    Seite 1 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    PRESSURE BOOSTING SYSTEMS

    1. Definition and Principle of a Booster unit2. Hyamat Range3. Hya-Solo Presentation4. Hyamat K/V/VP modes of operation

    5. Hyamat K/V/VP Presentation6. Equipement7. Selection of a Booster unit

  • 7/31/2019 Booster Units Training

    2/52

    Seite 2 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    Definition

    A booster unit is a device that can increase water system pressureand ensure consistent pressure during use.

    Water is generally supplied by a municipality.

    There are cases where the user is too far away from the main supply

    Or the user needs more pressure because of the particularity of his installation.

    Supplier Municipality Too high! Too far!

  • 7/31/2019 Booster Units Training

    3/52

    Seite 3 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    Application

    Hotel & hospital

    Factories

    Water supply of building

    Irrigation

    Reinforcement network of water

    Water supply (replacement)

  • 7/31/2019 Booster Units Training

    4/52

    Seite 4 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    Pressure Boosting System gives more comfort

    No water supply No pressure! A device gives more

    pressure

    V ^ \

  • 7/31/2019 Booster Units Training

    5/52

  • 7/31/2019 Booster Units Training

    6/52

    Seite 6 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    Pump

    Non return valve

    Valve

    Valve

    Pressure Tank

    Control System

    Protection

    Pressure gaugeBasic device

  • 7/31/2019 Booster Units Training

    7/52

    Seite 7 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    The pump is started up and switched off by pressure gauge

    0

    10

    20

    30

    40

    50

    60

    70

    80

    0 2 4 6 8 10 12Q(m/h)

    H(m)

    PE

    Mode of operation of a unit: Basic function

    PA

    PE = Start up pressure

    PA = Schwitch off pressure

  • 7/31/2019 Booster Units Training

    8/52

    Seite 8 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    PRESSURE BOOSTING SYSTEMS

    1. Definition and Principle of a Booster unit2. Hyamat Range3. Hya-Solo Presentation5. Hyamat K/V/VP modes of operation6. Hyamat K/V/VP Presentation7. Equipement8. Selection of a Booster unit

  • 7/31/2019 Booster Units Training

    9/52

    Seite 9 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    Superbloc: SBC Hya-Solo E Hya-Solo D/DV

    Surpress Feu: SFHyamat K

    Surpresschrom SIC

    Hyamat V / VP

    Surpresschrom SICV / SICVP

    Hya-EcoSurpress Eco

    Product Pressure Boosting units

  • 7/31/2019 Booster Units Training

    10/52

    Seite 10 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    0

    20

    40

    60

    80

    100

    120

    140

    160

    1 10 100 1000Q (m/h)

    Pressure Boosting system at a glance: Hyamat

    Hyamat K/V/VP

    Hya-Eco

    Hya-Solo D/DV

    Hya-Solo E 7m/h 45 m/h 65 m/hVP: 200m/h

    K / V: 360 m/h

    65 m

    85 m

    160m

  • 7/31/2019 Booster Units Training

    11/52

  • 7/31/2019 Booster Units Training

    12/52

    Seite 12 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    HYAMAT Range

    0

    20

    40

    60

    80

    100

    120

    140

    160

    180

    0 100 160 340 350 500 640

    Q m/h

    H

    m

    Hyamat IndustryHyamat Building systems

  • 7/31/2019 Booster Units Training

    13/52

    Seite 13 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    V

    K

    VP

    Price

    Technology

    Hyamat

    Hya-Eco

    Product positioning (multi-pump systems)

  • 7/31/2019 Booster Units Training

    14/52

    Seite 14 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    PRESSURE BOOSTING SYSTEMS

    1. Definition and Principle of a Booster unit2. Hyamat Range3. Hya-Solo Presentation4. Hyamat K/V/VP modes of operation5. Hyamat K/V/VP Presentation6. Equipement7. Selection of a Booster unit

  • 7/31/2019 Booster Units Training

    15/52

    Seite 15 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    Hya-Solo

    Application: Fire-fighting systems for residential buildings,department stores and industrial plants

    Water supply systems for residential and

    office buildings Irrigation / sprinkling systems Rainwater utilisation systems Utility water supply systems for industrial plants

    Pumped liquid: Drinking water, fire-fighting water, utility water,cooling water, filtered rainwater containing noaggressive, abrasive or solid substances.

