Avaya RS9 Uninterruptible Power Systems(9–18 kVA, 9-Slot Models)

Site Preparation,Installation and Operator’s Manual

www.avayaups.com

Page 2: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot
Page 3: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Avaya RS9 Uninterruptible Power Systems(9–18 kVA, 9-Slot Models)

Site Preparation,Installation and Operator’s Manual

www.avayaups.com

Page 4: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Requesting a Declaration of ConformityUnits that are labeled with a CE mark comply with the following harmonized standards and EU directives:

S Harmonized Standards: EN 50091-1-1 and EN 50091-2; IEC 950 Third Edition

S EU Directives: 73/23/EEC, Council Directive on equipment designed for use within certain voltage limits93/68/EEC, Amending Directive 73/23/EEC89/336/EEC, Council Directive relating to electromagnetic compatibility92/31/EEC, Amending Directive 89/336/EEC relating to EMC

The EC Declaration of Conformity is available upon request for products with a CE mark. For copies of the ECDeclaration of Conformity, contact:

Powerware CorporationKoskelontie 13FIN-02920 EspooFinlandPhone: +358-9-452 661Fax: +358-9-452 665 68

Class A EMC StatementsFCC Part 15NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant topart 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference whenthe equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequencyenergy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radiocommunications. Operation of this equipment in a residential area is likely to cause harmful interference in which casethe user will be required to correct the interference at his own expense.

ICES-003This Class A Interference Causing Equipment meets all requirements of the Canadian Interference Causing EquipmentRegulations ICES-003.

Cet appareil numérique de la classe A respecte toutes les exigences du Reglement sur le matériel brouilleur du Canada.

EN 50091-2Some configurations are classified under EN 50091-2 as “Class-A UPS for Unrestricted Sales Distribution.” For theseconfigurations, the following applies:

WARNING This is a Class A-UPS Product. In a domestic environment, this product may cause radio interference, inwhich case, the user may be required to take additional measures.

VCCI Notice

Avaya and the Avaya logo are trademarks of Avaya Inc. and may be registered in certain jurisdictions.ConnectUPS is a trademark of Powerware Corporation.

ECopyright 2004 Avaya Inc. All rights reserved. No part of this document may be reproduced in any way without theexpress written approval of Avaya Inc.

Page 5: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

iAvayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

TABLE OF CONTENTS

1 Introduction 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Power Modules 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Battery Configurations 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Battery Charger Modules 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Safety Warnings 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Physical Features 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2 Installation Setup 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Equipment Clearances 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Location Requirements 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .UPS Setup 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Moving the Cabinets 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3 Electrical Installation 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Input Current Ratings 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .UPS Installation 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .System Wiring Diagram 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4 Battery Cabinet Installation 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5 UPS Startup 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Power and Battery Module Installation 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .UPS Startup 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Initial Startup Parameters 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6 Operation 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Turning the UPS On 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Removing Input Power 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Front Panel Display 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Using the Front Panel Display 34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Parameters 36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Changing Parameter Settings 36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Reading the Avaya RS9 System Logs 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Inverter Log 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Alarm Log 38. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Menu Map 39. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 6: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Table of Contents

ii Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

7 Communication 41. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .LanSafe Power Management Software 41. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Optional Internal Web/SNMP Card 42. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Optional Relay Card 42. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Communication Slots 42. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Dedicated Input Signals 43. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .DB-9 Communication Port 44. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

8 Maintenance 45. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Storage Temperature 46. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Battery Replacement 46. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Power Module or Battery Charger Module Replacement 47. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9 Specifications 49. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

10 Troubleshooting 53. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Alarms 54. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Obtaining Service 59. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Parts List 59. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 7: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

1Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

C H A P T E R 1

INTRODUCTIONThe Avayat RS9 uninterruptible power system (UPS) is a modular UPSthat contains battery modules and power control modules (referred to aspower modules). These modules plug into a rack cabinet structurecontaining additional control, communication, and display functionsthat enable integrated control of all power modules. The UPS is housedin a single cabinet, with extra battery capacity housed in auxiliarybattery cabinets.

Power ModulesThe pluggable power modules can be removed and replaced(hot-swapped) without powering the UPS down if the UPS has sufficientredundant capacity. Battery modules may also be hot-swapped formaintenance. Power control circuitry in the cabinet senses problems inpower modules, and automatically transfers control and load to theremaining power modules.

All power modules share the load requirements equally. For example,three power modules are capable of supplying a total of 9 kVA. If a loadrequires only 4.5 kVA, each power module supplies 1.5 kVA to theoutput. If one power module is removed or for some reason fails, each ofthe two remaining power modules would supply half of the load, or2.25 kVA. In other words, redundancy exists when the load can besupplied by less than all of the installed power modules.

Battery ConfigurationsThe Avaya RS9 UPS has two different options for additional batteryconfigurations:

S External Battery Module Cabinet (EBMC) - this cabinet is recommendedfor applications that require less than one hour of run time. OneEBMC can be connected to the UPS.

S Extended Battery Cabinet (EBC A through F) - this cabinet is recommendedfor applications that require more than one hour of run time. Up totwo EBCs can be connected to the UPS.

Page 8: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Introduction

2 Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

Battery Charger Modules

NOTE One battery charger module is required whenever one or two EBCs are used.A 9 kVA UPS system with 13 or 14 battery strings also requires one battery chargermodule.

The optional battery charger module is designed to provide additionalcurrent for faster recharging of UPS battery modules in systems withmany batteries. It is capable of providing up to 20 amperes of current foroptimum charging, based upon the condition and number of batteries inthe system.

The battery charger module is similar in appearance to a power module.The primary difference is the light-purple colored front label. It can beplugged into any UPS cabinet slot above the battery modules.

The battery charger module operates in automatic modes within the UPScabinet under control of the UPS power modules. It communicatesthrough a controller area network (CAN) bus with the power modules.The power modules monitor and control the battery charger. Alarmconditions detected by the battery charger module are logged andannounced by the UPS system (see “Alarm Log” on page 38). Normaloutput voltage is 133 Vdc.

