The full range of Bock indoor and outdoor condensing units
Bock Australia Pty Ltd | Condensing Unit Catalogue
GEA Refrigeration Technologies engineering for a better world
2 | www.bockaust.com.au 05/2012 - BockCU-Gb Subject to change without notice
GEA Refrigeration Technologies, part of the internationally active GEA Group, is a syn-
onym for industrial refrigeration technology. Since the end of the 19th century, it has been
our business to cool processes and products, and to control the temperature of goods in
transport. You will find our solutions in the food and beverage sector; in the petrochemi-
cal, chemical, and pharmaceutical industries; on fishing ships; in natural gas liquefaction;
in infrastructure facilities; and in ice factories. We are also at the top with know-how
when it comes to refrigeration at leisure facilities. After all, we have been excited about
refrigeration for decades now. As a result, our staff enthusiastically goes about its deve-
lopment and production projects – to include preventive and remedial maintenance of
your refrigeration systems.
This enthusiasm is highly apparent in the daily work of all companies in our Segment.
Whether it’s complete systems or individual valves: we have the experience in every sec-
tion of our company to optimally design, manufacture, and install refrigeration systems.
And to take full advantage of this experience, we not only carry out development in our
own company: we also manufacture, assemble, and test the core components. A chain is,
after all, only as strong as its weakest link: and this also applies equally well to refrigera-
tion technology, cooling processes, and cooling chains.
This makes it all the more important that you have a partner – in GEA Refrigeration
Technologies – that has learned to master refrigeration from A to Z. And all of this since
1896, when Willem Grasso founded his refrigeration division. From this history of GEA
Refrigeration Technologies, you will profit in the form of technical expertise and top
sector know-how.
But we all live in the present and think about the future. We ponder a future in which
more and more processes need energy around the world, and fewer natural resources are
available. As a result, we have taken it as our goal to create solutions that are not only
long-life and cost-effective, but also energy-saving and environment-protecting. We feel
obligated to sustainability in many respects. Our objective is to produce longlife and ma-
terial-saving products over the long run – as well as products that use environmentally
benign refrigerants. And we aim to produce efficiently. But our responsibility does not end
at the factory gate. As a result, we take great pains to ensure that our systems are energy-
efficient and that they protect the climate. With GEA Refrigeration Technologies, you can
also count on optimal economy: saving energy indeed means reducing money spent for
energy. At the same time, you protect the environment. Thanks to our refrigeration tech-
nology, your processes will run more economically and more ecologically. To maintain our
standard of living and to assure quality of life for future generations as well.
Our claim of combining economy with saving natural resources is reflected in all com-
ponents of our company, such as the following: compressors, chillers, heat pumps, ice
machines, fittings and valves, control systems, and many, many more. You can find proof
of the above throughout the world. Our international corporate network – and above all
our reference projects – are spread all over the globe.
In touch with our customers
GEA Refrigeration Technologies:Your partner for low temperatures
3www.bockaust.com.au |05/2012 - BockCU-Gb Subject to change without notice
DisclaimerThis brochure has been produced for you with the greatest of care. Nevertheless it is not possible to rule out mistakes completely. In such cases we cannot assume any liability. The contents correspond to the status on going to print. Deviations cannot be ruled out because of the ongoing developement process for our products.
The details are provided as unbinding general information and cannot substitute detailed, individual consultation. Reprints even only of excerpts only allowed with the explicit approval of Bock Australia Pty. Ltd. and GEA Bock GmbH. © Bock Australia Pty. Ltd., GEA Bock GmbH 2012
In touch with our customers
Bock Condensing Units
At a glance I 1
Plusbox, vertical outdoor units I 2
Plusbox, horizontal outdoor units I 3
Plusbox, horizontal sealed units I 4
Plusbox R Series I 5
Bock indoor condensing units I 6
05/2012 - BockCU-Gb Subject to change without notice4 | www.bockaust.com.au
Bock Condensing UnitsAt a glance
The Bock semi-hermetic compressor program provides a full per-
formance range of innovative and modern compressor designs in
2, 4, 6 and 8 cylinder constructions.
The ideal solution for any kind of application.
HG (Hermetic Gas-cooled)
Conventional suction gas-cooled compressor design
HA (Hermetic Air-cooled)
Special Bock design for deep-freezing (R22/R404A) with an air-
cooled motor and direct suction at the cylinder.
All the compressors display the same particularly
remarkable features:
- Outstanding running comfort
- High efficiency and reliability to the highest quality
standard
- Easy maintenance, e.g. interchangeable motors
- Oil pump lubrication
- Bock MP10 electronic motor protection, especially easy to operate
with LED status indicators
- Suitable for conventional and chlorine-free HFC refrigerants
The current program...8 model sizes with 26 capacity stages from 5,4 to 279,8 m³/h (50 Hz)
Available versions:
The Bock semi-hermetic program provides the following product
variants:
- Single-stage HG (HA) compressors
- Two-stage HGZ compressors
- Duplex DHG (DHA) compressors
- SHG (SHA) compressor units with receiver
- SHG (SHA) condenser units air-cooled
Forward looking compressor models
Bock offers a choice of interesting compressor versions in the
established semi-hermetic range for current market trends such as
alternative refrigerants, deep-freezing or EX protection.
- HA (Hermetic Air-cooled),
air-cooled compressors for deep-freezing applications
- CO2 Compressors (subcritical), for subcritical cascade systems
- CO2 Compressors (transcritical), for transcritical
CO2 applications
- R410A Compressors, for the refrigerant R410A
- ATEX (ATmospheres EXplosibles),
for explosion-risk environments
300
200
100
3H
ubvo
lum
en m
/h
HG8HG7HG(HA)6HG(HA)5HG(HA)4HG34e HA34PHG22e HA22PHG(HA)12PDis
plac
emen
t m
³/h
505/2012 - BockCU-Gb Subject to change without notice www.bockaust.com.au |
Bock Condensing Units
1
2
3
4
5
6Safe, reliable oil supply
- 4 and 6 cylinder with a conventional single circuit lubricating system
- Lubricating system incorporating an oil pump
- Large volume oil sump
- 8 cylinder compressor with a dual circuit lubricating system (two
oil circuits), each of the two main bearings supplied as the first
lubrication point
- Oil pump lubrication independent of direction of rotation
- Connection possibility for oil pressure monitoring ∆p-oil differential
pressure sensor
- Large volume oil sump
- Direct coupling option for oil level regulator as standard
Special features
Universal
- e.g. R134a, R404A, R507, R407C, R22
One compressor design for all standard refrigerants.
For air-conditioning applications, normal refrigeration and deep-
freezing
- Maximum allowed operating pressure (HP): 28 bar
High refrigeration capacity combined with minimum power
requirement
- Optimized gas flow
- Efficient service valves
- Minimum clearance volume
- Powerful economic drive motors
Wide range of applications without additional cooling
Deep-freezing range with R404A, R507 also available with
suction gas cooling (HG version)
Stable valve plate design
- Universally proven valve design with intake and discharge finger
reed valves clamped on one side
- Valve made of high quality impact-resistant spring steel
Replaceable motors
The compressors can be repaired in the field as the drive motor
can be exchanged.
Economic capacity control
- Cylinder cover incorporating a connection for capacity control
- Possible control stages:
4 cylinder: 50 %
6 cylinder: 33 % / 66 %
8 cylinder: 25 % / 50 % / 75 %
- Continuously variable speed control (25 - 70 Hz) using an exter-
nal frequency converter EFC/EFCe. See separate brochure "Bock
semi-hermetic compressors - Electronic Controls".
Minimum space requirement
Particularly low installation height and width.
Quiet and low vibration
- Generously dimensioned crank mechanism
- Optimized mass balance
- Large volume pressure section for pulsation absorption
- 4 cylinder design from as little as 19 m³/h
Oil pump
Oil overpressureOil return
Inlet lubricating
circuit 1
Inlet lubricating
circuit 2
05/2012 - BockCU-Gb Subject to change without notice6 | www.bockaust.com.au
Bock Condensing Units
Wear-resistant durable driving gear
- 2 and 4 cylinder compressor HG(HA)12 to HG(HA)34
- Solid construction and design
- Low friction sleeve bearings
- Aluminium pistons with two ring assembly
- 4 and 6 and 8 cylinder compressor HG(HA)4 to HG8
- Solid construction and design
- Surface-hardened crankshaft
- Low friction sleeve bearings
- Aluminium pistons with triple ring assembly, hard-chromium plated
sealing ring, HG(HA)4 with double ring assembly
- Aluminium connecting rod with high resistance piston bolt bearings
starting HG(HA)5
Special features
Solid construction and design
HG(HA)12-34 HG(HA)4
HG(HA)5 HG8
- Valve made of high quality impact-resistant spring steel
- Concentric reed valve on the suction side finger reed valve
1 2
2 1
705/2012 - BockCU-Gb Subject to change without notice www.bockaust.com.au |
Bock Condensing Units
1
2
3
4
5
6Oil sump heater
- Optional in 2 and 4 cylinder compressors HG(HA)12 up to HG(HA)34
- PTC heater, self-regulating
- Replacement without opening the refrigeration circuit
- Standard in 4 and 6 and 8 cylinder compressors
HG(HA)4 up to HG8
- Immersion case design
- Replacement possible without opening the refrigerating circuit
Variable suction line valve position (HG)
4 cylinder 8 cylinder
- Shutoff valve rotates through 90° (2 and 4 cylinder) suction cover rotates through 90° (8 cylinder)
- Flexible location for suction line connection
Special features
05/2012 - BockCU-Gb Subject to change without notice8 | www.bockaust.com.au
Bock Condensing Units
Electric switch box
- Robust aluminium construction
- Easy electrical installation due to large internal volume
- Terminal block with cables in glass seal model
- Hinged and removable lifting cover
with a single quick fastener
- Terminal strip for add-on components
- Protection system: IP66
- Easy electrical installation due to large internal volume
- Terminal block with cables in glass seal model
- Hinged lifting cover with a single quick fastener (6 cylinder),
- Cover with simple snap closure (8 cylinder)
- Insulation between terminal studs
- Inspection window for compressor monitoring (8 cylinder)
- Protection system: 4 cylinder IP65; 6 and 8 cylinder IP54
Special features
Economic capacity control (option)Via capacity regulator Cylinder cover incorporating a connection for capacity control
Possible control stages:
4 cylinder: 50 %,
6 cylinder: 33 % / 66 %,
8 cylinder: 25 % / 50 % / 75 %
Via frequency converter Continuously variable speed control using the Bock EFC / EFCe
(Electronic Frequency Control)
- Up to 25% less power consumption
- EFC Continuously variable speed control directly mounted on
the compressor HG(HA)12 to HG(HA)34
- EFCe Continuously variable speed control for individual set-up
HG4 to HG8, HA on request
- Further information see separate brochure
"Bock semi-hermetic compressors - Electronic Controls".