  • 7/31/2019 Booster Units Training

    16/52

    Seite 16 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    Designation Principle for Hya-Solo

    Type seriesE = single-phase a.c. current

    D = three-phase currentSpeed control

    (V = variable with frequency converter)

    Pump size

    Number of stages

    Inlet pressure in bar (for V: from - to)

    Hya-Solo D V / 04 05 / 2 - 4

  • 7/31/2019 Booster Units Training

    17/52

    Seite 17 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    HYA - SOLO E

    Hya-Solo E / 0405

    Type series E

    Pump size 0405

    With Movitec VE 2-6 and VE 4-5

    Characteristic: Movitec VE

    with integrated non return valve All wet parts of the pump in stainless steel

    Operating data (standard variant):Pd up to 10 barPinlet up to 3,5 barTliquid up to 70C

    up to 25C acc. To DIN 1988 (DVGW)Tambient up to 40C

    Supply voltage1~230V 50Hz

  • 7/31/2019 Booster Units Training

    18/52

    Seite 18 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    HYA - SOLO D/DV

    Hya-Solo D / 1808 / 0,3

    Type series D, DV Pump size 2, 4, 10, 18, 32, 45, 65 Number of stages Inlet pressure (bar)

    With Movitec V 2m/h - 65m/h

    Characteristic: Movitec V All wet parts of the pump in stainless steel

    Operating data (standard variant):Pd up to 16 barPinlet up to 6 barTliquid up to 70C

    up to 25C acc. To DIN 1988 (DVGW)Tambient up to 40CSupply voltage

    3~400V 50Hz

  • 7/31/2019 Booster Units Training

    19/52

    Seite 19 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    Selection chartHya-Solo

    Head

    02 04 1832

    4510

    Movitec

  • 7/31/2019 Booster Units Training

    20/52

    Seite 20 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    Hya-Solo

    Permissible inlet pressure fluctuations

    for Hya-Solo D +0,3/-0,2 barfor Hya-Solo DV see characteristic curves

    The sum of inlet pressure and shutoff head must not exceed 10 barfor Hya-Solo E and 16 bar for Hya-Solo D/DV.

  • 7/31/2019 Booster Units Training

    21/52

    Seite 21 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    Hya-Solo

    Hya-Solo E

    Hya-Solo D/DV 4/10

    Hya-Solo D/DV 18/32/45/65

  • 7/31/2019 Booster Units Training

    22/52

    Seite 22 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    Design:Hya-Solo E Fully automatic, package single-pump unit with 8 l

    membrane-type accumulator. The unit is started updepending on the pressure and switched off

    depending on the flow.

    Hya-Solo D Fully automatic, package single-pump unit. The

    unit is started up and switched off depending on thepressure.

    Hya-Solo DV Fully automatic, package single-pump unit withspeed control. The unit is started up depending onthe pressure and switched off depending on the

    flow rate.

  • 7/31/2019 Booster Units Training

    23/52

    Seite 23 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    The pump is started up depending on the pressureand switched off depending on the flow

    0

    10

    20

    30

    40

    50

    60

    0 1 2 3 4 5 6 7Q(m/h)

    H(m)

    PE

    Hya-Solo E

    PE = Start up pressure

    Q = Schwitch off Flow rate

    Q1

  • 7/31/2019 Booster Units Training

    24/52

    Seite 24 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    Hya-Solo E

    Low energy consumption

    due to high-efficiency

    hydraulic

    Corrosion-resistant

    hydraulic

    Integrated swingcheck valve

    Integrated dry-

    running protection

    Reserve volume for lowwater withdrawal

    quantities, low switchingfrequency thanks to

    DVGW-approved

    accumulator

    Easy adaptation to the operating

    conditions by setting the start-up

    pressure to values from 2 to 3.5bar

    Installation free from solid-borne noise transmission

    because of elastic elements

  • 7/31/2019 Booster Units Training

    25/52

    Seite 25 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    The pump is started up and switched off depending on the pressure

    0

    10

    20

    30

    40

    50

    60

    70

    80

    0 2 4 6 8 10 12Q(m/h)

    H(m)

    PE

    Hya-Solo D

    PA

    PE = Start up pressure

    PA = Schwitch off pressure

  • 7/31/2019 Booster Units Training

    26/52

    Seite 26 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    Hya-Solo D/DV

    Daily functional check run

    controlled by timer (option)

    DVGW-approved

    control tank with directflow to DIN 4807-5 Fully automatic

    control unit

    Permanently filled dischargepipe thanks to check valve

    System pressure indicated

    by pressure gauge

    Lack-of-water protection bymeans of the pressure

    control device (option)

    Installation free from solid-borne noise transmission

    because of elastic elements

  • 7/31/2019 Booster Units Training

    27/52

    Seite 27 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    Speed control system with a single pump started up depending on the pressureand switsched off on the flow.