Safety WarningsRead the following precautions before you install the UPS.

IMPORTANT SAFETY INSTRUCTIONSSAVE THESE INSTRUCTIONS

SAVE THESE INSTRUCTIONS. This manual contains important instructions that youshould follow during installation and maintenance of the UPS and batteries. Pleaseread all instructions before operating the equipment and save this manual for futurereference.

CAUTIONS A maximum of seven power and/or battery charger modules can be installed in the

system.

S Battery modules used in the Avaya RS9 system weigh 30 lb (14 kg). Use care inlifting and moving battery modules.

Page 9: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Introduction

3Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

S All input and output wiring must be copper and adequate to carrying currents aslisted in Table 9 on pages 50 and 51.

S Torque all bolts holding input and output power conductors to values specified inTable 2 on page 12.

S The user is required to provide power input and output disconnect devices for theUPS. These must be within sight of the UPS and easily accessible.

Physical FeaturesFigure 1 shows the 9-slot UPS cabinet and identifies basic Avaya RS9system features. A 9-slot External Battery Module Cabinet is alsoavailable.

Front PanelDisplay

Front CoverPanels

Cabinet Base

Figure 1. Nine-Slot Cabinet (Front View)

Page 10: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Introduction

4 Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

CommunicationSlots

Entrance Panel

Figure 2. 9-Slot Cabinet (Rear View)

Handle/LatchRelease

Insertion/ExtractionCams

HandleThumbscrew

Figure 3. Power Module (700248974)

Page 11: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Introduction

5Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

Handle/LatchRelease

Insertion/ExtractionCams

HandleThumbscrew

Figure 4. Battery Charger Module (700249030)

Secondary StopRelease

Latch Release

Figure 5. Battery Module (700248982)

Page 12: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Introduction

6 Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

Page 13: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

7Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

C H A P T E R 2

INSTALLATION SETUPThis chapter explains how to setup and install the Avaya RS9 cabinets:

S Clearances and location requirements

S UPS Setup

S Moving the cabinets

Equipment ClearancesAll cabinets require the following clearances to allow for servicing andadequate ventilation:

S From the side panels: 6I (15.2 cm)

S Top and back: 12I (30.5 cm)

S Front: 36I (91.5 cm)

If flexible conduit connects the UPS to the service input and loaddistribution panels, you may be able to gain access for servicing bymoving the UPS. If this is the case, you must still leave 12I (30.5 cm)clearance at the back and 6I (15.2 cm) at the sides of the UPS forventilation.

NOTE Do not block the ventilation holes on each side and the back of the unit.

Location RequirementsInstall the Avaya RS9 UPS as close as possible to the equipment orthe load distribution panel it will protect. If this distance is more than25 ft (7.6m), transient noise can reappear in the electrical distributionsystem.

If a separate battery cabinet is installed (either an External BatteryModule Cabinet or Extended Battery Cabinet), the battery cabinets mustbe adjacent to the Avaya RS9 UPS.

Page 14: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Installation Setup

8 Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

UPS SetupThe Avaya RS9 UPS is shipped in a carton on a shipping pallet. Powerand battery modules are shipped in separate boxes on another pallet.

NOTE Do not attempt to lift the cabinet by the module shelves or other convenientedges or panels.

CAUTIONDo NOT lower the casters or attempt to move the cabinet with the power or batterymodules installed.

1. Lower the four cabinet casters (one at each corner of thecabinet base) by using a 1/2I hex-style socket wrench to turneach bolt clockwise.

2. With all casters fully extended, carefully roll the cabinet downthe ramp and to its intended operating location.

3. Turn all four caster bolts counter-clockwise until the cabinetrests on the floor. Place a plastic cap into each bolt access hole.

NOTE If the floor is uneven and the cabinet is tilted or unstable, you may need toplace a thin steel plate under a corner. Do not use the caster bolts to level thecabinet.

If you ordered an optional battery cabinet (either EBMC or EBCA through F), continue to “Battery Cabinet Installation” on page 19.

If you do not have a battery cabinet, continue to “Electrical Installation”on page 11 to hardwire the UPS.

Page 15: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Installation Setup

9Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

Moving the CabinetsThe Avaya RS9 UPS and EBMC are very heavy with power and batterymodules installed. Before moving the cabinets, remove the power andbattery modules. Move the modules separately from the cabinets.

CAUTIONDo NOT attempt to raise the cabinet with the power or battery modules installed.

Use the following procedure to raise the cabinet before rolling it on itscasters.

1. Ensure that the cabinet contains no power or battery modules.

2. Locate the four plastic caps covering the caster bolts at thecorners of the cabinet base.

3. Pry the caps out of the bolt access holes.

4. Use a 1/2I hex-style socket wrench to turn each of the fourbolts clockwise. Doing so lowers the casters to allow the cabinetto roll on the casters.

5. After rolling the cabinet to its intended operating location, turnall four caster bolts counter-clockwise until the cabinet rests onthe floor. Place a plastic cap into each bolt access hole.

6. After properly positioning and leveling the cabinet, insertpower and battery modules into the cabinet as described in“UPS Startup” on page 23.

Page 16: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Installation Setup

10 Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

Page 17: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

11Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

C H A P T E R 3

ELECTRICAL INSTALLATION

W A R N I N GOnly qualified service personnel (such as a licensed electrician) MUST perform theelectrical installation. Risk of electrical shock.

The UPS input must be hardwired through conduit to a main powersource circuit breaker. The UPS output may be hardwired to a circuitbreaker in a distribution panel (as shown in Figure 6).

BuildingServicePanel

LoadDistribution

Panel

User-supplied(If Required) External Batteries

(Optional)

Figure 6. Avaya RS9 Typical Installation

Page 18: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Electrical Installation

12 Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

Input Current RatingsTable 1 contains the required circuit breaker ratings for hardwiredinstallations.

