Battery and DC Backup System Protection and Coordination

  • Upload
    zar-chi

  • View
    219

  • Download
    1

Embed Size (px)

Citation preview

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    1/43

    BATTERY & DCBATTERY & DC BACKUPBACKUPSYSTEM PROTECTIONSYSTEM PROTECTION

    COORDINATIONCOORDINATION

    Hassam Nasrat P.Eng.

    8/28/2011 Primax Technologies Inc. 1

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    2/43

    Protection Coordination AGAIN?

    Its been already well covered by many

    studies and books...

    8/28/2011 Primax Technologies Inc. 2

    IntroductionIntroduction

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    3/43

    Very simple:

    99% of all available literature and

    standards are about AC applications.

    Very few cover DC faults.

    8/28/2011 Primax Technologies Inc. 3

    IntroductionIntroduction

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    4/43

    In this presentation, Well focus on

    Fault (short circuit) coordination

    assuming that overload protection is much

    easier to define and manage.Challenge

    Better understand the whole DC backup

    system fault behaviour in order to get to aconclusion for safe and reliable solution.

    8/28/2011 Primax Technologies Inc. 4

    IntroductionIntroduction

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    5/43

    RationalRational

    In typical DC backup systems multiple sourcesof energy are:

    connected in parallel simultaneously contributing into the faultEach has different time constant and

    amplitude

    Fault effect reflected on AC mains must betaken in consideration.

    Ex. 2 chargers, 1 or more batteries, inductiveloads, fully charged capacitors....

    8/28/2011 Primax Technologies Inc. 5

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    6/43

    Once breaking current of each source isdefined, one has to refer to the country

    standard to specify the requiredcomponents

    IEC std ratings and requirements mayvary from CSA, UL, IEEE, NFPA...

    8/28/2011 Primax Technologies Inc. 6

    RuleRule

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    7/43

    BottomBottom lineline

    Fuses, circuit breakers, switches, bus bars,cables and other equipment need to

    operate safely and reliably during fault:

    Breakers and Fuses

    Need to open SELECTIVELY

    Cables, switches, bus bars...Need to WITHSTAND the fault energy

    8/28/2011 Primax Technologies Inc. 7

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    8/43

    BasicsBasics

    For the purpose of this discussion we define

    the following: Fault: refers to a very low impedance path

    created when both polarity conductors are

    shorted.

    Failure: refers to over-current: Ex. Failingload, leakage in battery or DC source has lost

    regulation

    As always, Ohms law applies: I = V / Z

    Z: individual component impedance including interconnectingcable resistance.

    8/28/2011 Primax Technologies Inc. 8

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    9/43

    Steady state faultSteady state fault

    During fault evolution:

    System voltage decays gradually.The decay rate is related to impedance

    rate-of-changeof all parallel sources over the period of

    time before that protection devices open.

    This calculation is less accurate than theinitial fault current.

    8/28/2011 Primax Technologies Inc. 9

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    10/43

    EffectsEffects

    At the occurrence of a fault, a badly coordinated protection

    device may lead to:

    Device failure: Circuit breaker contacts may weld duringopening, so the fault is not interrupted

    Explosion: the device will explode due to the energyavailable during the fault arcing.

    Fire: due to the arc ignition of material during the contactopening

    Injury or death: Operators will be operating in unsafeenvironment.

    Note: Arc flash hazard level is directly proportional to theduration of the arc fault.

    8/28/2011 Primax Technologies Inc. 10

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    11/43

    Energy sourcesEnergy sources

    To define minimum protection fault currentratings, we need to evaluate the

    contribution in the fault of each of the DCcomponents

    8/28/2011 Primax Technologies Inc. 11

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    12/43

    TypicalTypical layoutslayouts

    Lets looks first to typical DC backupsystem layouts:

    8/28/2011 Primax Technologies Inc. 12

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    13/43

    TypicalTypical layoutlayout8/28/2011 Primax Technologies Inc. 13

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    14/43

    RedundantRedundant layoutlayout8/28/2011 Primax Technologies Inc. 14

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    15/43

    RedundantRedundant complexcomplex layoutlayout8/28/2011 Primax Technologies Inc. 15

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    16/43

    TypicalTypical nuclearnuclear layoutlayout8/28/2011 Primax Technologies Inc. 16

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    17/43

    TypicalTypical batterybattery chargercharger layoutlayout8/28/2011 Primax Technologies Inc. 17

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    18/43

    BatteryBattery Charger outputCharger output underunder faultfault

    8/28/2011 Primax Technologies Inc. 18

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    19/43

    Contribution of different DCContribution of different DCcomponentscomponents

    8/28/2011 Primax Technologies Inc. 19

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    20/43

    BatteryBattery

    Depending on the battery technology, plate

    thickness and number, specific gravity (inthe case of Lead acid batteries) available

    fault current may vary.

