/DC modules

    4...7 Service 1A Shelter (BS-241 II)with AC/DC modules; in this

    case, there is no Shelter #3

    4,..., 7 Service Shelter 2 with Link Equipment and Backup Batteries

    Tab. 1.1 Shelter Numbering

    iThe numbering of the service Shelters begins with 3 (4 for BS-241 II), even if there is

    no Extension Shelter. Fig. 1.6shows a BS-241 with one Base Shelter and two Exten-

    sion Shelters.

    http://modules.pdf/http://modules.pdf/http://modules.pdf/http://modules.pdf/
  • 8/12/2019 bs241it

    17/130

    A30808-X3247-M357-3-7630 17

    Installation TestBase Transceiver Station Equipment

    ITMN:BTSE BS-241 / 241 II

    Fig. 1.6 Example for BS-241 (Front View)

    Base Shelter Extension Shelter Extension Shelter

    LMT

    FAN#0 FAN#1

    FAN#2 FAN#3

    FAN#4 FAN#5

    BS-241

    DCP

    CU

    #0

    CU

    #1

    CU

    #2

    CU

    #3

    CU

    #4

    CU

    #5

    CU

    #6

    CU

    #7

    D

    IAMCO#0

    D

    IAMCO#1

    CORE#

    0

    CORE#

    2

    CORE#

    1

    CORE#

    3

    Plinth

    OVPT

    BS-241 BS-241

    HPDU

    HPDU

    HPDU

    HPDU

    HPDU

    HPDU

    Plinth Plinth

    FAN#0 FAN#1

    FAN#2 FAN#3

    FAN#4 FAN#5

    DCP

    CU#0

    CU#1

    CU

    #2

    CU

    #3

    CU#4

    CU#5

    CU

    #6

    CU

    #7

    DIAMCO#0

    DIAMCO#1

    FAN#0 FAN#1

    FAN#2 FAN#3

    FAN#4 FAN#5

    DCP

    CU#0

    CU#1

    CU

    #2

    CU

    #3

    CU#4

    CU#5

    CU

    #6

    CU

    #7

    DIAMCO#0

    DIAMCO#1

    (F)DUAMCO#1

    orFICOM#1

    (F)DUAMCO#2

    orFICOM#2

    (F)DUAMCO#3

    orFICOM#3

    orFICOM#0

    COAMCO

    (F)DUAMCO#0

    COAMCO

    COAMCO

    COAMCO

    (F)DUAMCO#1

    orFICOM#1

    (F)DUAMCO#2

    orFICOM#2

    (F)DUAMCO#3

    orFICOM#3

    orFICOM#0

    COAMCO

    (F)DUAMCO#0

    COAMCO

    COAMCO

    COAMCO

    (F)DUAMCO#1

    orFICOM#1

    (F)DUAMCO#2

    orFICOM#2

    (F)DUAMCO#3

    orFICOM#3

    orFICOM#0

    COAMCO

    (F)DUAMCO#0

    COAMCO

    COAMCO

    COAMCO

    TMA7

    TMA6

    TMA0

    TMA7

    TMA6

    TMA0

    TMA7

    TMA6

    TMA0

  • 8/12/2019 bs241it

    18/130

    18 A30808-X3247-M357-3-7630

    ITMN:BTSE BS-241 / 241 II Installation TestBase Transceiver Station Equipment

    1.2.2 Mounting and Installation of BTSE

    Check the internal/external interfaces and least replaceable units (LRU). For more de-

    tailed information refer to the MMN:BTSE BS-241 / 241 II.

    1.2.2.1 Check of Base Transceiver Station BTSE

    Check for delivery quality and quantity on site:

    installation of BTS Shelter (Shelter fixing, fixed boards)

    damage to Shelter (paintwork, dents)

    correct insertion of modules

    system/Shelter cabling

    grounding, earthing

    main breakers

    external interfaces: power supply, antenna and Abis wiring

    1.2.3 Check of BTSE Modules

    1.2.3.1 Module Identification

    After the configuration of the modules in a BTSE thecode numbersand functional states

    are also electronically readable via LMT, see chapter 5.3 Module Identification by Inven-

    tory Data and Label.

    1.2.3.2 Modules in the SheltersThe following table gives an overview of which modules can be installed in the Shelter-

    types.

    Module BaseRack/Shelter

    Extension 1/2Rack/Shelter

    Service 1Rack/Shelter

    Service 2Rack/Shelter

    COBA X

    COSA X

    CU X X

    FICOM X X

    (F)DUAMCO X X

    DIAMCO X XDCP X X X X

    ACTP X X X X

    ACTM X

    AC/DC X

    DCBCTRL X

    BATTERY X X

    LE X

    http://bs241mt.pdf/http://bs241mt.pdf/
  • 8/12/2019 bs241it

    19/130

    A30808-X3247-M357-3-7630 19

    Installation TestBase Transceiver Station Equipment

    ITMN:BTSE BS-241 / 241 II

    1.2.3.3 BTSE Modules

    The entire BTSE contains several cells called BTS:

    Up to 12 Cells are available.

    Check whether the BTSE modules are correctly configured.

    Redundancy

    CORE redundancy can be installed. In the CORE, the functionality of clock genera-

    tion, link interface, and Call Control is implemented. The BCCH redundancy is matter of SW. The task "BCCH reconfiguration" runs in

    the BTSEplus and the functionality is independent of the type of antenna combining.

    AC/DC redundancy is carried out as n+1 redundancy. N+1 AC/DC Converters oper-

    ate in load sharing, but n AC/DCs are able to supply the whole BTSEplus.

    1.2.4 Antenna and Feeder Cable

    The types of antennas and feeder cables have to be checked!

    Hardware (HW) related modules:

    Per CELL:

    (F)DUAMCO (Flexible)Duplexer Amplifier Multicoupler

    DIAMCO Dual Integrated Amplifier Multicoupler

    FICOM Filter Combiner

    TMA Tower Mounted Amplifier

    HPDU High Power Duplexer

    Per Transceiver TRX:

    CU Carrier Unit

    In addition there are common modules:

    COBA Core Basis

    COSA Core Satellite

    ACT Alarm Collection Terminal

    Basic-Modules:DCP DC Panel

    FAN Fan

    OVPT Overvoltage Protection

    AC/DC Alternating Current/Direct Current

    DCBCTRL DC and Battery Controller

    BB Backup Battery

  • 8/12/2019 bs241it

    20/130

    20 A30808-X3247-M357-3-7630

    ITMN:BTSE BS-241 / 241 II Installation TestBase Transceiver Station Equipment

    1.2.5 Module HW Coding

    Every type of module has its own code key to ensure they are fitted in the correct slot

    position. The on-board code must match the backplane code of the BTSE Shelter.

    1.3 Visual Inspection of BTSE Electrics

    1.3.1 Polarity of DC Input and Tolerance

    The BTSE requires -48 V DC with a tolerance of -15%/+20% (-40,8V...-57,6V) for cor-

    rect operation (positive pole is grounded).

    Check this voltage.

    1.3.2 Circuit Breakers

    Shelter internal breakers are available at the DC Panel for several modules to supply

    direct current (DC).

    The breakers are mounted at the DC Panel on the top of the Shelter.

    There are different types of DC Panel for Base Shelter (Fig. 1.7), Extension Shelter,

    Service Shelter 1 and Service Shelter 2.

    Check for fully equipped breakers and that all breakers are being switched off.