1
2
1
2
3
3
1
2
1
2
2
1
1
2
905/2012 - BockCU-Gb Subject to change without notice www.bockaust.com.au |
Bock Condensing Units
1
2
3
4
5
6
Bock MP10 Electronic Motor Protection
- Standard with all 2, 4 and 6 cylinder compressors
- Temperature monitoring with PTC sensors and optical status
indicators
- Discharge gas temperature sensor (option)
- Further information see separate brochure
"Bock semi-hermetic compressors - Electronic Controls".
Bock Compressor Management BCM2000
- Innovative and advanced compressor management system
- Optional for 4- and 6 cylinder compressors
- Further information see separate brochure
"Bock semi-hermetic compressors - Electronic Controls".
Special features
Start unloader with the Bock ESS (option)
(Electronic Soft Start)
- Optional for HG22 and HG34
- Continuous compressor start-up to nominal speed
- No need for conventional start unloaders
- IP20 unit for installation in switch cabinet (supplied loose)
- Further information see separate brochure
"Bock semi-hermetic compressors - Electronic Controls".
Single phase AC operation with Bock ESP (option)
(Electronic Single Phase)
- Standard three phase AC compressor can be used on a single
phase supply
- No start-up or operating condensers or relays required
- Unit designed for installation in switch cabinet
- Further information see separate brochure
"Bock semi-hermetic compressors - Electronic Controls".
05/2012 - BockCU-Gb Subject to change without notice10 | www.bockaust.com.au
Bock Condensing UnitsOperating limits
R404A/R507 Operating limits
HGX12P / HGX22e / HGX34e /
HGX4 / HGX5 / HGX6 1 / HGX7 / HGX8 2
HAX12P / HAX22P / HAX34P / HAX4
100-10-20-30-40-5020
30
40
50
60
70
t (°C)o
t (°C)c
? toh<20K
t +20°Coh
58
-5 7,5-45-10-20-30-40-50
20
30
40
50
6058
? toh<20K
t (°C)o
t (°C)c
t +20°Coh
HAX5 HAX6
0-10-20-30-40-5020
30
40
50
6058
? toh<20K
t (°C)o
t (°C)c
HAX5/830-4
HAX5/945-4
HAX5/725-4
t +20°Coh
-10-20-30-40-5020
30
40
50
6058
? toh<20K
t +20°Coh
t (°C)o
t (°C)c
HAX6/1080-4
HAX6/1240-4
HAX6/1410-4
Max. permissible operating pressure (LP/HP)1): 19/28 bar 1) LP = low pressure HP = high pressure
1 HGX6/1410-4S
Max. evaporating temperature tO = 2 °C
HGX6/1410-4
Max. evaporating temperature tO = -7 °C
2 HGX8/2830-4
Max. evaporating temperature tO = 0 °C
Unlimited application range
-HG Supplementary cooling or reduced suction gas temperature -HA reduced suction gas temperature
Motor version -S- (more powerful motor)
tO Evaporating temperature (°C)
tC Condensing temperature (°C)
∆tOh Suction gas superheat (K)
tOh Suction gas temperature (°C)
1105/2012 - BockCU-Gb Subject to change without notice www.bockaust.com.au |
Bock Condensing Units
1
2
3
4
5
6
Notes
R404A/R507 Notes
Operating limits
Compressor operation is possible within the limits shown on the ap-
plication diagrams. Please note the coloured areas. Compressor appli-
cation limits should not be chosen for design purposes or continuous
operation.
Restrictions to the operating limits may occur when using the Bock
EFC (Electronic Frequency Control).
Further explanation see separate brochure "Bock semi-hermetic com-
pressors - Electronic Controls".
Performance data
The performance data for R404A/R507 are based on European
Standard EN 12900 with a 50 Hz power supply frequency.
This signifies: 20 °C suction gas temperature without liquid sub-
cooling.
This leads to significant differences compared to systems with liquid
subcooling and/or other suction gas temperatures.
Performance data were compiled for R404A and R507.
The base values are the data for R404A.
Conversion factor for 60 Hz = 1,2
Performance data for other operating points, see GEA Bock software.
ASERCOM certified performance data
For compressors with this label, the performance
data are certified according to the strict require-
ments of ASERCOM.
ASERCOM is the Association of European Refrigeration Compressors
and Controls Manufacturers.
Information about the Association and the constantly updated over-
view of certified Bock compressors can be found at www.asercom.org
and www.bock.de.
05/2012 - BockCU-Gb Subject to change without notice12 | www.bockaust.com.au
Bock Condensing Units
R134a Operating limitsHGX12P / HGX22e / HGX34e HGX4 / HGX5 / HGX6 / HGX7 / HGX8
Unlimited application range
Supplementary cooling or
reduced suction gas temperature
Motor version -S- (more powerful motor)
tO Evaporating temperature (°C)
tC Condensing temperature (°C)
∆tOh Suction gas superheat (K)
tOh Suction gas temperature (°C)
1) LP = low pressure HP = high pressureMax. permissible operating pressure (LP/HP)1): 19/28 bar
Operating limits
R134a Notes
Operating limits
Compressor operation is possible within the limits shown on the ap-
plication diagrams. Please note the coloured areas. Compressor appli-
cation limits should not be chosen for design purposes or continuous
operation.
Restrictions to the operating limits may occur when using the Bock
EFC (Electronic Frequency Control). Further explanation see separate
brochure "Bock semi-hermetic compressors - Electronic Controls".
Performance data
The performance data for R134a are based on ISO-DIS 9309
(DIN 8928) with a 50 Hz power supply frequency. This signifies:
25 °C suction gas temperature without liquid subcooling.
For Pluscom compressors and HGX8/2470-4 operating at 50 Hz al-
ready comply with EN 12900. This signifies 20 °C suction gas tem-
perature without liquid subcooling.
This results in significant differences compared to specifications with
liquid undercooling and/or suction-gas temperatures.
A comprehensive modification to 20 °C suction gas temperature will
follow at a later date.
Conversion factor for 60 Hz = 1,2
Performance data for other operating points, see GEA Bock software.
ASERCOM certified performance data
For compressors with this label, the performance
data are certified according to the strict require-
ments of ASERCOM.
ASERCOM is the Association of European Refrigeration Compressors
and Controls Manufacturers.
Information about the Association and the constantly updated over-
view of certified Bock compressors can be found at www.asercom.org
and www.bock.de.