Table 1. Required Input Circuit Breaker Sizes (200–240 Vac, 60 Hz)

UPS Capacity Input CircuitBreaker Rating

UPS with 1 BatteryCharger Module

UPS with 2 BatteryCharger Modules

9 kVA 60A 75A 100A

12 kVA 80A 100A 125A

15 kVA 100A 125A 125A

18 kVA 125A 125A 125A

NOTE To accommodate the feature of easy system expandability, it is recommended thatinitial installation of the Avaya RS9 UPS contain wiring to support a 18 kVA unit.

See Table 2 for recommended conductor size to wire the input circuitbreaker.

Table 2. Recommended Wire Sizes

Input Circuit Breaker Size 75°C Copper Wire Size Conductor Screw Torque

60A 4 AWG (21.2 mm2) 35 in lb (4.0 Nm)

75A, 80A 3 AWG (26.7 mm2) 45 in lb (5.1 Nm)

100A 2 AWG (42.1 mm2) 55 in lb (6.2 Nm)

125A 1/0 AWG (53.5 mm2) 65 in lb (7.3 Nm)

FOR U.S. INSTALLATIONS, READ THIS IMPORTANT NOTE!

Conductor sizes shall be no smaller than the 75°C wire size based on the ampacities given inTable 310–16 of the National Electrical Code, ANSI/NFPA 70-1999, and article 220. All circuitconductors, including neutral conductor, must be the same size (ampacity) wire. Code mayrequire a larger AWG size than shown in this table because of temperature, number ofconductors in the conduit, or long service runs. Follow local code requirements.

Page 19: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Electrical Installation

13Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

UPS Installation

W A R N I N GOnly qualified service personnel (such as a licensed electrician) MUST perform theelectrical installation. Risk of electrical shock.

CAUTIONTo prevent electrical shock or damage to the equipment, verify that the Avaya RS9 UPSis OFF before you remove the entrance panel. The circuit breaker or disconnect switchmust also be off at the AC input service panel.

1. Unscrew and remove the top two rear panels of the UPS (seeFigure 7).

The entrance panel, located in the second section, containsknockout openings for entrance and exit conduits. SeeFigure 7.

Wiring for optional emergency power-off (EPO) passes throughthe opening at the top back of the cabinet. Wiring for anoptional generator input signal must pass through a separateopening. Installing this wiring is described in Steps 8 and 9 onpage 17.

Page 20: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Electrical Installation

14 Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

Entrance Panel

Wiring Access Holefor Optional EPO

Wiring Access Holefor an OptionalGenerator InputSignal

Figure 7. UPS Power Entrance Panel and Wiring Knockouts

2. Remove the knockouts in the entrance panel for AC input andAC output wiring.

3. Install the conduit adapters. AC input and AC outputconductors must be run through separate conduits. UPS outputcircuits must be installed in dedicated conduit systems and notshared with other electrical circuits.

4. Torque the screws holding all input and output powerconductors to the values specified in Table 2 on page 12.

Page 21: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Electrical Installation

15Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

5. Figure 8 shows input and output wiring terminals inside theAvaya RS9 UPS cabinet.

3 2 1

+DC X1X2N

-DC

N

-DC

X2

+DC X1

Backplane BoardTerminatingStuds

Figure 8. UPS Input and Output Terminals

6. Wire the UPS for the proper input voltage as shown in Figure 9.

The Avaya RS9 UPS uses split-phase power modules thatsupply two output voltages: 100/100 for 200, 110/110 for 220,120/120 for 240, 120/120 for 208, or 127/127 for 220 Vac, asselected through the front panel display.

(3-Wire Plus Ground Input) (2 PEN)100/200, 110/220, 120/208, 120/240, 127/220 Vac

3 2 1L2

L1

N

GND

Figure 9. UPS Input Wiring

Page 22: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Electrical Installation

16 Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

7. See Figure 12 on page 18 for the output wiring diagram. MakeUPS output connections on the backplane board terminatingstuds. Compression lugs (supplied in the accessory kit) may beinstalled on the proper terminating studs. Wires may also beterminated with ring terminals, which are attached to theoutput terminating studs.

Figure 10 shows output wiring configurations for variousoutput voltages. You must also set the operating menuparameter 4-2-4 for the required output voltage.

NOTE For Avaya RS9 UPS models with low-voltage hardwire output, itis recommended to divide the total load as equally as possible between X1 and X2, asshown in Figure 10.

NOTE Failure to balance the loads may cause an overload alarm even if the fullcapacity of the UPS has not been reached.

N/-DC

100/200, 110/220, 127/220, 120/208, or 120/240V OutParameter 4-2-4 set to 200, 220, 208, or 240, as required.

X2 X1XX

N

L1

X

L2100, 110, 127, or 120

50%

100, 110, 127, or 12050%

X1X2

200, 220208, or 240

Figure 10. Split-Phase Output Connections

Page 23: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Electrical Installation

17Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

8. If any external hardwired control signals are required (EPO orGenerator On), unscrew and remove the top rear panel of thecabinet and locate the terminal block (see Figure 11).

CAUTIONEPO circuits are not isolated from line voltage, and wiring must be installed accordingto local codes using conduit or suitable primary supply cables.

The Generator On signal is isolated from line voltage and canbe treated as NEC Class 2 wiring.

Use 14–20 AWG, 600V wire (UL) or 14–26 AWG, 300V wire(CSA) for all input control signals.

Generator On(Normally Open)

SignalCommon

Emergency Power-Off (Normally Closed)

Generator Set

Plastic Cable Tie

Figure 11. Input Control Signal Wiring

9. Place the signal wires through the proper conduit or grommetabove the terminal block and attach to appropriate terminals.Secure each connection by torquing terminal screws to amaximum 3.5 in lb (0.4 Nm). Provide strain relief for cables byinstalling plastic cable ties.

NOTE Do not strain relieve EPO wiring with the same cable tie used for Generator Onwires.

10. Remove the jumper between terminals 5 and 6 only if you arewiring from an EPO switch. (See “Changing ParameterSettings” on page 36 for information about accessing menu 4,submenu 3, item 2 to view or change the EPO switch type.)