    Module Code Key

    (F)DUAMCO 7

    FICOM 7

    DIAMCO 8

    CU 6

    COBA 1

    COSA 2

    Tab. 1.2 Module HW Code Key

  • 8/12/2019 bs241it

    21/130

    A30808-X3247-M357-3-7630 21

    Installation TestBase Transceiver Station Equipment

    ITMN:BTSE BS-241 / 241 II

    Fig. 1.7 DC Panel (Example)

    Breaker 1 2 3 4 5 6 7 8 9 10

    Type 16A 16A 16A 16A 4A 10A 4A 4A 4A 10A

    Unit CU

    0-1

    CU

    2-3

    CU

    4-5

    CU

    6-7

    DIAMCO

    ACOM/

    ACTP/

    *SMOKE

    (*not BS-

    241U)

    INTER-

    NAL

    FAN

    CORE/

    COBA,

    COSA

    CORE/

    COBA,

    COSA

    red.

    not

    used

    HEX

    (only in

    Shelter

    with

    HEX)

    Tab. 1.3 DC Breakers for BS-241 Base Shelter

    Breaker 1 2 3 4 5 6 10

    Type 16A 16A 16A 16A 4A 10A 10A

    Unit CU

    0-1

    CU

    2-3

    CU

    4-5

    CU

    6-7

    DIAMCO

    ACOM/

    ACTP/

    *SMOKE

    (*not BS-

    241U)

    INTER-

    NAL

    FAN

    HEX

    (only in

    Shelter

    with

    HEX)

    Tab. 1.4 DC Breakers for BS-241 Extension Shelter

  • 8/12/2019 bs241it

    22/130

  • 8/12/2019 bs241it

    23/130

    A30808-X3247-M357-3-7630 23

    Installation TestBase Transceiver Station Equipment

    ITMN:BTSE BS-241 / 241 II

    1.3.3 External Alarms

    There are three types of ACT modules.

    ACTM for Base Rack optional

    ACTP for each rack, for Base Rack optionalACTC for all racks is part of the DC Panel.

    All racks are equipped with one ACTC which is part of the DC Panel. In the Base Rack

    the ACTC is directly connected to the COBA. In the other racks the ACTC is connected

    to the ACTP. On each ACTC 16 Alarms are available, 7 Rack Alarms (RAL) that are cre-

    ated automatically during the creation of RACK and FAN and 9 Operator Alarms (OAL).

    The OAL have to be created via 3.17 "Create the Alarm Configuration (ENVABTSE)"

    and have the numbering ENVA 0 - ENVA 8.

    The Base Rack can be equipped with ACTM. The ACTM supports 48 additional ENVAs,

    that have the numbering ENVA 9 - ENVA 56, and 8 Operator Commands (not supported

    by SW of BR5.5). The installation of ACTM is optional. If no ACTM is installed, in the

    Base Rack 16 Alarms are available.The ENVAs 0-6 and ENVA 8 are connected to the DC Panel (described in IMN:BTSE

    BS-241) and should be named as in the table below.

    Breaker 1 2 3 4 5 6 7 8

    Type max

    25A

    max

    25A

    max

    25A

    max

    25A

    max

    25A

    max

    25A

    max

    25A

    max

    25A

    Unit LE/

    Wave 0

    LE/

    Wave 1

    LE/

    Wave 2

    LE/

    Wave 3

    LE/

    Wave 4

    LE/

    Wave 5

    LE/

    Wave 6

    LE/

    Wave 7

    Tab. 1.9 DC Breakers for BS-241 II Service1 Shelter

    Breaker 1 2 3 4 5 6 7 8

    Type max.25A

    max.25A

    max.25A

    max.25A

    max.25A

    max.25A

    max.25A

    max.25A

    Unit LE/

    Wave 0

    LE/

    Wave 1

    LE/

    Wave 2

    LE/

    Wave 3

    LE/

    Wave 4

    LE/

    Wave 5

    ACTC:

    FAN

    ACTC:

    DC IN

    Tab. 1.10 DC Breakers for BS-241II Service2 Shelter

    ENVA Name Connector on DC Panel

    0 Heatexchanger 0 HX 0 (not used for Shelter with HEX)

    1 Heatexchanger 1 HX 1 (not used for Shelter with HEX)

    2 Heatexchanger 2 HX 2 (not used for Shelter with HEX)

    3 Shelter in service SIS

    Tab. 1.11 Settings for ENVA

    http://bs241is.pdf/http://bs241is.pdf/http://bs241is.pdf/http://bs241is.pdf/
  • 8/12/2019 bs241it

    24/130

  • 8/12/2019 bs241it

    25/130

    A30808-X3247-M357-3-7630 25

    Installation TestBase Transceiver Station Equipment

    ITMN:BTSE BS-241 / 241 II

    Fig. 1.8 Star/Loop/Multidrop/Cross Connect Configuration

    1.4.2 Antenna Connection

    Check the connection of TX and RX coax jumper cables.

    1.4.2.1 TX Antenna Connection

    The TX antenna coax jumper cable must be directly connected to the 7/16" FICOM/

    (F)DUAMCO antenna connector.

    Multidrop Cross Connect

    BSC

    BTSE 2BTSE 1 BTSE 3

    Star Loop

    BSC

    BTSE 2BTSE 1 BTSE 3

    BSC

    BTSE 2BTSE 1 BTSE 3

    BTSE 1BSC

    BTSE 3BTSE 2 BTSE 4

  • 8/12/2019 bs241it

    26/130

    26 A30808-X3247-M357-3-7630

    ITMN:BTSE BS-241 / 241 II Installation TestBase Transceiver Station Equipment

    1.4.2.2 RX Antenna Connection

    The RX antennas are connected via a jumper cable to the inputs N_female on the DI-

    AMCO and 7/16" on the (F)DUAMCO. For diversity use the (F)DUAMCO / DIAMCO has

    to be connected to two Antennas.(F)DUAMCO uses the same jumper cable for TX and RX path. The DIAMCO is connect-

    ed via jumper cable (Fig. 1.16).

    1.4.2.3 Tower Mounted Amplifier (TMA) Connection

    If an antenna is present check for correct RF cabling connections of TMA. The (F)DUA-

    MCO / DIAMCO supply the DC power for TMA at their antenna ports via the RF coax

    cable.

    Fig. 1.9 TMA (Example)

    1.4.3 RF System Cabling

    There are several RF boards interconnected with RF-cables.

    Check whether the corresponding Carrier Units (CU modules) are connected to their

    branching equipment FICOM, (F)DUAMCO, DIAMCO.

    Handle with extreme care when connecting/changing modules!

    Antennaconnection

    BTSEconnection

  • 8/12/2019 bs241it

    27/130

  • 8/12/2019 bs241it

    28/130

    28 A30808-X3247-M357-3-7630

    ITMN:BTSE BS-241 / 241 II Installation TestBase Transceiver Station Equipment

    Fig. 1.10 RF System Cabling CU - DUAMCO (Example)

    TX

    RX

    RX Diversity

    CU DUAMCO 4:2

  • 8/12/2019 bs241it

    29/130

    A30808-X3247-M357-3-7630 29

    Installation TestBase Transceiver Station Equipment

    ITMN:BTSE BS-241 / 241 II

    Fig. 1.11 RF System Cabling CU - FICOM and DIAMCO - CU (Example)

    1.4.4 Antenna Combining

    The (F)DUAMCO / FICOM have to be installed in the ACOM slots. To achieve short ca-

    bling between CU and ACOM the ACOM slots are assigned to definite CU slots.

    1.4.4.1 DUAMCO

    The DUAMCO 2:2,4:2 occupy one ACOM slot each andare installed in the assigned slot

    for the CU that must be combined.

    The DUAMCO 8:2 occupies two ACOM slots and is installed either on the left or on the

    right two slots.

    AntennaConnection

    FICOMBase module

    CU DIAMCO

    iAll unused RX and RXCA connectors must be terminated with a 50 load when the

    corresponding antenna port of the (F)DUAMCO is connected to an antenna or cascad-

    ing output of (F)DUAMCO / DIAMCO / COAMCO.

    The open TX inputs of (F)DUAMCO / COAMCO do not need to be terminated in nor-mal operation.

  • 8/12/2019 bs241it

    30/130

    30 A30808-X3247-M357-3-7630

    ITMN:BTSE BS-241 / 241 II Installation TestBase Transceiver Station Equipment

    1.4.4.2 FDUAMCO

    For each system GSM 850, GSM 900, GSM 1800 and GSM 1900 one type of FDUAM-

    CO units is available, which can be configured by jumper cables for One-To-One mode

    (= FDUAMCO 2:2) or Two-To-One mode (= FDUAMCO 4:2).The FDUAMCO unit can be configured to different modes by application of two jumpers.

