ba_sarexc1_amexc1_en.pdf

Embed Size (px)

Citation preview

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    1/64

    CertificateRegistration No.12 100/104 4269

    Electric multi-turn actuators

    Operation instructions

    SAExC 07.1 SAExC 16.1SARExC 07.1 SARExC 16.1

    with actuator controlsAUMA MATIC AMExC 01.1

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    2/642

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1with actuator controls AUMA MATIC AMExC 01.1 Operation instructions

    Table of contents Page1. Safety instructions 41.1 Range of application 41.2 Electrical connection 41.3 Maintenance 41.4 Warnings and notes 42. Short description 53. Technical data 6

    4. Additional information to the wiring diagram legend 95. Transport, storage and packaging 105.1 Transport 105.2 Storage 105.3 Packaging 106. Mounting to valve/ gearbox 117. Mounting positions of the local controls 138. Electrical connection 148.1 Ex-plug/ socket connector with terminal board (KP) 168.2 Connection with Ex-plug-in terminal connection (KES) 17

    9. Manual operation 1810. Operation and indications of the local controls 1911. Opening the switch compartment 2111.1 Removing the cover from the switch compartment 2111.2 Pulling off the indicator disc (option) 2112. Setting the limit switching 2212.1 Setting end position CLOSED (black section) 2212.2 Setting end position OPEN (white section) 2212.3 Checking the limit switches 2213. Setting the DUO limit switching (option) 23

    13.1 Setting direction CLOSE (black section) 2313.2 Setting direction OPEN (white section) 2313.3 Checking the DUO limit switches 2314. Setting the torque switching 2414.1 Setting 2414.2 Checking the torque switches 2415. Test run 2515.1 Checking the direction of rotation 2515.2 Checking the setting of the limit switching 2615.3 Checking the type of seating 2615.4 Checking the PTC tripping device 26

    16. Setting the potentiometer (option) 2717. Setting the electronic position transmitter RWG (option) 2817.1 Setting 2-wire system 4 20 mA and 3- /4-wire system 0 20 mA 2917.2 Setting 3- / 4- wire system 4 20 mA 30

    Scope of these instructions: These instructions valid for multi-turn actuators of the type rangeSAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1 with the actua-tor controls AMExC 01.1.These operation instructions are only valid for clockwise closing,i.e. driven shaft turns clockwise to close the valve.

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    3/643

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1Operation instructions with actuator controls AUMA MATIC AMExC 01.1

    Page18. Setting the mechanical position indicator (option) 3119. Closing the switch compartment 3120. Actuator controls AUMA MATIC 3220.1 Functions of the diagnosis LEDs on the interface board (standard version) 3220.2 Programming the logic board 3320.3 EMERGENCY - OPEN and EMERGENCY - CLOSE signal (option) 3421. Electronic positioner (option) 3521.1 Technical data 3521.2 Setting 3521.2.1 Setting type of signal 3621.2.2 Setting actuator behaviour on loss of signal 3721.3 Positioner adjustment for end position CLOSED (standard version) 3821.4 Positioner adjustment for end position OPEN (standard version) 3921.5 Setting the sensitivity 39

    21.6 Positioner adjustment for end position OPEN (inverse operation) 4121.7 Positioner adjustment end position CLOSED (inverse operation) 4221.8 Positioner in Split Range version (option) 4321.8.1 Split Range: description of functions 4321.8.2 Programming 4321.8.3 Positioner adjustment for Split Range 4322. Timer (option) 4522.1 Functions of the diagnosis LEDs (timer) 4522.2 Setting start and end of stepping mode via DUO limit switching (option) 4622.3 Setting ON and OFF times 4723. Fuses 4823.1 Fuses within the actuator controls 4823.2 Motor protection 4924. Enclosure protection IP 68 (option) 5025. Maintenance 5126. Lubrication 5227. Disposal and recycling 5228. Service 5229. Spare parts list multi-turn actuator SA(R)ExC 07.1 SA(R)ExC 16.1 5430. Spare parts list controls AMExC 01.1 with plug/ socket connector (KP) 5631. Spare parts list controls AMExC 01.1 with terminal connection (KES) 5832. PTB certificate 6033. Declaration of Conformity and Declaration of Incorporation 62

    Index 63Addresses of AUMA offices and representatives 64

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    4/64

    1. Safety instructions1.1 Range of application

    AUMA actuators are designed for the operation of industrial valves,e.g. globe valves, gate valves, butterfly valves and ball valves.For other applications, please consult us. The manufacturer is not liable for

    any possible damage resulting from use in other than the designated appli-cations. Such risk lies entirely with the user.Observance of these operation instructions is considered as part of the con-trols/ actuators designated use.

    1.2 Electrical connectionWork performed in potentially explosive atmospheres is subject to specialregulations (national standards) which have be observed.Work at the open actuator under voltage must only be performed if it isassured that for the duration of the work there is no danger of explosion.During electrical operation, certain parts inevitably carry lethal voltages.Work on the electrical system or equipment must only be carried out by askilled electrician himself or by specially instructed personnel under the con-trol and supervision of such an electrician and in accordance with the appli-cable electrical engineering rules.

    1.3 MaintenanceThe maintenance instructions (refer to page51) must be observed, other-wise a safe operation of the actuator is no longer guaranteed.

    1.4 Warnings and notesFailure to observe the warnings and notes may lead to serious injuries ordamage. Qualified personnel must be thoroughly familiar with all warningsand notes in these operation instructions.Correct transport, proper storage, mounting and installation, as well as care-ful commissioning are essential to ensure a trouble-free and safe operation.During operation, the multi-turn actuator warms up and surface tempera-tures > 60 C may occur. Check the surface temperature prior to contact inorder to avoid burns.The following references draw special attention to safety-relevant proce-dures in these operation instructions. Each is marked by the appropriatepictograph.

    This pictograph means: Note!Note marks activities or procedures which have major influence on the cor-rect operation. Non-observance of these notes may lead to consequentialdamage.

    This pictograph means: Electrostatically endangered parts!If this pictograph is attached to a printed circuit board, it contains partswhich may be damaged or destroyed by electrostatic discharges. If theboards need to be touched during setting, measurement, or for exchange, itmust be assured that immediately before a discharge through contact withan earthed metallic surface (e.g. the housing) has taken place.

    This pictograph means: Warning!Warning marks activities or procedures which, if not carried out correctly,can affect the safety of persons or material.

    4

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1with actuator controls AUMA MATIC AMExC 01.1 Operation instructions

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    5/64

    2. Short descriptionAUMA multi-turn actuators of the type range SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1 are driven by an electric motor and controlledby the actuator controls AUMA MATIC AMExC 01.1, which is included in thescope of delivery.

    A handwheel is provided for manual operation.The limitation of travel is realised via limit switches in both end positions.Torque seating is also possible in both end positions. The type of seating isdetermined by the valve manufacturer.

    Both the multi-turn actuator and the controls have a modular design, i.e.they are designed in accordance with the principle of a modular constructionsystem.This means that each actuator or each controls are individually manufac-tured and combined for a specific valve automation task. An order-specificcommission number, printed on the name plate, is assigned to each actua-tor/ controls. You can use this commission number to download the wiringdiagram, inspection records and further information from the Internet.Our website:http://www.auma.com

    CommissioningPlease note that for low temperature versions ( 50 C), the controlsrequires a heat-up time.This heat-up time is applicable in case the actuator and the controls are notlive and have cooled down to ambient temperature. In case commissioninghas to be performed under these conditions, the following heat-up timeshave to be observed:

    60 min. at 50 C80 min. at 60 C

    5

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1Operation instructions with actuator controls AUMA MATIC AMExC 01.1

    0

    10

    20

    30

    40

    50

    0 10 20 30 40 60

    60

    70

    80

    50

    t [min.]

    [C]

    Figure 1: Heat-up time chart

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    6/64

    3. Technical data

    Features and functionsExplosion protection Standard: II2G EEx de IIC T4

    II2G c IIC T4Option: II2G EEx d IIC T4

    II2G c IIC T4Protection types Motor compartment: d flameproof enclosure EEx dSwitch compartment: d flameproof enclosure EEx dControls housing: d flameproof enclosure EEx dTerminal compartment: e increased safety EEx e

    d (option) flameproof enclosure EExdGear housing: c constructional safety

    EC type examination certificate PTB 01 ATEX 1087Type of duty1) Standard: SAExC Short time duty S2 - 15 min

    SARExC Intermittent duty S4 - 25 %Option: SAExC Short time duty S2 - 30 min

    SARExC Intermittent duty S4 - 50 %Motors 3-ph AC asynchronous motor, type IM B9 according to IEC 34Insulation class F, tropicalizedMotor protection Standard: SAExC: PTC thermistors (according to DIN 44082)

    SARExC: PTC thermistors (according to DIN 44082)Option: SAExC: Thermoswitches (NC)

    Self-locking Yes, for output speeds from 4 to 90 rpmLimit switching Counter gear mechanism for end positions CLOSED and OPEN

    for 1 to 500 turns per stroke (optional for 1 to 5,000 turns per stroke)Standard: Single switch (1 NC and 1 NO) for each end positionOptions: Tandem switch (2 NC and 2 NO) for each end position,

    switches galvanically isolatedTriple switch (3 NC and 3 NO) for each end position,switches galvanically isolatedIntermediate position switch (DUO limit switching),adjustable for any intermediate position

    Torque switching Infinitely adjustable torque switching for direction OPEN and CLOSEStandard: Single switch (1 NC and 1 NO) for each directionOptions: Tandem switch (2 NC and 2 NO) for each direction,switches galvanically isolated

    Position feedback signal,analogue (options)

    Potentiometer or 0/4 20 mA (RWG)For further details see separate data sheet

    Mechanical position indicator(option)