    0

    10

    20

    30

    40

    50

    60

    70

    80

    0 2 4 6 8 10 12Q(m/h)

    H(m)

    PE

    Hya-Solo DV

    PE = Start up pressure

    Q1 = Schwitch off pressure

    Q1

    100%

    75%

    80%

  • 7/31/2019 Booster Units Training

    28/52

    Seite 28 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    Hya-Solo D/DV 15/30/45

    Daily functional check run

    controlled by timer (option)

    Membrane-type

    accumulator with

    direct flow to DIN 4807-5

    System pressure

    indicated by

    pressure gauge Permanently filled discharge

    pipe thanks to check valve

    Pump can bedismantled via flange

    Lack-of-water protection by

    means of the pressure control

    device (option)

    Corrosion-resistant: hydraulic and

    pump shroud made of stainless steel

    Fully automatic control unit

  • 7/31/2019 Booster Units Training

    29/52

  • 7/31/2019 Booster Units Training

    30/52

  • 7/31/2019 Booster Units Training

    31/52

    Seite 31 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    Two to six pumps arestarted up and switched

    off by the control unit inline with the actualdemand.

    Hyamat K Pressure-controlled cascade operation

  • 7/31/2019 Booster Units Training

    32/52

    Seite 32 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    A base load pump is

    continuously controlled,with the peak load

    pumps being started upand switched off in linewith the demand.

    Hyamat VContinuous speed control of one pump

    set value

  • 7/31/2019 Booster Units Training

    33/52

    Seite 33 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    Continuously variable

    speed adjustment ofeach pump.

    The peak load pumps

    are started up andswitched off in line with

    the demand.All pumps run at the

    same speed.

    Hyamat VP Continuous speed control of each pump

    set value

  • 7/31/2019 Booster Units Training

    34/52

    Seite 34 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    Other combinations and control modesAvailable on request (example: 1 or 2 jockeypumps as low load pumps)

  • 7/31/2019 Booster Units Training

    35/52

    Seite 35 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    PRESSURE BOOSTING SYSTEMS

    1. Definition and Principle of a Booster unit2. Hyamat Range3. Hya-Solo Presentation4. Hyamat K/V/VP modes of operation5. Hyamat K/V/VP Presentation

    6. Equipement7. Selection of a Booster unit

  • 7/31/2019 Booster Units Training

    36/52

    Seite 36 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    Hyamat K / V / VP

    Applications:

    Pumped liquid:

    Residential buildings Hospitals

    Office Buildings

    Hotels

    Department stores Industry

    Other

    applications

    Drinking water, service water,

    fire-fighting water, cooling water,

    provided that it is neither chemicallynor mechanically aggressive to the

    system materials

  • 7/31/2019 Booster Units Training

    37/52

    Seite 37 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    HYAMAT K, V und VP

    Hyamat K 6 / 1808 / 0,3

    Type series K, V, VP Number of pumps Pump size 2, 4, 10, 18, 32, 45 Number of stages Inlet pressure (bar)

    Mit Movitec V von 2m/h bis 45m/h

    Characteristic: Movitec V

    All wet parts of the pump in stainless steel

    Type series

    K (pressure-dependent cascade operation)

    V (continuously variable speedadjustment of one pump)

    VP (continuously variable speedadjustment of all pumps)

  • 7/31/2019 Booster Units Training

    38/52

  • 7/31/2019 Booster Units Training

    39/52

  • 7/31/2019 Booster Units Training

    40/52

    Seite 40 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    Hyamat K / V / VP

    Materials

    Pumps Movitec V

    suction/discharge casing stainless steel

    hydraulic stainless steel

    seal FPM 80

    plain bearing aluminium oxide

    mechanical seal to DIN 24960

    spring-loaded ring hard carbon, resin-impregnated

    seat ring aluminium oxide

  • 7/31/2019 Booster Units Training

    41/52

  • 7/31/2019 Booster Units Training

    42/52

    Seite 42 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    Features / Benefit

    System using a frequency inverter High operating reliability in case

    for each pump of failure of a pump or frequencyinverter

    Synchronous pump operation High pressure constancy at

    dynamic consumer installations

    Fully speed-controlled High efficiency due to the capability

    pressure boosting unit of the system to use the variableinlet pressure

    Pump and frequency inverter Standard products instead ofare separated integrated solutions (control

    cabinet muffles frequencyinverter noise)

    Hyamat VP

  • 7/31/2019 Booster Units Training

    43/52

    Seite 43 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    PRESSURE BOOSTING SYSTEMS

    1. Definition and Principle of a Booster unit2. Hyamat Range3. Hya-Solo Presentation4. Hyamat K/V/VP modes of operation5. Hyamat K/V/VP Presentation