    FDUAMCO 2:2

    The FDUAMCO in 2:2 configurations is used for 2 antennas with 1 carrier each.

    For this configuration, the connectors 2 and 3 have to be jumpered.

    The second free jumper per module can be placed at connector 4

    FDUAMCO 4:2

    The FDUAMCO in 4:2 configurations is used for 2 antennas with 2 carriers each.

    For this configuration, the connectors TX 0 and TX 1 are used as TX inputs. One jumperis applied for the connectors 1 and 2. The second jumper is placed between connectors

    3 and 4.

    FDUAMCO 8:2

    For an 8:2 configuration a COAMCO can be used in conjunction with a FDUAMCO in

    4:2 configuration (see Fig. 1.13).

    Fig. 1.12 FDUAMCO in 2:2/4:2 Configuration

    1

    2

    3

    4

    1

    2

    3

    4

    1

    2

    3

    4

    1

    2

    3

    4

    FDUAMCO in 4:2 configurationFDUAMCO in 2:2 configuration

    Upper part of FDUAMCOUpper part of FDUAMCO

    = jumpers = connectors

  • 8/12/2019 bs241it

    31/130

    A30808-X3247-M357-3-7630 31

    Installation TestBase Transceiver Station Equipment

    ITMN:BTSE BS-241 / 241 II

    Fig. 1.13 FDUAMCO / COAMCO in 8:2 Configuration

    1.4.4.3 COAMCO

    The COAMCO consists of two identical Modules (0/1), each having a transmit and a re-

    ceive path. A COAMCO is used in conjunction with a FDUAMCO in 4:2 configuration to

    provide an 8:2 configuration. (see Fig. 1.13). The COAMCO combines 2 additional car-

    riers per module with the 2 carriers from the output 4 of the FDUAMCO and feeds the 4

    carriers back to the input 3 of the FDUAMCO.

    COAMCOFDUAMCO

    Tx 0...3

    Tx 4...7

    Rx 0...7 Rx 8...15

    AntennaConnections

    4

    3

    2

    1

    4

    3

    2

    1

    4

    3

    4

    3

    iNo specific alarm exists for a defective COAMCO module. Check the LEDs POWER /

    ALARM at the COAMCO module. Red LED lights signal a defective COAMCO module.

  • 8/12/2019 bs241it

    32/130

    32 A30808-X3247-M357-3-7630

    ITMN:BTSE BS-241 / 241 II Installation TestBase Transceiver Station Equipment

    1.4.4.4 FICOM

    Usage of FICOM modules of different variants

    There are several different FICOM modules (FIPLUB2RV3, FIPLUB2RV4,FIPLUX2RV3, FIPLUX2RV4).

    Installation of FICOM modules

    For each cell one FICOM plus base module (FIPLUB) has to be installed. To combine

    more than 2 carriers the base module can be expanded by the FICOM plus expansion

    module (FIPLUX). The expansion can be done to one side only per base module.

    Expansion of FICOM can be only done inside each Shelter. To combine more than 8

    carriers a base module has to be installed in the extension Shelter

    Fig. 1.14 FICOM Modules for 8 Carriers in 1-Cell Configuration

    !One Base Module can be expanded by 3 Expansion Modules, all modules in this com-

    bination must have the same variant (all ...V3 or all ...V4).

    iOpen expansion connectors RF EXP of FICOM modules have to be terminated with the

    terminator delivered with the FICOM base module.

    !It is suggested to fix the jumper cable very carefully, don't torque to strong. The cable

    should not move. Otherwise the cable inner conductor will tear.

    Mounting Location

    Cell 0

    Slot/ FICOMNumber 0 1 2 3

    Base Expansion Expansion Expansion

    ANTOUT

    TESTOUT

    RF EXP RF EXP RF EXP RF EXP

    TX0 TX1 TX0 TX1 TX0 TX1 TX0 TX1

  • 8/12/2019 bs241it

    33/130

    A30808-X3247-M357-3-7630 33

    Installation TestBase Transceiver Station Equipment

    ITMN:BTSE BS-241 / 241 II

    Fig. 1.15 FICOM Modules in 2-Cell Configuration

    The mounting location of the FICOM modules depends on the Cell configuration and an-

    tenna combining.

    It is possible to have a mixed installation of (F)DUAMCO and FICOM modules, within

    one Shelter.

    1.4.4.5 HPDU

    The High Power Duplexer is an RF module with the requirement to save antennas in the

    TX path. For FICOM use two antennas per cell are necessary for RX diversity and oneantenna is necessary for TX.

    The main functions of HPDU is combining RX and TX signal. In the TX path the HPDU

    is filtering the TX signals coming from the shelter and feeding them to the TX/RX anten-

    na. In the RX path the function is filtering the incoming signal.

    The HPDU is placed between antenna and FICOM/DIAMCO. The cabling is described

    in Tab. 1.12.

    1.4.5 Antenna Multicoupling

    Multicoupling can be done by DIAMCO, (F)DUAMCO or COAMCO. Each DIAMCO /

    (F)DUAMCO / COAMCO can drive as many CUs as RX output connectors are available.

    Cell 1Cell 0

    Base free Expansion Base

    Mounting Location

    Slot/ FICOMNumber 0 1 2 3

    ANTOUT

    TESTOUT

    RF EXP

    TX0 TX1

    ANTOUT

    TESTOUT

    RF EXP

    TX0 TX1 TX0 TX1

    RF EXP

  • 8/12/2019 bs241it

    34/130

  • 8/12/2019 bs241it

    35/130

    A30808-X3247-M357-3-7630 35

    Installation TestBase Transceiver Station Equipment

    ITMN:BTSE BS-241 / 241 II

    "X": any position allowed

    Fig. 1.17 View of DIP Switch (Factory Setting)

    TMA on / MUCO mode on X X X

    attenuator LNA 0 dB off X X X

    attenuator LNA 0 dB on off off off

    attenuator LNA 1 dB on on off off

    attenuator LNA 2 dB on off on off

    attenuator LNA 3 dB on on on off

    attenuator LNA 4 dB on off off on

    attenuator LNA 5 dB on on off on

    attenuator LNA 6 dB on off on on

    attenuator LNA 7 dB on on on on

    factory setting off off off off

    iSwitch 1 does not work when a TMA Alarm is present.

    Function Switch1

    Switch2

    Switch3

    Switch4

    Tab. 1.13 Switch Settings for DIAMCO/(F)DUAMCO

    1 2 3 4

    off off off off

  • 8/12/2019 bs241it

    36/130

    36 A30808-X3247-M357-3-7630

    ITMN:BTSE BS-241 / 241 II Installation TestBase Transceiver Station Equipment

    1.4.5.2 DUAMCO / FDUAMCO

    Fig. 1.18 (F)DUAMCO DIP Switch and Antenna Connection (Example)

    The switch settings for (F)DUAMCO is the same as for DIAMCO, described in

    Tab. 1.13.

    1.4.5.3 Cascadation of Multicouplers

    For supplying more receiver inputs, the multicoupler can be cascaded in order to save

    Antennas in the RX path. Cascading can be done twice, the possible configurations are

    shown in Tab. 1.14.

    The chain goes from antenna to BTSE, so the first device is the one nearest to the an-

    tenna. The Parameter LNAPRED has to be set if there is a TMA installed to activate the

    TMA. If there is no TMA, LNAPRED has to be set only for the 1. and 2. Cascadation.

    1 2 3 4

    DIP Switch

    (hidden behind plate)

    Antenna Connector

    First Device 1. Cascadation 2. Cascadation

    DIAMCO DIAMCO

    DIAMCO DIAMCO DIAMCO

    (F)DUAMCO DIAMCO

    Tab. 1.14 Cascading of Multicouplers

    http://bsplcml.pdf/http://bsplcml.pdf/
  • 8/12/2019 bs241it

    37/130

  • 8/12/2019 bs241it

    38/130

    38 A30808-X3247-M357-3-7630

    ITMN:BTSE BS-241 / 241 II Installation TestBase Transceiver Station Equipment

    1.4.6.1 Boot Software (FW)

    Some modules contain special on board boot software on EEPROMs.

