Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : [email protected] W: www.exova.com BS 8458:2015: Annex C Method for Measuring the Capability of a Watermist System to Control a Fire – “Room Fire Tests for Watermist Systems with Automatic Nozzles” A Report To: Plumis Document Reference: 356258 Date: 18th January 2016 Issue No.: 3 Page 1 This report in issued in accordance with our terms and conditions, a copy of which is available on request. Registered Office: Exova (UK) Ltd, Lochend Industrial Estate, Newbridge, Midlothian EH28 8PL United Kingdom. Reg No.SC 70429

BS 8458:2015: Annex C - Intelligent Mist · 2017-08-24 · ‑filled pipe should be used and in accordance with BS 8458: 2015: 6.1 (c) the nozzle, external to the room, should not

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: BS 8458:2015: Annex C - Intelligent Mist · 2017-08-24 · ‑filled pipe should be used and in accordance with BS 8458: 2015: 6.1 (c) the nozzle, external to the room, should not

Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom

T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : [email protected] W: www.exova.com

BS 8458:2015: Annex C

Method for Measuring the Capability of a Watermist System to Control a Fire – “Room Fire Tests for Watermist Systems with Automatic Nozzles” A Report To: Plumis Document Reference: 356258

Date: 18th January 2016

Issue No.: 3 Page 1

This report in issued in accordance with our terms and conditions, a copy of which is available on request.

Registered Office: Exova (UK) Ltd, Lochend Industrial Estate, Newbridge, Midlothian EH28 8PL United Kingdom. Reg No.SC 70429

Page 2: BS 8458:2015: Annex C - Intelligent Mist · 2017-08-24 · ‑filled pipe should be used and in accordance with BS 8458: 2015: 6.1 (c) the nozzle, external to the room, should not

BS 8458:2015: Annex C

Executive Summary Objective To demonstrate the capability of a watermist system to control a fire when tested

in accordance with BS 8458:2015: Annex C.

Generic Description Product reference Thickness / diameter / angle

Weight per unit area or density

Automist “Smartscan” targeted water mist fire suppression system

“Automist Smartscan System” Not applicable Not applicable

Individual components used to manufacture the system: Nozzle “Smartscan vertical flat 65º spray

nozzle” 65º flat cone Not applicable

Pipe “Production High Pressure Hose 150bar Working Pressure”

Internal: Ø 6.3mm External: Ø 11.5mm

Unable to provide

Pump “Production Pluvia Pump” Not applicable Not applicable Heat alarm “Ei164 Heat Alarm” Not applicable Not applicable Please see page 6 of this test report for the full description of the system tested

Test Sponsor Plumis, HMS President (1918), Victoria Embankment, London, EC4Y 0HJ

Test Results:

Thermocouple location Maximum temperature °C

Test 1

Test 2

Test 3

Test 4

Test 5

75mm below the underside of the ceiling 94 178 144 92 307 Ceiling temperature – 6.5mm above the

underside of the ceiling 36 39 36 36 45

1.6m above the floor, furthest from fire 38 80 67 43 71 1.6m above the floor, centre (if applicable) 35 80 138 69 104

1.6m above the floor, close to fire 32 62 68 37 67 Key: Test 1 – Room corner (Spray head on opposite wall) Test 2 – Room corner (Spray on same wall wall) Test 3 – Centre (Spray head on opposite wall) Test 4 – Centre (Spray head on opposite wall) Ventilation test Test 5 – Centre (Spray head on opposite wall) Open room test

Where the thermocouples were positioned at 1.6m above the floor, the temperatures did not exceed 55°C for any 120 s interval, during test 1, 2, 3, 4 & 5. The fire test maximum temperatures as defined in BS 8458:2015: Table 2 are detailed in Appendix 2.

Conclusion The temperatures during tests 1 and 2 were all declining 2 minutes after the nozzle operation (See Figures 1 and 2). The watermist system suppressed the fuel packages and met all the criteria specified in Clause 6.1 (a), (b) and Table 2 of BS 8458:2015.

Date of Test 29th July, 21st, 27th August 2015

Document No.: 356258 Page No.: 2 of 22

Author: T. Kinder Issue Date: 18th January 2016

Client: Plumis Issue No.: 3

Page 3: BS 8458:2015: Annex C - Intelligent Mist · 2017-08-24 · ‑filled pipe should be used and in accordance with BS 8458: 2015: 6.1 (c) the nozzle, external to the room, should not

BS 8458:2015: Annex C

Reason for Revision

This document replaces Issue 2 (dated 22nd December 2015) of the same number which has been withdrawn. Subsequent to the report being issued, the Draft BS 8458: 2014 DPC document has been re- issued as BS 8458:2015.The sponsor of the test has requested an updated report that references this new standard.