1305/2012 - BockCU-Gb Subject to change without notice www.bockaust.com.au |
Bock Condensing Units
1
2
3
4
5
6
Scope of supply HG HG12P HG22e HG34e HG4 HG5 HG6 HG7 HG8
Semi-hermetic two cylinder reciprocating compressorwith drive motor for direct start220-240 V ∆ / 380-420 V Y - 3 - 50 Hz265-290 V ∆ / 440-480 V Y - 3 - 60 HzSingle-section compressor housing with hermetically integrated electric motor
Semi-hermetic four cylinder reciprocating compressorwith drive motor for direct start220-240 V ∆ / 380-420 V Y - 3 - 50 Hz265-290 V ∆ / 440-480 V Y - 3 - 60 HzSingle-section compressor housing with hermetically integrated electric motor
Semi-hermetic four cylinder reciprocating compressorwith drive motor for part winding start380-420 V Y/YY - 3 - 50 Hz440-480 V Y/YY - 3 - 60 HzMotor unit flanged onto the compressor housing
Semi-hermetic six cylinder reciprocating compressorwith drive motor for part winding start380-420 V ∆ / YYY - 3 - 50 Hz440-480 V ∆ / YYY - 3 - 60 HzSingle-section compressor housing with hermetically integrated electric motor
Semi-hermetic eight cylinder reciprocating compressorwith drive motor for part winding star380-420 V ∆ / YYY - 3 - 50 Hz440-480 V ∆ / YYY - 3 - 60 HzSingle-section compressor housing with hermetically integrated electric motor
Winding protection with PTC resistor sensors and electronic triggering unit Bock MP10
Individual protection of the cylinder heads with thermal protection thermostats, readily wired and connected with Bock Compressor Management BCM2000
Oil temperature sensor in the oil sump, readily wired and connected with Bock Compressor Management BCM2000
Oil differential pressure sensor (Δp-switch Kriwan make), ready wired and connected with Bock Compressor Management BCM2000
Oil pump cover with screwed connection for differential oil pressure sensor (∆p-switch Kriwan make)
Possibility to connect to oil level controllers makes ESK, AC+R or CARLY
1) 1) 1)
Possibility to connect to oil level controllers make Traxoil 1) 1) 1) 1) 1) 1) 1) 1)
Oil sump heater 230 V - 1 - 50/60 Hz, 80 W
Oil sump heater 230 V - 1 - 50/60 Hz, 140 W
Oil sump heater 230 V - 1 - 50/60 Hz, 200 W
Oil service valve
Oil charge: HG: FUCHS Reniso SP 46 HGX: FUCHS Reniso Triton SE 55
Sight glass
Two sight glasses
Three sight glasses
Prepared for capacity regulator (1 cylinder cover)
Prepared for capacity regulator (2 cylinder covers)
Prepared for capacity regulator (3 cylinder covers)
Decompression valve
Suction and discharge line valve
Inert gas charge
4 anti-vibration pads enclosed
Scope of supply
1) Only possible with additional adapter
05/2012 - BockCU-Gb Subject to change without notice14 | www.bockaust.com.au
Bock Condensing UnitsTechnical data
HG
Type
Numberof
cylinders
Displacement50 / 60 Hz
(1450/1740 rpm)
Electrical data Weight Connections 6 Oil chargeVoltage
1
Max. working current
2
Max. powerconsump-
tion2
Startingcurrent
(rotor locked)
Discharge lineDV
Suction lineSV
m³/h A kW A kg mm I inch mm I inch Ltr.∆ / Y ∆ / Y
HG12P/60-4 S 2 5,40 / 6,40 3 6,8 / 3,9 2,2 40 / 23 48,0 12 I 1/2 16 I 5/8 0,8HG12P/75-4 2 6,70 / 8,10 3 7,1 / 4,1 2,3 40 / 23 48,0 12 I 1/2 16 I 5/8 0,8HG12P/75-4 S 2 6,70 / 8,10 3 8,0 / 4,6 2,6 43 / 25 49,0 12 I 1/2 16 I 5/8 0,8HG12P/90-4 2 8,00 / 9,60 3 8,5 / 4,9 2,8 43 / 25 49,0 12 I 1/2 16 I 5/8 0,8HG12P/90-4 S 2 8,00 / 9,60 3 8,8 / 5,1 2,9 45 / 26 49,0 12 I 1/2 16 I 5/8 0,8HG12P/110-4 2 9,40 / 11,30 3 9,2 / 5,3 3,1 43 / 25 49,0 12 I 1/2 16 I 5/8 0,8HG12P/110-4 S 2 9,40 / 11,30 3 10,6 / 6,1 3,6 45 / 26 49,0 12 I 1/2 16 I 5/8 0,8HG22e/125-4 2 11,10 / 13,30 3 9,3 / 5,4 3,0 69 / 40 74,0 16 I 5/8 22 I 7/8 1,0HG22e/125-4 S 2 11,10 / 13,30 3 10,8 / 6,2 3,6 69 / 40 74,0 16 I 5/8 22 I 7/8 1,0HG22e/160-4 2 13,70 / 16,40 3 11,1 / 6,4 3,7 69 / 40 74,0 16 I 5/8 22 I 7/8 1,0HG22e/160-4 S 2 13,70 / 16,40 3 13,1 / 7,6 4,4 87 / 50 76,0 16 I 5/8 22 I 7/8 1,0HG22e/190-4 2 16,50 / 19,80 3 13,8 / 8,0 4,8 69 / 40 74,0 16 I 5/8 22 I 7/8 1,0HG22e/190-4 S 2 16,50 / 19,80 3 16,2 / 9,4 5,6 87 / 50 75,0 16 I 5/8 22 I 7/8 1,0HG34e/215-4 4 18,80 / 22,60 3 14,0 / 8,1 4,8 87 / 50 92,0 22 I 7/8 28 I 1 1/8 1,3HG34e/215-4 S 4 18,80 / 22,60 3 18,3 / 10,5 6,0 132 / 76 97,0 22 I 7/8 28 I 1 1/8 1,3HG34e/255-4 4 22,10 / 26,60 3 17,0 / 9,8 6,0 87 / 50 91,0 22 I 7/8 28 I 1 1/8 1,3HG34e/255-4 S 4 22,10 / 26,60 3 21,1 / 12,2 7,2 132 / 76 96,0 22 I 7/8 28 I 1 1/8 1,3HG34e/315-4 4 27,30 / 32,80 3 21,1 / 12,2 7,4 111 / 64 94,0 22 I 7/8 28 I 1 1/8 1,3HG34e/315-4 S 4 27,30 / 32,80 3 25,5 / 14,7 8,9 132 / 76 97,0 22 I 7/8 28 I 1 1/8 1,3HG34e/380-4 4 33,10 / 39,70 3 26,1 / 15,1 9,3 111 / 64 93,0 22 I 7/8 28 I 1 1/8 1,3HG34e/380-4 S 4 33,10 / 39,70 3 31,2 / 18,0 11,1 132 / 76 96,0 22 I 7/8 28 I 1 1/8 1,3
*PW 1+2 *PW1 / PW 1+2HG4/465-4 4 40,50 / 48,60 4 18 11,0 57 / 75 148 28 / 11/8 35 / 13/8 2,7HG4/465-4 S 4 40,50 / 48,60 4 27 13,0 82 / 107 151 28 / 11/8 35 / 13/8 2,7HG4/555-4 4 48,20 / 57,80 4 27 12,9 82 / 107 150 28 / 11/8 35 / 13/8 2,7HG4/555-4 S 4 48,20 / 57,80 4 34 15,2 107 / 140 153 28 / 11/8 35 / 13/8 2,7HG4/650-4 4 56,60 / 67,90 4 27 15,7 82 / 107 152 28 / 11/8 42 / 15/8 2,7HG4/650-4 S 4 56,60 / 67,90 4 34 18,4 107 / 140 155 28 / 11/8 42 / 15/8 2,7HG5/725-4 4 62,90 / 75,50 4 33 16,5 82 / 107 198 28 / 11/8 42 / 15/8 3,6HG5/725-4 S 4 62,90 / 75,50 4 37 19,4 107 / 140 201 28 / 11/8 42 / 15/8 3,6HG5/830-4 4 72,20 / 86,70 4 33 18,9 82 / 107 197 28 / 11/8 42 / 15/8 3,6HG5/830-4 S 4 72,20 / 86,70 4 49 22,3 126 / 160 203 28 / 11/8 42 / 15/8 3,6HG5/945-4 4 82,20 / 98,60 4 37 22,6 107 / 140 201 35 / 13/8 54 / 21/8 3,6HG5/945-4 S 4 82,20 / 98,60 4 49 28,6 126 / 160 205 35 / 13/8 54 / 21/8 3,6HG6/1080-4 4 93,70 / 112,40 4 47 26,3 149 / 189 218 35 / 13/8 54 / 21/8 3,6HG6/1080-4 S 4 93,70 / 112,40 4 57 31,0 172 / 212 223 35 / 13/8 54 / 21/8 3,6HG6/1240-4 4 107,60 / 129,10 4 57 30,5 172 / 212 222 35 / 13/8 54 / 21/8 3,6HG6/1240-4 S 4 107,60 / 129,10 4 71 36,0 204 / 250 224 35 / 13/8 54 / 21/8 3,6HG6/1410-4 4 122,40 / 146,90 4 57 35,6 172 / 212 219 35 / 13/8 54 / 21/8 3,6HG6/1410-4 S 4 122,40 / 146,90 4 71 42,6 204 / 250 222 35 / 13/8 54 / 21/8 3,6HG7/1620-4 6 140,60 / 168,80 5 76 38,7 223 / 340 278 42 / 15/8 54 / 21/8 4,5HG7/1620-4 S 6 140,60 / 168,80 5 83 46,3 268 / 373 299 42 / 15/8 54 / 21/8 4,5HG7/1860-4 6 161,40 / 193,70 5 83 44,6 268 / 373 296 42 / 15/8 54 / 21/8 4,5HG7/1860-4 S 6 161,40 / 193,70 5 98 53,3 343 / 494 292 42 / 15/8 54 / 21/8 4,5HG7/2110-4 6 183,60 / 220,30 5 98 51,2 343 / 494 289 42 / 15/8 64 / 25/8 4,5HG7/2110-4 S 6 183,60 / 220,30 5 115 60,5 344 / 500 297 42 / 15/8 64 / 25/8 4,5HG8/2470-4 8 214,30 / 257,10 5 102 60,0 274 / 301 432 54 / 21/8 76 / 31/8 9,0HG8/2470-4 S 8 214,30 / 257,10 5 155 72,5 475 / 551 432 54 / 21/8 76 / 31/8 9,0HG8/2830-4 8 245,90 / 295,10 5 155 77,5 475 / 551 429 54 / 21/8 76 / 31/8 9,0HG8/2830-4 S 8 245,90 / 295,10 5 170 84,5 520 / 605 449 54 / 21/8 76 / 31/8 9,0HG8/3220-4 8 279,80 / 335,80 5 155 78,3 475 / 551 423 54 / 21/8 76 / 31/8 9,0HG8/3220-4 S 8 279,80 / 335,80 5 170 94,2 520 / 605 443 54 / 21/8 76 / 31/8 9,0
1505/2012 - BockCU-Gb Subject to change without notice www.bockaust.com.au |
Bock Condensing Units
1
2
3
4
5
6
Explanations:
Tolerance (± 10%) relates to the mean value of the voltage range. Other voltages and current types on request.