    The allocation of the EPROMs is listed in the Release Note. The new boot software can

    be downloaded via LMT.

    1.4.6.2 Software Images SWI

    Some modules receive the SWI via the LMT.

    1.4.6.3 Switch Settings on ACT

    For switch settings please see HW:BTSE Modules, ACTP .

    Module Board FILE NAME

    COBA COBA2P8 btbbcx01.swi

    COBA4P12 btbbcx03.swi

    CU CUxxx btbbix01.swi

    ECU/FCU btbbix07.swi

    GCU btbbix10.swi

    Tab. 1.16 Boot Software

    OBJECT FILE NAME

    SWL HSxxxxxx.SWL

    depending on variant of ciphering

    VAM VSxxxxxx.VAM

    depending on variant of ciphering

    COBA2P8 BTSBCX01.SWI

    COBA4P12 BTSBCX03.SWI

    CU BTSBIX01.SWI

    ECU/FCU BTSBIX07.SWI

    Tab. 1.17 Software Images SWI

    http://modules.pdf/http://modules.pdf/
  • 8/12/2019 bs241it

    39/130

    A30808-X3247-M357-3-7630 39

    Installation TestBase Transceiver Station Equipment

    ITMN:BTSE BS-241 / 241 II

    1.4.6.4 Switch Settings on COBA2P8

    The COBA contains three transceiver submodules for 75, 100 , or 120 impedance

    matching.

    Fig. 1.19 COBA

    Port 1

    S1

    Port 2

    S2

    External ClockSynchronization

  • 8/12/2019 bs241it

    40/130

  • 8/12/2019 bs241it

    41/130

    A30808-X3247-M357-3-7630 41

    Installation TestBase Transceiver Station Equipment

    ITMN:BTSE BS-241 / 241 II

    1.4.6.5 Switch Settings on COBA4P12

    Fig. 1.22 COBA4P12

    External ClockSynchronization

    iSettings for port 0 up to port 7 are made with the LMT.

    For example:

    Create BPORT:NAME=BPORT:0,L1PT=pcm30crc4,L1RAT=ProtocolSignal-

    ling,LCONF=star,LIMP=Imp100or120Ohm;

  • 8/12/2019 bs241it

    42/130

    42 A30808-X3247-M357-3-7630

    ITMN:BTSE BS-241 / 241 II Installation TestBase Transceiver Station Equipment

    External Clock Synchronization

    Fig. 1.23 External Clock Synchronization

    Impedance Switch 1 Switch 2 Switch 3 Switch 4 Switch 5 Switch 6 Switch 7 Switch 8

    75coaxial pair on off off on on on off off

    100 balanced twisted pair off on off off on on off off

    120 balanced twisted pair off off on off on on off off

    high (TTL) f < 100 kHz off off off on off off off off

    high (TTL) f > 100 kHz off off off on on on off off

    ON

    ON

    ON

    ON

    ON

    1 4 5 632

    1 4 5 632

    1 4 5 632

    1 4 5 632

    1 4 5 632

    TL f > 100kHz

    TL f < 100kHz

    75

    100

    120

    7 8

    7 8

    7 8

    7 8

    7 8

  • 8/12/2019 bs241it

    43/130

    A30808-X3247-M357-3-7630 43

    Installation TestBase Transceiver Station Equipment

    ITMN:BTSE BS-241 / 241 II

    1.4.6.6 Switch Settings on COSA

    Fig. 1.24 COSA

    Port 5

    S5

    Port 6

    S6

    Port 4

    S4

    Port 3

    S3

    Port 2

    S2

    Port 1

    S1

  • 8/12/2019 bs241it

    44/130

    44 A30808-X3247-M357-3-7630

    ITMN:BTSE BS-241 / 241 II Installation TestBase Transceiver Station Equipment

    Fig. 1.25 Switch Settings of Port 1 to Port 6

    Impedance Switch 1 Switch 2 Switch 3 Switch 4 Switch 5 Switch 6

    PCM30 120 off off off off off off

    PCM30 75 on on on off off off

    PCM24 100 off off off on on on

    ON

    1 4 5 632

    ON

    1 4 5 632

    ON

    1 4 5 632

    PCM30 120 PCM30 75 PCM24 100

  • 8/12/2019 bs241it

    45/130

    A30808-X3247-M357-3-7630 45

    Installation TestBase Transceiver Station Equipment

    ITMN:BTSE BS-241 / 241 II

    1.4.6.7 Switch Settings on DCBCTRL

    Fig. 1.26 DIP Switches for Battery Type, Battery Capacities and Slot-ID

    Battery Type

    Select a proper characteristic curve for battery charging.

    Selectable Battery Capacities

    Selectable Slot-ID

    Selectable Battery Type

  • 8/12/2019 bs241it

    46/130

  • 8/12/2019 bs241it

    47/130

  • 8/12/2019 bs241it

    48/130

    48 A30808-X3247-M357-3-7630

    ITMN:BTSE BS-241 / 241 II Installation TestBase Transceiver Station Equipment

    8. Creation of HW related MO

    9. Create BPORT

    10. Create Xconnect

    11. Set attributes for BTSE

    12. Backup generation

    13. BTSE phase 3

    14. Offline tests

    Finally all documents must be filled in and all activities must be confirmed by the cus-

    tomer.

    1.5.1 Recommended Test Equipment and Tools

    Several devices, instruments, accessories, and utensils must be

    provided and prepared for commissioning on site.

    1.5.1.1 Test Equipment

    The equipment, especially the available options change quickly. Therefore, the listedequipment may not be currently available. It is suggested that the equipment listed be-

    low or equivalent must be present for call simulation and verification of correct operation.

    Local Maintenance Terminal LMT

    For detailed requirements, refer to manual OGL:LMT Evolution.

    Spectrum Analyzer with GSM Measuring Functions

    HW:

    for example: HP8594A/E

    Option: 004/010/021/101/102/105

    SW:

    GSM 850 - 900: HP 85715B Personality Card

    GSM 1800: HP 85722B Personality Card

    GSM 1900: Option 20 for HP 85722B Personality Card

    Cable:

    RF cables with NN connectors

    RF cables with NSMA connectors

    RF cables with SMCSMA connectors

    Adapter:

    N_maleSMA_female

    7/16"_maleN_female

    http://ogllmtev.pdf/http://ogllmtev.pdf/
  • 8/12/2019 bs241it

    49/130

    A30808-X3247-M357-3-7630 49

    Installation TestBase Transceiver Station Equipment

    ITMN:BTSE BS-241 / 241 II

    RF Termination

    Depending on the BTSE and the equipped modules, some RF terminations must be

    present.

    Mobile Station MS

    Multimeter

    1.5.1.2 Tools

    Special tools for commissioning activities on site are listed below.

    Antistatic Set

    for ESD Module Handling

    SMA Tool

    with torque wrench for semi-rigid/flexi Cable Connectors

    SMC Tool

    with torque wrench for semi-rigid/flexi Cable Connectors

    Semi-Rigid Bending Tool

    for semi-rigid cable connection

    TDMA Measuring Tools (Tests with HP 8594A/E) and Trigger Adapter

    TX:

    50SMA ((F)DUAMCO,FICOM)

    RX:

    50SMC (DIAMCO,(F)DUAMCO)

    RXCA:

    50SMA (DIAMCO cascading output)

    HW:

    GSM 900 / 1800 mobile phone, e.g. S45

    GSM 1900 mobile phone, e.g. S55 Test Plug-In SIM

    HW:

    SIEMENS Multimeter

    HW:

    GSM 1900: HP 8594 Personality Card

    2 Measuring cables with BNC-Plugs male (sufficient length)

    Adapter SMA maleBNC female

    Trigger Adapter TAD-L S30861-U2003-X-*

    (100-pins AMP-Plug with 4 x BNC-Plug female

    1 Adapter N-Connector maleBNC female

    HP 8590 series spectrum analyzer operating manual

    Users Guide HP85715B GSM 850 - 900 Transmitter Measurement Person-

    ality Users Guide HP 85722B GSM 1800 Transmitter Measurement Personality

  • 8/12/2019 bs241it

    50/130

    50 A30808-X3247-M357-3-7630

    ITMN:BTSE BS-241 / 241 II Installation TestBase Transceiver Station Equipment

    1.5.2 Preparation and Presetting of Test Equipment

    1.5.2.1 Test Equipment

    For minimum test time and correct test results, the devices must be prepared on site.