    Check with battery manufacturers for theexact fault current.

    Time constant: consider 10ms

    8/28/2011 Primax Technologies Inc. 20

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    21/43

    BatteryBattery exampleexample

    Typical 350AH battery fault current at itsterminals:

    VLA 0.33 thick Flat calcium plate battery with1.215 SG: 3200A

    Tubular VLA 0.35 thick plate battery with 1.215SG: 3400A

    AGM VRLA : 4361A

    Gel VRLA: 3750A

    Ni-Cd Medium performance: 3200A

    8/28/2011 Primax Technologies Inc. 21

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    22/43

    FilterFilter CapacitorsCapacitors

    Capacitors are a source of large instantaneouscurrents

    Consider time constant 10 ms

    Ex. 8 x 10,000uF-200VDC- ESR:20m

    with line impedance of 0.1

    8/28/2011 Primax Technologies Inc. 22

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    23/43

    Capacitor discharge caseCapacitor discharge case8/28/2011 Primax Technologies Inc. 23

    C (uF) R() Vo RC(s) Vc Imax(A) Q (uC) I(A)

    Vo . e(-t/RC) Vo/R CVo(e-t/RC) oe(-t/RC))/R

    80 000 0,1 136 0,008 1360 10880000 1360

    at t=0 1360 At=RC(s) 0,008 I at 1 RC 500 A

    t=2 RC(s) 0,016 I at 2RC 184 A

    8 x 10,000uF-200VDCESR:20m

    with lineimpedance of0.1

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    24/43

    Charger/rectifierCharger/rectifier

    Magnitude of faults depends mainly on:

    AC mains impedance Power transformer impedance Inductive filter design Other series components

    As a rule of thumb take 15-20 times the full current ratingtime constant 25ms

    Ex. 500A battery charger with a 3.5% Z transformerimpedance may deliver up to10 000A during a short circuit until its own protection getsinto action to interrupt.

    8/28/2011 Primax Technologies Inc. 24

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    25/43

    Inductive loadsInductive loads

    Main concern is DC motors:They operate switchgear, turbine lube pumps

    During deceleration, motors act as a generatorscontributing in the short circuit.

    - Consider that all motors are connected and running atthe time of the fault

    - Typical motor armature has large L/R time constant 20-60ms lower di/dt longer time to clearprotection

    - Rule of thumb: Use 4 times of running FLA

    8/28/2011 Primax Technologies Inc. 25

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    26/43

    NoteNote

    Its not bad to have high fault availability from thesource to efficiently perform selective clearance.

    So if the protection fuse or breaker has larger I2t thanwhat the source can provide, then this protection

    cannot clear its load fault.

    Ex. Switchmode power supplies provide fast currentlimiting and current foldback feature leading to achallenge in clearing faults.

    8/28/2011 Primax Technologies Inc. 26

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    27/43

    ProtectionProtection

    Fuse or circuit breaker?

    Both provide over-current, short circuitprotection, selective coordination and arc

    flash protection.

    Breakers can provide remote monitoring,

    adjustability, reset and control.Semiconductor fuses for ex. can provide sub-cycle fault protection and long term overload

    capacity

    8/28/2011 Primax Technologies Inc. 27

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    28/43

    Fuse or circuit breaker?Fuse or circuit breaker?