Signatories

Responsible Officer T. Kinder * Technical Officer

Authorised T. Mort * Senior Technical Officer

* For and on behalf of Exova Warringtonfire. Report Issued: 18th January 2016

This version of the report has been produced from a .pdf format electronic file that has been provided by Exova Warringtonfire to the sponsor of the report and must only be reproduced in full. Extracts or abridgements of reports must not be published without permission of Exova Warringtonfire.

Document No.: 356258 Page No.: 3 of 22

Author: T. Kinder Issue Date: 18th January 2016

Client: Plumis Issue No.: 3

Page 4: BS 8458:2015: Annex C - Intelligent Mist · 2017-08-24 · ‑filled pipe should be used and in accordance with BS 8458: 2015: 6.1 (c) the nozzle, external to the room, should not

BS 8458:2015: Annex C

CONTENTS PAGE NO.

EXECUTIVE SUMMARY ........................................................................................................................... 2

SIGNATORIES ........................................................................................................................................... 3

TEST DETAILS .......................................................................................................................................... 5

DESCRIPTION OF SYSTEM ..................................................................................................................... 6

TEST RESULTS ........................................................................................................................................ 7

APPENDIX 1 .............................................................................................................................................. 9

APPENDIX 2 ............................................................................................................................................ 10

Figure 1 .................................................................................................................................................... 11

Figure 2 .................................................................................................................................................... 12

Figure 3 .................................................................................................................................................... 13

Figure 4 .................................................................................................................................................... 14

Figure 5 .................................................................................................................................................... 15

Figure 6 .................................................................................................................................................... 16

Figure 7 .................................................................................................................................................... 17

Figure 8 .................................................................................................................................................... 18

Figure 9 .................................................................................................................................................... 19

Figure 10 .................................................................................................................................................. 20

PHOTOGRAPHS ..................................................................................................................................... 21

REVISION HISTORY ............................................................................................................................... 22

Document No.: 356258 Page No.: 4 of 22

Author: T. Kinder Issue Date: 18th January 2016

Client: Plumis Issue No.: 3

Page 5: BS 8458:2015: Annex C - Intelligent Mist · 2017-08-24 · ‑filled pipe should be used and in accordance with BS 8458: 2015: 6.1 (c) the nozzle, external to the room, should not

BS 8458:2015: Annex C

Test Details Purpose of test To determine the performance of a system when it is subjected to the

conditions of test specified in BS 8458:2015 “Code of practice for design and installation” Annex C "Room fire tests for watermist systems with automatic nozzles". The test was performed in accordance with the procedure specified in BS 8458:2015: Annex C and this report should be read in conjunction with that Standard.

Deviation from test standard

BS 8458:2015: Annex C.3 details that a nozzle connected to a water‑filled pipe should be used and in accordance with BS 8458:2015: 6.1 (c) the nozzle, external to the room, should not operate. No thermal sensitive bulb or shared water supply is used with the “Automist Smartscan System” therefore the third nozzle, external to the room was deemed not to be applicable.

Instruction to test The test was conducted on the 29th July, 21st, 27th August 2015 at the request of Plumis, the sponsor of the test.

Provision of the system to test

The system was supplied by the sponsor of the test. Exova Warringtonfire was not involved in any selection or sampling procedure.

Conditioning of ignition and fuel packages

The plywood sheets, sacrificial boards, wooden frames, foam sheets and wood crib sticks were conditioned to constant mass at a temperature of 23 ± 2°C and a relative humidity of 50 ± 5% prior to testing. The cribs were conditioned, such that the moisture content was 10 ± 2%, 3 mm below the wood stick surface prior to testing.

Ignition package Ignition packages, as detailed in Annex B.1.3 were used.

Fuel package Fuel packages, as detailed in Annex B.1.4 were used.

Test room The test room was erected, as detailed in Annex B.1.1.

Operating pressure

The systems operating pressure was 90bar. The operating pressures throughout the tests are presented in Figures 1, 2, 3, 4 and 5.

Water flow rate The systems water flow rate at operation was 6.0l/min.