    Spectrum Analyzer

    RF Termination

    1.5.2.2 Software (SW)

    For all tests, only released SW (corresponding to the BTSE HW/SW release) is allowed

    to be running on the test equipment (TE).

    1.5.2.3 Boot Software/Firmware (SW/FW)

    For all tests, only the released SW is allowed to be running on the BTSE corresponding

    to the BTSE HW/SW/FW release/revision.

    1.5.3 BTSE Power ON

    1.5.3.1 Breakers

    Depending on the configuration of equipped modules, only the corresponding breakers

    have to be switched on. For the Base Shelter see Tab. 1.3, for the Extension Shelter

    see Tab. 1.4.

    All other breakers are switched off.

    HW: The HP8594A/E needs a warm-up time of 20 minutes depending on the

    available options.

    The display shows "OVEN COLD" during the heating phase. Afterwards a CAL-

    IBRATION must be carried out for defined measurement execution (Remove

    trigger signal from "Gate Trigger Input" while performing calibration).

    SW: The SW of the GSM 850 - 900/GSM 1800 card must be installed in ad-

    vance.

    Cable: For special tests, e.g. "Power versus Time", a BNC loop at thebackplane must be provided:

    GATE-OUTPUT (TTL) to EXTERN TRIGGER INPUT

    The cable from T-Frame (TAD-L) to GATE-INPUT (TTL)

    for TDMA-FRAME Trigger must be connected.

    See the analyzer operating manual for more detailed information.

    HW: Before RF measurements are executed, the following connectors must be

    terminated with 50 SMA/SMC resistors:

    TX: open FICOM/(F)DUAMCO inputs (SMA)

    RX: open (F)DUAMCO / DIAMCO outputs (SMC) RXCA: open (F)DUAMCO / DIAMCO outputs (SMA)

    TESTOUT: open (F)DUAMCO/FICOM outputs (SMA)

    iIn case of supervising all breakers with one common alarm sensor, all breakers have

    to be switched on, independent of the configuration.

  • 8/12/2019 bs241it

    51/130

    A30808-X3247-M357-3-7630 51

    Installation TestBase Transceiver Station Equipment

    ITMN:BTSE BS-241 / 241 II

    1.5.3.2 LED Indication

    The following LED description is only valid for the software installation.

    The modules have the normal LED indication set as shown below for normal operation.

    1. DIAMCO

    2. FICOM

    3. DUAMCO / FDUAMCO

    4. CU

    R red

    G green

    fl(R) flashing red

    fl(G) flashing green

    o off

    OK o o AL

    OK G o RS

    FICOM (base module) FIBLUB2 * V4

    TNF ALM o o TNF ALM

    G DC ON

    VSWR o o RESET

    FICOM (expansion module) FIBLUX2 * V4TNF ALM o o TNF ALM

    G DC ON

    o RESET

    FICOM (base module) FIBLUB2 * V3

    VSWR ALM o o TNF ALM 0

    DC ON G o TNF ALM 1

    RESET o

    FICOM (expansion module) FIBLUX2 * V3

    o TNF ALM 0DC ON G o TNF ALM 1

    TMA 0 o o TMA 1

    RESET o o o RESET 1

    VSWR 0 o o VSWR 1

    POWER 0 G G POWER 1

    OK fl(G) o SW

    RES o R PA

  • 8/12/2019 bs241it

    52/130

    52 A30808-X3247-M357-3-7630

    ITMN:BTSE BS-241 / 241 II Installation TestBase Transceiver Station Equipment

    4. FlexCU

    5. COBA2P8

    5. COBA4P12

    6. COSA6P16

    6. COSA4P12

    7. ACT

    OK fl(G) o RES

    SW 0 o o SW 1

    PA 0 R R PA 1

    ACT fl(G) fl(R) RCOBA

    FLOC o o HMO

    ABIS 1 o o ABIS 2

    ACT fl(G) fl(R) RCOBA

    FLOC o o HMO

    ABIS 1 o o ABIS 2

    ABIS 3 o o ABIS 4

    ACT fl(G) fl(R) RCOSA

    ABIS 7 o o ABIS 8

    ABIS 5 o o ABIS 6

    ABIS 3 o o ABIS 4

    ACT fl(G) fl(R) RCOSA

    ABIS 5 o o ABIS 6

    ABIS 7 o o ABIS 8

    To be activated by SW o o Reset ofC

  • 8/12/2019 bs241it

    53/130

    A30808-X3247-M357-3-7630 53

    Installation TestBase Transceiver Station Equipment

    ITMN:BTSE BS-241 / 241 II

    2 Tasklist

    2.1 SW Download and Activation

    The SW has to be downloaded from the LMT to the BTSE . . . . . . . . . . . . . . . . . . . . (see 3.1)

    2.2 Shelter

    The Sheltertype has to be defined . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . (see 3.2)

    2.3 Creation of HW Related Managed Objects

    Each HW related managed object has to be created separately.. . . . . . . . . . . . . . . . (see 3.3)

    2.4 Setting attributes for BTSEThe attributes for the BTSE have to be set. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . (see 3.18)

    2.5 BPORT

    The PCM line configurations must be determined . . . . . . . . . . . . . . . . . . . . . . . . . . . (see 3.19)

    2.6 XConnect

    The Cross Connect has to be defined . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . (see 3.20)

    2.7 BTSMSettings for the A-bis have to be set. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . (see 3.21)

    2.8 LAPDLE

    Enter values for LAPD Channel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . (see 3.22)

    2.9 CORE Redundancy

    Enable the CORE Redundancy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . (see 3.23)

    2.10 Check the State of all ModulesCheck the state of all modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . (see 3.24)

    2.11 Changing the BTSE to Phase 3

    Change the BTSE from phase 2 to 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . (see 3.29)

  • 8/12/2019 bs241it

    54/130

    54 A30808-X3247-M357-3-7630

    ITMN:BTSE BS-241 / 241 II Installation TestBase Transceiver Station Equipment

  • 8/12/2019 bs241it

    55/130

    A30808-X3247-M357-3-7630 55

    Installation TestBase Transceiver Station Equipment

    ITMN:BTSE BS-241 / 241 II

    3 Procedures

  • 8/12/2019 bs241it

    56/130

    56 A30808-X3247-M357-3-7630

    ITMN:BTSE BS-241 / 241 II Installation TestBase Transceiver Station Equipment

  • 8/12/2019 bs241it

    57/130

    A30808-X3247-M357-3-7630 57

    Installation TestBase Transceiver Station Equipment

    ITMN:BTSE BS-241 / 241 II

    3.1 SW Download and Activation

    1 Reset of Core Basis COBA

    Switch off the right pair of CORE modules (COBA and COSA) with the breaker

    concerned on the DC-Panel.

    Reset the left COBA with the push button on the board.

    After about 15 seconds, the COBA reaches the start connection status.

    2 Connect LMT CableConnect the LMT cable to the LMT 15-pin SUB-D connector on the DC-Panel.

    3 Log on LMTb To log on LMT:

    1. Start the LMT program in the corresponding directory of the Start menu

    (Start:\Programs\LMT Evolution (string of version)\LMT Evolution).