- The specifications for max. power consumption apply for 50Hz operation. For 60Hz operation, the specifications have to be multiplied by the factor 1.2. The max. working current remains unchanged.
- Take account of the max. operating current / max. power
consumption when designing contactors, leads and fuses. Switches: Service category AC3
220-240 V ∆ / 380-420 V Y - 3 - 50 Hz 265-290 V ∆ / 440-480 V Y - 3 - 60 Hz
380-420 V Y/YY - 3 - 50 Hz PW440-480 V Y/YY - 3 - 60 Hz PWPW = Part Winding, motors for part winding start(no start unloaders required)- Winding ratios: HG(HA)4, HG(HA)5, HG(HA)6 = 66% / 33%- Designs for Y/∆ on request
380-420 V ∆/ YYY - 3 - 50 Hz PW440-480 V ∆/ YYY - 3 - 60 Hz PWPW = Part Winding, motors for part winding start(no start unloaders required)- Winding ratios: HG7, HG8 = 60% / 40%- Designs for Y/∆ on request
For soldering connections
4
5
6
1
2
3
HA
Type
Numberof
cylinders
Displacement50 / 60 Hz
(1450/1740 rpm)
Electrical data Weight Connections 6 Oil chargeVoltage
1
Max.workingcurrent
2
Max. powerconsump-
tion2
Startingcurrent
(rotor locked)
2
Discharge lineDV
Suction lineSV
m³/h A kW A kg mm I inch mm I inch Ltr.∆ / Y ∆ / Y
HA12P/60-4 2 5,40 / 6,40 3 5,5 / 3,2 1,7 40 / 23 52,0 12 I 1/2 12 I 1/2 0,8HA12P/75-4 2 6,70 / 8,10 3 5,9 / 3,4 1,8 40 / 23 53,0 12 I 1/2 12 I 1/2 0,8HA12P/90-4 2 8,00 / 9,60 3 6,6 / 3,8 2,0 43 / 25 53,0 12 I 1/2 12 I 1/2 0,8HA12P/110-4 2 9,40 / 11,30 3 6,9 / 4,0 2,2 43 / 25 53,0 12 I 1/2 12 I 1/2 0,8HA22P/125-4 2 11,10 / 13,30 3 7,1 / 4,1 3,0 69 / 40 80,0 12 I 1/2 16 I 5/8 1,0HA22P/160-4 2 13,70 / 16,40 3 8,2 / 4,8 4,0 87 / 50 82,0 12 I 1/2 16 I 5/8 1,0HA22P/190-4 2 16,50 / 19,80 3 9,0 / 5,2 4,0 87 / 50 81,0 12 I 1/2 16 I 5/8 1,0HA34P/215-4 4 18,80 / 22,60 3 10,9 / 6,3 3,7 87 / 50 98,0 16 I 5/8 22 I 7/8 1,3HA34P/255-4 4 22,10 / 26,60 3 12,5 / 7,2 4,3 87 / 50 98,0 16 I 5/8 22 I 7/8 1,3HA34P/315-4 4 27,30 / 32,80 3 16,2 / 9,4 5,3 132 / 76 100,0 16 I 5/8 22 I 7/8 1,3HA34P/380-4 4 33,10 / 39,70 3 18,9 / 11,0 6,4 132 / 76 100,0 16 I 5/8 22 I 7/8 1,3
*PW 1+2 *PW1 / PW 1+2HA4/465-4 4 40,50 / 48,60 4 21 11,2 82 / 107 155,0 28 / 11/8 35 / 13/8 2,7HA4/555-4 4 48,20 / 57,80 4 26 13,3 107 / 140 157,0 28 / 11/8 35 / 13/8 2,7HA4/650-4 4 56,60 / 67,90 4 26 15,6 107 / 140 156,0 28 / 11/8 35 / 13/8 2,7HA5/725-4 4 62,90 / 75,50 4 26 12,5 107 / 140 204,0 28 / 11/8 42 / 15/8 3,6HA5/830-4 4 72,20 / 86,70 4 26 12,8 126 / 160 207,0 28 / 11/8 42 / 15/8 3,6HA5/945-4 4 82,20 / 98,60 4 26 12,9 126 / 160 205,0 28 / 11/8 42 / 15/8 3,6HA6/1080-4 4 93,70 / 112,40 4 31 15,8 172 / 212 223,0 28 / 11/8 42 / 15/8 3,6HA6/1240-4 4 107,60 / 129,10 4 31 15,9 172 / 212 221,0 28 / 11/8 42 / 15/8 3,6HA6/1410-4 4 122,40 / 146,90 4 31 16,2 172 / 212 219,0 28 / 11/8 42 / 15/8 3,6
Oil sump heater 110-240 V - 1 - 50/60 Hz (option)HG(HA)12, HG(HA)22, HG(HA)34: 50-120 W PTC heater, self-regulating, installation in housing bore
Oil sump heater 230 V - 1 - 50/60 Hz (standard)- HG(HA)4: 80 W- HG(HA)5, HG(HA)6, HG7: 140 W - HG8: 200 W Permanently set version, installation in immersion sleeve
Fan motors for the HA version 230 V - 1 - 50/60 Hz- HA12P: 40 W / 0,3 A- HA22P, HA34P: 72 W / 0,53 A- HA4, HA5, HA6: 140 W / 0,71 A
* PW = Part Winding, motors for part winding start 1 = 1. part winding 2 = 2. part winding
Technical data
05/2012 - BockCU-Gb Subject to change without notice16 | www.bockaust.com.au
Bock Condensing Units
Plusbox model single coil
Plusbox - vertical outdoor units
Vertical Outdoor Condensing Units with single and twin coil
Standard Design Secifications
- Bock Pluscom Semi Hermetic Compressor - Powdercoated Sheet Metal Enclosure - Generous Condenser sizes for the Australian Climate - Dual Pressure Control with Flexilines - Discharge Line Vibration Eliminator - Internal Float Oil Separator - Liquid Receiver, Drier & Sightglass - Electrical Panel fully wired (Includes Isolation Switch) - Crankcase Heater - Electronic Motor Protection - Oil Charge - Polyolester as standard (Mineral on request) - All condensers are coated with melamine enamel for extended life
Optional Extras
- Liquid Line Solenoid Valve - Suction Accumulator - Capacity Control - HP Fan Cycle Switch - Oil Level Monitoring - Crankcase Pressure Regulator - Pressure Relief Valves - TRAXOIL Oil Regulator - Electronic fan speed contoller available - Condensers can be additionally coated with Blygold coating guaranteed and tested for 5000 hour salt spray test
Plusbox model twin coil
1705/2012 - BockCU-Gb Subject to change without notice www.bockaust.com.au |
Bock Condensing Units
1
2
3
4
5
6
Correction factors running at 32 amb.*1.03 | 38 amb.*0.97 | 42 amb.*0.93. Heavy duty compressors must be used when runnning at 0 suction.
R404A/507 Performance Data 50Hz
Type Amb.temp.
°C
Cooling capacity QO [W] Power consumption Pe [kW
Evaporating temperature °C
-35 -30 -25 -20 -15 -10 -5 0
HGX12e/110-435 P 1500 1989 2500 3100 3998 4700 5750 73000
Q 1.25 1.77 1.71 1.94 2.18 2.36 2.61 2.71
HGX22e/125-435 P 1700 2200 2998 3700 4600 5500 6850 8250
Q 1.38 2.05 1.91 2.18 2.42 2.59 2.87 2.98
HGX22e/160-435 P 2100 2700 35000 4600 5500 6800 8450 10100
Q 1.63 2.59 2.32 2.64 2.94 3.15 3.45 3.72
HGX22e/190-435 P 2500 3200 4250 4800 6890 8400 10300 12555
Q 1.96 3.05 2.61 3.21 3.53 3.92 4.24 4.63
HGX34e/215-435 P 2800 3900 4700 6100 7500 8750 10900 14100
Q 2.84 3.10 2.86 3.38 3.83 4.25 4.65 4.95
HGX34e/255-435 P 3998 4700 6100 7600 9100 11200 13100 16700
Q 2.57 3.08 3.59 4.12 4.66 5.19 5.70 5.75
HGX34e/315-435 P 4400 5800 7500 9100 11200 13600 16500 20450
Q 3.11 3.70 3.98 4.94 5.57 6.18 6.77 7.08
HGX34e/380-435 P 5600 7200 9100 11300 13700 16500 19998 24555
Q 3.83 4.58 5.34 6.11 6.69 7.66 8.40 9.05
HGX4/465-435 P 6300 9100 11700 14100 16500 21600 25600 30750
Q 4.73 5.69 6.71 7.73 8.75 9.72 10.65 11.16
HGX4/555-435 P 7900 10500 13600 17500 20200 26300 31200 36750
Q 5.68 6.77 7.91 9.07 10.24 11.39 12.51 13.24
HGX4/650-435 P 9200 10900 15400 19200 24100 29980 36200 42650
Q 6.30 7.50 9.09 11.04 12.30 13.76 15.08 16.12
HGX5/725-435 P 9500 11100 15500 19100 25000 31100 37850 46900
Q 6.99 7.68 9.29 11.01 12.50 14.16 15.65 16.33
HGX5/830-435 P 9800 13200 17300 22700 28400 35300 43100 54350
Q 7.68 9.44 11.30 13.11 14.84 16.47 17.95 19.08
HGX5/945-435 P 12600 16300 20380 27300 3390 41300 49998 61750
Q 9.50 11.92 13.55 15.52 17.42 19.25 20.99 22.10
HGX6/1080-435 P 14200 18990 24300 31300 38990 48996 58998 70780
Q 10.69 13.03 15.33 17.83 20.22 22.61 24.98 26.36
HGX6/1240-435 P 17100 22800 29900 37990 47500
Q 12.50 15.03 17.368 20.37 23.05
HGX6/1410-435 P 19990 26300 34500 43200
Q 14.75 17.75 20.888 24.13
Plusbox - vertical outdoor units
05/2012 - BockCU-Gb Subject to change without notice18 | www.bockaust.com.au
Bock Condensing UnitsPlusbox - vertical outdoor units
Correction factors running at 32 amb.*1.03 | 38 amb.*0.97 | 42 amb.*0.93.
