Upload
zar-chi
View
219
Download
1
Embed Size (px)
Citation preview
7/28/2019 Battery and DC Backup System Protection and Coordination
1/43
BATTERY & DCBATTERY & DC BACKUPBACKUPSYSTEM PROTECTIONSYSTEM PROTECTION
COORDINATIONCOORDINATION
Hassam Nasrat P.Eng.
8/28/2011 Primax Technologies Inc. 1
7/28/2019 Battery and DC Backup System Protection and Coordination
2/43
Protection Coordination AGAIN?
Its been already well covered by many
studies and books...
8/28/2011 Primax Technologies Inc. 2
IntroductionIntroduction
7/28/2019 Battery and DC Backup System Protection and Coordination
3/43
Very simple:
99% of all available literature and
standards are about AC applications.
Very few cover DC faults.
8/28/2011 Primax Technologies Inc. 3
IntroductionIntroduction
7/28/2019 Battery and DC Backup System Protection and Coordination
4/43
In this presentation, Well focus on
Fault (short circuit) coordination
assuming that overload protection is much
easier to define and manage.Challenge
Better understand the whole DC backup
system fault behaviour in order to get to aconclusion for safe and reliable solution.
8/28/2011 Primax Technologies Inc. 4
IntroductionIntroduction
7/28/2019 Battery and DC Backup System Protection and Coordination
5/43
RationalRational
In typical DC backup systems multiple sourcesof energy are:
connected in parallel simultaneously contributing into the faultEach has different time constant and
amplitude
Fault effect reflected on AC mains must betaken in consideration.
Ex. 2 chargers, 1 or more batteries, inductiveloads, fully charged capacitors....
8/28/2011 Primax Technologies Inc. 5
7/28/2019 Battery and DC Backup System Protection and Coordination
6/43
Once breaking current of each source isdefined, one has to refer to the country
standard to specify the requiredcomponents
IEC std ratings and requirements mayvary from CSA, UL, IEEE, NFPA...
8/28/2011 Primax Technologies Inc. 6
RuleRule
7/28/2019 Battery and DC Backup System Protection and Coordination
7/43
BottomBottom lineline
Fuses, circuit breakers, switches, bus bars,cables and other equipment need to
operate safely and reliably during fault:
Breakers and Fuses
Need to open SELECTIVELY
Cables, switches, bus bars...Need to WITHSTAND the fault energy
8/28/2011 Primax Technologies Inc. 7
7/28/2019 Battery and DC Backup System Protection and Coordination
8/43
BasicsBasics
For the purpose of this discussion we define
the following: Fault: refers to a very low impedance path
created when both polarity conductors are
shorted.
Failure: refers to over-current: Ex. Failingload, leakage in battery or DC source has lost
regulation
As always, Ohms law applies: I = V / Z
Z: individual component impedance including interconnectingcable resistance.
8/28/2011 Primax Technologies Inc. 8
7/28/2019 Battery and DC Backup System Protection and Coordination
9/43
Steady state faultSteady state fault
During fault evolution:
System voltage decays gradually.The decay rate is related to impedance
rate-of-changeof all parallel sources over the period of
time before that protection devices open.
This calculation is less accurate than theinitial fault current.
8/28/2011 Primax Technologies Inc. 9
7/28/2019 Battery and DC Backup System Protection and Coordination
10/43
EffectsEffects
At the occurrence of a fault, a badly coordinated protection
device may lead to:
Device failure: Circuit breaker contacts may weld duringopening, so the fault is not interrupted
Explosion: the device will explode due to the energyavailable during the fault arcing.
Fire: due to the arc ignition of material during the contactopening
Injury or death: Operators will be operating in unsafeenvironment.
Note: Arc flash hazard level is directly proportional to theduration of the arc fault.
8/28/2011 Primax Technologies Inc. 10
7/28/2019 Battery and DC Backup System Protection and Coordination
11/43
Energy sourcesEnergy sources
To define minimum protection fault currentratings, we need to evaluate the
contribution in the fault of each of the DCcomponents
8/28/2011 Primax Technologies Inc. 11
7/28/2019 Battery and DC Backup System Protection and Coordination
12/43
TypicalTypical layoutslayouts
Lets looks first to typical DC backupsystem layouts:
8/28/2011 Primax Technologies Inc. 12
7/28/2019 Battery and DC Backup System Protection and Coordination
13/43
TypicalTypical layoutlayout8/28/2011 Primax Technologies Inc. 13
7/28/2019 Battery and DC Backup System Protection and Coordination
14/43
RedundantRedundant layoutlayout8/28/2011 Primax Technologies Inc. 14
7/28/2019 Battery and DC Backup System Protection and Coordination
15/43
RedundantRedundant complexcomplex layoutlayout8/28/2011 Primax Technologies Inc. 15
7/28/2019 Battery and DC Backup System Protection and Coordination
16/43
TypicalTypical nuclearnuclear layoutlayout8/28/2011 Primax Technologies Inc. 16
7/28/2019 Battery and DC Backup System Protection and Coordination
17/43
TypicalTypical batterybattery chargercharger layoutlayout8/28/2011 Primax Technologies Inc. 17
7/28/2019 Battery and DC Backup System Protection and Coordination
18/43
BatteryBattery Charger outputCharger output underunder faultfault
8/28/2011 Primax Technologies Inc. 18
7/28/2019 Battery and DC Backup System Protection and Coordination
19/43
Contribution of different DCContribution of different DCcomponentscomponents
8/28/2011 Primax Technologies Inc. 19
7/28/2019 Battery and DC Backup System Protection and Coordination
20/43
BatteryBattery
Depending on the battery technology, plate
thickness and number, specific gravity (inthe case of Lead acid batteries) available
fault current may vary.