    Continuous indication, adjustable indicator disc with symbols OPEN and CLOSED

    Running indication Blinker transmitterHeater in switch compartment Standard: Resistance type heater with 5 W, 24 V DC

    Options: Self-regulating PTC heater, 5 20 W24 48 V AC/DC, 110 250 V AC/DC or 380 400 V AC

    Motor heater (option) SAExC/ SARExC 07.1 10.1: 12.5 WSAExC/ SARExC 14.1 16.1: 25 W

    Manual operation Manual drive for setting and emergency operation, handwheel does not rotate duringelectrical operation.Option: Handwheel lockable

    Connection to controls AUMA plug/ socket connector with screw type connectionOutput drive types A, B1, B2, B3, B4 according to EN ISO 5210

    A, B, D, E according to DIN 3210C according to DIN 3338Special output drives: AF, AK, AG, IB1, IB3

    Power supply, mains frequencyand current consumption

    For mains voltage and mains frequency, refer to name plates at the controls and the motorPermissible variation of the nominal voltage: 10 %Permissible variation of the mains frequency: 5 %Motor current consumption: Refer to motor name plateCurrent consumption of the controls depending on the mains voltage:100 to 120 V AC = max. 600 mA

    208 to 240 V AC = max. 300 mA380 to 500 V AC = max. 150 mAExternal supply of the electronics(option)

    24 V DC + 20 % / 15 %,Observe current consumption of the controls

    1) Based on 20 C ambient temperature and an average load with running torque according to Technical data SAExC or SARExC.The type of duty must not be exceeded

    6

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1with actuator controls AUMA MATIC AMExC 01.1 Operation instructions

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    7/64

    Rated power Refer to motor name plateNote: The controls is designed for the rated power of the actuator

    Overvoltage category Category IIISwitchgear Standard: Reversing contactors2) (mechanically and electrically interlocked)

    for motor power up to 1.5 kWOption: Reversing contactors2) (mechanically and electrically interlocked)

    for motor power up to 7.5 kWControl Standard: Control inputs 24 V DC, OPEN - STOP - CLOSE (via opto-isolator,with one common), current consumption: approx. 10 mA per inputObserve min. duration of impulse for modulating actuators

    Option: Control inputs 220 V AC, OPEN - STOP - CLOSE (via opto-isolator,with one common), current consumption: approx. 15 mA per input

    Output signals Standard: 5 output relays with gold-plated contacts:4 potential-free NO contacts with one common:

    max. 250 V AC, 0.5 A (resistive load)Standard configuration:End position OPEN, end position CLOSED, selector switch REMOTE,selector switch LOCAL1 potential-free change-over contact, max. 250 V AC, 0.5A (resistive load)for collective fault signalStandard configuration:

    Torque fault, phase failure, motor protection trippedVoltage output Standard: Auxiliary voltage 24 V DC, max. 50 mA for supply of the control inputs,galvanically isolated from internal voltage supply

    Option: Auxiliary voltage 115 V AC, max. 30 mA for supply of the control inputs,3),galvanically isolated from internal voltage supply

    Local controls Standard: Selector switch LOCAL - OFF - REMOTE (lockable in all three positions)Reset motor protectionPush buttons OPEN - STOP - CLOSE3 indication lights:End position CLOSED (yellow), collective fault signal (red), end positionOPEN (green)

    Option: Protection cover, lockableFunctions Standard: Switch-off mode adjustable

    limit or torque seating for end position OPEN and end position CLOSED

    Overload protection against excessive torques over the whole travelExcessive torque (torque fault) can be excluded by collective fault signalPhase failure monitoring with automatic phase correctionPush-to-run operation or self-retaining in REMOTEPush-to-run operation or self-retaining in LOCALBlinker transmitter signal can be switched on or off by actuator (option)

    Options: Positioner4):Nominal position value via analogue input E1 = 0/4 20 mAAdjustable behaviour on loss of signalAdjustable sensitivity (dead band) and pause timeSplit Range operation

    Motor protection evaluation Standard: Monitoring of the motor temperature with PTC tripping devicein combination with PTC thermistors in the actuator motor

    Options: Thermal overload relay in combination with thermoswitches inthe actuator motor

    Electrical connection Standard: Ex-plug/socket connector with terminal board (KP)Options: Ex-plug-in terminal connection (KES)

    Electrical connection designed as flameproof enclosure EEx d (KE)Parking frame for wall mounting of the disconnected plugProtection cover for plug compartment (when plug is removed)

    Threads for cable glands Standard: Metric threadsOptions: Pg-threads, NPT-threads, G-threads

    Wiring diagram Wiring diagram according to commission number included in deliveryFurther options for version with RWG in the actuatorPosition feedback(option)

    Analogue output E2 = 0/4 20 mA (load max. 500 )

    2) The lifetime guaranteed by the manufacturer amounts to min. 2 million cycles3) Not possible in combination with PTC tripping device4) Requires position transmitter (potentiometer or RWG) in actuator

    7

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1Operation instructions with actuator controls AUMA MATIC AMExC 01.1

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    8/64

    Service conditionsEnclosure protection accordingto EN 60 5295)

    Standard: IP 67Option: IP 68For both enclosure protections (IP 67 und IP 68) the terminal compartment is additionallysealed against the interior double sealed

    Corrosion protection Standard: KN Suitable for installation in industrial units, in water or power plantswith a low pollutant concentration

    Options: KS Suitable for installation in occasionally or permanently aggressiveatmosphere with a moderate pollutant concentration(e.g. in wastewater treatment plants, chemical industry)

    KX Suitable for installation in extremely aggressive atmospherewith high humidity and high pollutant concentration

    KX-G same as KX, however aluminium-free version (outer parts)Finish coating Standard: Two-component iron-mica combinationStandard colour Standard: Grey (DB 702, similar to RAL 9007)

    Option: Other colours are possible on requestAmbient temperature6) Standard: 20 C to + 40 C

    Options: 40 C to + 40 C low temperature 50 C to + 40 C, extreme low temperature incl. heating system

    Vibration resistance7)

    according to IEC 60 068-2-6

    1 g, from 10 Hz to 200 Hz

    (only actuator with controls. Not valid in combination with gearboxes)Lifetime SAExC 07.1 10.1: 20,000 operations (OPEN - CLOSE - OPEN)with 30 turns per stroke

    SAExC 14.1 16.1: 15,000 operations (OPEN - CLOSE - OPEN)with 30 turns per stroke

    SARExC 07.1 10.1: 5 million operations/ starts8)SARExC 14.1 16.1: 3.5 million operations/ starts8)

    Weight Multi-turn actuator: refer to Technical data SAExC or SARExCActuator controls: approx. 12 kg (including Ex-plug/ socket connector

    with terminal board)AccessoriesWall bracket9) AUMA MATIC mounted separately from the actuator, including plug/ socket connector.

    Connecting cables on request.Recommended for high ambient temperatures, difficult access, or in case of heavy

    vibrations during service.Further informationEU directives ATEX Directive: (94/9/EC)

    Electromagnetic Compatibility (EMC): (89/336/EEC)Low Voltage Directive: (73/23/EEC)Machinery Directive: (98/37/EC)

    Reference documents Product description Electric multi-turn actuators SAExC/ SARExCProduct description, Actuator controls AUMA MATICInformation Electric actuators and valve gearboxes according to ATEXDimension sheets SAExC/ SARExC ...with integral controls AUMA MATICTechnical data AMExC 01.1Technical data SAExC/ SARExCElectrical data SAExC/ SARExC

    5) For version in enclosure protection IP 68, higher corrosion protection KS or KX is strongly recommended6) Under certain conditions (special sizing) up to + 60 C possible. Version with RWG from 40 C to max. + 40 C (+ 60 C)

    7) Resistant to vibrations during start-up or for failures of the plant. However, a fatigue strength may not be derived from this8) The lifetime of modulating actuators depends on the load and the number of starts. A high starting frequency will rarely improve the modulating accuracy. Toreach the longest possible maintenance and fault-free operation time, the number of starts per hour chosen should be as low as permissible for the process

    9) Cable length between actuator and AUMA MATIC max. 100 m. Not suitable for version with potentiometer in the actuator. Instead of the potentiometer, an RWGhas to be used in the actuator

    8

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1with actuator controls AUMA MATIC AMExC 01.1 Operation instructions

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    9/64

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    10/64

    5. Transport, storage and packaging5.1 Transport . For transport to place of installation, use sturdy packaging.. Do not attach ropes or hooks to the handwheel for the purpose of lifting by

    hoist.

    . If multi-turn actuator is mounted on valve, attach ropes or hooks for thepurpose of lifting by hoist to valve and not to multi-turn actuator.Fitting the handwheel:For transport purposes, handwheels as from a diameter of 400 mm are sup-plied separately.

    Engage manual operation prior to mounting the handwheel!If the manual operation is not engaged, damage can occur atthe change-over mechanism.. Engage manual operation (figure2):

    Manually lift the red change-over lever while slightly turning the shaft backand forth until manual operation engages. The manual operation is cor-rectly engaged if the change-over lever can be lifted by approx. 85.

    Manual force is sufficient for operating the change-overlever. It is not necessary to use an extension. Excessiveforce may damage the change-over mechanism.. Attach handwheel onto the red change-over lever on shaft (figure3).. Secure handwheel using the circlip supplied.

    5.2 Storage . Store in well-ventilated, dry room.. Protect against floor dampness by storage on a shelf or on a wooden pallet.. Cover to protect against dust and dirt.. Apply suitable corrosion protection agent to bare surfaces.If multi-turn actuators are to be stored for a long time (more than 6 months),the following points must be observed additionally:. Prior to storage: Protect bare surfaces, in particular the output drive parts

    and mounting surface, with long-term corrosion protection agent.. Check for corrosion approximately every 6 months. If first signs of corro-sion show, apply new corrosion protection.