    2. Enter your user ID and password in the appearing LogOn window.

    3. Click on the OK button.

    iStarting with BR7.0, a second LMT software is available: the new LMT Evolution. For

    logging on the LMT Evolution, refer to the operator guidelines OGL:LMT Evolution.

    iA directory for the software to be downloaded must be present on the harddisk of the

    LMT containing all files of the relevant software load.

    The V.11/X.21 interface (HDLC-Adapter, DLHC) has been installed and tested in ad-

    vance.

    LED indication of COBA:

    ACT fl(G) R RCOBA

    FLOC o(R) o(R) HMO

    ABIS 1 o(R) o(R) ABIS 2

    System Response:

    Several changed state event reports follow. They can be examined in the Mes-

    sage Viewer window.

    The BTSE is now in phase 1. In this phase, you can download and activate the

    Software.

    http://ogllmtev.pdf/http://ogllmtev.pdf/
  • 8/12/2019 bs241it

    58/130

    58 A30808-X3247-M357-3-7630

    ITMN:BTSE BS-241 / 241 II Installation TestBase Transceiver Station Equipment

    4 SW DownloadPerform the following steps:

    b BSSNE Btsep Br:

    MANAGED-ELEMENT

    SOFTWARE-MANAGEMENT

    DNLALLEXE

    DNLALLEXE:SRCDIR="\hs010808",OVERWRITE=YES;

    The LMT performs an automatic logoff after a few minutes. If the session is

    closed, please log on again.

    5 SW Activationb BSS

    NE Btsep Br:

    BSS-FUNCTIONAL

    BTSMBTSM:

    ACTIVATE BTSM

    ACTIVATE BTSM:NAME=BTSM:0,FILEID="hs010808.swl",FILESWV="01-01-

    08-00-08-00_98-08-21"

    System Response:

    In the Message Viewer window, the command result is displayed: Operation

    successful. The session will be closed.

    System Response:

    Several messages are displayed that provide information on the progress and

    the end of the download for each file.

    LED indication of COBA:

    ACT fl(G) o(R) RCOBA

    FLOC o(R) o(R) HMO

    ABIS 1 o(R) o(R) ABIS 2

    http://bsplcml.pdf/http://bsplcml.pdf/http://bsplcml.pdf/http://bsplcml.pdf/
  • 8/12/2019 bs241it

    59/130

    A30808-X3247-M357-3-7630 59

    Installation TestBase Transceiver Station Equipment

    ITMN:BTSE BS-241 / 241 II

    6 Log On LMTb To log on LMT:

    1. Click on the LogOn icon on the tool bar.

    2. Enter your user ID and password in the appearing LogOn window.

    3. Click on the OK button.

    END

    System Response:

    The BTSE is now in phase 2. In this phase, the operation & maintenance soft-

    ware and the call processing software is running, but the BTSE is not yet con-

    nected to the BSC. Call processing is disabled.

  • 8/12/2019 bs241it

    60/130

    60 A30808-X3247-M357-3-7630

    ITMN:BTSE BS-241 / 241 II Installation TestBase Transceiver Station Equipment

    3.2 Rack

    The first step of the creation of the HMO is the creation of the shelter.

    Only the Base Shelter is automatically created, but the shelter type have to be set.

    The Extension/Service Shelter have to be created and the shelter type have to be set

    too.

    The Shelter numbering is described in the introduction (1.2.1).

    1 Rack Creation ......(see OGL:LMTEvolution)

    The following action has to be repeated for each shelter of the BTSE.

    b BSSNE Btsep Br:

    BSS-EQUIPMENT

    BTSEP

    BTSEP:

    RACK

    CREATE RACK

    NAME=RACK:

    TYPRACK=(see below)

    Racktype: Choose the BTSE Type that has to be installed

    BS-241 for Base Shelter (no. 0) or Extention Shelter (no. 1/2)

    BS-241SR for the Service Shelter (no. 3 ...7)

    Create RACK:NAME=RACK:,TYPRACK=BS241;

    END

    System Response:

    The command is acknowledged (ACK).

    Several changed state event reports follow. They can be examined in the Mes-

    sage Viewer window.

    http://ogllmtev.pdf/http://ogllmtev.pdf/http://bsplcml.pdf/http://ogllmtev.pdf/http://ogllmtev.pdf/http://bsplcml.pdf/
  • 8/12/2019 bs241it

    61/130

  • 8/12/2019 bs241it

    62/130

    62 A30808-X3247-M357-3-7630

    ITMN:BTSE BS-241 / 241 II Installation TestBase Transceiver Station Equipment

    Now proceed with the following creation procedures. h...Procedure: 3.4

    END

    For finding the mounting position of the MOs and modules in the rack see: MMN:BTSE BS-241 / 241 II

    Base Rack/Shelter Extension Rack/Shelter Service 1 Rack/Shelter Service 2 Rack/Shelter

    http://bs241mt.pdf/http://bs241mt.pdf/http://bs241mt.pdf/http://bs241mt.pdf/http://bs241mt.pdf/http://bs241mt.pdf/http://bs241mt.pdf/
  • 8/12/2019 bs241it

    63/130

    A30808-X3247-M357-3-7630 63

    Installation TestBase Transceiver Station Equipment

    ITMN:BTSE BS-241 / 241 II

    3.4 ACDCP

    iThe HMO "ACDCP"is realized by the module "DCBCTRL".

    iFor BS-241 systems, ACDCP and BATTERY objects can only be created in a Service1

    Shelter (Rack # 3), although the battery hardware may also be located in a Service2

    Shelter (Racks # 4 ... 7).

    For BS-241 II systems, ACDCP and BATTERY objects can not be created at all, since

    this is not necessary in these systems.

    The AC/DC and battery function in a BS-241 II system is monitored via the 4 following

    environmental alarms (see also Create the Alarm Configuration (ENVABTSE)):

    - Mains Breakdown (MBR)

    - Battery Breakdown (BBR)

    - Battery Charger Fault (BCHF)

    - DC Voltage out of Tolerance (48OTB)

    In order to use the feature "emergency configuration", the associatedString (ASTRING)

    for the alarm "Mains Breakdown" (MBR) must be exactly ##ACDC_FAULT.

    The four above alarm connections are provided with a normally closed relay contact.

    Therefore each of these 4 alarms are to be configured as High Active.

    Example:

    CREATE ENVABTSE:NAME=RACK:4/ENVABTSE:2, INTINF=high,

    ASEV=DEFAULT_DB, ASTRING="##ACDC_FAULT";

  • 8/12/2019 bs241it

    64/130

    64 A30808-X3247-M357-3-7630

    ITMN:BTSE BS-241 / 241 II Installation TestBase Transceiver Station Equipment

    1 ACDCP Creation ......(see OGL:LMTEvolution)

    The following action must be repeated for all equipped modules.

    b BSSNE Btsep Br:

    BSS-EQUIPMENT

    BTSEP

    BTSEP:

    RACK

    RACK:

    ACDCP

    CREATE ACDCP

    NAME=ACDCP:

    For the Service 1 Rack, the rack number is 3.

    Create ACDCP:NAME=RACK:/ACDCP:;

    END

    System Response:

    The command is acknowledged (ACK).

    Several changed state event reports follow. They can be examined in the Mes-

    sage Viewer window.

    http://ogllmtev.pdf/http://ogllmtev.pdf/http://bsplcml.pdf/http://ogllmtev.pdf/http://ogllmtev.pdf/http://bsplcml.pdf/
  • 8/12/2019 bs241it

    65/130

    A30808-X3247-M357-3-7630 65

    Installation TestBase Transceiver Station Equipment

    ITMN:BTSE BS-241 / 241 II

    3.5 ACT

    In the Sheltertypes can be installed different ACTs (1.3.3). To activate the Alarm Collec-

    tion Terminal the HMO ACT has to be created in each Extension/Service Shelter.

    In the Base Shelter ACT has only to be created in case of installed ACTM!