11. When all connections have been made and checked, reinstallthe UPS cabinet rear panels using the original screws.

Page 24: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Electrical Installation

18 Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

System Wiring DiagramThe following notes are referenced in Figure 12.

NOTE 1 The customer must provide input overcurrent protection as stated in NECSection 240-21 or local codes. Size the protection device according to local coderequirements (see Table 1 on page 12).

NOTE 2 All AC circuit conductors, including the neutral and equipment groundingconductors, must be the same size (ampacity), have the same rating (75°C) copperwire, and be sized according to the input circuit breaker. The UPS input and outputconductors must be run through separate conduits.

NOTE 3 See “Equipment Clearances” on page 7 for installation and serviceclearances before installing the UPS. It is recommended to use flexible conduit so thatthe UPS can be moved for servicing.

NOTE 4 UPS output circuits shall be installed in dedicated conduit systems and notshared with other electrical circuits.

S 110/220 Input, 110/220 OutputS 120/208 Input, 120/208 OutputS 120/240 Input, 120/240 OutputS 100/200 Input, 100/200 OutputS 127/220 Input, 127/220 Output

NOTE 1 NOTE 2

NOTE 2NOTE 3NOTE 4

NOTE 4

Figure 12. Split-Phase Wiring Diagram (Hardwired Output)

Page 25: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

19Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

C H A P T E R 4

BATTERY CABINET INSTALLATIONNOTE If you are not installing an optional battery cabinet, continue to “UPS Startup”on page 23.

The Avaya RS9 UPS has two different options for additional batteryconfigurations:

S External Battery Module Cabinet - the EBMC is recommended forapplications that require less than one hour of run time. Use theinstructions in this chapter to connect the battery cabinet to the UPS.

S Extended Battery Cabinet - an EBC is recommended for applications thatrequire more than one hour of run time. Refer to the EBC manual forinstallation instructions.

CAUTIONS Before connecting an EBMC to the UPS cabinet, verify that all AC input power is

removed from the UPS by opening the input service circuit breaker.

S Never dispose of batteries in a fire. Batteries may explode when exposed toflames. In the event of a fire involving the UPS and its batteries, use only carbondioxide fire extinguishers or those approved for use in electrical fire fighting.

S Batteries can present a risk of electrical shock or burn from high short circuitcurrent. Observe proper precautions. Servicing should be performed by qualifiedservice personnel knowledgeable of batteries and required precautions. Keepunauthorized personnel away from batteries.

S Never open or mutilate batteries. Released electrolyte is harmful to the skin andeyes, and may be extremely toxic.

S Proper disposal of batteries is required. Refer to your local codes for disposalrequirements.

1. Open the carton containing the external battery cabinet cables.

2. Locate the 3-slot section in the UPS cabinet that contains thepower entrance panel. Unscrew and remove the rear panel ofthis section (see Figure 13).

Page 26: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Battery Cabinet Installation

20 Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

Entrance Panel

Battery CableConnectionPoint

Figure 13. UPS Power Entrance Panel

3. Verify all hazardous voltages have been removed from thebackplane by testing with a voltmeter or other test device.

4. Feed one end of all three battery cables through the strain-reliefclamp located on the cable assembly’s entry plate (seeFigure 14).

5. Secure each battery cable to the cable assembly as shown inFigure 14. Torque all nuts to 75–85 in lb (8.5–9.6 Nm).

6. If the battery cable will be installed in customer-suppliedflexible or other conduit (as required by local wiring codes),loosen the two screws holding the strain-relief clamp shown inFigure 14. Remove the clamp by loosening the star nut on theinside of the entry plate, leaving the nut in place. Replace theclamp with a panel-to-conduit feedthrough and secure it withthe star nut.

Page 27: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Battery Cabinet Installation

21Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

Cable Assembly

+–

Figure 14. Battery Cable Installation

7. Reinstall the UPS cabinet rear panel using the original screws.

8. If the battery cable will be installed in flexible or other conduit,pull the conductors through the conduit. Attach the conduit toboth the UPS power entrance panel and the battery cabinetentrance panel as shown in Figure 15.

+

Figure 15. Battery Cable Installed in Battery Cabinet

Page 28: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Battery Cabinet Installation

22 Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

9. Secure the +, the –, and the conductors to the propercompression lugs on the battery cabinet backplane as shown inFigure 15. Torque all three compression lugs to 75–85 in lb(8.5–9.6 Nm).

10. Reinstall the rear panel using the original screws.

11. Continue to “UPS Startup” on page 23.

Page 29: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

23Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

C H A P T E R 5

UPS STARTUPThis section provides step-by-step instructions for starting your AvayaRS9 system. Follow these procedures closely to avoid potential damageto your equipment or the UPS and to protect yourself and others fromhazardous operating conditions.

CAUTIONS This UPS contains its own energy source (batteries). The output receptacles may

carry hazardous voltage even when the UPS is not connected to an AC supply.When AC input voltage is present, the Avaya RS9 system can provide outputvoltage even though its batteries are disconnected. To confirm that there is no UPSoutput voltage, always disconnect all of the AC input sources and unplug allbattery strings and optional Extended Battery Cabinets.

S To reduce the risk of fire or electric shock, install this UPS in a temperature andhumidity controlled, indoor environment, free of conductive contaminants. Ambienttemperature must not exceed 40°C (104°F). Do not operate near water orexcessive humidity (95% max).

S For optimum battery life, ambient temperature should not exceed 25°C (77°F).Battery life is substantially reduced if ambient temperature is higher.

Page 30: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

UPS Startup

24 Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

Power and Battery Module InstallationUse the following procedure to install the power and battery modulesand the optional battery charger module into the Avaya RS9 cabinet:

1. Remove the front cover panel(s) of the cabinet.

The panels have spring latches on the left and right sides thathold them in place.

NOTE Place battery modules below all power and/or battery charger modules in theUPS cabinet. Two battery modules (side-by-side) are required to complete each batterystring.