    After mounting, connect actuator immediately to electricalsystem, so that the heater prevents condensation.

    5.3 PackagingOur products are protected by special packaging for the transport ex works.The packaging consists of environmentally friendly materials which can eas-ily be separated and recycled.We use the following packaging materials: wood, cardboard, paper, and PEfoil. For the disposal of the packaging material, we recommend recyclingand collection centres.

    10

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1with actuator controls AUMA MATIC AMExC 01.1 Operation instructions

    85

    Figure 2 Figure 3

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    11/64

    6. Mounting to valve/ gearbox. Prior to mounting the multi-turn actuator must be checked

    for damage. Damaged parts must be replaced by originalspare parts.. After mounting to valve/ gearbox, touch up any possibledamage to paint finish.. Increased temperatures at valve mounting flange or valvestem:If increased temperatures > 40 C are to be expected at thevalve mounting flange or the valve stem (e.g. due to hotmedia), please consult AUMA. Temperatures > 40 C are notconsidered with regards to the non-electrical explosion protec-tion.

    The multi-turn actuator leaves the factory in position CLOSED (limit switchCLOSED tripped).

    . Check if mounting flange fits the valve/ gearbox.

    Spigot at flanges should be loose fit!

    The output drive types B1, B2, B3, or B4 (figure4) are delivered with boreand keyway (usually according to ISO 5210).

    For output drive type A (figure6), the internal thread of the stem nut mustmatch the thread of the valve stem. If not ordered explicitly with thread, thestem nut is unbored or with pilot bore when delivered. For finish machiningof stem nut, refer to next page.

    . Check whether bore and keyway match the input shaft of valve/ gearbox.. Thoroughly degrease mounting faces at multi-turn actuator and valve/ gearbox.. Apply a small quantity of grease to input shaft of valve/ gearbox.. Place actuator on valve/ gearbox and fasten. Fasten bolts(quality min. 8.8, refer to table1) evenly crosswise.

    11

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1Operation instructions with actuator controls AUMA MATIC AMExC 01.1

    Figure 4

    Output drive type B1/B2Plug sleeve

    Output drive type B3/B4Bore with keyway

    Strength class 8.8 T A (Nm)M 8 25M 10 50M 12 87

    M 16 220

    Table 1: Fastening torque for bolts

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    12/64

    Finish machining of stem nut (output drive type A):

    The output drive flange does not have to be removed from the actuator..Remove spigot ring (80.2, figure 5) from mounting flange..Take off stem nut (80.3) together with thrust bearing (80.01) and thrust

    bearing races (80.02)..Remove thrust bearing and thrust bearing races from stem nut..Drill and bore stem nut and cut thread.When fixing in the chuck, make sure stem nut runs true!.Clean the machined stem nut..Apply Lithium soap EP multi-purpose grease to thrust bearing and races,then place them on stem nut..Re-insert stem nut with thrust bearings into the mounting flange. Ensurethat dogs are placed correctly in the slots of the hollow shaft..Screw in spigot ring until it is firm against the shoulder..Press Lithium soap EP multi-purpose grease on mineral oil base into thegrease nipple with a grease gun (for quantities, please refer to table):

    Protection tube for rising valve stem.Seal thread with hemp, Teflon tape, or thread sealing material..Screw protection tube (1) into thread (figure 6) and tighten it firmly..Push down the sealing (2) to the housing..Check whether cap (3) is available and without damage.

    12

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1with actuator controls AUMA MATIC AMExC 01.1 Operation instructions

    Output drive A 07.2 A 10.2 A 14.2 A 16.2Qty 1) 1.5 g 2 g 3 g 5 g1) For greases with a density = 0.9 kg/dm

    Table 2: Grease quantities for output drive type A

    3

    1

    2

    Figure 6: Protection tube for rising valve stem

    Figure 5

    80.3

    80.2

    Output drive type AStem nut

    80.01/80.02

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    13/64

    7. Mounting positions of the local controlsThe mounting position of the local controls is designed according to theorder. If, after mounting the actuator to the valve or the gearbox on site, thelocal controls is in an unfavourable condition, the mounting position can eas-ily be changed at a later date.

    Four mounting positions are possible:

    Changing the mounting position

    . Flameproof enclosure! Before opening, ensure that thereis no explosive gas and no voltage.

    . Turn local controls by a maximum of 180!. Ensure that the wires are neither twisted nor jammed.. Loosen 4 bolts and remove the local controls.. Turn local controls in one of the four positions and re-place on the actua-

    tor.. Clean sealing faces of housing and cover.. Check whether O-ring is in good condition.. Apply a thin film of non-acidic grease to the sealing faces.. Preserve joint surfaces with an acid-free corrosion protection agent.Flameproof enclosure! Handle cover and housing parts withcare. Joint surfaces must not be damaged or soiled in any

    way. Do not jam cover during fitting.. Replace cover on switch compartment and fasten bolts evenly crosswise.

    13

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1Operation instructions with actuator controls AUMA MATIC AMExC 01.1

    Figure 7: Mounting position A

    Actuator

    Figure 8: Mounting position B

    Actuator

    Figure 9: Mounting position C

    Actuator

    Figure 10: Mounting position D

    Actuator

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    14/64

    8. Electrical connection. When working in potentially explosive areas, observe the

    European Standards EN 60079-14 Electrical Installationsin Hazardous Areas and EN 60079-17 Inspection andMaintenance of Electrical Installations in Hazardous

    Areas.. Work on the electrical system or equipment must only becarried out by a skilled electrician himself or by speciallyinstructed personnel under the control and supervision ofsuch an electrician and in accordance with the applicableelectrical engineering rules.. Observe warnings at the actuator:

    Wiring diagramThe wiring diagram applicable to the actuator is attached to the handwheelin a weather-proof bag, together with the operation instructions. In case thewiring diagram is not available, it can be obtained from AUMA (state com-mission no., refer to name plate) or downloaded directly from the Internet(www.auma.com).

    External fuseFor short-circuit protection and for releasing the actuator, fuses and discon-nect switches have to be provided by the customer.The current values for sizing the switch can be derived from the current con-sumption of the motor plus the current consumption of the controls.Motor current consumption:Refer to name plate on motor (nominal current).Current consumption of the controls depending on the mains voltage:100 to 120 V AC = max. 650 mA208 to 240 V AC = max. 325 mA380 to 500 V AC = max. 190 mAThe maximum permissible fuse for controls with a rated power of 1.5 kW is16 A (gL/ gG), and for controls with a rated power of 7.5 kW, the valueamounts to 32 A (gL/ gG).

    Cable installation in accordance with EMCSignal and bus cables are susceptible to interference.Motor cables are interference sources.. Lay cables being susceptible to interference or sources of interference at

    the highest possible distance from each other.. The interference immunity of signal and bus cables increases if the cablesare laid close to the ground potential.. If possible, avoid laying long cables and make sure that they are installedin areas being subject to low interference.. Avoid long parallel paths with cables being either susceptible to interfer-ence or interference sources.. For the connection of remote position transmitters (potentiometer, RWG),screened cables must be used.

    14

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1with actuator controls AUMA MATIC AMExC 01.1 Operation instructions

    A T T E N T I O N

    DO NOT REMOVE

    COVER WHILE

    CIRCUIT IS LIVE

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    15/64

    HeaterAs standard, the control unit of the actuator is equipped with a heater to pre-vent condensation within the actuator. Unless ordered otherwise, the heateris internally supplied. For external supply (option), the heater always has tobe connected.Some actuators are optionally equipped with an additional motor heater.The motor heater is always externally supplied and has to be connectedaccording to the wiring diagram.

    Actuator controls on wall bracket (accessory)

    For version on wall bracket, please observe the following:

    . Versions with potentiometer in the actuator are not suitable. Instead of thepotentiometer, an RWG has to be used in the actuator.Permissible cable distance between actuator and AUMA MATIC amountsto a maximum of 100 m.. Preconfectioned cables for the connection between actuator and AUMAMATIC on wall bracket can be obtained from AUMA on request.In case no preconfectioned cables are used, the following has to beobserved in addition:. Use suitable flexible and screened connecting cables.. Connect the wires in correct phase sequence.Check the direction of rotation before switching on (see page25)

    Subsequent mounting of the actuator controls on the actuatorIn case the actuator and the actuator controls have different commissionnumbers (refer to name plates), the designations of the terminal plan andthe wiring diagram (KMS . . .) have to match for both devices.

    15

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1Operation instructions with actuator controls AUMA MATIC AMExC 01.1

    Figure 11: AMExC 01.1 on wall bracket

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    16/64

    8.1 Ex-plug/ socket connector with terminal board (KP). Before mains connection: Check whether type of current, supply voltage,and frequency comply with motor data (refer to name plate at motor).

    Opening the terminal compartment. Loosen bolts (1) (figure12) and remove cover.The terminal compartment is designed for explosion protection EEx e(increased safety). The flameproof compartment (type of protection EEx d)remains hereby closed.. Insert cable glands with EEx e approval and of size suit-

    able for connecting cables.(The enclosure protection stated on the name plate is onlyensured if suitable cable glands are used).. Seal cable entries which are not used with suitable plugs.

    Connecting the cables. Remove cable sheathing in a length of 120 140 mm.Strip wires: controls 8 mm, motor 12 mm.. 2 wires for each connection permitted.

    . Connect cables according to order-related wiring diagram.Max. cross sections:- Power terminals (U1, V1, W1, U2, V2, W2) andprotective earth (symbol: ) = 2.5 6 mm (flexible or solid)

    - Control contacts (1 to 50) = 0.75 1.5 m (flexible or solid). For stranded wires use end-sleeves according to DIN 46228.. After connection ensure that cable glands and screw plugs are fitted bothtightly and water-tight.