    1 ACT Creation ......(see OGL:LMTEvolution)

    b BSSNE Btsep Br:

    BSS-EQUIPMENT

    BTSEP

    BTSEP:

    RACK

    RACK:

    ACT

    CREATE ACT

    NAME=ACT:

    Check the correct Shelternumbering. ......(see 1.2.1)

    CREATE ACT:NAME=RACK:/ACT:;

    END

    iSet the correct Shelter adress for each Shelter as described in HW:BTSE Modules,

    ACTP .

    System Response:

    The command is acknowledged (ACK).

    Several changed state event reports follow. They can be examined in the Mes-

    sage Viewer window.

    http://ogllmtev.pdf/http://ogllmtev.pdf/http://bsplcml.pdf/http://modules.pdf/http://modules.pdf/http://ogllmtev.pdf/http://ogllmtev.pdf/http://modules.pdf/http://modules.pdf/http://bsplcml.pdf/
  • 8/12/2019 bs241it

    66/130

    66 A30808-X3247-M357-3-7630

    ITMN:BTSE BS-241 / 241 II Installation TestBase Transceiver Station Equipment

    3.6 Battery

    iThe battery hardware may be located in a Service1 Shelter (Rack # 3) and / or

    Service2 Shelter (Rack # 4 ... 7).

    iFor BS-241 systems, ACDCP and BATTERY objects can only be created in a Service1

    Shelter (Rack # 3), although the battery hardware may also be located in a Service2

    Shelter (Racks # 4 ... 7).

    For BS-241 II systems, ACDCP and BATTERY objects can not be created at all, since

    this is not necessary in these systems.

    The AC/DC and battery function in a BS-241 II system is monitored via the 4 following

    environmental alarms (see also Create the Alarm Configuration (ENVABTSE)):

    - Mains Breakdown (MBR)

    - Battery Breakdown (BBR)

    - Battery Charger Fault (BCHF)

    - DC Voltage out of Tolerance (48OTB)

    In order to use the feature "emergency configuration", the associatedString (ASTRING)

    for the alarm "Mains Breakdown" (MBR) must be exactly ##ACDC_FAULT.

    The four above alarm connections are provided with a normally closed relay contact.

    Therefore each of these 4 alarms are to be configured as High Active.

    Example:

    CREATE ENVABTSE:NAME=RACK:4/ENVABTSE:2, INTINF=high,

    ASEV=DEFAULT_DB, ASTRING="##ACDC_FAULT";

  • 8/12/2019 bs241it

    67/130

    A30808-X3247-M357-3-7630 67

    Installation TestBase Transceiver Station Equipment

    ITMN:BTSE BS-241 / 241 II

    1 Battery Creation ......(see OGL:LMTEvolution)

    b BSSNE Btsep Br:

    BSS-EQUIPMENT

    BTSEP

    BTSEP:

    RACK

    RACK:

    BATTERY

    CREATE BATTERY

    NAME=BATTERY:

    Check the correct rack numbering.

    In case of BS-241 systems, all BATTERY objects must be created in Rack # 3.

    In case of BS-241 II systems, the BATTERY objects are not created at all.

    CREATE BATTERY:NAME=RACK:/BATTERY:;

    END

    System Response:

    The command is acknowledged (ACK).

    Several changed state event reports follow. They can be examined in the Mes-

    sage Viewer window.

    http://ogllmtev.pdf/http://ogllmtev.pdf/http://bsplcml.pdf/http://ogllmtev.pdf/http://ogllmtev.pdf/http://bsplcml.pdf/
  • 8/12/2019 bs241it

    68/130

    68 A30808-X3247-M357-3-7630

    ITMN:BTSE BS-241 / 241 II Installation TestBase Transceiver Station Equipment

    3.7 COSA

    For COBA2P8 in connection with COSA6P16:(For COBA4P12/COSA4P12 see be-

    low)

    The COSA has to be created for using more than two PCM lines or more than 8 CUs,

    also for using the cross connect function. For a BS-241 / 241 II there can be 8 PCM lines

    connected. PCM line 1 and 2 are supplied by COBA. For the PCM lines 3 - 8 COSA has

    to be installed.

    For COBA4P12 in connection with COSA4P12:(For COBA2P8/COSA6P16 see

    above)

    The COSA must be created to use more than four PCM lines or if an Extension Shelter

    is installed. For a BS-241 / 241 II, there can be 8 PCM lines connected. PCM line 1 to 4

    are supplied by COBA. For the PCM lines 58, the COSA must be installed.

    1 COSA Creation ......(see OGL:LMTEvolution)

    b BSSNE Btsep Br:

    BSS-EQUIPMENT

    BTSEP

    BTSEP:

    RACK

    RACK:

    COSA

    CREATE COSA

    NAME=COSA:

    COSA can only be installed in Base Shelter, the shelter number is 0.

    CREATE COSA:NAME=RACK:/COSA:;

    END

    i In case of core redundancy two COSAs have to be created.Repeat this procedure twice for COSA 0 and COSA 1.

    System Response:

    The command is acknowledged (ACK).

    Several changed state event reports follow. They can be examined in the Mes-

    sage Viewer window.

    http://ogllmtev.pdf/http://ogllmtev.pdf/http://bsplcml.pdf/http://ogllmtev.pdf/http://ogllmtev.pdf/http://bsplcml.pdf/
  • 8/12/2019 bs241it

    69/130

    A30808-X3247-M357-3-7630 69

    Installation TestBase Transceiver Station Equipment

    ITMN:BTSE BS-241 / 241 II

    3.8 CU

    For creation of FlexCUs continue with Chapter FlexCU.

    In the Base Shelter and Extension Shelters can be equipped with 8 CUs each. For more

    than 8 CUs per BS-241 / 241 II,the module COSA has to be created.

    1 CU Creation ......(see OGL:LMTEvolution)

    The following action must be repeated for all equipped modules.

    b BSSNE Btsep Br:

    BSS-EQUIPMENT

    BTSEP

    BTSEP:

    RACK

    RACK:

    CU

    CREATE CU

    NAME=CU:

    RXLEVADJ adjustValue= adjustDivValue= (see below)

    TXLEVADJ= (see below)

    Check the correct rack number. ......(see 1.2.1)

    iThe module CU may also be an EDGE CU (ECU) or a GMSK CU (GCU)!

    iIt is possible to use ECUs, GCUs or FlexCUs, but please note the following:

    Since the GSM 1800 GCU has more RF output power than the GSM 1800 CU, mixed

    cell configurations might result in slight changes of some performance counters and

    CU dependent coverage. It is not recommended to use the antenna hopping mode in

    this configuration.

    i In case of a change from CUs to ECUs in the BS-241 II, the 60A-MSU must bechanged to 80A-MSU (Not BS-241 II DC, in that case the 100A-MSU remains).

    iThe ECU can be configured with (F)DUAMCO modules only.

    http://ogllmtev.pdf/http://ogllmtev.pdf/http://bsplcml.pdf/http://ogllmtev.pdf/http://ogllmtev.pdf/http://bsplcml.pdf/
  • 8/12/2019 bs241it

    70/130

    70 A30808-X3247-M357-3-7630

    ITMN:BTSE BS-241 / 241 II Installation TestBase Transceiver Station Equipment

    ......(see TED: BS-24x)

    Create CU:NAME=RACK:/CU:,RXLEVADJ=-,TXLE-VADJ=;

    END

    The parameter RXLEVADJ must be set in case of different cable length in the

    RX path. Default value for adjustVal = 0, adjustDivValue = 0. Adjustable values

    are:

    RXLEVADJadjustValue: -24.0 ... 24.0 in steps of 1.0

    adjustDivValue: -24.0 ... 24.0 in steps of 1.0

    TXLEVADJ

    Adjustable values are:

    TXLEVADJ: -63.0 ... 63.0 in steps of 1.0

    The following formula is used to determine this value:

    TXLEVADJ = attenuation factor of the used combiner + attenuation factor of RF

    cable.

    Note: use values without minus/plus sign for the formula!

    Example:

    Combiner: -1.5 dB

    Cable: -0.5 dB

    (1.5 dB) + (0.5 dB) = 2 dB means TXLEVADJ=2

    See TED: BS-24x for typical attenuation factors in the TX path.