Document No.: 356258 Page No.: 5 of 22

Author: T. Kinder Issue Date: 18th January 2016

Client: Plumis Issue No.: 3

Page 6: BS 8458:2015: Annex C - Intelligent Mist · 2017-08-24 · ‑filled pipe should be used and in accordance with BS 8458: 2015: 6.1 (c) the nozzle, external to the room, should not

BS 8458:2015: Annex C

Description of system The description of the system given below has been prepared from information provided by the sponsor of the test. All values quoted are nominal, unless tolerances are given.

General description Automist “Smartscan” targeted water mist fire

suppression system System reference “Automist Smartscan System” Name of manufacturer Plumis Detailed description Automist pre-engineered active targeted, single nozzle,

watermist fire suppression system

Nozzle

Product reference “Smartscan vertical flat 65º spray nozzle” General description Flat cone 65º 316SS single nozzle with M10x1 thread,

0.576 K factor. Name of manufacturer Plumis supply chain Angle 65º flat cone Colour reference “316 stainless steel”

“Silver” (observed by Exova Warringtonfire)

Pipe

Product reference “Production High Pressure Hose 150bar Working Pressure”

Generic type PE (Polyethylene) core, Polyester braid, PVC (Polyvinylchloride) outer

Name of manufacturer Plumis supply chain Diameter Internal: Ø 6.3mm

External: Ø 11.5mm Wall thickness 2.6mm Length 4000mm Density See Note 1 below Colour reference “Black” Flame retardant details See Note 2 below

Pump

Product reference “Production Pluvia Pump” General description Automist Pluvia high pressure pump. 6.0 l/min, 90 bar

working pressure, 120bar pressure limit. Name of manufacturer Plumis supply chain

Heat alarm

Product reference “Ei164 Heat Alarm” General description Aico 57° fixed point heat alarm Name of manufacturer Ei Electronics Colour reference “White”

Brief description of manufacturing process See Note 1 below Note 1. The sponsor was unable to provide this information. Note 2. The sponsor of the test has confirmed that no flame retardant additives were utilised in

the production of the component.

Document No.: 356258 Page No.: 6 of 22

Author: T. Kinder Issue Date: 18th January 2016

Client: Plumis Issue No.: 3

Page 7: BS 8458:2015: Annex C - Intelligent Mist · 2017-08-24 · ‑filled pipe should be used and in accordance with BS 8458: 2015: 6.1 (c) the nozzle, external to the room, should not

BS 8458:2015: Annex C

Test Results Applicability of test results

The test results relate only to the behaviour of the system under the particular conditions of test, they are not intended to be the sole criterion for assessing the potential fire hazard of the system in use.

The test results relate only to the system in the form in which it was tested. Small differences in the composition of the system may significantly affect the performance during the test and may therefore invalidate the test results. Care should be taken to ensure that any system which is supplied or used is fully represented by the system which was tested.

Test results

Thermocouple location Maximum temperature °C

Test 1

Test 2

Test 3

Test 4

Test 5

75mm below the underside of the ceiling 94 178 144 92 307 Ceiling temperature – 6.5mm above the

underside of the ceiling 36 39 36 36 45

1.6m above the floor, furthest from fire 38 80 67 43 71 1.6m above the floor, centre (if applicable) 35 80 138 69 104

1.6m above the floor, close to fire 32 62 68 37 67 Key: Test 1 – Room corner (Spray head on opposite wall) Test 2 – Room corner (Spray on same wall wall) Test 3 – Centre (Spray head on opposite wall) Test 4 – Centre (Spray head on opposite wall) Ventilation test Test 5 – Centre (Spray head on opposite wall) Open room test

Where the thermocouples were positioned at 1.6m above the floor, the temperatures did not exceed 55°C for any 120 s interval, during test 1, 2, 3, 4 & 5. The fire test maximum temperatures as defined in BS 8458:2015: Table 2 are detailed in Appendix 2.

Document No.: 356258 Page No.: 7 of 22

Author: T. Kinder Issue Date: 18th January 2016

Client: Plumis Issue No.: 3

Page 8: BS 8458:2015: Annex C - Intelligent Mist · 2017-08-24 · ‑filled pipe should be used and in accordance with BS 8458: 2015: 6.1 (c) the nozzle, external to the room, should not

BS 8458:2015: Annex C

Conclusion The temperatures during tests 1 and 2 were all declining 2 minutes after

the nozzle operation (See Figures 1 and 2). The watermist system suppressed the fuel packages and met all the criteria specified in Clause 6.1 (a), (b) and Table 2 of BS 8458:2015.

Observations The visual observations taken during the tests are shown in Appendix 1.