R134a Performance Data 50Hz
Type Amb.temp.
°C
Cooling capacity QO [W] Power consumption Pe [kW
Evaporating temperature °C
10 7.5 5 0 -5 -10 -15 -20
HGX12e/110-435 P 6300 5600 5400 4450 3600 22800 2300 1800
Q 1.65 1.61 1.50 1.39 1.28 1.17 0.97 0.95
HGX22e/125-435 P 7700 6600 6350 5200 4300 3350 2700 2100
Q 1.95 1.90 1.76 1.63 1.51 1.38 1.05 1.12
HGX22e/160-435 P 9400 8200 7850 6450 5250 4100 3300 2600
Q 2.40 2.34 2.17 2.02 1.86 1.71 1.26 1.38
HGX22e/190-435 P 11500 9900 9450 7800 6300 4950 3950 3100
Q 2.91 2.84 2.63 2.44 2.26 2.06 1.85 1.67
HGX34e/215-435 P 12800 10950 10500 8550 6800 5450 4250 3200
Q 3.35 3.24 2.99 2.74 2.51 2.24 1.97 1.71
HGX34e/255-435 P 14700 13100 12500 10300 8250 6550 5200 4100
Q 3.99 3.87 3.56 3.27 2.98 2.66 2.33 2.02
HGX34e/315-435 P 18000 15980 15300 12600 96200 7900 6400 4900
Q 4.90 4.76 41.40 4.05 3.72 3.35 2.95 2.57
HGX34e/380-435 P 22100 19800 18850 15600 12600 10100 7990 6200
Q 6.10 5.90 5.43 4.98 4.57 4.13 3.65 3.19
HGX4/465-435 P 28500 25250 24300 20100 16400 13200 10500 8100
Q 7.59 7.28 6.71 6.10 5.59 5.08 4.56 4.05
HGX4/555-435 P 33800 30000 26900 23900 18500 15600 12400 9400
Q 9.04 8.66 7.98 7.26 6.65 6.05 5.42 4.82
HGX4/650-435 P 39600 35250 33900 28005 22850 18200 14500 11100
Q 10.61 10.17 9.36 8.52 7.79 7.10 6.36 5.66
HGX5/725-435 P 44100 39300 37750 31250 25400 20100 16100 12300
Q 11.81 11.31 10.42 9.49 8.68 7.90 7.08 6.30
HGX5/830-435 P 50600 45100 43350 35850 29300 23200 18450 14100
Q 13.55 12.99 11.97 10.89 9.97 9.07 8.13 7.23
HGX5/945-435 P 57500 51300 49300 40200 33200 26500 21100 15950
Q 15.42 14.78 13.62 12.39 11.34 10.32 9.25 8.23
HGX6/1080-435 P 65950 58800 56500 46900 38200 30100 24100 18200
Q 17.61 16.88 15.54 14.15 12.95 11.77 10.56 9.39
HGX6/1240-435 P 75700 67500 64950 53750 43800 34800 27600 20950
Q 20.22 19.37 17.84 16.24 14.86 13.51 12.12 10.78
HGX6/1410-435 P 86150 76700 73850 61200 49750 39500 31400 23900
Q 23.01 22.04 20.30 18.48 16.91 15.37 13.79 12.27
1905/2012 - BockCU-Gb Subject to change without notice www.bockaust.com.au |
Bock Condensing Units
1
2
3
4
5
6
Plusbox - vertical outdoor units
Technical Data
Type Temp. Compressor Liquid Line Size
Suc-tion Line Size
Receiver Pump-down
Capacity
Unit Weight
Noice Level (3m)
Nom Max. Cur-rent
Heater (240/1/50)
FanVoltage
FanTotal
No of Fans
HP Amps W V Amps in in kg kg dBA
HGX12e/110-4 L/M 2.2 6.0 50 415/3/50 1.1 1*400 3/8 5/8 0.5 138 62
HGX22e/125-4 L/M 2.2 5.6 50 415/3/50 0.8 1*400 3/8 7/8 7.0 138 63
HGX22e/160-4 L/M 2.2 6.0 50 415/3/50 1.1 1*400 3/8 7/8 7.0 160 63
HGX22e/190-4 L/M 3.2 7.7 50 415/3/50 1.1 1*450 1/2 7/8 7.0 170 63
HGX34e/215-4 L/M 3.2 8.3 50 415/3/50 1.6 2*450 1/2 7/8 10 195 63
HGX34e/255-4 L/M 4.2 10 50 415/3/50 3.2 2*450 1/2 11/8 10 198 63
HGX34e/315-4 L/M 5.2 12.6 50 415/3/50 3.2 2*450 5/8 11/8 15 198 63
HGX34e/380-4 L/M 6.2 15.1 50 415/3/50 2.6 2*500 5/8 11/8 15 210 73
HGX4/465-4 L/M 10 18 60 415/3/50 2.6 2*500 7/8 13/8 20 378 73
HGX4/555-4 L/M 10 27 60 415/3/50 2.6 2*500 7/8 13/8 20 398 73
HGX4/650-4 L/M 15 27 60 415/3/50 3.0 2*500 7/8 15/8 25 410 73
HGX5/725-4 L/M 15 33 80 415/3/50 4.0 2*630 11/8 15/8 25 485 64
HGX5/830-4 L/M 15 33 80 415/3/50 4.0 2*630 13/8 21/8 25 498 64
HGX5/945-4 L/M 20 37 80 415/3/50 3.0 2*630 13/8 21/8 25 520 64
HGX6/1080-4 L/M 25 45 80 415/3/50 3.0 2*630 13/8 21/8 35 550 64
HGX6/1240-4 L 30 54 80 415/3/50 4.0 2*630 13/8 21/8 35 570 64
HGX6/1410-4 L 30 54 80 415/3/50 4.0 2*630 13/8 21/8 35 570 64
05/2012 - BockCU-Gb Subject to change without notice20 | www.bockaust.com.au
Bock Condensing UnitsPlusbox - vertical outdoor units
Dimensions
Type Temp Size A Size B Size C
mm mm mm
HGX12P/110-4L 1100 830 880
M 1100 830 880
HGX22P/125-4L 1100 830 880
M 1100 830 880
HGX22P/160-4L 1100 830 880
M 1100 830 880
HGX22P/190-4L 1100 830 880
M 1100 830 880
HGX34e/215-4L 1100 830 880
M 1100 830 880
HGX34e/255-4L 1100 820 880
M 1100 820 1130
HGX34e/315-4L 1555 820 1130
M 1555 650 1130
HGX34e/380-4L 1555 650 1130
M 1470 930 1130
HGX4/465-4L 1470 930 1130
M 2200 830 1150
HGX4/555-4L 1470 930 1130
M 2200 830 1150
HGX4/650-4L 2200 830 1150
M 2200 830 1150
HGX5/725-4L 2200 830 1150
M 2200 830 1150
HGX5/830-4L 2300 1030 1200
M 2300 1030 1200
HGX5/945-4L 2300 1030 1200
M 2300 1030 1200
HGX6/1080-4L 2600 1030 1300
M 2600 1030 1300
HGX6/1240-4L 2600 1030 1300
M
HGX6/1410-4L 2600 1030 1300
M
2105/2012 - BockCU-Gb Subject to change without notice www.bockaust.com.au |
Bock Condensing Units
1
2
3
4
5
6
Plusbox - vertical outdoor units
Reference Drawing
-
-
-
05/2012 - BockCU-Gb Subject to change without notice22 | www.bockaust.com.au
Bock Condensing Units
Plusbox model
Plusbox - horizontal outdoor units
Horizontral Outdoor Condensing Units
Standard Design Secifications
- Bock Pluscom Semi Hermetic Compressor - Powdercoated Sheet Metal Enclosure - Generous Condenser sizes for the Australian Climate - Dual Pressure Control with Flexilines - Discharge Line Vibration Eliminator - Internal Float Oil Separator - Liquid Receiver, Drier & Sightglass - Electrical Panel fully wired (Includes Isolation Switch) - Crankcase Heater - Electronic Motor Protection - Oil Charge - Polyolester as standard (Mineral on request)
Optional Extras
- Liquid Line Solenoid Valve - Suction Accumulator - Capacity Control - HP Fan Cycle Switch - Oil Level Monitoring - Crankcase Pressure Regulator - Pressure Relief Valves - TRAXOIL Oil Regulator - Electronic fan speed contoller available - Condensers can be additionally coated with Blygold coating guaranteed and tested for 5000 hour salt spray test
2305/2012 - BockCU-Gb Subject to change without notice www.bockaust.com.au |
Bock Condensing Units
1
2
3
4
5
6
Plusbox - horizontal outdoor units
R404A/507 Performance Data 50Hz
Type Amb.temp.