    Fuses Circuit Breakers

    DC Interrupting KA ++ -

    Flexibility (optional features) + +++++

    Adjustable - +++

    Resettable - ++++

    Reliability (maintenance) ++ -

    Arc flash protection +delay trip must be at minimum

    ++++

    8/28/2011 Primax Technologies Inc. 28

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    29/43

    8/28/2011 Primax Technologies Inc. 29

    Fuse dataFuse data

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    30/43

    8/28/2011 Primax Technologies Inc. 30

    FuseFuseblockblockdatadata

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    31/43

    8/28/2011 Primax Technologies Inc. 31

    Fuse coordinationFuse coordination curvescurves

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    32/43

    8/28/2011 Primax Technologies Inc. 32

    CircuitCircuit BreakerBreaker DataData

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    33/43

    8/28/2011 Primax Technologies Inc. 33

    CircuitCircuit BreakerBreaker DataData

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    34/43

    Case:Case:DC protectionDC protectioncoordinationcoordination

    8/28/2011 Primax Technologies Inc. 34

    HKD400

    HJD250

    At first, one

    can thinkthat

    protection is

    perfect:

    250A CB isfed from

    400A main

    CB!!

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    35/43

    BreakersBreakers coordinationcoordination8/28/2011 Primax Technologies Inc. 35

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    36/43

    CaseCase

    8/28/2011 Primax Technologies Inc. 36

    HKD400HKD400

    7250ASC 7250ASC

    3500ASC

    Total Fault at X:

    2x3500A+2x7250A=

    21500A+ inductive

    22kADC breakers

    X

    HJD250

    To

    Inverter

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    37/43

    Other protection considerationsOther protection considerations

    Soft startIf fault occurs during the soft start period of the rectifiers, available currents can

    be limited to lower value and chargers might shut down.

    Inherent current limitDepending on the fault evolution over time, rectifiers may or may not limit their

    output current during faults

    Ground Leakage alarmsin a floating DC system, this alarm will alert user for 1st polarity ground leakagewhich may not cause operation failure although it can be a safety hazard. A 2nd

    polarity ground leakage may cause high impedance fault through the ground.

    Connection cablesInterconnecting cable impedance reduces the fault current. This depends on their

    material, cross section and length. In general, battery interconnecting cablevoltage drop is accounted in the short circuit capabilities of the batteries.

    Ex. 4/0-259 strands copper cable has a DC resistance of 0.15 /km.

    8/28/2011 Primax Technologies Inc. 37

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    38/43

    Few applicable standardsFew applicable standards

    IEEE 946: Recommended Practice for the Design of DC Auxiliary Power

    Systems for Generating Stations

    IEEE 1375: Guide for the Protection of Stationary Battery Systems

    IEEE 1584 empirical equations are used to calculate arc-flash levels

    ANSI/IEEE C37.40 (1993), "Standard Service Conditions and Definitions forHigh-Voltage Fuses, Distribution Enclosed Single-Pole Air Switches, FuseDisconnecting Switches, and Accessories"

    IEC 60909: Short-circuit currents in three-phase-a.c. systems

    IEC 60947: Low-voltage switchgear and control gear

    IEC 60127 family: requirements applicable to fuses

    UL 489 and CSA 22.2-5-09 Harmonized Standards: Molded-Case CircuitBreakers, Molded-Case Switches and Circuit-Breaker Enclosures

    8/28/2011 Primax Technologies Inc. 38

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    39/43

    ConclusionConclusion

    During faults, DC system componentsresponse will be non linear, resulting into

    complicated behaviour.Consequently, rule of thumb and past

    experience might be needed to definebreaking currents.

    8/28/2011 Primax Technologies Inc. 39

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    40/43

    ConclusionConclusion

    However,in special or large applications,Rules of thumb might lead to

    overestimated values affecting the sizeand cost of the installation.

    So, in this case, more accurateassumptions and calculations must be

    made.

    8/28/2011 Primax Technologies Inc. 40

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    41/43

    ConclusionConclusion

    Take all precautions to properly define your

    equipment protection and selectivity:ASK FOR

    Breaking capacity of protection device

    Fault capabilities of all connected energysources

    Require professionals with relevant

    experience and background to help

    8/28/2011 Primax Technologies Inc. 41

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    42/43

    QUESTIONS?QUESTIONS?

    8/28/2011 Primax Technologies Inc. 42

  • 7/28/2019 Battery and DC Backup System Protection and Coordination

    43/43

    ThankThank you !you !

    8/28/2011 Primax Technologies Inc. 43