    Closing the terminal compartment. Clean sealing faces of housing and cover.. Check whether O-ring is in good condition.. Apply a thin film of non-acidic grease (e.g. Vaseline) to the sealing faces.. Replace cover and fasten bolts (1) evenly crosswise.. Fasten cable glands with the specified torque to ensure the required

    enclosure protection.Disconnection from the mains without removing the wiringIf the actuator must be taken from the valve, e.g. for service purposes, it canbe separated from the mains without having to remove the wiring(figure 13). For this purpose, the screws (2) are removed and the plug/ socket connector is pulled off. Cover and terminal board remain together.

    Flameproof enclosure! Before opening, ensure that noexplosive gas and no voltage is present.

    Before fitting the plug/ socket connector:

    . Clean sealing faces of housing and cover.. Check whether O-ring is in good condition.. Apply a thin film of non-acidic grease (e.g. Vaseline) to the sealing faces.. Preserve joint surfaces with an acid-free corrosion protection agent.Flameproof enclosure! Handle cover and housing parts withcare. Joint surfaces must not be damaged or soiled in anyway. Do not jam cover during fitting.. Fit plug/socket connector and fasten 4 bolts (2) evenly crosswise.

    Parking frame, protection cover (accessories)A special parking frame (figure14) for protection against touching the barecontacts and against environmental influences is available.The open terminal compartment can be closed using a protective cover(not illustrated).

    16

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1with actuator controls AUMA MATIC AMExC 01.1 Operation instructions

    Figure 12: Connection

    Cover

    (1)

    Terminal board

    Figure 13: Disconnection from the mains

    Cover

    Terminal board

    (2)

    Figure 14: Parking frame (accessory)

    Parking frame

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    17/64

    8.2 Connection with Ex-plug-in terminal connection (KES). Before mains connection: Check whether type of current, supply voltage,and frequency correspond to motor data (refer to name plate at motor).

    Opening the terminal compartment. Loosen bolts (1) (figure15) and remove cover.The terminal compartment is designed for explosion protection EEx e(increased safety). The flameproof compartment (type of protectionEEx d) remains hereby closed.. Insert cable glands with EEx e approval and of size suit-

    able for connecting cables.(The enclosure protection stated on the name plate is onlyensured if suitable cable glands are used).. Seal cable entries which are not used with suitable plugs.

    Connecting the cables. Connect cables according to order-related wiring diagram.Max. cross sections:

    - Power terminals (U, V, W) andprotective earth (symbol ) = max. 10 mm- Control contacts (1 to 50) = max. 2.5 mm flexible, max. 4 mm2 solid. For stranded wires use end-sleeves according to DIN 46228.. After connection ensure that cable glands and screw plugs are fitted bothtightly and water-tight.

    Closing the terminal compartment. Clean sealing faces of housing and cover.. Check whether O-ring is in good condition.. Apply a thin film of non-acidic grease (e.g. Vaseline) to the sealing faces.. Replace cover and fasten bolts (1) evenly crosswise.. Fasten cable glands with the specified torque to ensure the requiredenclosure protection.

    Disconnection from the mains without removing the wiringIf the actuator must be taken from the valve, e.g. for service purposes, it canbe separated from the mains without removing the wiring (figure16). Forthis purpose, the screws (2) are removed and the entire plug/ socket con-nector is pulled off. Cover and frame remain together.

    Flameproof enclosure! Before opening, ensure that noexplosive gas and no voltage is present.

    Before fitting the terminal connection:. Clean sealing faces of housing and cover.. Check whether O-ring is in good condition.. Apply a thin film of non-acidic grease (e.g. Vaseline) to the sealing faces.. Preserve joint surfaces with an acid-free corrosion protection agent.

    Flameproof enclosure! Handle cover and housing parts withcare. Joint surfaces must not be damaged or soiled in anyway. Do not jam cover during fitting.

    Fit terminal connection and fasten 4 bolts (2) evenly crosswise.Parking frame / protection cover (accessories)A special parking frame (figure17) for protection against touching the barecontacts and against environmental influences is available.The open terminal compartment can be closed using a protective cover(not illustrated).

    17

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1Operation instructions with actuator controls AUMA MATIC AMExC 01.1

    Figure 15: Connection

    Cover

    Frame

    (1)

    Figure 16: Disconnection from the mains

    Cover

    Frame (2)

    Figure 17: Parking frame (accessory)

    Parking frame

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    18/64

    9. Manual operationThe actuator may be operated manually for purposes of setting and com-missioning and in case of motor failure or power failure.Manual operation is engaged by an internal change-over mechanism.

    Engaging manual operation. Lift up change-over lever in the centre of the handwheel to approx. 85,while slightly turning the handwheel back and forth until manual operationengages (figure 18).

    Manual force is sufficient for operating the change-overlever. It is not necessary to use an extension. Excessiveforce may damage the change-over mechanism.

    . Release change-over lever (should snap back into initial position by springaction, figure19), if necessary, push it back manually.

    Operating the change-over lever while the motor is running(figure 20) can lead to increased wear at the change-overmechanism.

    . Turn handwheel into desired direction (figure21).Disengaging manual operationManual operation is automatically disengaged when motor is started again.The handwheel does not rotate during motor operation.

    18

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1with actuator controls AUMA MATIC AMExC 01.1 Operation instructions

    Figure 18 Figure 19

    Figure 20 Figure 21

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    19/64

    10. Operation and indications of the local controls

    Selector switch

    Position OFF (0):- No remote control possible- No local control possible- Actuator remains ready for signalisation

    signalisation (the controls power supply is maintained)

    Position Local control (I):The actuator can be operated locally via the push buttonsOPEN - STOP - CLOSE.

    Position Remote control (II):The actuator can be controlled from remote, e.g. via thecontrol room.

    Position Test (III):Test PTC tripping device (refer to page26)Only available in combination with motor protection(PTC thermistor).Red indication light (fault) is illuminated.

    Position Reset (III):Reset fault signal (red indication light) after the motor pro-tection has tripped (refer to page49).Only available in combination with motor protection(PTC thermistor).

    19

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1Operation instructions with actuator controls AUMA MATIC AMExC 01.1

    Figure 22: Local controls

    Selector switch

    Push buttons Indication lights

    Reset

    I II

    III

    0

    TestIII

    Reset

    I II

    III

    0

    TestIII

    Reset

    I II

    III

    0

    TestIII

    ResetIII

    TestIII

    I II0

    TestIII

    Reset

    I II

    III

    0

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    20/64

    Push buttonsIf the selector switch is in position local control (I), use the push buttonsOPEN - STOP - CLOSE to operate the actuator locally.

    OPEN: Actuator runs in direction OPEN

    STOP: Actuator stops

    CLOSE: Actuator runs in direction CLOSE

    The operation commands OPEN - CLOSE can be used for control duringpush-to-run operation or in the self-retaining mode.

    In the push-to-run operation, the actuator runs as long as the push button ispressed.In the self-retaining mode, the actuator runs to the defined end position,unless another command has been received beforehand.For further information on the programming, refer to page33.

    Indication lightsThe 3 indication lights give the following signals (standard indication).

    Illuminated (green): Actuator is in end position OPEN

    Collective fault signal (red)

    Illuminated (yellow): Actuator is in end position CLOSED

    Collective fault signal:The collective fault signal (red indication light) will be activated if one of thefollowing events occurs:. Torque fault, i.e. the set torque (page24) was exceeded before reaching

    an end position.

    . Motor protection has tripped (refer to page49), i.e. the motor is overheated.. A phase failure (for 3-phase AC motors) has occurred.. Test PTC tripping deviceIndication lights are blinking:If the actuator is equipped with a blinker, the indication lights can be used asrunning indication.If the blinker transmitter is active (page33), the respective indication lightblinks during operation.

    20

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1with actuator controls AUMA MATIC AMExC 01.1 Operation instructions

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    21/64

    11. Opening the switch compartmentTo be able to carry out the following settings (up to and including clause18.), the switch compartment must be opened and, if installed, the indicatordisc must be removed.

    These settings are only valid for clockwise closing, i.e. driven shaft turnsclockwise to close the valve.

    When working in potentially explosive areas, observe theEuropean Standards EN 60079-14 Electrical Installations inHazardous Areas and EN 60079-17 Inspection and Mainte-nance of Electrical Installations in Hazardous Areas.Work on the electrical system or equipment must only becarried out by a skilled electrician himself or by speciallyinstructed personnel under the control and supervision ofsuch an electrician and in accordance with the applicableelectrical engineering rules.

    11.1 Removing the cover from the switch compartment

    Flameproof enclosure! Before opening, ensure that noexplosive gas and no voltage is present.

    . Remove 4 bolts and take off the cover at the switch compartment(figure23 or figure25).

    11.2 Pulling off the indicator disc (option)

    . If installed, pull off indicator disc (figure24). Open end wrench(approx. 14 mm) may be used as lever.

    21

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1Operation instructions with actuator controls AUMA MATIC AMExC 01.1

    Figure 23: Cover with indicator glass

    D S R

    W D R

    Figure 24: Pulling off the indicator disc

    Indicator disc

    Figure 25: Cover without indicator glass

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    22/64

    12. Setting the limit switching12.1 Setting end position CLOSED (black section)

    . Turn handwheel clockwise until valve is closed.. Turn handwheel back by approximately half a turn (overrun). During testrun check overrun and, if necessary, correct setting of the limit switching.. Press down and turn setting spindle A (figure26) with screw driver(5 mm) in direction of arrow, thereby observe pointer B.While a ratchet is felt and heard, the pointer B moves 90 every time.When pointer B is 90 from mark C, continue turning slowly. When pointerB has reached the mark C, stop turning and release setting spindle. If youoverride the tripping point inadvertently (ratchet is heard after the pointerhas snapped), continue turning the setting spindle in the same directionand repeat setting process.