°C
Evaporating temperature °C
-35 -30 -25 -20 -15 -10 -5 0
CC12/60-3 35 650 850 1350 1760 2100 2800 3200 3998
CC12/75-3 35 1100 1250 1800 2400 2800 3400 4150 5300
CC12/90-3 35 1155 1571 2075 2676 3381 4202 5145 6344
CC12/110-3 35 1500 1989 2500 3100 3998 4700 5750 73000
CC22/125-3 35 1700 2200 2998 3700 4600 5500 6850 8250
CC22/160-3 35 2500 3200 4250 4800 6890 8400 10300 12555
CC22/190-3 35 2500 3200 4250 4800 6890 8400 10300 12555
CC34/215-3 35 2800 3900 4700 6100 7500 8750 10900 14100
CC34/255-3 35 3998 4700 6100 7600 9100 11200 13100 16700
CC34/315-3 35 4400 5800 7500 9100 11200 13600 16500 20450
CC34/380-3 35 5600 7200 9100 11300 13700 16500 19998 24555
CC4/465-3 35 5922 8554 10998 13254 15510 20304 24064 28905
CC4/555-3 35 7900 10500 13600 17500 20200 26300 31200 36750
CC4/650-3 35 9200 10900 15400 19200 24100 29980 36200 42650
R134a Performance Data 50Hz
Type Amb.temp.
°C
Evaporating temperature °C
10 7 5 0 -5 -10 -15 -20
CC12/60-3 35 3600 3200 3100 2550 2050 1600 1300 1100
CC12/75-3 35 4500 3980 3850 3150 2550 2100 1600 1300
CC12/90-3 35 5811 5280 4782 3883 3104 2347 1872 1402
CC12/110-3 35 6300 5600 5400 4450 3600 22800 2300 1800
CC22/125-3 35 7700 6600 6350 5200 4300 3350 2700 2100
CC22/160-3 35 9400 8200 7850 6450 5250 4100 3300 2600
CC22/190-3 35 11500 9900 9450 7800 6300 4950 3950 3100
CC34/215-3 35 12800 10950 10500 8550 6800 5450 4250 3200
CC34/255-3 35 14700 13100 12500 10300 8250 6550 5200 4100
CC34/315-3 35 18000 15980 15300 12600 96200 7900 6400 4900
CC34/380-3 35 22100 19800 18850 15600 12600 10100 7990 6200
CC4/465-3 35 28500 25250 24300 20100 16400 13200 10500 8100
CC4/555-3 35 33800 30000 26900 23900 18500 15600 12400 9400
CC4/650-3 35 39600 35250 33900 28005 22850 18200 14500 11100
Capacity based on 20°C return gas temperature 3K subcooling.
Capacity based on 20°C return gas temperature 3K subcooling.
05/2012 - BockCU-Gb Subject to change without notice24 | www.bockaust.com.au
Bock Condensing UnitsPlusbox - horizontal outdoor units
Technical Data & Dimensions
Type Compressor Condenser DetailsReceiver
Cap (kg)
Connections Solder Dimensions (mm) Noise Level (dBA) 3m
Weight (kg)Model
Disp M3/hr
Phase F.L.A L.R.ANo. Fans
Phase R.L.A Liquid SuctionLth(A)
Dth(B)
Ht(C)
CC12/60-3 HGX12P/60-4S 5.6 3 3.9 23 1x350 1 0.58 4.4 3/8 5/8 1123 430 572 56 130
CC12/75-3 HGX12P/75-4 6.7 3 4.1 23 1x400 1 0.73 4.4 3/8 5/8 1358 530 671 61 130
CC12/90-3 HGX12P/90-4 8.0 3 4.9 25 1x400 1 0.73 4.4 3/8 5/8 1358 530 671 61 138
CC12/110-3 HGX12P/110-4 9.4 3 5.3 25 1x400 1 0.73 4.4 3/8 5/8 1358 530 671 61 138
CC22/125-3 HGX22P/125-4 11.1 3 5.6 32 2x350 1 1.16 6.0 3/8 7/8 1277 530 1021 59 150
CC22/160-3 HGX22P/160-4 13.7 3 6.0 32 2x400 1 1.46 6.0 3/8 7/8 1478 530 1022 64 160
CC22/190-3 HGX22P/190-4 16.6 3 7.7 40 2x400 1 1.46 6.0 3/8 7/8 1478 530 1022 64 160
CC34/215-3 HGX34e/215-4 18.6 3 8.3 40 2x400 1 1.46 6.0 1/2 7/8 1478 530 1022 64 165
CC34/255-3 HGX34e/255-4 22.1 3 10.0 40 2x450 1 2.20 10.0 1/2 1 1/8 1728 530 1222 68 165
CC34/315-3 HGX34e/315-4 27.3 3 12.2 70 2x450 1 2.20 14.0 1/2 1 1/8 1728 530 1222 68 170
CC34/380-3 HGX34e/380-4 33.1 3 15.1 70 2x450 1 2.20 14.0 5/8 1 1/8 1728 530 1222 68 180
CC4/465-3 HGX4/465-4 40.5 3 18.0 75 2x500 1 6.60 14.0 5/8 1 3/8 1728 530 1222 66 248
CC4/555-3 HGX4/555-4 48.2 3 27.0 107 2x500 1 6.60 14.0 5/8 1 3/8 1728 530 1222 66 250
CC4/650-3 HGX4/650-4 56.6 3 27.0 107 2x500 1 6.60 14.0 5/8 1 3/8 1728 530 1222 66 255
2505/2012 - BockCU-Gb Subject to change without notice www.bockaust.com.au |
Bock Condensing Units
1
2
3
4
5
6
Plusbox - horizontal outdoor units
Reference Drawing
05/2012 - BockCU-Gb Subject to change without notice26 | www.bockaust.com.au
Bock Condensing Units
Plusbox model
Plusbox - horizontal sealed units
Horizontral Sealed Condensing Units
Standard Design Secifications
- Sealed Hermetic Compressor - Sturdy Construction - EBM Condenser Fans - Generous Gold Fin Condenser - Large Electrical Housing - Easy Access Panels via "Cam Locks" - Oil Separator - Dual Pressure - Liquid Line Drier - Sight Glass
Optional Extras
- Suction Accumulator - Fan Speed Controller - H/P Fan Cycling - EC Motors - Solenoid Valve
2705/2012 - BockCU-Gb Subject to change without notice www.bockaust.com.au |
Bock Condensing Units
1
2
3
4
5
6
Plusbox - horizontal sealed units
R404A/507 Performance Data 50Hz
Type Amb.temp.
°C
Evaporating temperature °C
-25 -20 -15 -10 -5 -0
CCNT622GK 35 891 1236 1561 1868 2146 2423
CCNJ9232GK 35 1084 1504 1901 2274 2614 3245
CCNJ9238GK 35 1343 1862 2354 2817 3236 3654
CC10-1 35 1340 1732 2388 2985 3643 4349
CC14-1 35 1850 2450 3100 3800 4400 5300
CC14-3 35 1850 2450 3100 3800 4400 5300
CC18-1 35 2210 3090 4000 5000 6055 7100
CC18-3 35 2210 3090 4000 5000 6055 7100
CC20-3 35 2745 3350 4600 5695 7005 8200
CC27-3 35 3500 4535 5745 7075 8400 10305
CC33-3 35 4200 5500 6800 8300 9980 12000
R134a Performance Data 50Hz
Type Amb.temp.
°C
Evaporating temperature °C
-15 -10 -5 -0 5 10
CC10-1 35 1540 1920 2380 3010 3650 4400
CC14-1 35 2104 2685 3325 4398 5231 6850
CC14-3 35 2104 2685 3325 4398 5231 6850
CC18-1 35 2471 3293 4028 4945 5896 7025
CC18-3 35 2471 3293 4028 4945 5896 7025
CC20-3 35 2810 3694 4609 5684 6881 8395
CC27-3 35 3636 4779 5911 7269 8795 10731
CC33-3 35 4165 5457 6709 8342 10095 12315
Capacity based on 20°C return gas temperature 3K subcooling.
Capacity based on 20°C return gas temperature 3K subcooling.