Temperatures The temperatures logged during the tests are presented in Figures 1, 2, 3, 4 and 5.

Fire test layout Diagrams detailing the fire test layouts are presented in Figures 6, 7, 8, 9 and 10.

Validity The specification and interpretation of fire test methods are the subject of ongoing development and refinement. Changes in associated legislation may also occur. For these reasons it is recommended that the relevance of test reports over five years old should be considered by the user. The laboratory that issued the report will be able to offer, on behalf of the legal owner, a review of the procedures adopted for a particular test to ensure that they are consistent with current practices, and if required may endorse the test report. This report may only be reproduced in full. Extracts or abridgements shall not be published without permission of Exova Warringtonfire.

Document No.: 356258 Page No.: 8 of 22

Author: T. Kinder Issue Date: 18th January 2016

Client: Plumis Issue No.: 3

Page 9: BS 8458:2015: Annex C - Intelligent Mist · 2017-08-24 · ‑filled pipe should be used and in accordance with BS 8458: 2015: 6.1 (c) the nozzle, external to the room, should not

BS 8458:2015: Annex C

Appendix 1

Observations during test of Test 1 00:01 Test start, the fire loads were ignited. 00:45 Heat alarm sounded. Nozzle began to scan room. 00:50 Nozzle activated. 30:50 Test terminated.

Observations during test of Test 2 00:01 Test start, the fire loads were ignited. 00:46 Heat alarm sounded. Nozzle began to scan room. 01:54 Nozzle activated. 31:54 Test terminated.

Observations during test of Test 3 00:01 Test start, the fire loads were ignited. 00:28 Heat alarm sounded. Nozzle began to scan room. 02:04 Nozzle activated. 32:04 Test terminated.

Observations during test of Test 4 00:01 Test start, the fire loads were ignited. 00:47 Heat alarm sounded. Nozzle began to scan room. 01:06 Nozzle activated. 31:06 Test terminated.

Observations during test of Test 5 00:01 Test start, the fire loads were ignited. 00:27 Heat alarm sounded. Nozzle began to scan room. 01:21 Nozzle activated. 31:21 Test terminated.

Document No.: 356258 Page No.: 9 of 22

Author: T. Kinder Issue Date: 18th January 2016

Client: Plumis Issue No.: 3

Page 10: BS 8458:2015: Annex C - Intelligent Mist · 2017-08-24 · ‑filled pipe should be used and in accordance with BS 8458: 2015: 6.1 (c) the nozzle, external to the room, should not

BS 8458:2015: Annex C

Appendix 2

Table 2 Fire test maximum temperatures

Thermocouple location Maximum allowable temperature °C 75mm below the underside of the ceiling 320 1.6 m above the floor 95

1.6 m above the floor 55 (for not more than any 120 s interval)

Document No.: 356258 Page No.: 10 of 22

Author: T. Kinder Issue Date: 18th January 2016

Client: Plumis Issue No.: 3

Page 11: BS 8458:2015: Annex C - Intelligent Mist · 2017-08-24 · ‑filled pipe should be used and in accordance with BS 8458: 2015: 6.1 (c) the nozzle, external to the room, should not

BS 8458:2015: Annex C

Figure 1

0.00

20.00

40.00

60.00

80.00

100.00

120.00

00:0

001

:00

02:0

003

:00

04:0

005

:00

06:0

007

:00

08:0

009

:00

10:0

011

:00

12:0

013

:00

14:0

015

:00

16:0

017

:00

18:0

019

:00

20:0

021

:00

22:0

023

:00

24:0

025

:00

26:0

027

:00

28:0

029

:00

30:0

031

:00

75mm Below Ceiling

6.5mm above ceiling surface

1.6m above floor (furthest from fire)

1.6mm above floor (centre)

1.6m above floor (close to fire)

Replicated nozzle

Pressure

EWF No: 356258 - Test No: 1

Tem

pera

ture

(°C)

Time (m)

Pressure (BAR)

Document No.: 356258 Page No.: 11 of 22

Author: T. Kinder Issue Date: 18th January 2016

Client: Plumis Issue No.: 3

Page 12: BS 8458:2015: Annex C - Intelligent Mist · 2017-08-24 · ‑filled pipe should be used and in accordance with BS 8458: 2015: 6.1 (c) the nozzle, external to the room, should not