    12.2 Setting end position OPEN (white section)

    . Turn handwheel counterclockwise until valve is open.. Turn handwheel back by approximately half a turn (overrun). During testrun check overrun and, if necessary, correct setting of the limit switching.. Press down and turn setting spindle D (figure26) with screw driver(5 mm) in direction of arrow, thereby observe pointer E.While a ratchet is felt and heard, the pointer E moves 90 every time.When pointer E is 90 from mark F, continue turning slowly.When pointer E has reached the mark F, stop turning and release settingspindle. If you override the tripping point inadvertently (ratchet is heardafter the pointer has snapped), continue turning the setting spindle in thesame direction and repeat setting process.

    12.3 Checking the limit switchesThe red test buttons T and P (figure26) are used for manual operation ofthe limit switches.

    . Turning T in direction of the arrow LSC (WSR) triggers limit switch CLOSED.The red indication light (fault) on the local controls is illuminated.. Turning P in direction of the arrow LSO (WL) triggers limit switch OPEN.The red indication light (fault) on the local controls is illuminated.. After checking the switches, the fault (red indication light) has to be resetusing the OPEN or CLOSE push buttons of the local controls for operationin the opposite direction.

    22

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1with actuator controls AUMA MATIC AMExC 01.1 Operation instructions

    Figure 26: Control unit

    A

    T

    B

    C

    D

    P

    E

    F

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    23/64

    13. Setting the DUO limit switching (option)Any application can be switched on or off via the two intermediate positionswitches.

    For setting, the switching point (intermediate position) must

    be approached from the same direction as afterwards inelectrical operation.

    13.1 Setting direction CLOSE (black section). Move valve to desired intermediate position.. Press down and turn setting spindle G (figure27) with screw driver(5 mm) in direction of arrow, while observing pointer H.While a ratchet is felt and heard, the pointer H moves 90 every time.When pointer H is 90 from mark C, continue turning slowly. When pointerH has reached the mark C, stop turning and release setting spindle. If youoverride the tripping point inadvertently (ratchet is heard after the pointerhas snapped), continue turning the setting spindle in the same directionand repeat setting process.

    13.2 Setting direction OPEN (white section). Move valve to desired intermediate position.. Press down and turn setting spindle K (figure27) with screw driver(5 mm) in direction of arrow, while observing pointer L.

    While a ratchet is felt and heard, the pointer L moves 90 every time.When pointer L is 90 from mark F, continue turning slowly. When pointerL has reached the mark F, stop turning and release setting spindle. If youoverride the tripping point inadvertently (ratchet is heard after the pointerhas snapped), continue turning the setting spindle in the same directionand repeat setting process.

    13.3 Checking the DUO limit switchesThe red test buttons T and P (figure27) are used for manual operation ofthe DUO limit switches.

    . Turning T in direction of the arrowTSC (DSR) triggers DUO limit switch CLOSED.The torque switch CLOSEDisactuated at the same time.

    . Turning P in direction of the arrow TSO (DL) triggers DUO limit switch OPEN.The torque switch OPENis actuated at the same time.. Afterchecking the switches, the fault (red indication light) has to be reset usingthe OPENor CLOSE push buttons of the local controls for operation in the oppo-site direction.

    23

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1Operation instructions with actuator controls AUMA MATIC AMExC 01.1

    Figure 27: Control unit

    G

    T

    H

    C

    K

    P

    L

    F

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    24/64

    14. Setting the torque switching14.1 Setting . The set torque must suit the valve!. This setting must only be changed with the consent of the

    valve manufacturer!

    .Loosen both lock screws O at the torque dial (figure28).. Turn torque dial P to set it to the required torque (1 da Nm = 10 Nm).Example:Figure 28 shows the following setting:3.5 da Nm = 35 Nm for direction CLOSE4.5 da Nm = 45 Nm for direction OPEN. Tighten lock screws O again

    . The torque switches can also be operated in manualoperation.. The torque switching acts as overload protection over fulltravel, also when stopping in the end positions by limitswitching.

    14.2 Checking the torque switchesThe red test buttons T and P (figure26) are used for manual operation ofthe torque switches:

    . Turning T in direction of the arrow TSC (DSR) triggers torque switchCLOSED.The red indication light (fault) on the local controls is illuminated.. Turning P in direction of the arrow TSO (DL) triggers torque switchOPEN.The red indication light (fault) on the local controls is illuminated.. If a DUO limit switching (optional) is installed in the actuator, the intermedi-ate position switches will be operated at the same time.. After checking the switches, the fault (red indication light) has to be resetusing the OPEN or CLOSE push buttons of the local controls for operationin the opposite direction.

    24

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1with actuator controls AUMA MATIC AMExC 01.1 Operation instructions

    Figure 28: Torque switching heads

    Setting CLOSED Setting OPEN

    O O

    P

    O

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    25/64

    15. Test runWork at the open actuator under voltage must only beperformed if it is assured that for the duration of the work there is no danger of explosion.

    15.1 Checking the direction of rotationThis check is only necessary for mounting on wall bracket.When the AUMA MATIC controls are mounted directly to the actuator, theautomatic phase correction ensures the correct direction of rotation, even ifthe phases are crossed over during electrical installation.

    . If provided, place indicator disc on shaft.The direction of rotation of the indicator disc (figure29) indicates thedirection of rotation of the output drive.. If there is no indicator disc, the direction of rotation can also be observedon the hollow shaft. For this purpose, remove screw plug (no. 27)(figure30).

    . Move actuator manually to intermediate position or to sufficient distancefrom end position.. Set selector switch to local control (I) (figure31).

    . Switch on the voltage supply.. Press push button CLOSE (figure32) and observe the directionof rotation:If the indicator disc turns counterclockwise, the direction of rotationis correct.

    If the direction of rotation is wrong, switch off immediately.Afterwards, correct phase sequence in the connecting cable fromthe wall bracket to the actuator and repeat test run.

    25

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1Operation instructions with actuator controls AUMA MATIC AMExC 01.1

    Figure 29: Indicator disc CLOSED OPEN

    Figure 30: Opening the hollow shaft

    27

    S1/S2

    Figure 31: Selector switch LOCAL

    Figure 32: Push button CLOSE Figure 33: Push button STOP

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    26/64

    15.2 Checking the setting of the limit switching. Set selector switch to position OFF (0) (figure34).

    The controls power supply is maintained in position OFF.

    . Move actuator manually into both end positions of the valve.. Check if limit switching is set correctly for both end positions. Herebyobserve that the appropriate switch is tripped in each end position and

    released again after the direction of rotation is changed. If this is not thecase, the limit switching must be set again.

    When limit switching is set correctly:. Set selector switch to local control (I) (figure31).. Perform test run at the local controls via push buttons OPEN - STOP -CLOSE.

    15.3 Checking the type of seatingThe valve manufacturer states whether switching off in the end positionsshould be by limit switch (limit seating) or torque switch (torque seating).. For checking the setting, refer to page33, subclause 20.2.

    15.4 Checking the PTC tripping device. Turn selector switch to position TEST (wiping) (figure35).If the PTC tripping device is working properly, the tripping of the motor pro-tection is signalled via the collective fault signal (refer to wiring diagram)and via the fault indication light on the local controls.

    . Turn selector switch to position RESET (wiping) (figure36):The fault signal is reset if the device is working properly.

    In case the selector switch position TEST does not initiate a fault signal, thewiring and the selector switch have to be checked by the AUMA service.

    If no other options (clauses 16. to 18.) require setting:. Close switch compartment (see page 31, clause 19.).26

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1with actuator controls AUMA MATIC AMExC 01.1 Operation instructions

    Figure 34: Selector switch LOCAL

    Figure 35: Selector switch TEST

    Figure 36: Selector switch RESET

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    27/64

    16. Setting the potentiometer (option) For remote indication

    . Move valve toend position CLOSED.. Turn potentiometer (E2) clockwise to the stop.End position CLOSED corresponds to 0 %, end position OPEN to 100 %.. Turn potentiometer (E2) slightly back.

    Due to the ratio of the reduction gearings for the positiontransmitter, the complete resistance range is not alwaysutilized for the whole travel. Therefore, an external possi-bility for adjustment (setting potentiometer) must beprovided.

    . Perform fine-tuning of the zero point at external setting potentiometer(for remote indication).

    27

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1Operation instructions with actuator controls AUMA MATIC AMExC 01.1

    Figure 37: Control unit

    E2

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    28/64

    17. Setting the electronic position transmitter RWG (option) For remote indication or external control

    After mounting the actuator on the valve, check setting and adjust, if neces-sary (refer to subclauses 17.1 or 17.2).

    The position transmitter board (figure38) is located under the cover plate(figure39).

    28

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1with actuator controls AUMA MATIC AMExC 01.1 Operation instructions

    Terminal plans KMS TP_ _ 4 / _ _ _

    3- or 4- wire system

    KMS TP _ 4 _ / _ _ _KMS TP _ 5 _ / _ _ _

    2-wire systemOutput current Ia 0 20 mA, 4 20 mA 4 20 mAPowersupply Uv

    24 V DC, 15 %smoothed

    14 V DC + (I x RB),max. 30 V

    Max. inputcurrent

    I 24 mA at 20 mAoutput current

    20 mA

    Max. load RB 600 W (Uv - 14 V) / 20 mA

    Table 3: Technical data RWG 4020

    Figure 38: Position transmitter board

    S1

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    29/64

    17.1 Setting 2-wire system 4 20 mA and 3- /4-wire system 0 20 mA

    . Connect voltage to electronic position transmitter.. Move valve toend position CLOSED.. Connect ammeter for 0 20 mA to measuring points (figure39).The circuit (external load) must be connected(observe max. load R B), or the appropriate poles at the termi-nals (refer to wiring diagram) must be linked, otherwise novalue can be measured.