Check with battery manufacturers for theexact fault current.
Time constant: consider 10ms
8/28/2011 Primax Technologies Inc. 20
7/28/2019 Battery and DC Backup System Protection and Coordination
21/43
BatteryBattery exampleexample
Typical 350AH battery fault current at itsterminals:
VLA 0.33 thick Flat calcium plate battery with1.215 SG: 3200A
Tubular VLA 0.35 thick plate battery with 1.215SG: 3400A
AGM VRLA : 4361A
Gel VRLA: 3750A
Ni-Cd Medium performance: 3200A
8/28/2011 Primax Technologies Inc. 21
7/28/2019 Battery and DC Backup System Protection and Coordination
22/43
FilterFilter CapacitorsCapacitors
Capacitors are a source of large instantaneouscurrents
Consider time constant 10 ms
Ex. 8 x 10,000uF-200VDC- ESR:20m
with line impedance of 0.1
8/28/2011 Primax Technologies Inc. 22
7/28/2019 Battery and DC Backup System Protection and Coordination
23/43
Capacitor discharge caseCapacitor discharge case8/28/2011 Primax Technologies Inc. 23
C (uF) R() Vo RC(s) Vc Imax(A) Q (uC) I(A)
Vo . e(-t/RC) Vo/R CVo(e-t/RC) oe(-t/RC))/R
80 000 0,1 136 0,008 1360 10880000 1360
at t=0 1360 At=RC(s) 0,008 I at 1 RC 500 A
t=2 RC(s) 0,016 I at 2RC 184 A
8 x 10,000uF-200VDCESR:20m
with lineimpedance of0.1
7/28/2019 Battery and DC Backup System Protection and Coordination
24/43
Charger/rectifierCharger/rectifier
Magnitude of faults depends mainly on:
AC mains impedance Power transformer impedance Inductive filter design Other series components
As a rule of thumb take 15-20 times the full current ratingtime constant 25ms
Ex. 500A battery charger with a 3.5% Z transformerimpedance may deliver up to10 000A during a short circuit until its own protection getsinto action to interrupt.
8/28/2011 Primax Technologies Inc. 24
7/28/2019 Battery and DC Backup System Protection and Coordination
25/43
Inductive loadsInductive loads
Main concern is DC motors:They operate switchgear, turbine lube pumps
During deceleration, motors act as a generatorscontributing in the short circuit.
- Consider that all motors are connected and running atthe time of the fault
- Typical motor armature has large L/R time constant 20-60ms lower di/dt longer time to clearprotection
- Rule of thumb: Use 4 times of running FLA
8/28/2011 Primax Technologies Inc. 25
7/28/2019 Battery and DC Backup System Protection and Coordination
26/43
NoteNote
Its not bad to have high fault availability from thesource to efficiently perform selective clearance.
So if the protection fuse or breaker has larger I2t thanwhat the source can provide, then this protection
cannot clear its load fault.
Ex. Switchmode power supplies provide fast currentlimiting and current foldback feature leading to achallenge in clearing faults.
8/28/2011 Primax Technologies Inc. 26
7/28/2019 Battery and DC Backup System Protection and Coordination
27/43
ProtectionProtection
Fuse or circuit breaker?
Both provide over-current, short circuitprotection, selective coordination and arc
flash protection.
Breakers can provide remote monitoring,
adjustability, reset and control.Semiconductor fuses for ex. can provide sub-cycle fault protection and long term overload
capacity
8/28/2011 Primax Technologies Inc. 27
7/28/2019 Battery and DC Backup System Protection and Coordination
28/43
Fuse or circuit breaker?Fuse or circuit breaker?