    6. Equipement7. Selection of a Booster unit

  • 7/31/2019 Booster Units Training

    44/52

    Seite 44 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    Hyamat K / V / VP

    Start-up and shutdown of up to

    six high pressure pumps,as required

    Even distribution ofpump operation

    automaticpump changeover

    General fault message

    volt-free contact

    High reliability

    constant monitoring of

    the function of theconnected sensors

    DVGW-approved

    valves

    Corrosion protection thanks

    to stainless steel piping

    No structure-borne sound

    pumps are uncoupled from

    the base

    Flow goes through

    the control vessel

    DIN 4807-5,

    DVGW-approved

    Full enclosure

    (optional)

    retrofitting, easy to service protects from dirt attractive design low-noise approx. 51-61 dB(A)

  • 7/31/2019 Booster Units Training

    45/52

    Seite 45 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    In drinking water application to

    DIN 4807-5, flow must go through

    the accumulator.

    Piping

    Flow passing through the accumulator

  • 7/31/2019 Booster Units Training

    46/52

    Seite 46 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    V = 275 x Qm x (Pe+1) x (Pa+1)F x P x (Pg+1) x N

    V = Tank volume (liter)Pe = Pressure switch on (bar)Pa = Pressure switch off (bar)

    P = Pa - Pe (bar)Qm = average flow of the pumpe

    between Pa and Pe (m/h)

    F = Motor start allowed per hourPg = Air Pressure of the tank (bar)

    (Pg = Pe-0,5)N = Number of pumps

    Determination of the volume of an accumulator

    0

    10

    20

    30

    40

    50

    60

    70

    0 1 2 3 4 5 6Q(m/h)

    H(m)

    Pe

    Pa

    Qm

    (Pa = 4,5 bar)

    (Pe = 3,5 bar)

    (P = 1 bar)

    (Qm = 3,5 m/h)

    Exemple: for 2 Pumps with F=15V = 199 liter

  • 7/31/2019 Booster Units Training

    47/52

    Seite 47 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    Hyamat VPwithout or with cladding (optional)

    (Surpresschrom SICVP)

  • 7/31/2019 Booster Units Training

    48/52

    Seite 48 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    PRESSURE BOOSTING SYSTEMS

    1. Definition and Principle of a Booster unit2. Hyamat Range3. Hya-Solo Presentation4. Hyamat K/V/VP modes of operation5. Hyamat K/V/VP Presentation

    6. Equipement7. Selection of a Booster unit

  • 7/31/2019 Booster Units Training

    49/52

    Seite 49 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    Hyamat K / V / VP

  • 7/31/2019 Booster Units Training

    50/52

    Seite 50 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    Selection

    A pressure booster units is defined by the flowrates and the pressure.Hs = Static Head...........................................m

    H = Head loses (devices, pipes,etc...)........mPu = Pressure user.......................................bar

    The pressure after the Booster unit

    = Hinlet + Hs + H + (Pu x10)

    The flow rates is defined according rules ofcalculation given from the norms.for example:

    DIN1988/5 Germany NFP 41101 and DTU 6011 France

    Booster unit

    Hinlet

    H

    Pmax=3,3bar

    pmin=2,2bar

    Hs

    H

    Pu

    Pressure to produce = Hs+H+(Pux10)

    P B i S

  • 7/31/2019 Booster Units Training

    51/52

    Seite 51 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    Data required for selection of a pressure boosting unit (PBU)

    PBU capacity (Q):

    Stand-by pump: yes/no

    Start-up pressure for PBU (pE):

    min. inlet pressure upstream of PBU (pmin):

    max inlet pressure upstream of PBU (pmax):

    PBU discharge head (H):

    Pressure boosting concepts: Cascade operation /

    Speed control of one pump/of all pumps

    CAUTION! Do not forget the dry-running protection equipment!

    pmax

    pminpEPBU

    H/Q~~

    discharge sideInlet side

    P B ti S t

  • 7/31/2019 Booster Units Training

    52/52

    Seite 52 von 54Building Services Pumps

    Pressure Boosting System

    V34, Productmanagement

    10/2004

    Number of pumps

    Capacity m3/h

    Head (max) m

    Automatic dry-run

    protection

    Control

    System dischargepressure bar

    2 to 3 2 to 6 2 to 6 2 to 4

    up to 7 up to 65 up to 45 up to 360 up to 360 up to 200

    no yes yes yes yes yes

    standard accessory accessory accessory accessory standard

    cascade

    D Cascade

    DV 1 pumpspeed-controlled

    cascade cascade1 pump

    speed-

    controlled

    all pumps

    speed-

    controlled

    Pipes of stainless steel

    Pressure Boosting system at a glance