    . Turn potentiometer (E2) clockwise to the stop.. Turn potentiometer (E2) slightly back.

    . Turn potentiometer 0 clockwise until output current starts to increase.. Turn potentiometer 0 back until the following value is reached:for 3- or 4-wire system: approx. 0.1 mAfor 2-wire system: approx. 4.1 mA.This ensures that the signal remains above the dead and live zero point.. Move valve to end position OPEN.. Set potentiometer max. to end value 20 mA.. Approach end position CLOSED again and check minimum value(0.1 mA or 4.1 mA). If necessary, correct the setting.

    If the maximum value cannot be reached, the selection of thereduction gearing must be checked.

    29

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1Operation instructions with actuator controls AUMA MATIC AMExC 01.1

    Figure 39

    0 (0/4 mA) max. (20 mA)

    Meas.point (+)0/4 20 mA

    Meas.point ()0/4 20 mA

    Cover plate E2

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    30/64

    17.2 Setting 3- / 4- wire system 4 20 mA

    . Connect voltage to electronic position transmitter.. Move valve toend position CLOSED.. Connect ammeter for 0 20 mA to measuring points (figure40).The circuit (external load) must be connected(observe max. load R B), or the appropriate poles at the termi-nals (refer to wiring diagram) must be linked, otherwise novalue can be measured.

    . Turn potentiometer (E2) clockwise to the stop.. Turn potentiometer (E2) slightly back.

    . Turn potentiometer 0 clockwise until output current starts to increase.. Turn back potentiometer 0 until a residual current of approx. 0.1 mA isreached.

    . Move valve to end position OPEN.. Set potentiometer max. to end value 16 mA.. Move valve to end position CLOSED.. Set potentiometer 0 from 0.1 mA to initial value 4 mA.This results in a simultaneous shift of the end value by 4 mA, so that therange is now 4 20 mA.. Approach both end positions again and check setting. If necessary, correctthe setting.

    If the maximum value cannot be reached, the selection of thereduction gearing must be checked.

    30

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1with actuator controls AUMA MATIC AMExC 01.1 Operation instructions

    Figure 40

    0 (0/4 mA) max. (20 mA)

    Meas. point (+)0/4 20 mA

    Meas. point ()0/4 20 mA

    Cover plate E2

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    31/64

    18. Setting the mechanical position indicator (option)

    . Place indicator disc on shaft.. Move valve toend position CLOSED.. Turn lower indicator disc (figure41) until symbol CLOSED is in align-ment with the mark on the cover (figure42).. Move actuator to end position OPEN.. Hold lower indicator disc CLOSED in position and turn upper disc withsymbol OPEN until it is in alignment with the mark on the cover.

    Indicator disc rotates approximately 180 to 230 at full travel from OPEN toCLOSED or vice versa. For this purpose, a suitable reduction gearing wasinstalled in our works.If the turns per stroke of the actuator are changed at a later date, the reduc-tion gearing may have to be exchanged.

    19. Closing the switch compartment

    . Clean sealing faces of housing and cover. Check whether O-ring is in good condition.. Apply a thin film of non-acidic grease to the sealing faces.. Preserve joint surfaces with an acid-free corrosion protection agent.Flameproof enclosure! Handle cover and housing parts withcare. Joint surfaces must not be damaged or soiled in any

    way. Do not jam cover during fitting.. Replace cover on switch compartment and fasten bolts evenly crosswise.Check the multi-turn actuator for damage to paint finish. Ifdamage to paint-finish has occurred after mounting, it has tobe touched up to avoid corrosion.

    31

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1Operation instructions with actuator controls AUMA MATIC AMExC 01.1

    Figure 41

    Indicator disc

    Figure 42

    Mark

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    32/64

    20. Actuator controls AUMA MATICDuring all work at the controls observe:

    Work at the open actuator under voltage must only beperformed if it is assured that for the duration of the work

    there is no danger of explosion.

    20.1 Functions of the diagnosis LEDs on the interface board (standard version)

    V14 is illuminated: Phase failure and/ or motor protection tripped.In combination with motor protection (PTC thermistor)(option):Reset by selector switch positionIII at local controls

    V15 is illuminated: Torque fault: Torque switch operated in mid-travelThe LEDs STOP, CLOSE, OPEN indicate the available control commands(only in selector switch position REMOTE).

    32

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1with actuator controls AUMA MATIC AMExC 01.1 Operation instructions

    Figure 43: Positions of the boards within the controls

    Timer board(option)

    Cover plateInterface board

    Logic boards

    Cover

    Positioner board(option)

    Figure 44: Cover plate on interface board

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    33/64

    20.2 Programming the logic board

    The type of seating limit or torque seating (switch S1-2 and switch S3-2,figure45) must be determined by the valve manufacturer.

    . Set desired programming according to table4 at the switch S2-2.

    33

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1Operation instructions with actuator controls AUMA MATIC AMExC 01.1

    Position 1:Limitseatingin end position OPEN

    Position 2:Torqueseatingin end position OPEN

    Position 1:Limitseatingin end position CLOSED

    Position 2:Torqueseatingin end position CLOSED

    S3-2

    S1-2

    S2-2

    Figure 45: Logic board A2

    DIP switch S2-2 Programming(ON = pressed)

    Direction CLOSE Direction OPEN

    Self-retaining REMOTE

    Push-to-run operation REMOTE

    Self-retaining LOCAL

    Push-to-run operation LOCAL

    Blinker transmitter (option)activated deactivated

    Torque fault: Torque switch trip-ping (in mid-travel) contained incollective fault signal

    included not included

    Table 4

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    34/64

    20.3 EMERGENCY - OPEN and EMERGENCY - CLOSE signal (option)

    (5th digit in wiring diagram MSP C, D, or P)

    When an EMERGENCY run command is given, the actuator operates the

    valve to the predetermined end position (effective in all three selector switchpositions:LOCAL, OFF, REMOTE).

    . The input at terminal XK 1 (refer to wiring diagram) must be connected toan NC contact (closed circuit principle) at + 24 V DC.. If EMERGENCY - OPEN or EMERGENCY - CLOSE signal is generallynot desired:Take off cover plate and disconnect links B1 (for EMERGENCY - CLOSE)and B2 (for EMERGENCY - OPEN).

    34

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1with actuator controls AUMA MATIC AMExC 01.1 Operation instructions

    Figure 46: Cover plate for EMERGENCY - OPEN or EMERGENCY - CLOSE option

    Links:B1(EMERGENCY-CLOSE)B2(EMERGENCY-OPEN)

    LED forEMERGENCY run command

    B2B1

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    35/64

    21. Electronic positioner (option)21.1 Technical data

    21.2 SettingThe positioner in the actuator controls AUMA MATIC is programmedaccording to the purchase order details and is set together with the actuatorprior to delivery.Due to peculiarities of the regulating system not known beforehand, a read- justment may become necessary. Before adjusting the positioner, the pro-gramming of the positioner should be checked.

    . Check programming of the logic board according to subclause20.2.

    The self-retaining REMOTE function (see table 4) must be

    switched off in conjunction with the positioner.. Take off cover plate (figure47) and carry out required programming atpositioner board (figure48) according to tables6 and 7.

    Prior to setting, it must be ensured that the circuit for theposition feedback E2 (see wiring diagram) is closed(measuring device or link). In case of missing signal E2, theLED (V10) E1/E2 < 4 mA (figure47) is illuminated and thepositioner shows no reaction.

    35

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1Operation instructions with actuator controls AUMA MATIC AMExC 01.1

    Command signal (input signal E1, set value) 0/4 20 mA (option: 0 5 V)Feedback (input signal E2, actual value) 0/4 20 mA (option: 0 5 V)Sensitivity (dead band) E (P9) 0.5 % 2.5 %Fine tuning Sens (P7)(useful for output speeds < 16 rpm only) min. 0.25 %

    Pause time t-off (P10) 0.5 10 sInput resistance 250 OhmModulating duty with stepping mode (not required for modulating setting):Running time t-on (P8)effective until error is 25 %; then set value isautomatically reduced by 3.

    0.5 15 s

    Table 5: Technical data for positioner

    Figure 47: Cover plate positioner

    V10 (red)

    P10

    P8

    Label with signal indication(in our example:E1 = 4 20 mA, E2 = 4 20 mA)

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    36/64

    21.2.1 Setting type of signalThe signal type (current/ voltage signal) of nominal value E1 and actualvalue E2 is set in the factory and marked with a label on the cover plate ofthe positioner (refer to figure47).If the setting is subject to subsequent change, the marking also has to bechanged. Furthermore, the wiring diagram indicated on the name plate ofthe actuator controls also changes (see page 56).

    36

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1with actuator controls AUMA MATIC AMExC 01.1 Operation instructions

    Figure 48: Positioner board A7

    V28V27V18V10

    P10MP4()MP3(+)MP2(+)MP1()

    S1-7

    P9 (E)P7 (Sens)P3 (0)P4 (max)

    S2-7S3-7

    E1{E2{

    Meas.points:

    ProgrammingCommand signal

    Setpoint E1Feedback

    Actual value E21)via DIP switch S1-7

    (see figure 48)4 20 mA0 20 mA

    4 20 mA0 20 mA

    4 20 mA0 20 mA 0 5 V

    0 5 V 4 20 mA0 20 mA

    0 5 V 0 5 V

    0 10 V 4 20 mA0 20 mA

    0 10 V 0 5 V

    1) Signals for internal feedback:0/4 20 mA from electronic position transmitteror 0 5 V from precision potentiometer 5 k

    Table 6: Possible settings

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    37/64

    21.2.2 Setting actuator behaviour on loss of signal

    In case of a loss of signal of nominal value E1 or actual value E2, the reac-tion of the actuator can be programmed via the switch S2-7. The completerange of choices, however, is only available with signals 4 20 mA.