Fuses Circuit Breakers
DC Interrupting KA ++ -
Flexibility (optional features) + +++++
Adjustable - +++
Resettable - ++++
Reliability (maintenance) ++ -
Arc flash protection +delay trip must be at minimum
++++
8/28/2011 Primax Technologies Inc. 28
7/28/2019 Battery and DC Backup System Protection and Coordination
29/43
8/28/2011 Primax Technologies Inc. 29
Fuse dataFuse data
7/28/2019 Battery and DC Backup System Protection and Coordination
30/43
8/28/2011 Primax Technologies Inc. 30
FuseFuseblockblockdatadata
7/28/2019 Battery and DC Backup System Protection and Coordination
31/43
8/28/2011 Primax Technologies Inc. 31
Fuse coordinationFuse coordination curvescurves
7/28/2019 Battery and DC Backup System Protection and Coordination
32/43
8/28/2011 Primax Technologies Inc. 32
CircuitCircuit BreakerBreaker DataData
7/28/2019 Battery and DC Backup System Protection and Coordination
33/43
8/28/2011 Primax Technologies Inc. 33
CircuitCircuit BreakerBreaker DataData
7/28/2019 Battery and DC Backup System Protection and Coordination
34/43
Case:Case:DC protectionDC protectioncoordinationcoordination
8/28/2011 Primax Technologies Inc. 34
HKD400
HJD250
At first, one
can thinkthat
protection is
perfect:
250A CB isfed from
400A main
CB!!
7/28/2019 Battery and DC Backup System Protection and Coordination
35/43
BreakersBreakers coordinationcoordination8/28/2011 Primax Technologies Inc. 35
7/28/2019 Battery and DC Backup System Protection and Coordination
36/43
CaseCase
8/28/2011 Primax Technologies Inc. 36
HKD400HKD400
7250ASC 7250ASC
3500ASC
Total Fault at X:
2x3500A+2x7250A=
21500A+ inductive
22kADC breakers
X
HJD250
To
Inverter
7/28/2019 Battery and DC Backup System Protection and Coordination
37/43
Other protection considerationsOther protection considerations
Soft startIf fault occurs during the soft start period of the rectifiers, available currents can
be limited to lower value and chargers might shut down.
Inherent current limitDepending on the fault evolution over time, rectifiers may or may not limit their
output current during faults
Ground Leakage alarmsin a floating DC system, this alarm will alert user for 1st polarity ground leakagewhich may not cause operation failure although it can be a safety hazard. A 2nd
polarity ground leakage may cause high impedance fault through the ground.
Connection cablesInterconnecting cable impedance reduces the fault current. This depends on their
material, cross section and length. In general, battery interconnecting cablevoltage drop is accounted in the short circuit capabilities of the batteries.
Ex. 4/0-259 strands copper cable has a DC resistance of 0.15 /km.
8/28/2011 Primax Technologies Inc. 37
7/28/2019 Battery and DC Backup System Protection and Coordination
38/43
Few applicable standardsFew applicable standards
IEEE 946: Recommended Practice for the Design of DC Auxiliary Power
Systems for Generating Stations
IEEE 1375: Guide for the Protection of Stationary Battery Systems
IEEE 1584 empirical equations are used to calculate arc-flash levels
ANSI/IEEE C37.40 (1993), "Standard Service Conditions and Definitions forHigh-Voltage Fuses, Distribution Enclosed Single-Pole Air Switches, FuseDisconnecting Switches, and Accessories"
IEC 60909: Short-circuit currents in three-phase-a.c. systems
IEC 60947: Low-voltage switchgear and control gear
IEC 60127 family: requirements applicable to fuses
UL 489 and CSA 22.2-5-09 Harmonized Standards: Molded-Case CircuitBreakers, Molded-Case Switches and Circuit-Breaker Enclosures
8/28/2011 Primax Technologies Inc. 38
7/28/2019 Battery and DC Backup System Protection and Coordination
39/43
ConclusionConclusion
During faults, DC system componentsresponse will be non linear, resulting into
complicated behaviour.Consequently, rule of thumb and past
experience might be needed to definebreaking currents.
8/28/2011 Primax Technologies Inc. 39
7/28/2019 Battery and DC Backup System Protection and Coordination
40/43
ConclusionConclusion
However,in special or large applications,Rules of thumb might lead to
overestimated values affecting the sizeand cost of the installation.
So, in this case, more accurateassumptions and calculations must be
made.
8/28/2011 Primax Technologies Inc. 40
7/28/2019 Battery and DC Backup System Protection and Coordination
41/43
ConclusionConclusion
Take all precautions to properly define your
equipment protection and selectivity:ASK FOR
Breaking capacity of protection device
Fault capabilities of all connected energysources
Require professionals with relevant
experience and background to help
8/28/2011 Primax Technologies Inc. 41
7/28/2019 Battery and DC Backup System Protection and Coordination
42/43
QUESTIONS?QUESTIONS?
8/28/2011 Primax Technologies Inc. 42
7/28/2019 Battery and DC Backup System Protection and Coordination
43/43
ThankThank you !you !
8/28/2011 Primax Technologies Inc. 43