BS 8458:2015: Annex C

Figure 2

0.00

20.00

40.00

60.00

80.00

100.00

120.00

140.00

160.00

180.00

200.0000

:00

01:0

002

:00

03:0

004

:00

05:0

006

:00

07:0

008

:00

09:0

010

:00

11:0

012

:00

13:0

014

:00

15:0

016

:00

17:0

018

:00

19:0

020

:00

21:0

022

:00

23:0

024

:00

25:0

026

:00

27:0

028

:00

29:0

030

:00

31:0

0

75mm Below Ceiling

6.5mm above ceiling surface

1.6m above floor (furthest from fire)

1.6m from floor (centre)

1.6m above floor (close to fire)

Replicated nozzle

Pressure

EWF No: 356258 - Test No: 2

Tem

pera

ture

(°C)

Time (m)

Pressure (BAR)

Document No.: 356258 Page No.: 12 of 22

Author: T. Kinder Issue Date: 18th January 2016

Client: Plumis Issue No.: 3

Page 13: BS 8458:2015: Annex C - Intelligent Mist · 2017-08-24 · ‑filled pipe should be used and in accordance with BS 8458: 2015: 6.1 (c) the nozzle, external to the room, should not

BS 8458:2015: Annex C

Figure 3

0.00

20.00

40.00

60.00

80.00

100.00

120.00

140.00

160.0000

:00

01:0

002

:00

03:0

004

:00

05:0

006

:00

07:0

008

:00

09:0

010

:00

11:0

012

:00

13:0

014

:00

15:0

016

:00

17:0

018

:00

19:0

020

:00

21:0

022

:00

23:0

024

:00

25:0

026

:00

27:0

028

:00

29:0

030

:00

31:0

0

75mm Below Ceiling

6.5mm above ceiling surface

1.6m above floor (furthest from fire)

1.6m above floor (close to fire)

Replicated nozzle

Pressure

EWF No: 356258 - Test No: 3

Tem

pera

ture

(°C)

Time (m)

Pressure (BAR)

Document No.: 356258 Page No.: 13 of 22

Author: T. Kinder Issue Date: 18th January 2016

Client: Plumis Issue No.: 3

Page 14: BS 8458:2015: Annex C - Intelligent Mist · 2017-08-24 · ‑filled pipe should be used and in accordance with BS 8458: 2015: 6.1 (c) the nozzle, external to the room, should not

BS 8458:2015: Annex C

Figure 4

0.00

20.00

40.00

60.00

80.00

100.00

120.0000

:00

01:0

002

:00

03:0

004

:00

05:0

006

:00

07:0

008

:00

09:0

010

:00

11:0

012

:00

13:0

014

:00

15:0

016

:00

17:0

018

:00

19:0

020

:00

21:0

022

:00

23:0

024

:00

25:0

026

:00

27:0

028

:00

29:0

030

:00

31:0

0

75mm Below Ceiling

6.5mm above ceiling surface

1.6m above floor (furthest from fire)

1.6m from floor (centre)

1.6m above floor (close to fire)

Replicated nozzle

Pressure

EWF No: 356258 - Test No: 4

Tem

pera

ture

(°C)

Time (m)

Pressure (BAR)

Document No.: 356258 Page No.: 14 of 22

Author: T. Kinder Issue Date: 18th January 2016

Client: Plumis Issue No.: 3

Page 15: BS 8458:2015: Annex C - Intelligent Mist · 2017-08-24 · ‑filled pipe should be used and in accordance with BS 8458: 2015: 6.1 (c) the nozzle, external to the room, should not

BS 8458:2015: Annex C

Figure 5

0.00

50.00

100.00

150.00

200.00

250.00

300.00

350.0000

:00

01:0

002

:00

03:0

004

:00

05:0

006

:00

07:0

008

:00

09:0

010

:00

11:0

012

:00

13:0

014

:00

15:0

016

:00

17:0

018

:00

19:0

020

:00

21:0

022

:00

23:0

024

:00

25:0

026

:00

27:0

028

:00

29:0

030

:00

31:0

0

75mm Below Ceiling

6.5mm above ceiling surface

1.6m above floor (furthest from fire)

1.6m above floor (close to fire)

Replicated nozzle

Pressure

EWF No: 356258 - Test No: 5

Tem

pera

ture

(°C)

Time (m)

Pressure (BAR)

Document No.: 356258 Page No.: 15 of 22

Author: T. Kinder Issue Date: 18th January 2016

Client: Plumis Issue No.: 3

Page 16: BS 8458:2015: Annex C - Intelligent Mist · 2017-08-24 · ‑filled pipe should be used and in accordance with BS 8458: 2015: 6.1 (c) the nozzle, external to the room, should not