2. Insert the battery modules into the cabinet.

Push each module firmly until the front latch snaps to securethe battery module (see Figure 16). Repeat for each additionalbattery module.

NOTE A maximum of seven power and/or battery charger modules can be installed inthe system.

3. Insert the power modules into the upper slots of the cabinet.When required, insert the battery charger module above thebattery modules in the UPS cabinet. To install the powermodule or battery charger module:

Lower the front down slightly and lift the rear edge over thesafety stop on the center support rail. Keep the module handleextended until the module is fully inserted (see Figure 16).

Raise the module handle to secure the module into the cabinet.Be sure the handle latch snaps into place. Tighten thethumbscrew on the handle.

Page 31: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

UPS Startup

25Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

Figure 16. Inserting the Modules

4. If you installed an optional External Battery Module Cabinet,repeat Steps 1 and 2 to install the battery modules into theEBMC.

5. Reinstall the front cover panel(s).

6. Continue to the following section, “UPS Startup.”

UPS StartupTo start the UPS, use the following steps:

1. Confirm that an electrician has completed and tested theconnection to the proper power source.

2. If battery cabinets are installed (either EBMC or EBCA through F), check the cord connections between the UPS andthe battery cabinet.

3. Ensure that all power modules are properly installed andlatched into the UPS cabinet.

Page 32: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

UPS Startup

26 Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

4. If you are installing power management software, connect yourcomputer to the UPS communication port using the suppliedcommunication cable.

DB-9 Connector forComputer Cable

Figure 17. Communication Port

5. When starting the UPS, apply input power to the UPS byclosing the service circuit breaker.

6. If battery cabinets are installed, use the following instructionsaccording to the type of cabinet:

EBMC - Close the DC disconnect switch button on the back ofthe battery cabinet. Insert the switch key supplied with thecabinet into the button and turn clockwise 1/2-turn. Pull thebutton out to close the switch. Turn the key backcounter-clockwise, and remove the key.

EBC A through F - Switch the battery circuit breaker on each EBCfront panel to the ON (���) position.

7. The UPS front panel display automatically turns on wheneverinput power is present and at least one power module isinstalled. Set up the initial operating parameters through thefront panel display (see “Initial Startup Parameters” onpage 27).

NOTE The unit has no physical On/Off switch. The UPS On/Off function must beaccessed through the front panel display.

8. If applicable, test proper operation of optional external controlsignals and computer communication before connecting theload. (See “DB-9 Communication Port” on page 44 for details.)

9. Turn on the equipment that is connected to the UPS.

Page 33: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

UPS Startup

27Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

Initial Startup ParametersThe first time the UPS is turned on, you must set or verify certainoperating parameters before placing the UPS into operation. Use thefollowing procedure to set these initial configuration parameters.

1. Enter the correct user security password: 0377. Move left andright by pressing the buttons below the <- and -> on thedisplay. To change the value of the selected digit, press the Y

and B buttons. When the password shows 0377, press thebutton.

ENTER PASSWORDPassword - 0000<- -> ESC

2. Select the desired language for the display. Use the Y and B

buttons to scroll between English, French, German, andSpanish. Enter your selection by pressing the button.

3. Set the clock for the local time and date. If the time or the dateis correct as displayed, press the button to advance to thenext configuration setting. Time must be entered in 24-hourformat.

Press the <- and -> buttons to move left and right. Press the Y

and B buttons to increase or decrease the value of each selecteddigit. When the displayed value is correct, press the button.

Set Timetime 14:51:38<- -> ESC

Page 34: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

UPS Startup

28 Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

4. The output voltage is the most important operating parameteryou must set as part of the initial configuration screens. Selectthe desired UPS output voltage using the Y and B buttons.Possible selections are 200, 208, 220, 230, and 240 Vac. (Lowvoltages are derived from these voltages, as shown in Figure 10on page 16.) Press the button when the desired output valueis displayed.

5. If the system includes separate battery cabinets (either EBMCor EBC), record the ampere-hour capacity of batteries installedin these cabinets. If using an EBMC, count the number ofbattery strings (two battery modules, side-by-side equals onestring). Each battery string contains 7.2 ampere-hours. If usingan EBC, refer to Table 3 for the total ampere-hour value thatcorresponds to the type of EBC(s) being used. Enter the totalvalue in the next startup screen.

Table 3. EBC Ampere-Hour Values

Type of EBC Being Used Total Ampere-Hour Value to Enter

EBC A 130

EBC B 182

EBC C 260

EBC D 330

EBC E 390

EBC F 520

(2) EBC D 660

(2) EBC E 780

(2) EBC F 1040

External Capacityextamphr 0028.8<- -> ESC

Page 35: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

UPS Startup

29Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

6. The system signals an alarm when the required output cannotbe maintained with the loss of redundant power modules. Thealarm is essentially disabled with a redundancy level set at 0.

If you want the system to notify you when the number ofredundant power modules is less than a specified level, enter aredundancy level. Each increment above 0 indicates thenumber of modules that can be removed from operation beforethe alarm occurs. This setting only affects the alarm; the systemcontinues to operate as an N+X system even if this parameter isleft at the default value of 0.

Set RedundancyRSetting 0<- -> ESC

7. To password-protect the UPS On/Off function, press the Y or Bbutton to make your selection; then press the button. If apassword is required, the UPS On and Off functions areaccessible only after first entering the correct password value(0377).

ON OFF Password?No

ESC

8. The UPS is now ready to operate, and displays the normalOn/Off function screen.

These configuration parameters are accessible during normalUPS operation by pressing the Config button through the frontpanel display.

Page 36: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

UPS Startup

30 Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

Page 37: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

31Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

C H A P T E R 6

OPERATIONThe Avaya RS9 UPS operates in several different modes. Normally itoperates under internal control, called Auto mode, to automaticallyprotect loads connected to it. It also functions under operator control toenable manual override should servicing or testing be required.

Figure 18 is an illustration of the operating modes. In Auto mode, theUPS automatically switches between modes depending on line and loadconditions.

Double Conversion(Line Conditioning) Internal Bypass

Battery Off

Figure 18. UPS Operating Modes Under Auto Mode Control

Double Conversion mode produces output power from the internal DCbus. The AC input power is rectified and boosted to supply this DC bus.The UPS switches automatically to and from Battery mode with nointerruption (0 ms transfer time) as AC input power drops and returns.Batteries are charged in this mode.

Battery mode produces power from the batteries to supply the internalDC bus.

Internal Bypass (Bypass) mode shunts power flow around the DC/ACinternal circuitry to keep the output powered with no line conditioning.Electromagnetic interference (EMI) and surge circuitry still protect theloads from voltage spikes and noise.

Page 38: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Operation

32 Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

Off mode turns off the output and most internal circuitry. Within thismode, another mode (Sleep) turns off all internal circuitry when AC lineis not present and battery voltage drops to a low threshold. If AC inputvoltage is not present in Off mode, the user can direct the UPS to enterSleep mode by selecting the Battery Protect (BP) feature (see “RemovingInput Power” on page 33). When AC input voltage returns in the Offmode (caused by a low battery alarm condition), the UPS automaticallyrecovers and, if the Auto Restart parameter is enabled, switches toDouble Conversion. Auto Restart is enabled as a factory-default.

After a discharge and subsequent low-battery shutdown, the UPS willautomatically recover from Sleep mode if the Auto Restart parameter isenabled.

Figure 19 shows the basic functional elements of the UPS.

Input(Utility)Power

Input Power (Boost)Converter

Internal DCPower Bus

DC/AC Power Inverter

Output Relay

Bypass Relay

Capacitor BankBattery ChargerBattery

Modules(Parallel)

Line/BatteryRelay

EMI/RFIFilter

Figure 19. Avaya RS9 UPS Functional Block Diagram

Turning the UPS OnThe unit has no physical On/Off switch. The UPS On/Off function mustbe accessed through the front panel display.

If the UPS has been turned off, press the ON button through the frontpanel display to turn the UPS on again.

Page 39: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Operation

33Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

If the UPS has been manually set to operate in Bypass or Battery mode,change the System Control Mode Preference (menu 4-1) selection toAuto to return to normal Auto mode operation.

NOTE The UPS will not start operating if AC input voltage or frequency is beyondacceptable limits or if the system mode selection is set to Battery. The UPS can not godirectly from Off to Battery.

Removing Input PowerAlways put the Avaya RS9 UPS into the Off mode before removing inputpower. Avaya RS9 system batteries will discharge if the input linevoltage is disconnected or turned off without first turning off the AvayaRS9 UPS.

If the input power source will be disconnected or turned off for morethan a day or two, you should put the UPS into Sleep mode. Do this byturning the UPS off, removing AC input power, and then pressing theON button and selecting Battery Protect (BP). Sleep mode allows theUPS to remain unpowered for up to six months without having toremove or recharge batteries.

Failure to properly power down the Avaya RS9 UPS could permanentlydamage any installed batteries. Also, if batteries become severelydischarged, the UPS might not start immediately when input power isrestored.

Front Panel DisplayThe front panel has an alphanumeric display, three LED indicators, andsix pushbuttons as described in Figure 20 and in Table 4.

1 2 9 USER #3Woutwatts 2.07 KWSlot Top ESC

2

3

4

A B C

1

Figure 20. UPS Front Panel

Page 40: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Operation

34 Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

Table 4. Front Panel Details

Item Description

1 Alphanumeric display of unit function and operating parameters. Also displays alarm/data logs.

2 Alarm LED (red). Illuminates to signal that the unit has detected an alarm condition.

3 Battery LED (yellow). Illuminates to signal that the unit is operating on battery power and producingoutput voltage.

4 Line LED (green). Illuminates to signal that the unit is operating on AC utility power and producingoutput voltage.

A and B Multi-function buttons, as labeled by the bottom line of the alphanumeric display.

C Menu/Escape button, for moving into and out of display menus. Also, for avoiding a change to aparameter value.

andY B Menu scroll up and down buttons. Also, for increasing/decreasing parameter value digits.

Enter button, to activate/accept displayed parameter or operating mode.

Using the Front Panel DisplayThe front panel display shows several important things (see Figure 21).The numbers in the upper left corner (for example, 1 2 9) are thedisplay location within the operating menu structure. The word in thetop center (for example, USER ) is the security level, which allowsvarious operating parameters to be changed.

1 2 9 USER #2Woutwatts 1.87 KWSlot Top ESC

A B C

Figure 21. Typical Front Panel Display

The number in the upper right corner (for example, #2) identifies thecabinet slot (numbered from the top down) for a specific powermodule’s parameters. #0 is defined as System, enabling you to observeoverall system operation.

Page 41: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Operation

35Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

One or two triangles at the right of the display tells you which arrowbuttons are active for moving to various parameters within a menu level.See Figure 26 on page 40 for the complete system menu.

The words or symbols in the bottom line of the display define thefunction of the three buttons below the display. In Figure 21, Slot(button A) enables you to observe the operation of a specific powermodule (the module in slot #2, in this case) or the overall system(selected as slot #0). Top (button B) takes you to the top item in thecurrent menu level (in this case, 1 2 1). And ESC (button C) enablesyou to move out of the current menu level (in this case, to menu 1 2).

During normal operation, the display appears as shown in Figure 22.Md: indicates the current UPS operating mode and St: indicates theoperational state. The number of power modules (M) and number ofbattery module strings (B) that are currently online, and the totalnumber of module slots in the cabinet—for example, M4-B7-12—isshown in the upper right corner of the display. (The count of batterystrings does not include additional battery strings contained in theExternal Battery Module Cabinet or Extended Battery Cabinets.)

Md: AUTO M4-B7-12St: ON LINEacvout 232 VConfig OFF Menu

Figure 22. Front Panel Display (Normal Operation)

Page 42: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Operation

36 Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

Operating parameters shown on the third line of the display varydepending on the operating mode. You can use the B and Y buttons toscroll through the available parameters. After five seconds of inactivity,the system automatically saves the parameter that was selected as thedefault display parameter. The parameters that are available for displayare:

S Phase 1 Input Voltage

S Phase 2 Input Voltage

S Phase 1 Output Voltage

S Phase 2 Output Voltage

S Total System Percent Load

S Phase 1 Percent Load

S Phase 2 Percent Load

S Battery Voltage

S Estimated Battery Run Time

ParametersThe parameters describe the Avaya RS9 system operation. Some usefulparameters are input and output voltage, input and output current, andbattery voltage. The UPS measures or records many other parameters.Some are operator-adjustable, such as the local date and time andvarious operating limits. All parameters are password-protected.Although every operating condition and parameter is accessible throughthe front panel display, you may change a value only if you have enteredthe correct password to allow you to change it.

NOTE After 10 minutes of inactivity, the UPS automatically deletes any activepassword level and returns to the normal running display.

Changing Parameter SettingsThe method of changing any operating parameter follows the sameprocedure as setting initial parameters, as described in “Initial StartupParameters” on page 27.

Use the Menu map (Figure 26 on page 40) to find the parameter youneed to change, and move through the menu structure until theparameter name appears on the display.

Page 43: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Operation

37Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

Press the button to access the parameter value. The Enter Passwordscreen automatically appears if permission is required for a particularparameter. Enter the appropriate password, if applicable, and thenchange the parameter value.

When you have changed the value, press the button again to save thechange. To avoid making a change, press ESC instead of the button.

Reading the Avaya RS9 System LogsThe Avaya RS9 system makes an entry in its logs each time it sounds analarm or runs on battery power. This information can help in diagnosingpower problems. You can display the UPS Inverter and Alarm logs onthe unit’s front panel display; these logs are in menu 2.

Inverter LogThe inverter (Battery mode) log is in menu 2, submenu 1. Move throughthe menu structure by pressing the Menu button and pressing the B

button to move down to menu 2. Press to move to submenu 1 andpress again to view the most recent entry in the inverter log.

The log stores up to 10 entries, in chronological order. You can use theB and Y buttons to scroll up and down through the log entries. Eachentry shows the date and time the unit switched to battery operation(in 24-hour format), and the duration of battery operation (in hours andminutes).

A typical entry might look like this:

2 1 1 #0I 09/29 13:56 01:04Line FaultSlot Top ESC

Figure 23. Inverter Log Entry

Page 44: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Operation

38 Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

In Figure 23, the most recent inverter log (2 1 1) is being displayed. Ifthe unit is still running on inverter (battery power), an asterisk (*) isdisplayed beside the date. “09/29” is the date of the Battery modeoperation: September 29. “13:56” means that Battery mode operationstarted at 1:56 p.m. And “01:04” means the batteries supplied power for1 hour and 4 minutes.

Table 5 contains a description of all inverter messages.

Table 5. Inverter Log Messages

Message Explanation

Line Fault UPS switched to battery because the input voltage was too high or too low.

Battery Test Battery test initiated inverter operation.

Manual Operator initiated inverter operation.

Alarm LogThe alarm log is in menu 2, submenu 2. Move through the menustructure by pressing the Menu button and pressing the B button tomove down to menu 2. Press , and press the B button to move downto submenu 2. The display shows the most recent entry in the alarm log.

The log stores up to 10 entries, in chronological order. You can use theY and B buttons to scroll up and down through the log entries. Eachentry shows the alarm code, the alarm date and time (in 24-hourformat), and the duration (in hours and minutes.)

A typical entry might look like this:

2 2 6 #0A 02/05 17:51 04:35Low BatterySlot Top ESC

Figure 24. Alarm Log Entry

Page 45: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Operation

39Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

In Figure 24, the sixth most-recent alarm (2 2 6) is being displayed. “A”means the Avaya RS9 system sounded alarm A (Low Battery). If thealarm is still active, an asterisk (*) is displayed beside the letter alarmcode. “02/05” is the date the alarm occurred: February 5. “17:51” meansthe alarm sounded at 5:51 p.m. And “04:35” means the alarm was activefor 4 hours and 35 minutes.

Some alarms indicate the specific power or battery module slot number.“Slot: XX” appears in the upper right hand corner of the display, asshown in Figure 25, indicating the slot number where the faultoccurred.

See “Troubleshooting” on page 53 for detailed information on alarms.

2 2 6 Slot: 7M 02/05 17:51 00:01Open CellSlot Top ESC

Figure 25. Alarm Entry for Specific Slot Number

Menu MapFigure 26 is an illustration of how to access all Avaya RS9 systemparameters. The menu structure has 6 primary-level menus, namedSystem Status Menu (1) through Service Menu (6). Under each primarymenu are secondary items, each numbered by its location under theprimary menu. Use the various buttons as shown in the map to navigateto the desired parameter.

Page 46: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Operation

40 Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

(ESC)

(Menu)

(Top)

(ESC)(ESC)

3 1 2 1 Battery Results3 1 2 2 Runtime at EOT3 1 2 3 DC Volts at EOT

4 2 1 System VA Limit 4 2 5 Redundancy Level4 2 2 Number Phases 4 2 6 External Capacity4 2 3 Nominal Frequency 4 2 7 Auto Restart4 2 4 Nominal AC Vout 4 2 8 Low Runtime Alarm

1 1 1 Input Frequency 1 1 4 ACIin Ph11 1 2 ACVin P1-N 1 1 5 ACIin Ph21 1 3 ACVin P2-N

1 2 1 Output Frequency 1 2 9 Wout1 2 2 ACVout P1-N 1 2 10 Wout P1-N1 2 3 ACVout P2-N 1 2 11 Wout P2-N1 2 4 ACIout P1-N 1 2 12 % Full Load1 2 5 ACIout P2-N 1 2 13 % Full Load P11 2 6 VAOut 1 2 14 % Full Load P21 2 7 VAout P1-N 1 2 15 PowerFactor L11 2 8 VAout P2-N 1 2 16 PowerFactor L2

