Seite 1 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
PRESSURE BOOSTING SYSTEMS
1. Definition and Principle of a Booster unit2. Hyamat Range3. Hya-Solo Presentation4. Hyamat K/V/VP modes of operation
5. Hyamat K/V/VP Presentation6. Equipement7. Selection of a Booster unit
7/31/2019 Booster Units Training
2/52
Seite 2 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
Definition
A booster unit is a device that can increase water system pressureand ensure consistent pressure during use.
Water is generally supplied by a municipality.
There are cases where the user is too far away from the main supply
Or the user needs more pressure because of the particularity of his installation.
Supplier Municipality Too high! Too far!
7/31/2019 Booster Units Training
3/52
Seite 3 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
Application
Hotel & hospital
Factories
Water supply of building
Irrigation
Reinforcement network of water
Water supply (replacement)
7/31/2019 Booster Units Training
4/52
Seite 4 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
Pressure Boosting System gives more comfort
No water supply No pressure! A device gives more
pressure
V ^ \
7/31/2019 Booster Units Training
5/52
7/31/2019 Booster Units Training
6/52
Seite 6 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
Pump
Non return valve
Valve
Valve
Pressure Tank
Control System
Protection
Pressure gaugeBasic device
7/31/2019 Booster Units Training
7/52
Seite 7 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
The pump is started up and switched off by pressure gauge
0
10
20
30
40
50
60
70
80
0 2 4 6 8 10 12Q(m/h)
H(m)
PE
Mode of operation of a unit: Basic function
PA
PE = Start up pressure
PA = Schwitch off pressure
7/31/2019 Booster Units Training
8/52
Seite 8 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
PRESSURE BOOSTING SYSTEMS
1. Definition and Principle of a Booster unit2. Hyamat Range3. Hya-Solo Presentation5. Hyamat K/V/VP modes of operation6. Hyamat K/V/VP Presentation7. Equipement8. Selection of a Booster unit
7/31/2019 Booster Units Training
9/52
Seite 9 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
Superbloc: SBC Hya-Solo E Hya-Solo D/DV
Surpress Feu: SFHyamat K
Surpresschrom SIC
Hyamat V / VP
Surpresschrom SICV / SICVP
Hya-EcoSurpress Eco
Product Pressure Boosting units
7/31/2019 Booster Units Training
10/52
Seite 10 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
0
20
40
60
80
100
120
140
160
1 10 100 1000Q (m/h)
Pressure Boosting system at a glance: Hyamat
Hyamat K/V/VP
Hya-Eco
Hya-Solo D/DV
Hya-Solo E 7m/h 45 m/h 65 m/hVP: 200m/h
K / V: 360 m/h
65 m
85 m
160m
7/31/2019 Booster Units Training
11/52
7/31/2019 Booster Units Training
12/52
Seite 12 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
HYAMAT Range
0
20
40
60
80
100
120
140
160
180
0 100 160 340 350 500 640
Q m/h
H
m
Hyamat IndustryHyamat Building systems
7/31/2019 Booster Units Training
13/52
Seite 13 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
V
K
VP
Price
Technology
Hyamat
Hya-Eco
Product positioning (multi-pump systems)
7/31/2019 Booster Units Training
14/52
Seite 14 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
PRESSURE BOOSTING SYSTEMS
1. Definition and Principle of a Booster unit2. Hyamat Range3. Hya-Solo Presentation4. Hyamat K/V/VP modes of operation5. Hyamat K/V/VP Presentation6. Equipement7. Selection of a Booster unit
7/31/2019 Booster Units Training
15/52
Seite 15 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
Hya-Solo
Application: Fire-fighting systems for residential buildings,department stores and industrial plants
Water supply systems for residential and
office buildings Irrigation / sprinkling systems Rainwater utilisation systems Utility water supply systems for industrial plants
Pumped liquid: Drinking water, fire-fighting water, utility water,cooling water, filtered rainwater containing noaggressive, abrasive or solid substances.