    The command is acknowledged (ACK).

    System Response:

    Several CHANGED STATE EVENT REPORTs will follow. They can be exam-

    ined in the Message Viewer window.

    The LED indication changes to

    OK fl(G) o SW

    RES o R PA

    http://ted24x.pdf/http://ted24x.pdf/http://ted24x.pdf/http://ted24x.pdf/
  • 8/12/2019 bs241it

    71/130

    A30808-X3247-M357-3-7630 71

    Installation TestBase Transceiver Station Equipment

    ITMN:BTSE BS-241 / 241 II

    3.9 ECU

    ECU is a Carrier Unit for the EDGE technology.For creation continue with procedure: h 3.8 "CU"

  • 8/12/2019 bs241it

    72/130

    72 A30808-X3247-M357-3-7630

    ITMN:BTSE BS-241 / 241 II Installation TestBase Transceiver Station Equipment

    3.10 FlexCU

    In the Base Shelter and Extension Shelters can be equipped with 8 CUs each. For more

    than 8 CUs per BS-241 / 241 II,the module COSA has to be created.

    1 FCUMAIN Creation ......(see OGL:LMTEvolution)

    The following action must be repeated for all equipped modules.

    b BSSNE Btsep Br:

    BSS-EQUIPMENT

    BTSEP

    BTSEP:

    RACK

    RACK:

    FCUMAIN

    CREATE FCUMAIN

    NAME=FCUMAIN:

    FCUMODE= (single or double CU mode)

    RXLEVADJ adjustValue= adjustDivValue= (see below)

    RXLEVADJN1D1 adjustValueN1= adjustDivValueD1= (see be-

    low)

    Check the correct shelter number. ......(see 1.2.1)

    The FlexCU is a Carrier Unit for two carriers, this allows aflexible switching between high coverage and high capacity

    cells in one rack.

    For creation of CU, ECU or GCU continue with procedure: h 3.8 "CU"

    iIt is possible to use CUs, ECUs, GCUs and FlexCUs in the same rack and the same

    cell,

    http://ogllmtev.pdf/http://ogllmtev.pdf/http://bsplcml.pdf/http://ogllmtev.pdf/http://ogllmtev.pdf/http://bsplcml.pdf/
  • 8/12/2019 bs241it

    73/130

    A30808-X3247-M357-3-7630 73

    Installation TestBase Transceiver Station Equipment

    ITMN:BTSE BS-241 / 241 II

    Create FCUMAIN:NAME=RACK:/FCUMAIN:,FCUMODE=,RXLEVADJ=-,RXLEVADJN1D1=-;

    2 FCUTR Creation

    The following action must be repeated for all equipped modules.

    b BSSNE Btsep Br:

    BSS-EQUIPMENT

    BTSEP

    BTSEP:

    RACK

    RACK:

    FCUTR

    CREATE FCUTR

    NAME=RACK:/FCUTR:

    TXLEVADJ= (see below)

    Check the correct shelter number. ......(see 1.2.1)

    The parameter RXLEVADJ must be set in case of different cable length in the

    RX path. Default value for adjustVal = 0, adjustDivValue = 0 Adjustable values

    are:

    RXLEVADJadjustValue: -24.0 ... 24.0 in steps of 1.0

    adjustDivValue: -24.0 ... 24.0 in steps of 1.0

    RXLEVADN1D1

    adjustValueN1: -24.0 ... 24.0 in steps of 1.0

    adjustValueD1: -24.0 ... 24.0 in steps of 1.0

    The command is acknowledged (ACK).

    System Response:

    Several CHANGED STATE EVENT REPORTs will follow. They can be exam-ined in the Message Viewer window.

    http://bsplcml.pdf/http://bsplcml.pdf/
  • 8/12/2019 bs241it

    74/130

    74 A30808-X3247-M357-3-7630

    ITMN:BTSE BS-241 / 241 II Installation TestBase Transceiver Station Equipment

    Create FCUTR:NAME=RACK:/FCUTR:,TXLEVADJ=;

    Administrative State = UNLOCKED

    Operational State = ENABLED

    Availability Status = NULL_value

    Alarm Status = cleared

    END

    TXLEVADJ

    Adjustable values are:

    TXLEVADJ: -63.0 ... 63.0 in steps of 1.0

    The command is acknowledged (ACK).

    System Response:

    Several CHANGED STATE EVENT REPORTs will follow. They can be exam-

    ined in the Message Viewer window.

    The LED indication changes to

    OK fl(G) o RES

    SW 0 o o SW 1

    PA 0 R R PA 1

  • 8/12/2019 bs241it

    75/130

    A30808-X3247-M357-3-7630 75

    Installation TestBase Transceiver Station Equipment

    ITMN:BTSE BS-241 / 241 II

    3.11 GCU

    GCU is a Carrier Unit for the GMSK technology only.For creation continue with procedure: h 3.8 "CU"

  • 8/12/2019 bs241it

    76/130

    76 A30808-X3247-M357-3-7630

    ITMN:BTSE BS-241 / 241 II Installation TestBase Transceiver Station Equipment

    3.12 FAN

    The Shelters can be equipped with 6 fans. During the creation of each fan the alarm for

    a defective fan is generated automatically.

    1 FANP Creation ......(see OGL:LMTEvolution)

    The following action must be repeated for all equipped modules.

    b BSSNE Btsep Br:

    BSS-EQUIPMENTBTSEP

    BTSEP:

    RACK

    RACK:

    FANP

    CREATE FANP

    NAME=FANP:

    CREATE FANP:NAME=RACK:/FANP:;

    END

    System Response:

    The command is acknowledged (ACK).

    Several changed state event reports follow. They can be examined in the Mes-

    sage Viewer window.

    http://ogllmtev.pdf/http://ogllmtev.pdf/http://bsplcml.pdf/http://ogllmtev.pdf/http://ogllmtev.pdf/http://bsplcml.pdf/
  • 8/12/2019 bs241it

    77/130

  • 8/12/2019 bs241it

    78/130

    78 A30808-X3247-M357-3-7630

    ITMN:BTSE BS-241 / 241 II Installation TestBase Transceiver Station Equipment

    1 DILNA Creation ......(see OGL:LMTEvolution)

    The following action must be repeated for all equipped modules.

    b BSSNE Btsep Br:

    BSS-EQUIPMENT

    BTSEP

    BTSEP:

    RACK

    RACK:

    DILNA

    CREATE DILNA

    NAME=DILNA:

    CELLNO=

    COMBMD= (see below)

    LNAPRED= (see below)

    predType=

    predRack=RACK

    predNo=

    SCELLNO=

    WDLNA= (see below)

    The combiner mode depends on the DIAMCO Type. Only the choice

    EightToTwo is possible.

    The LNAPRED must be activated in case of Cascading and TMA installed. The

    device that is installed before must be chosen.

    All CUs connected to DILNA have to be set as follows:CUxN = CU number x connected via the RX plug (normal RX path)

    CUxD = CU number x connected via the RXDIV plug (diversity RX path).

    Several entries are possible. ......1.4.5.3

    CREATE DILNA:NAME=RACK:/DILNA:,CELLNO=,COMB-

    MD=,LNAPRED=(-),

    SCELLNO=,WDLNA=;

    System Response:

    The command is acknowledged (ACK).

    Several changed state event reports follow. They can be examined in the Mes-

    sage Viewer window.

    http://ogllmtev.pdf/http://ogllmtev.pdf/http://bsplcml.pdf/http://ogllmtev.pdf/http://ogllmtev.pdf/http://bsplcml.pdf/
  • 8/12/2019 bs241it

    79/130

    A30808-X3247-M357-3-7630 79

    Installation TestBase Transceiver Station Equipment

    ITMN:BTSE BS-241 / 241 II

    Is a TMA installed? Y h...2N h...END

    2 DIDCTMA Creation

    The following action must be repeated for all equipped modules.

    b BSSNE Btsep Br:

    BSS-EQUIPMENT

    BTSEP

    BTSEP: