Balanced Ventilation:Heat and Energy Recovery
Michael LeBeau | Conservation Technologies | Duluth, MN
Efficient Fresh Air forLow Energy Buildings
Better Buildings By Design
Conference 2010
Burlington, Vermont February 11, 2010
•Efficiency Vermont is a Registered Provider with The American Institute of Architects Continuing Education Systems. Creditearned on completion of this program will be reported to CES Records for AIA members. Certificates of Completion for non-AIA members are available on request.
Better Buildings By Design 2010
This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any material of construction or any method or manner of handling, using, distributing, or dealing in any material or product. Questions related to specific materials, methods, and services will be addressed at the conclusion of this presentation.
Learning Objectives
• At the end of this program, participants will be able to:– Discover why and when to choose heat or
energy recovery ventilation.– Identify how these technologies fit into a
systems approach to building. – Understand latest advances in technology and
resulting equipment-availability. – Implement balancing and verification
strategies.
4
5
6
Different kind of air
• Ventilation
• Combustion
• Makeup
7
Ventilation Services
• The removal of polluted air from a building and its replacement with fresh outdoor air.
– Pollutant / moisture source focused exhaust best.
– Distribution of fresh air into all habitable rooms.
– Controlled airflow based on need.
8
9
An Integrated Approach to Building Systems
• Tight buildings for ventilation control• Quiet efficient mechanical ventilation• Safe combustion appliances• Whole building pressure management• Planned fresh air paths
10
11
The Different Roles of Mechanical Ventilation
• Indoor relative humidity management.• Internally generated pollutant control.• Delivery of fresh, outside air to living
spaces.• To accomplish the above quietly and
efficiently.
12
Types of ventilation systems
• Exhaust driven– Removing air from a building using fan power.– Usually not planning the replacement air path.
• Supply driven– Bringing outside air into a building with fans.– Letting it find it’s way out or providing a way.
• Balanced– Powered airflow both in and out at roughly the
same rate.
13
All ventilation is balanced
14
15
16
17
18
19
Mechanically Balanced Options
• Some combination of exhaust and supply options.
• HRV / ERV• Most effective as we succeed in our efforts
to build more airtight buildings.• Heat / energy recovery increasingly cost
effective as energy costs continue to climb.
20
Fully Ducted
21
Ducted ExhaustFresh to Furnace
22
HRV or ERV?
• ERV best for cooling dominated climates.• ERV often not recommended below 25F.?• Total energy recovery?• HRV needs drain.• HRV core more durable.
23
Equipment Ratings
• Home Ventilating Institute• HVI.org• Certified Product Directory
– Section 1 - Home Ventilating Fans– Section 2 - Static Vents– Section 3 - HRV’s and ERV’s
24
Design Considerations• Ventilation needs are carefully assessed.• Ventilation strategy chosen from options.• Physical space limitations of building.• Climate driven needs factored in.• Operating costs (electrical and added heating
/ cooling loads) evaluated.• Installation cost.• Accessibility for maintenance.• Future upgrade options and associated costs.
25
Installation Priorities
• Design ventilation rate actually achieved.• Quiet and comfortable delivery of services.• Understandable and effective controls.• Effective exhaust and supply distribution.• Durable equipment, materials and methods
used.• Integration with other building systems.• Doesn’t compromise building envelope.
26
Maintenance Provisions
• Simple and obvious accessibility.• Durable maintenance features.• End user documentation and orientation.• Maintenance service options offered.• Maintenance reminders are ideal.
27
System Sizing and Design
• Start with .35 ACH continuous• Factor in site, # of occupants etc• Plan on higher rates for first year• Consider potential usage of building as well
as current• Separate kitchen range exhaust• Choose from existing equipment choices
28
Installation Requirements• Space for HRV
– Proximity to exterior hoods• Access to fresh air• Minimize flex duct use
– Drain nearby– Minimum 60 degree room– Noise concerns– Power
29
System Requirements (cont)
• Space for duct runs– Separate wall stack per room– Room for adequate branch and trunk lines and
fittings• Duct joints sealed for proper distribution• Ducts outside of envelope insulated to R8• Controls and wire runs
30
Bath (-)
Bedroom (+)
Kitchen(-)
Living Room(+)
Master Suite (+)
Bath(-)
Closet
Closet
F
F
F
Fireplace F
EE
E
Fully Ducted Whole House Ventilation
(Building neutral relative to outside)
Clo
set
31
32
33
Fully Ducted System
34
High Efficiency HRV
35
North American Advances
• ECM motors finally making an appearance.• Higher recovery efficiencies in ERV’s and
HRV’s
36
88% Heat Recovery34 watts at 66 cfm95 watts at 150 cfm
37
Defrost and equipment issues
• Using solar and internal gains to defrost or:• Using electrical energy to defrost.• Need to take a closer look at U.S. heat
recovery standards being discounted.
38
The Physical Realities
• Space issues• Conflicts with other mechanical systems• Retro-fit options• Quality control• Available equipment options• Cost
39
40
41
42
7” Trunk and 6” Branch Lines
43
6” oval wall stacks
44
Stackhead box for round grille
45
Exhaust duct extended in soffit
46
Branch lines joining trunk in floor trusses
47
Sealed joints and fittings
48
Properly sized, smooth ducts
49
Exterior hoods with adequate opening for minimum restriction
50
51
System Durability
• Ventilation fans need to be able to run continuously for years.
• Ducts, especially inaccessible ones, need to be durable, airtight and, ideally, cleanable.
• Filter housings should be able to take years of regular maintenance.
• Grilles should be cleanable.• Don’t sacrifice long term durability for short term
upfront cost savings.
52
Maintenance
• Provide simple, understandable and obvious maintenance features.
• Educate end user or facility staff on maintenance needs, process and schedule.
• Offer maintenance services.• Automatic maintenance reminders are very
effective.
53
Integration needs and opportunities
• Space needs – work with designers to dedicate space for equipment, ducts, exterior hoods and controls.
• Resolve structural and envelope penetrations created by system installation.
• Coordinate installation details with other trades – avoid conflicts and backtracking.
54
Measure air flows and balance
• Air flows into and out of the house should be within 10% of balanced
• Excess fresh air flow will cause core frosting in cold weather
• Excess exhaust air flow will contribute to depressurization of house
• Measure air flows with dry, frost free core and clean filters
57
Exhaust intakes will collect debris and need to be cleanable
58
Fresh air spills out from behind this indirect lighting fixture
59
An Example of a Central Ventilation Control
- Intermittent- Low speed - High speed- Dehumidistat- Maintenance
reminder
60
High Speed Override Options
• Continuous low speed operation• Manual override at wall control• Touch pad switches (20/40/60 min.)• Crank timers• Dehumidistat
61
High Speed Override Switch
62
Make-up Air Modifications
• An HRV / ERV ducting can be tapped to provide make up air for exhaust devices.
• Diversion of exhaust air back indoors using motorized dampers and current sensors.
• Limited to airflow capacity of ventilator.• Takes advantage of residual heat in exhaust
air and existing blower and ducts.
63
Maintenance RequirementsEvery 2-3 Months
• Clean filters • Check intake hood for blockage• Check control operation
64
Maintenance RequirementsAnnually
• Clean core and interior • Inspect blower motors and defrost dampers• Flush condensate drain hose• Check blowers for caking• Clean exhaust grilles as needed• Maintenance contract
65
Homeowner Orientation
• Proper use of controls• Cleaning
– Filters– Hoods– Ventilator
• Documentation and manuals• Contact numbers• Optional maintenance contract
66
Fan Energy
• Fairly small electrical load but runs often or continuously.
• Significant aggregate savings possible with more efficient motors and strategies.
• ECM motors, smart controls and better duct design are main opportunities in North America.
• Natural and hybrid designs being developed elsewhere.
67
Looking Ahead
• Consider future ventilation needs when designing ventilation for new buildings. Especially in difficult or expensive to upgrade components like ducts.
• Assume greatly increased energy costs in the near future when weighing options.
68
Developments Elsewhere
• Natural and hybrid ventilation strategies growing in popularity in Europe and elsewhere.
• Very efficient fans being developed with smart controllers to assist natural stack and wind forces harnessed to provide ventilation.
• Integrated heat / energy recovery features to minimize energy penalties of ventilation.
69
Norwegian hybrid vent research
70
Natural ventilation w/ heat recovery near London (BedZed)
71
72
Passive House Applications
• Ventilation Heat Distribution• Integrated Solar Thermal• Earth Coupled Outside Air Tempering
73
Solar Thermal w/ Gas Backup
74
Fresh air tempering/ Post core heating
75
76
Water to air heat exchanger
77
78
Pex tubing buried in excavation
79
80
81
82
Make-up air via HRV Exhaust Diversion