7/31/2019 Booster Units Training
16/52
Seite 16 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
Designation Principle for Hya-Solo
Type seriesE = single-phase a.c. current
D = three-phase currentSpeed control
(V = variable with frequency converter)
Pump size
Number of stages
Inlet pressure in bar (for V: from - to)
Hya-Solo D V / 04 05 / 2 - 4
7/31/2019 Booster Units Training
17/52
Seite 17 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
HYA - SOLO E
Hya-Solo E / 0405
Type series E
Pump size 0405
With Movitec VE 2-6 and VE 4-5
Characteristic: Movitec VE
with integrated non return valve All wet parts of the pump in stainless steel
Operating data (standard variant):Pd up to 10 barPinlet up to 3,5 barTliquid up to 70C
up to 25C acc. To DIN 1988 (DVGW)Tambient up to 40C
Supply voltage1~230V 50Hz
7/31/2019 Booster Units Training
18/52
Seite 18 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
HYA - SOLO D/DV
Hya-Solo D / 1808 / 0,3
Type series D, DV Pump size 2, 4, 10, 18, 32, 45, 65 Number of stages Inlet pressure (bar)
With Movitec V 2m/h - 65m/h
Characteristic: Movitec V All wet parts of the pump in stainless steel
Operating data (standard variant):Pd up to 16 barPinlet up to 6 barTliquid up to 70C
up to 25C acc. To DIN 1988 (DVGW)Tambient up to 40CSupply voltage
3~400V 50Hz
7/31/2019 Booster Units Training
19/52
Seite 19 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
Selection chartHya-Solo
Head
02 04 1832
4510
Movitec
7/31/2019 Booster Units Training
20/52
Seite 20 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
Hya-Solo
Permissible inlet pressure fluctuations
for Hya-Solo D +0,3/-0,2 barfor Hya-Solo DV see characteristic curves
The sum of inlet pressure and shutoff head must not exceed 10 barfor Hya-Solo E and 16 bar for Hya-Solo D/DV.
7/31/2019 Booster Units Training
21/52
Seite 21 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
Hya-Solo
Hya-Solo E
Hya-Solo D/DV 4/10
Hya-Solo D/DV 18/32/45/65
7/31/2019 Booster Units Training
22/52
Seite 22 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
Design:Hya-Solo E Fully automatic, package single-pump unit with 8 l
membrane-type accumulator. The unit is started updepending on the pressure and switched off
depending on the flow.
Hya-Solo D Fully automatic, package single-pump unit. The
unit is started up and switched off depending on thepressure.
Hya-Solo DV Fully automatic, package single-pump unit withspeed control. The unit is started up depending onthe pressure and switched off depending on the
flow rate.
7/31/2019 Booster Units Training
23/52
Seite 23 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
The pump is started up depending on the pressureand switched off depending on the flow
0
10
20
30
40
50
60
0 1 2 3 4 5 6 7Q(m/h)
H(m)
PE
Hya-Solo E
PE = Start up pressure
Q = Schwitch off Flow rate
Q1
7/31/2019 Booster Units Training
24/52
Seite 24 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
Hya-Solo E
Low energy consumption
due to high-efficiency
hydraulic
Corrosion-resistant
hydraulic
Integrated swingcheck valve
Integrated dry-
running protection
Reserve volume for lowwater withdrawal
quantities, low switchingfrequency thanks to
DVGW-approved
accumulator
Easy adaptation to the operating
conditions by setting the start-up
pressure to values from 2 to 3.5bar
Installation free from solid-borne noise transmission
because of elastic elements
7/31/2019 Booster Units Training
25/52
Seite 25 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
The pump is started up and switched off depending on the pressure
0
10
20
30
40
50
60
70
80
0 2 4 6 8 10 12Q(m/h)
H(m)
PE
Hya-Solo D
PA
PE = Start up pressure
PA = Schwitch off pressure
7/31/2019 Booster Units Training
26/52
Seite 26 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
Hya-Solo D/DV
Daily functional check run
controlled by timer (option)
DVGW-approved
control tank with directflow to DIN 4807-5 Fully automatic
control unit
Permanently filled dischargepipe thanks to check valve
System pressure indicated
by pressure gauge
Lack-of-water protection bymeans of the pressure
control device (option)
Installation free from solid-borne noise transmission
because of elastic elements
7/31/2019 Booster Units Training
27/52
Seite 27 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
Speed control system with a single pump started up depending on the pressureand switsched off on the flow.