    The following reactions are possible:Fail as is:Actuator stops immediately and remains in this position.Fail closeActuator moves the valve to the end position CLOSED.Fail open:Actuator moves the valve to the end position OPEN.

    37

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1Operation instructions with actuator controls AUMA MATIC AMExC 01.1

    Behaviour on loss of signal of Prerequisite 1) Programming

    E1 E2 Command signalSetpoint E1Feedback

    Actual value E22)via DIP switch S2-7

    (see figure 48)

    fail as is 4 20 mA 4 20 mA

    fail close4 20 mA 4 20 mA

    0 20 mA0 5 V 4 20 mA

    fail open4 20 mA 4 20 mA

    4 20 mA 0 20 mA0 5 V

    fail as is fail open 4 20 mA 0 5 V

    fail close fail open

    4 20 mA0 20 mA 0 5 V

    0 20 mA 4 20 mA

    0 20 mA0 5 V0 10 V

    0 20 mA0 5 V

    fail close fail as is0 20 mA 4 20 mA

    0 10 V 4 20 mA

    1) During loss of signal, signals from 0 20 mA and 0 5 V may be misinterpreted since E1 or E2 (without any fault) can alsobe < 4 mA (end position CLOSED = 0 mA or 0 V) when working properly.

    2) Signals for internal feedback:0/4 20 mA from electronic position transmitter or 0 5 V from precision potentiometer 5 k

    Table 7: Possible settings (recommended settings are shaded in grey)

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    38/64

    21.3 Positioner adjustment for end position CLOSED (standard version)

    Before beginning the setting of the positioner, it has to beensured that the limit and torque switching of the actuatoras well as the feedback have been set (clauses 16. and 17.).

    . Set selector switch (local controls) to position LOCAL.. Move multi-turn actuator by pressing push button toend position CLOSED.. Supply nominal value E1 of 0 or 4 mA (see wiring diagram).. Turn potentiometer t-off (P10) counterclockwise to the stop(figure49).

    Missing signals E1/ E2 or wrong polarity are indicated byLED (V10) E1/E2 < 4 mA" (figures47 or 49)

    . Connect voltmeter to measuring points MP3 and MP4 (figure49) for mea-suring the nominal value (0 5 V).For a nominal value E1 of 0 mA, the voltmeter shows 0 V.For a nominal value E1 of 4 mA, the voltmeter shows 1 V.In case nominal value (0 V or 1 V) is not correct:Correct nominal value signal in control room.. Connect voltmeter to measuring points MP2 and MP1 for measuring theactual value signal.For an actual value E2 of 0 mA, the voltmeter shows 0 V.For an actual value E2 of 4 mA, the voltmeter shows 1 V.If measured value is not correct:Adjust position feedback according to clause16. and 17. and repeatpositioner adjustment.

    38

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1with actuator controls AUMA MATIC AMExC 01.1 Operation instructions

    I f

    Possible LED display:(refer to figures49 and 50)

    T h e n

    Required setting in end position CLOSED:(refer to figures49 and 50)

    the LEDs are not illuminated Turn potentiometer 0 (P3) slightly clockwise untilLED (V27 yellow) is illuminated

    LED (V28 green) isilluminated

    Turn potentiometer 0 (P3) slightly clockwise untilLED (V28 green) is no longer illuminated andLED (V27 yellow) is illuminated

    LED (V27 yellow)is illuminated

    Turn potentiometer 0 (P3) counterclockwise untilLED (V27 yellow) is no longer illuminated.Then turn potentiometer 0 (P3) slightly clockwise untilLED (V27 yellow) is illuminated

    Table 8

    Figure 49: Positioner board A7

    V28V27V18V10

    P10MP4()MP3(+)MP2(+)MP1()

    S1-7

    P9 (E)P7 (Sens)P3 (0)P4 (max)

    S2-7S3-7

    E1{E2{

    Meas.points:

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    39/64

    21.4 Positioner adjustment for end position OPEN (standard version)

    . Run multi-turn actuator by pressing push button (local controls) toendposition OPEN.. Connect voltmeter to measuring points MP2 and MP1 for measuring theactual value E2:When position feedback is set correctly, the voltmeter shows 5 V.If measured value is not correct:Adjust position feedback according to clause16. and 17. and repeatpositioner adjustment.. Connect max. command signal (nominal value E1) = 20 mA.. Connect voltmeter to measuring points MP4 and MP3 for measuring thenominal value E1:For a nominal value of 20 mA, the voltmeter shows 5 V.If measured value is not 5 V:Check the externally supplied command signal E1.

    21.5 Setting the sensitivity . Set selector switch at the local controls to position REMOTE.. Set command signal E1 according to label on cover plate (see figure50).The sensitivity (D E / dead band) is set to maximum value (2.5 %) in thefactory.. The deadband can be increased by turning the potentiometer D E (P9)clockwise. Left stop = small dead band (= high sensitivity). For a precisesetting of the dead band, a set point device with setting options in the 0.1mA range is required.. A better sensitivity (D Emin= 0.25 %) can be achieved by turning the potenti-ometer P7 (sens) clockwise.

    When setting D E, the following must be observed:If the number of starts is too high, this will lead to unneces-sary wear at the valve and actuator. Therefore the maximumpossible dead band acceptable for the process must be set.

    To prevent exceeding the max. permissible number of starts (refer to Techni-cal data sheets for modulating actuators) in extreme cases, a pause timebetween 0.5 s (left stop) and 10s (right stop) may be set with the potentio-meter t-off (P10).

    39

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1Operation instructions with actuator controls AUMA MATIC AMExC 01.1

    I f

    LED display:(refer to figures49 and 50)

    T h e n

    Required setting in end position OPEN:(refer to figures49 and 50)

    the LEDs are not illuminated Turn potentiometer max. (P4) slightly counterclockwise untilLED (V28 green) is illuminated

    LED (V28 green)is illuminated

    Turn potentiometer max (P4) clockwise until LED (V28 green)is no longer illuminated.Then turn potentiometer max (P4) slightly counterclockwise untilLED (V28 green) is illuminated

    LED (V27 yellow)is illuminated

    Turn potentiometer max (P4) slightly counterclockwise untilLED (V27 yellow) is no longer illuminated andLED (V28 green) is illuminated

    Table 9

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    40/6440

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1with actuator controls AUMA MATIC AMExC 01.1 Operation instructions

    Figure 50: Cover plate for positioner

    Label with signal indication(in our example: E1 = 4 20 mA, E2 = 4 20 mA)

    V28 (green)V27(yellow)V18 (red)V10 (red)

    P10

    Figure 51: Cover plate for positioner A7

    V28V27V18V10

    P10MP4()MP3(+)MP2(+)MP1()

    S1-7

    P9 (E)P7 (Sens)P3 (0)P4 (max)

    S2-7S3-7

    E1{E2{

    Meas.points:

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    41/64

    21.6 Positioner adjustment for end position OPEN (inverse operation)

    In standard version the maximum input signal (E1 = 20 mA) results in opera-tion to end position OPEN.. By switching the code switch S3-7 (figure52) to position 1, an inversion

    of this signal definition (inverse operation) can be achieved.. In case an RWG (option) is installed, the connections 7 (red) and 5 (black)on the positioner board (figure38) of the actuator have to be exchanged.. In case a potentiometer is installed, (option) the connections 21 (red) and22 (black) at the potentiometer must be interchanged.

    Before beginning the setting of the positioner, it has to beensured that the limit and torque switching of the actuatoras well as the feedback have been set (clauses 16. and 17.).

    . Set selector switch (local controls) to position LOCAL.. Run actuator with push button toend position OPEN .. Supply nominal value E1 of 0 or 4 mA (see wiring diagram).

    . Turn potentiometer t-off (P10) counterclockwise to the stop(figure52).

    Missing signals E1/ E2 or wrong polarity are indicated byLED (V10) E1/E2 < 4 mA" (figures50 or 52)

    . Connect voltmeter to measuring points MP3 and MP4 (figure52) for mea-suring the nominal value (0 5 V).For a nominal value E1 of 0 mA, the voltmeter shows 0 V.For a nominal value E1 of 4 mA, the voltmeter shows 1 V.In case nominal value (0 V or 1 V) is not correct:Correct nominal value signal in control room.. Connect voltmeter to measuring points MP2 and MP1 for measuring theactual value signal.For an actual value E2 of 0 mA, the voltmeter shows 0 V.For an actual value E2 of 4 mA, the voltmeter shows 1 V.Adjust position feedback according to clause16. and 17. and repeatpositioner adjustment.

    41

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1Operation instructions with actuator controls AUMA MATIC AMExC 01.1

    I f

    Possible LED display:(refer to figures50 and 52)

    T h e n

    Required setting in end position OPEN:(refer to figures50 and 52)

    the LEDs are not illuminated Turn potentiometer 0 (P3) slightly clockwise untilLED (V28 green) is illuminated

    LED (V27 yellow)is illuminated

    Turn potentiometer 0 (P3) slightly clockwise untilLED (V27 yellow) is no longer illuminated andLED (V28 green) is illuminated

    LED (V28 green)is illuminated

    Turn potentiometer 0 (P3) counterclockwise untilLED (V28 green) is no longer illuminated.Then turn potentiometer 0 (P3) slightly clockwise untilLED (V27 yellow) is illuminated

    Table 10

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    42/64

    21.7 Positioner adjustment end position CLOSED (inverse operation)

    . Run actuator with push button (local controls) toend positionCLOSED.. Connect voltmeter to measuring points MP2 and MP1 for measuring theactual value E2:When position feedback is set correctly, the voltmeter shows 5 V.If measured value is not correct:Adjust position feedback according to clauses16. and 17. and repeatpositioner adjustment.. Connect max. command signal (nominal value E1) = 20 mA.. Connect voltmeter to measuring points MP4 and MP3 for measuring thenominal value E1:For a nominal value of 20 mA, the voltmeter shows 5 V.If measured value is not 5 V:Check the externally supplied command signal E1.