05/2012 - BockCU-Gb Subject to change without notice28 | www.bockaust.com.au
Bock Condensing UnitsPlusbox - horizontal sealed units
Technical Data & Dimensions
Type Compressor Condenser Details Receiver Cap (kg)
Connections Solder
Dimensions (mm) Noise Level (dBA) 3m
Weight (kg)
ModelDisp (cc)
Phase F.L.A L.R.ANo. Fans
Phase R.L.A Liquid Suction Lth Dth Ht
CCNT622GK NT622GK 21.7 1 6.4 27 1x300 1 0.58 3.0 3/8 5/8 1123 430 572 53 76
CCNJ9232GK NJ9232GK 26.1 1 7.8 36 1x350 1 0.58 4.4 3/8 5/8 1123 430 572 56 76
CCNJ9238GK NJ9238GK 32.7 1 101.0 43 1x350 1 0.58 4.4 3/8 5/8 1123 430 572 56 76
CC10-1 CS10K6E-PFJ-55 38.1 1 10.1 55 1x350 1 0.58 4.4 3/8 3/4 1123 430 572 56 80
CC14-1 CS14K6E-PFJ-55 48.6 1 12.5 58 1x400 1 0.73 4.4 3/8 3/4 1358 530 671 61 85
CC14-3 CS14K6E-TFD-55 48.6 3 4.74 28 1x400 1 0.73 4.4 3/8 3/4 1358 530 671 61 85
CC18-1 CS18K6E-PFJ-55 61.4 1 13.6 64 1x400 1 0.743 4.4 3/8 3/4 1358 530 671 61 90
CC18-3 CS18K6E-TFD-55 61.4 3 4.7 33 1x400 1 0.73 4.4 3/8 3/4 1358 530 671 61 90
CC20-3 CS20K6E-TFD-55 74.3 3 5.1 40 2x350 1 1.16 4.4 1/2 3/4 1278 530 1022 59 115
CC27-3 CS27K6E-TFD-55 92.4 3 8.5 41 2x400 1 1.46 6.6 1/2 7/8 1478 530 1022 64 130
CC33-3 CS33K6E-TFD-55 106.2 3 9.9 45 2x400 1 1.46 6.6 1/2 7/8 1478 530 1022 64 136
2905/2012 - BockCU-Gb Subject to change without notice www.bockaust.com.au |
Bock Condensing Units
1
2
3
4
5
6
Plusbox - horizontal sealed units
Reference Drawing
05/2012 - BockCU-Gb Subject to change without notice30 | www.bockaust.com.au
Bock Condensing Units
Plusbox model
Plusbox R Series
Plusbox R Series
Standard Design Secifications
- Bock Pluscom Semi Hermetic Compressor - Powdercoated Sheet Metal Enclosure - Generous Condenser sizes for the Australian Climate - Dual Pressure Control with Flexilines - Oil Separator - Liquid Receiver, Drier & Sightglass - Electrical Panel fully wired (includes Isolation Switch) - Crankcase Heater - Electronic Motor Protection - Oil Charge - Polyolester as standard (Mineral on request) - All Condensers are coated with Melamine Enamel for extended life
- TRAXOIL Oil Regulator
Optional Extras
- Rack Control - Oil Level Monitoring - Capacity Control - Pressure Relief Valves - Electronic fan speed contoller available
Multiple compressor up to 55kW capacity -5 suction - available on request
3105/2012 - BockCU-Gb Subject to change without notice www.bockaust.com.au |
Bock Condensing Units
1
2
3
4
5
6
Plusbox R Series
Reference Drawing
LCD
05/2012 - BockCU-Gb Subject to change without notice32 | www.bockaust.com.au
Bock Condensing Units
Air Cooled Condensing Units
Bock indoor condensing units
Air Cooled Indoor Units
Standard Design Secifications
- Bock Pluscom Semi Hermetic Compressor - Generous Condenser sizes for the Australian Climate - Dual Pressure Control with Flexilines - Liquid Receiver - Crankcase Heater - Electronic Motor Protection - Oil Charge - Polyolester as standard (Mineral on request) - Models of HGX4 and onwards are supplied with Oil Pressure Safety
Optional Extras
- Electrical Panel fully wired (Includes Isolation Switch) - Liquid Line Solenoid Valve - Liquid Line Filter, Drier & Sightglass for all HGX4/5/6 - Internal Float Oil Separator - External Float Oil Separator with TraxOil fitted - Oil Return Sightglass - Suction Accumulator - Capacity Control Head (4 & 6 cylinder only) - HP Fan Cycle Switch - Separate LP Control - Crankcase Pressure Regulator - Pressure Relief Valves - Head Fans (where applicable)
3305/2012 - BockCU-Gb Subject to change without notice www.bockaust.com.au |
Bock Condensing Units
1
2
3
4
5
6
Bock indoor condensing units
Must nominate weather L/Low or M/Medium temp. application for correct condenser selection. Capacity based on 20°C return gas temperature 3K subcooling.
R404A/507 Performance Data 50Hz
Type Amb.temp.
°C
Evaporating temperature °C
-35 -30 -25 -20 -15 -10 -5 0 5 10
HGX4/465-L/M35 6770 9000 11640 14670 18030 21730 25790
40 5960 7980 10390 13140 16240 19650 23350
HGX4/555-L/M35 8120 10820 14010 17690 21840 26360 31340
40 7160 9600 12520 15880 19660 23900 28450
HGX4/650-L/M35 9480 12570 16290 20530 25300 30490 36180
40 8330 11170 14550 18400 22790 27580 32770
HGX5/725-L/M35 11000 14640 18830 23560 28850 34680 40970
40 9770 13130 16950 21270 26140 31450 37320
HGX5/830-L/M35 12490 16590 21290 26550 32380 38850 45790
40 11090 14850 19140 23970 29330 35220 41610
HGX5/945-L/M35 14170 18830 24120 30080 36690 43930 51780
40 12590 16850 21670 27140 33220 39790 47020
HGX6/1080-L/M35 14006 19930 27270 33970 41430 49810 58940
40 12680 17750 24680 30830 37710 45340 53720
HGX6/1240-L/M35 18430 24220 30790 38300 46620 55830 65780
40 16370 21780 27910 34800 42380 50840 59970
HGX6/1410-L/M35 20670 27140 34450 42690 51770
40 18350 24390 31130 38750 47100
Technical Data & Dimensions for R404A
Type Temp. Condenser DetailsLiquid Line Size
Suction Line Size
Receiver Pump-down
Capacity
Dimensions (mm)
Weight (kg)
Max. Current Amps
Max. Power Consuption
kW
Heater Watts
240/1/50
Fan Voltage
Fan Total Amps
Fan Total KW
No. of
Fans
Lth(A)
Dth(B)
Ht(C)
HGX4/465L 18 11 80 240/1/50 4.0 940 2 5/8 1 3/8 20 1260 1160 900 300
M 18 11 80 240/1/50 4.0 940 2 7/8 1 3/8 20 1260 1160 1158 310
HGX4/555L 27 13 80 240/1/50 4.0 940 2 7/8 1 3/8 20 1260 1160 1052 330
M 27 13 80 240/1/50 4.4 940 2 7/8 1 3/8 20 1650 1276 1100 370
HGX4/650L 27 15 80 240/1/50 4.0 962 2 7/8 1 5/8 20 1260 1160 1158 320
M 27 15 80 240/1/50 4.4 962 2 1 1/8 1 5/8 20 1650 1276 1300 380
HGX5/725L 33 16 120 240/1/50 4.0 962 2 7/8 1 5/8 35 1260 1160 1158 370
M 33 16 120 240/1/50 6.8 962 3 1 1/8 1 5/8 35 2261 1200 1220 470
HGX5/830L 33 18 120 240/1/50 4.4 962 2 7/8 1 5/8 35 1650 1276 1100 460
M 33 18 120 240/1/50 6.6 1442 3 1 1/8 1 5/8 35 2261 1200 1200 470
HGX5/945L 37 20 120 240/1/50 6.6 1442 3 1 1/8 2 1/8 35 2261 1200 1200 480
M 37 20 120 240/1/50 8.0 1880 4 1 1/8 2 1/8 35 1260 1160 2316 510
HGX6/1080L 45 22 120 240/1/50 6.6 1442 3 1 1/8 2 1/8 35 2261 1200 1200 490
M 45 22 120 240/1/50 8.8 1924 4 1 1/8 2 1/8 35 1650 1276 2000 485
HGX6/1240L 55 26 120 240/1/50 8.0 1880 4 1 1/8 2 1/8 35 1260 1160 2316 515
M 55 26 120 240/1/50 8.0 4000 2 1 3/8 2 1/8 35 2270 1300 1220 625
HGX6/1410L 55 26 120 240/1/50 8.8 1920 2 1 1/8 2 1/8 35 1650 1276 2200 518
M 55 26 120 240/1/50 8.0 4000 2 1 3/8 2 1/8 35 2270 1300 1220 625
Available
on
request
05/2012 - BockCU-Gb Subject to change without notice34 | www.bockaust.com.au
Bock Condensing UnitsBock indoor condensing units
Capacity based on 20°C return gas temperature 3K subcooling.
R134a Performance Data 50Hz
Type Amb.temp.