0
10
20
30
40
50
60
70
80
0 2 4 6 8 10 12Q(m/h)
H(m)
PE
Hya-Solo DV
PE = Start up pressure
Q1 = Schwitch off pressure
Q1
100%
75%
80%
7/31/2019 Booster Units Training
28/52
Seite 28 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
Hya-Solo D/DV 15/30/45
Daily functional check run
controlled by timer (option)
Membrane-type
accumulator with
direct flow to DIN 4807-5
System pressure
indicated by
pressure gauge Permanently filled discharge
pipe thanks to check valve
Pump can bedismantled via flange
Lack-of-water protection by
means of the pressure control
device (option)
Corrosion-resistant: hydraulic and
pump shroud made of stainless steel
Fully automatic control unit
7/31/2019 Booster Units Training
29/52
7/31/2019 Booster Units Training
30/52
7/31/2019 Booster Units Training
31/52
Seite 31 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
Two to six pumps arestarted up and switched
off by the control unit inline with the actualdemand.
Hyamat K Pressure-controlled cascade operation
7/31/2019 Booster Units Training
32/52
Seite 32 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
A base load pump is
continuously controlled,with the peak load
pumps being started upand switched off in linewith the demand.
Hyamat VContinuous speed control of one pump
set value
7/31/2019 Booster Units Training
33/52
Seite 33 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
Continuously variable
speed adjustment ofeach pump.
The peak load pumps
are started up andswitched off in line with
the demand.All pumps run at the
same speed.
Hyamat VP Continuous speed control of each pump
set value
7/31/2019 Booster Units Training
34/52
Seite 34 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
Other combinations and control modesAvailable on request (example: 1 or 2 jockeypumps as low load pumps)
7/31/2019 Booster Units Training
35/52
Seite 35 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
PRESSURE BOOSTING SYSTEMS
1. Definition and Principle of a Booster unit2. Hyamat Range3. Hya-Solo Presentation4. Hyamat K/V/VP modes of operation5. Hyamat K/V/VP Presentation
6. Equipement7. Selection of a Booster unit
7/31/2019 Booster Units Training
36/52
Seite 36 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
Hyamat K / V / VP
Applications:
Pumped liquid:
Residential buildings Hospitals
Office Buildings
Hotels
Department stores Industry
Other
applications
Drinking water, service water,
fire-fighting water, cooling water,
provided that it is neither chemicallynor mechanically aggressive to the
system materials
7/31/2019 Booster Units Training
37/52
Seite 37 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
HYAMAT K, V und VP
Hyamat K 6 / 1808 / 0,3
Type series K, V, VP Number of pumps Pump size 2, 4, 10, 18, 32, 45 Number of stages Inlet pressure (bar)
Mit Movitec V von 2m/h bis 45m/h
Characteristic: Movitec V
All wet parts of the pump in stainless steel
Type series
K (pressure-dependent cascade operation)
V (continuously variable speedadjustment of one pump)
VP (continuously variable speedadjustment of all pumps)
7/31/2019 Booster Units Training
38/52
7/31/2019 Booster Units Training
39/52
7/31/2019 Booster Units Training
40/52
Seite 40 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
Hyamat K / V / VP
Materials
Pumps Movitec V
suction/discharge casing stainless steel
hydraulic stainless steel
seal FPM 80
plain bearing aluminium oxide
mechanical seal to DIN 24960
spring-loaded ring hard carbon, resin-impregnated
seat ring aluminium oxide
7/31/2019 Booster Units Training
41/52
7/31/2019 Booster Units Training
42/52
Seite 42 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
Features / Benefit
System using a frequency inverter High operating reliability in case
for each pump of failure of a pump or frequencyinverter
Synchronous pump operation High pressure constancy at
dynamic consumer installations
Fully speed-controlled High efficiency due to the capability
pressure boosting unit of the system to use the variableinlet pressure
Pump and frequency inverter Standard products instead ofare separated integrated solutions (control
cabinet muffles frequencyinverter noise)
Hyamat VP
7/31/2019 Booster Units Training
43/52
Seite 43 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
PRESSURE BOOSTING SYSTEMS
1. Definition and Principle of a Booster unit2. Hyamat Range3. Hya-Solo Presentation4. Hyamat K/V/VP modes of operation5. Hyamat K/V/VP Presentation
6. Equipement7. Selection of a Booster unit
7/31/2019 Booster Units Training
44/52
Seite 44 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
Hyamat K / V / VP
Start-up and shutdown of up to
six high pressure pumps,as required
Even distribution ofpump operation
automaticpump changeover
General fault message
volt-free contact
High reliability
constant monitoring of
the function of theconnected sensors
DVGW-approved
valves
Corrosion protection thanks
to stainless steel piping
No structure-borne sound
pumps are uncoupled from
the base
Flow goes through
the control vessel
DIN 4807-5,
DVGW-approved
Full enclosure
(optional)
retrofitting, easy to service protects from dirt attractive design low-noise approx. 51-61 dB(A)
7/31/2019 Booster Units Training
45/52
Seite 45 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
In drinking water application to
DIN 4807-5, flow must go through
the accumulator.