    42

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1with actuator controls AUMA MATIC AMExC 01.1 Operation instructions

    I f

    LED display:(refer to figures50 and 52)

    T h e n

    Required setting in end position CLOSED:(refer to figures50 and 52)

    the LEDs are not illuminated Turn potentiometer max (P4) slightly counterclockwise untilLED (V27 yellow) is illuminated

    LED (V27 yellow)is illuminated

    Turn potentiometer max (P4) clockwise until LED (V27 yellow)is no longer illuminated.Then turn potentiometer max (P4) slightly counterclockwise untilLED (V27 yellow) is illuminated.

    LED (V28 green)is illuminated

    Turn potentiometer max (P4) slightly counterclockwise until theLED (V28 green) is no longer illuminated andLED (V27 yellow) is illuminated.

    Table 11

    Figure 52: Positioner board A7

    V28V27V18V10

    P10MP4()MP3(+)MP2(+)MP1()

    S1-7

    P9 (E)P7 (Sens)P3 (0)P4 (max)

    S2-7S3-7

    Meas.points:

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    43/64

    21.8 Positioner in Split Range version (option)

    For Split Range, a modified version of the positioner is used. The standardversion is not suitable for Split Range operation.Split Range operation is only possible with the position transmitter RWG.

    21.8.1 Split Range: description of functions

    In Split Range operation, a setpoint is shared by up to four positioners. Atypical example is a pipeline with a bypass. The actuator mounted on thebypass reacts in the lower range (0 10 mA), the actuator on the mainvalve in the upper range (10 20 mA). Other values such as 4 12 mA and12 20 mA can also be set.

    21.8.2 ProgrammingDIP 5 at code switch S1-7 must always be in position ON for Split Range

    version.

    The further programming of the positioner via the code switches S2-7 andS3-7 can be made in the same way as during normal operation.

    21.8.3 Positioner adjustment for Split Range (see also example further down the page)

    . Supply the specified minimum command signal (nominal value E1) for thepositioner and check by measuring with voltmeter at the measuring pointsMP3 and MP4 (figure53).. Connect voltmeter between measuring point M3 and measuring point MP1.Calculate setting value:Initial value = E 1min [in Ampere] x 250 OhmSet initial value with potentiometer P5.. Supply specified maximum command signal (nominal value E1) and checkby measuring at the measuring points MP3 and MP4.. Connect voltmeter between measuring point M9 and measuring point MP1.Set potentiometer P6 to 5 V.. Supply input signal E1 from minimum to maximum value and check the setrange 0 5 V at measuring point M9. If necessary, readjust with P5 or P6.. Apply the same procedure to the second actuators positioner and setaccording to the specified nominal values E1.. After setting the Split Range operation, perform further readjustment asdescribed on page 38.

    43

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1Operation instructions with actuator controls AUMA MATIC AMExC 01.1

    ProgrammingCommand signal

    Setpoint E1Feedback1)

    Actual value E2via DIP switch S1-7

    (see figure 53)4 12/12 20 mA0 10/10 20 mA

    4 20 mA0 20 mA

    4 12/12 20 mA0 10/10 20 mA 0 5 V

    1) Signals for internal feedback:0/4 20 mA from electronic position transmitter

    or 0 5 V from precision potentiometer 5 k

    Table 12: Possible settings for Split Range operation

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    44/64

    Example:Two actuators are to be operated in Split Range version. Actuator 1 must bein position CLOSED with a nominal value signal E1 of 0 mA and in positionOPEN with a signal of 10 mA.Actuator 2 must be in position CLOSED with a nominal value signal of10 mA and in position OPEN with a signal of 20 mA.

    . Positioner actuator 1:Supply E1 = 0 mA, set with P5 = 0 V at M3 (measured against MP1),supply E1 = 10 mA, set with P6 = 5V at M9 (measured against MP1).. Positioner actuator 2:Supply E1 = 10 mA, set with P5 = 0 V at M3 (measured against MP1),supply E1 = 20 mA, set with P6 = 5V at M9 (measured against MP1).. Perform adjustments and settings for E2, etc. Afterwards the nominalvalue E1 can be transmitted through both actuators (connected in series).When operating within range E1 = 0 10 mA, actuator 1 moves, actuator2 remains in end position CLOSED. When operating within rangeE1 = 10 20 mA, actuator 2 moves, actuator 1 remains in end positionOPEN.

    44

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1with actuator controls AUMA MATIC AMExC 01.1 Operation instructions

    Figure 53: Positioner board A7, Split Range version

    Meas.points

    Meas.pointsE1{E2{

    P9 (E)P7 (Sens)P3 (0)P4 (max)

    P6P5

    S3-7

    S2-7

    S1-7

    V10 (red)

    P10

    V18 (red)V27 (yellow)V28 (green)

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    45/64

    22. Timer (option)The timer board is used to increase the operating time for the entire or anyportion of the valve travel.

    Example:

    In order to avoid water hammer in long pipelines, stepping mode can bechosen for any part of the travel.

    . Instead of the interface board the timer is installed in the actuator controlsAUMA MATIC.. Electronic timer is not possible in combination with positioner.

    22.1 Functions of the diagnosis LEDs (timer)

    V14 is illuminated: Phase failure and/ or motor protection tripped, reset byselector switch positionIII at local controls.

    V15 is illuminated: Torque fault: Tripping torque was exceeded beforereaching the end position.

    V21 is illuminated: Stepping mode in direction CLOSE is switched on.V22 is illuminated: Stepping mode in direction OPEN is switched on.

    45

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1Operation instructions with actuator controls AUMA MATIC AMExC 01.1

    Figure 54: Cover plate for timer A1.6

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    46/64

    22.2 Setting start and end of stepping mode via DUO limit switching (option)

    Start and end of stepping mode can also be set via external switches(use potential-free contacts).

    Direction OPEN, first normal operation then stepping mode. Run valve in direction OPEN to the desired start of stepping mode.. Press down and turn setting spindle G (figure55) with screw driver(5 mm) in direction of arrow, thereby observe LED V22 (figure54).Start of stepping mode in direction OFF is set correctly if the LED changesfrom off to on (see sketch on the left).

    Direction CLOSE, first normal operation then stepping mode. Run valve in direction CLOSE to the desired start of stepping mode.. Press down and turn setting spindle K (figure55) with screw driver(5 mm) in direction of arrow, thereby observe LED V21 (figure54).

    Start of stepping mode in direction CLOSE is set correctly if the LEDchanges from off to on (see sketch on the left).

    Direction OPEN, first stepping mode then normal operation. Run valve in direction OPEN to the desired end of stepping mode.. Press down and turn setting spindle G (figure55) with screw driver(5 mm) in direction of arrow, thereby observe LED V22 (figure54).

    End of stepping mode is correctly set if the LED changes from on to off(see sketch on the left).

    Direction CLOSE, first stepping mode then normal operation. Run valve in direction CLOSE to the desired end of stepping mode.. Press down and turn setting spindle K (figure55) with screw driver(5 mm) in direction of arrow, thereby observe LED V21 (figure54).End of stepping mode is correctly set if the LED changes from on to off(see sketch on the left).

    46

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1with actuator controls AUMA MATIC AMExC 01.1 Operation instructions

    V 22 off V22 on

    normal operation stepping

    Start stepping mode OPEN

    V 21 on V21 off

    stepping normal operation

    Start stepping mode CLOSEDFigure 55: Control unit

    G K

    V 22 on V22 off

    stepping normal operation

    End stepping mode OPEN

    V 21 off V21 on

    normal operation stepping

    End stepping mode CLOSED

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    47/64

    22.3 Setting ON and OFF times

    ON and OFF times can be set independently of each other between 1 30seconds at the 4 potentiometers R10 to R13.

    Clockwise rotation: Time extensionCounterclockwise rotation: Time reduction

    R10 (t-off) : OFF time in direction OPEN

    R11 (t-on) : Running time in direction OPEN

    R12 (t-off) : OFF time in direction CLOSE

    R13 (t-on) : Running time in direction CLOSE

    47

    Multi-turn actuators SAExC 07.1 SAExC 16.1/ SARExC 07.1 SARExC 16.1Operation instructions with actuator controls AUMA MATIC AMExC 01.1

    Figure 56: Cover plate for timer A1.6 R 10R 11

    R 12R 13

  • 7/27/2019 ba_sarexc1_amexc1_en.pdf

    48/64

    23. Fuses. Flameproof enclosure! Before opening, ensure that no

    explosive gas and no voltage is present.. When replacing fuses, only fuses according to table 13may be used.

    23.1 Fuses within the actuator controls

    Fuses (figures 58 and 57) are accessible after removal of the local controlcover.

    F1/F2: Primary fuses on power supply unitF3: Internal 24 V DC supply, RWG, logic boardF4: Internal 24 V AC supply (optional: 115 V AC);

    Heater, tripping device for PTC thermistors,control reversing contactors. After replacing the fuses, screw local controls back on again.

    . Carefully lead cables back into the housing to preventthem from jamming.. Flameproof enclosure! Handle cover and housing partswith care. Joint surfaces must not be dam