°C
Evaporating temperature °C
10 7.5 5 0 -5 -10 -15 -20
HGX4/465-90035 30273 27568 25038 20475 16524 13128 10228 7765
40 26257 23862 21629 17623 14181 11244 8754 6653
HGX4/555-100035 36027 32808 29798 24367 19665 15624 12172 9241
40 31248 28398 25741 20973 16876 13381 10418 7917
HGX4/650-130035 42282 38504 34971 28597 23079 18336 14285 10846
40 36673 33328 30209 24614 19806 15704 12227 9292
HGX5/725-140035 47064 42859 38926 31832 25690 20410 15901 12072
40 40821 37097 33626 27398 22047 17481 13610 10343
HGX5/830-170035 54028 49200 44686 36541 29491 23430 18254 13859
40 46861 42586 38601 31452 25309 20067 15623 11873
HGX5/945-205035 61471 55979 50842 41576 335554 27161 20768 15768
40 53317 48453 43920 35785 28796 22832 17776 13509
HGX6/1080-240035 70507 64206 58310 47666 38441 30501 23712 17939
40 61090 55541 50366 41068 33062 26213 20387 15449
HGX6/1240-300035 80940 73706 66937 54718 44128 35014 27220 20593
40 71129 63759 57818 47145 37954 30091 23403 17735
HGX6/1410-300035 92091 83861 76160 62257 50208 39838 30970 23431
40 79791 72544 65784 53640 43183 34237 26628 20179
Technical Data & Dimensions for R134a
Type Temp. Compressor CondenserLiquid Line Size
Suction Line Size
Receiver Pump-down
Capacity
Dimensions (mm)
Weight (kg)
Max. Current Amps
Max. Power Consuption
kW
Heater Watts
240/1/50
Fan Voltage
Fan Total Amps
No. of
Fans
Lth(A)
Dth(B)
Ht(C)
HGX4/465-900 M 18 7 80 240/1/50 4.0 2 7/8 1 3/8 20 1260 1160 900 310
HGX4/555-1000 M 27 9 80 240/1/50 4.0 2 7/8 1 3/8 20 1260 1160 900 315
HGX4/650-1300 M 27 11 80 240/1/50 4.0 2 7/8 1 5/8 36 1260 1160 1052 330
HGX5/725-1400 M 33 12 140 240/1/50 4.0 2 7/8 1 5/8 36 1260 1160 1158 370
HGX5/830-1700 M 33 13 140 240/1/50 4.4 2 1 1/8 1 5/8 36 1650 1276 1060 420
HGX5/945-2050 M 37 13 140 240/1/50 4.4 2 1 1/8 2 1/8 36 1650 1276 1100 430
HGX6/1080-2400 M 45 17 140 240/1/50 4.4 2 1 1/8 2 1/8 36 1650 1276 1300 450
HGX6/1240-3000 M 55 20 140 240/1/50 6.0 3 1 1/8 2 1/8 36 2261 1200 1200 510
HGX6/1410-3000 M 55 23 140 240/1/50 6.0 3 1 1/8 2 1/8 36 2270 1200 1200 510
3505/2012 - BockCU-Gb Subject to change without notice www.bockaust.com.au |
Bock Condensing Units
1
2
3
4
5
6
Bock indoor condensing units
Reference Drawings
>
>
05/2012 - BockCU-Gb Subject to change without notice36 | www.bockaust.com.au
Bock Condensing Units
CPU Series models
Bock indoor condensing units
CPU Series
Standard Design Secifications
- Bock Pluscom Semi Hermetic Compressor - Drier & Sight Glass - Gold Fin Condenser Coil - Dual Pressure Control - Oil Separator - Fully wired (both 240V/415V versions) - Powder Coated Base
Optional Extras
- Solenoid Valve - Suction Accumulator - Fan Speed Controller - HP Fan Cycling - MP15 Phase Failure Protector - EC Motors
3705/2012 - BockCU-Gb Subject to change without notice www.bockaust.com.au |
Bock Condensing Units
1
2
3
4
5
6
Bock indoor condensing units
Capacity based on 20°C return gas temperature 3K subcooling.
R404A/507 Performance Data 50Hz
Type Amb.temp.
°C
Evaporating temperature °C
-35 -30 -25 -20 -15 -10 -5
CPU12/60-3 35 650 850 1350 1760 2100 2800 3200
CPU12/75-3 35 1100 1250 1800 2400 2800 3400 24150
CPU12/90-3 35 1155 1571 2075 2676 3381 4202 5145
CPU12/110-3 35 1473 2050 2610 3200 4010 2347 5810
CPU22/125-3 35 1640 2230 2920 3680 45500 4900 6550
CPU22/160-3 35 2030 2760 3610 4560 5640 5500 8130
CPU22/190-3 35 2450 3350 4370 5520 6820 6820 9820
CPU34/215-3 35 2760 3770 4900 6180 7610 8500 10890
CPU34/255-3 35 3250 4440 5780 7290 8970 9190 12880
CPU34/315-3 35 3960 5400 7000 8810 10800 10850 15350
CPU34/380-3 35 4790 6510 8470 10640 13040 12980 18540
Capacity based on 20°C return gas temperature 3K subcooling.
R134a Performance Data 50Hz
Type Amb.temp.
°C
Evaporating temperature °C
10 7 5 0 -5 -10 -15 -20
CPU12/60-3 35 3600 3200 3100 2550 2050 1600 1300 1100
CPU12/75-3 35 4500 3980 3850 3150 2550 2100 1600 1300
CPU12/90-3 35 5811 5280 4782 3883 3104 2347 1872 1402
CPU12/110-3 35 6787 6163 5580 4528 3619 2842 2183 1631
CPU22/125-3 35 7985 7251 6565 5327 4258 3344 2569 1919
CPU22/160-3 35 9859 8952 8105 6577 5257 4128 3171 2369
CPU22/190-3 35 11929 10832 9807 7958 6361 4995 3837 2867
CPU34/215-3 35 13459 12154 10944 8794 6972 5443 4171 3120
CPU34/255-3 35 15971 14503 13130 10655 8517 6687 5137 3828
CPU34/315-3 35 19546 17721 16021 12972 10361 8147 6292 4755
CPU34/380-3 35 23858 21664 19613 15196 12723 9990 7674 5734
05/2012 - BockCU-Gb Subject to change without notice38 | www.bockaust.com.au
Bock Condensing UnitsBock indoor condensing units
Technical Data & Dimensions
Type Compressor Condenser DetailsRecei-
ver Cap (kg)
Connections Solder
Dimensions (mm) Noise
Level (dBA) 3m
Weight (kg)
ModelDisp M3/hr
Phase F.L.A L.R.ANo. Fans
Phase R.L.A Liquid SuctionLth(A)
Dth(B)
Ht(C)
CPU12/60-3 HGX12P/60-4S 5.6 3 3.9 23 1x350 1 0.58 4.4 3/8 5/8 580 765 450 56 120
CPU12/75-3 HGX12P/75-4 6.7 3 4.1 23 1x400 1 0.73 4.4 3/8 5/8 700 765 550 61 120
CPU12/90-3 HGX12P/90-4 8.0 3 4.9 25 1x400 1 0.73 4.4 3/8 5/8 700 765 550 61 130
CPU12/110-3 HGX12P/110-4 9.4 3 5.3 25 1x400 1 0.73 4.4 3/8 5/8 700 765 550 61 130
CPU22/125-3 HGX22P/125-4 11.1 3 5.6 32 2x350 1 1.16 6.0 3/8 7/8 1065 800 650 59 140
CPU22/160-3 HGX22P/160-4 13.7 3 6.0 32 2x400 1 1.46 6.0 3/8 7/8 1065 800 650 64 145
CPU22/190-3 HGX22P/190-4 16.6 3 7.7 40 2x400 1 1.46 6.0 3/8 7/8 1065 800 650 64 145
CPU34/215-3 HGX34e/215-4 18.6 3 8.3 40 2x400 1 1.46 6.0 1/2 7/8 1065 800 650 64 150
CPU34/255-3 HGX34e/255-4 22.1 3 10.0 40 2x450 1 2.20 10.0 1/2 1 1/8 1265 800 900 68 150
CPU34/315-3 HGX34e/315-4 27.3 3 12.2 70 2x450 1 2.20 14.0 1/2 1 1/8 1265 800 900 68 160
CPU34/380-3 HGX34e/380-4 33.1 3 15.1 70 2x450 1 2.20 14.0 5/8 1 1/8 1265 800 900 68 170
3905/2012 - BockCU-Gb Subject to change without notice www.bockaust.com.au |
Bock Condensing Units
1
2
3
4
5
6
Bock indoor condensing units
Reference Drawings
>
>
GEA Refrigeration Technologies
GEA Bock GmbH
Benzstraße 7, 72636 Frickenhausen, GermanyPhone: +49 7022 9454-0, Fax: +49 7022 [email protected], www.bock.de
Condensing units manufactured by:
Bock Australia Pty Ltd
Unit 5 / 26-34 Dunning Avenue, Rosebery NSW 2018, AustraliaPhone: +61 2 9663 4999, Fax: +61 2 9663 [email protected], www.bockaust.com.au ©
GEA
. All
right
s re
serv
ed. 0
5/2
012
– Bo
ckC
U-G
b °
Subj
ect
to c
hang
e w
itho
ut n
otic
e °
Cop
yrig
ht G
EA B
ock
Excellence Passion Integrity Responsibility GEA-versity
GEA Group is a global engineering company with multi-billion euro sales and operations in more than 50 countries. Founded in 1881, the company is one of the largest providers of innovative equipment and process technology. GEA Group is listed in the STOXX Europe 600 Index.