Piping
Flow passing through the accumulator
7/31/2019 Booster Units Training
46/52
Seite 46 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
V = 275 x Qm x (Pe+1) x (Pa+1)F x P x (Pg+1) x N
V = Tank volume (liter)Pe = Pressure switch on (bar)Pa = Pressure switch off (bar)
P = Pa - Pe (bar)Qm = average flow of the pumpe
between Pa and Pe (m/h)
F = Motor start allowed per hourPg = Air Pressure of the tank (bar)
(Pg = Pe-0,5)N = Number of pumps
Determination of the volume of an accumulator
0
10
20
30
40
50
60
70
0 1 2 3 4 5 6Q(m/h)
H(m)
Pe
Pa
Qm
(Pa = 4,5 bar)
(Pe = 3,5 bar)
(P = 1 bar)
(Qm = 3,5 m/h)
Exemple: for 2 Pumps with F=15V = 199 liter
7/31/2019 Booster Units Training
47/52
Seite 47 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
Hyamat VPwithout or with cladding (optional)
(Surpresschrom SICVP)
7/31/2019 Booster Units Training
48/52
Seite 48 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
PRESSURE BOOSTING SYSTEMS
1. Definition and Principle of a Booster unit2. Hyamat Range3. Hya-Solo Presentation4. Hyamat K/V/VP modes of operation5. Hyamat K/V/VP Presentation
6. Equipement7. Selection of a Booster unit
7/31/2019 Booster Units Training
49/52
Seite 49 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
Hyamat K / V / VP
7/31/2019 Booster Units Training
50/52
Seite 50 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
Selection
A pressure booster units is defined by the flowrates and the pressure.Hs = Static Head...........................................m
H = Head loses (devices, pipes,etc...)........mPu = Pressure user.......................................bar
The pressure after the Booster unit
= Hinlet + Hs + H + (Pu x10)
The flow rates is defined according rules ofcalculation given from the norms.for example:
DIN1988/5 Germany NFP 41101 and DTU 6011 France
Booster unit
Hinlet
H
Pmax=3,3bar
pmin=2,2bar
Hs
H
Pu
Pressure to produce = Hs+H+(Pux10)
P B i S
7/31/2019 Booster Units Training
51/52
Seite 51 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
Data required for selection of a pressure boosting unit (PBU)
PBU capacity (Q):
Stand-by pump: yes/no
Start-up pressure for PBU (pE):
min. inlet pressure upstream of PBU (pmin):
max inlet pressure upstream of PBU (pmax):
PBU discharge head (H):
Pressure boosting concepts: Cascade operation /
Speed control of one pump/of all pumps
CAUTION! Do not forget the dry-running protection equipment!
pmax
pminpEPBU
H/Q~~
discharge sideInlet side
P B ti S t
7/31/2019 Booster Units Training
52/52
Seite 52 von 54Building Services Pumps
Pressure Boosting System
V34, Productmanagement
10/2004
Number of pumps
Capacity m3/h
Head (max) m
Automatic dry-run
protection
Control
System dischargepressure bar
2 to 3 2 to 6 2 to 6 2 to 4
up to 7 up to 65 up to 45 up to 360 up to 360 up to 200
no yes yes yes yes yes
standard accessory accessory accessory accessory standard
cascade
D Cascade
DV 1 pumpspeed-controlled
cascade cascade1 pump
speed-
controlled
all pumps
speed-
controlled
Pipes of stainless steel
Pressure Boosting system at a glance