BS 8458:2015: Annex C

Figure 6

Test 1 Key

Corner test ignition and fuel package Nozzle

Thermocouple Replicated third nozzle

Drawing not to scale

6m

1.25m high nozzle

3.53m

Document No.: 356258 Page No.: 16 of 22

Author: T. Kinder Issue Date: 18th January 2016

Client: Plumis Issue No.: 3

Page 17: BS 8458:2015: Annex C - Intelligent Mist · 2017-08-24 · ‑filled pipe should be used and in accordance with BS 8458: 2015: 6.1 (c) the nozzle, external to the room, should not

BS 8458:2015: Annex C

Figure 7

Test 2 Key

Corner test ignition and fuel package Nozzle

Thermocouple Replicated third nozzle

Drawing not to scale

6m

1.25m high nozzle

2m

Document No.: 356258 Page No.: 17 of 22

Author: T. Kinder Issue Date: 18th January 2016

Client: Plumis Issue No.: 3

Page 18: BS 8458:2015: Annex C - Intelligent Mist · 2017-08-24 · ‑filled pipe should be used and in accordance with BS 8458: 2015: 6.1 (c) the nozzle, external to the room, should not

BS 8458:2015: Annex C

Figure 8

Test 3 Key

Centre test ignition and fuel package Nozzle

Thermocouple Replicated third nozzle

Drawing not to scale

1.25m high nozzle

4m

Document No.: 356258 Page No.: 18 of 22

Author: T. Kinder Issue Date: 18th January 2016

Client: Plumis Issue No.: 3

Page 19: BS 8458:2015: Annex C - Intelligent Mist · 2017-08-24 · ‑filled pipe should be used and in accordance with BS 8458: 2015: 6.1 (c) the nozzle, external to the room, should not

BS 8458:2015: Annex C

Figure 9

Test 4 Key

Centre test ignition and fuel package Nozzle

Thermocouple Replicated third nozzle

Fan

Drawing not to scale

1.25m high nozzle

4m

Document No.: 356258 Page No.: 19 of 22

Author: T. Kinder Issue Date: 18th January 2016

Client: Plumis Issue No.: 3

Page 20: BS 8458:2015: Annex C - Intelligent Mist · 2017-08-24 · ‑filled pipe should be used and in accordance with BS 8458: 2015: 6.1 (c) the nozzle, external to the room, should not

BS 8458:2015: Annex C

Figure 10

Test 5 Key

Centre test ignition and fuel package Nozzle

Thermocouple

Drawing not to scale

1.25m high nozzle

4m

Document No.: 356258 Page No.: 20 of 22

Author: T. Kinder Issue Date: 18th January 2016

Client: Plumis Issue No.: 3

Page 21: BS 8458:2015: Annex C - Intelligent Mist · 2017-08-24 · ‑filled pipe should be used and in accordance with BS 8458: 2015: 6.1 (c) the nozzle, external to the room, should not

BS 8458:2015: Annex C

Photographs

Photographs of ignition and fuel package before a test

Photographs of nozzle system before a test

Photographs during a test

Photograph after a test

Document No.: 356258 Page No.: 21 of 22

Author: T. Kinder Issue Date: 18th January 2016

Client: Plumis Issue No.: 3

Page 22: BS 8458:2015: Annex C - Intelligent Mist · 2017-08-24 · ‑filled pipe should be used and in accordance with BS 8458: 2015: 6.1 (c) the nozzle, external to the room, should not

BS 8458:2015: Annex C

Revision History Issue No : 2 Issue Date: 22nd December 2015

Revised By: T. Kinder Approved By: T. Mort

Reason for Revision: This document replaces Issue 1 (dated 15th September 2015) of the same number which

has been withdrawn. Subsequent to the report being issued, the sponsor of the test has confirmed that details in

the Key for Test 4 and Test 5 were incorrect and the correct details have been detailed in this issue 2 report.

Issue No : 3 Issue Date: 18th January 2016

Revised By: T. Kinder Approved By: T. Mort

Reason for Revision: This document replaces Issue 2 (dated 22nd December 2015) of the same number which

has been withdrawn. Subsequent to the report being issued, the Draft BS 8458: 2014 DPC document has been

re- issued as BS 8458:2015.The sponsor of the test has requested an updated report that references this new

standard.

Document No.: 356258 Page No.: 22 of 22

Author: T. Kinder Issue Date: 18th January 2016

Client: Plumis Issue No.: 3