1 3 1 Battery Volts1 3 2 Run Time1 3 3 Seconds on Battery

(ESC)

4 3 1 Inv. Relay Delay4 3 2 EPO Mode4 3 3 Ext. Bypass Mode

5 1 Time5 2 Date5 3 Model Name5 4 Serial Number5 5 Software Version

1 1 Input Status

3 1 3 1 Test Interval3 1 3 2 Test Time

1 2 Output Status

1 3 Battery Status

2 1 Inverter Log(Logs 1–10)

2 2 Alarm Log(Logs 1 - 10)

2 3 Clear Logs

3 1 Battery Test

3 2 Fan Test

4 1 Mode Preference

4 2 Control Settings

4 3 Comm. Settings

1 System Status Menu

2 Logs

3 Diagnostics

4 System Control

5 System ID

6 Service Menu

3 1 1 Execute Test

3 1 2 Test Results

3 1 3 Test Config

(ESC)

(ESC)

(ESC)

(ESC)

(ESC)

(ESC)

(ESC)

(ESC)

(ESC)

(ESC)

(Top)

(Top)

(Top)

(Top)

(Top)

Figure 26. Avaya RS9 System Menu Map

Page 47: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

41Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

C H A P T E R 7

COMMUNICATIONAvaya offers several methods of communicating with your Avaya RS9system in addition to the front panel display:

S LanSafe Power Management Software

S Optional Internal Web/SNMP Card

S Optional Relay Card

S Communication Slots

S Dedicated Input Signals

S DB-9 Communication Port

LanSafe Power Management SoftwareEach Avaya RS9 UPS ships with LanSafe Power Management Softwareand an interface cable. To begin installing LanSafe software, see theinstructions accompanying the Software Suite CD.

LanSafe software uses an RS-232 serial link to communicate with theUPS, and it provides you with up-to-date graphics of UPS power andsystem data and power flow. It also gives you a complete record ofcritical power events, and it notifies you of important UPS or powerinformation. If there is a power outage and the Avaya RS9 system batterypower becomes low, LanSafe software can automatically shut down yourcomputer system to protect your data before the UPS shutdown occurs.

Page 48: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Communication

42 Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

Optional Internal Web/SNMP CardThis card provides the Avaya RS9 system with its own ethernet networkconnection, allowing it to be remotely monitored and controlled viaindustry-standard internet browsers. The HTML interface enables UPSmonitoring and management from anywhere on the internet or withinyour intranet. In addition, third-party Simple Network ManagementProtocol (SNMP) software packages may also be used to communicateremotely with the Avaya RS9 system.

The Web/SNMP Card also allows UPS-dependent computer systems toautomatically shut down during extended power outages using theNetWatch client software provided on the Software Suite CD.

Optional Relay CardThe relay card provides true relay contact output to peripheral devices.Outputs are user-selectable as normally open or normally closed. Referthe instructions included with the relay card for more detail.

Communication SlotsThe Avaya RS9 UPS has two communication slots that allow quickinstallation of the optional Web/SNMP card or other similarcommunication interfaces. These interface cards extend the capabilitiesof the Avaya RS9 system to provide compatibility with network andremote monitoring/management systems.

Page 49: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Communication

43Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

Dedicated Input SignalsEmergency Power-Off: Connection to a facility Emergency Shutdownswitch provides a method for emergency Avaya RS9 system shutdown.Opening this connection creates an immediate shutdown of the AvayaRS9 UPS output.

On-Generator: An external signal that the input power is being suppliedby a generator. Closure of this contact causes the UPS to change thefollowing parameters to preset values that are designed to optimizeperformance during periods of generator instability:

S Phase Lock Window and Frequency Slew Rate. These parametersincrease the rate at which the UPS tracks the input line, which causesfewer recognized line faults during generator instability.

S Frequency Glitch Count. This parameter increases the number of badfrequency cycles before the unit transfers to battery power. Thisallows the UPS to operate smoothly during generator instabilitywithout transferring to battery.

S Maximum Delta and Line Delta. These parameters widen theacceptable input voltage range, allowing the UPS to ignore anytransient voltage regulation problems a generator may experienceduring unstable periods.

These parameters are also available to trained service personnel throughthe Service Menu.

See Figure 7 on page 14 and Figure 11 on page 17 to make theconnection for all dedicated input signals.

Page 50: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Communication

44 Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

DB-9 Communication PortFigure 27 shows the Avaya RS9 DB-9 communication port and Table 6explains the functions of the pins.

DB-9 Connector forComputer Cable

Figure 27. Communication Port

Table 6. DB-9 Port Signals

Pin Function Description

1 Low Battery Alarm Pin 1 shifts from RS-232 Low (positive voltage) to RS-232 High (negative voltage) andremains high whenever the UPS enters a Low Battery alarm state.

2 RS-232 Transmit Data Sends outgoing RS-232 communication data at 9600 baud, 8 bits, no parity, 1 stop bit.

3 RS-232 Receive Data/RS-232 Shutdown

RS-232 Receive Data Function. Receives incoming RS-232 communication data at9600 baud, 8 bits, no parity, 1 stop bit.RS-232 Shutdown Function. If Pin 3 receives an RS-232 Low signal (+Vdc) for at least5 seconds, but not more than 7 seconds, during an AC Failure condition, the UPS outputshuts off following a delay of 120 seconds (±5 seconds).S The UPS output shuts off even if the normal AC input power is restored during the

120 second delay.S The UPS output automatically restarts after the UPS determines the normal AC input

power is stable.S The shutdown and restart timing represented by the functionality of Pin 3 is

independent from the shutdown and restart timing specified from the host software.

4 Reserved Loopback to Pin 6.

5 Common Signal Ground

6 Reserved Loopback to Pin 4.

7 No Connection Open pin

8 AC Fail Signal(On-Battery)

Pin 8 shifts from RS-232 Low (positive voltage) to RS-232 High (negative voltage) andremains high for 15 seconds (±1 second) after the UPS detects an AC Failure condition,assuming the condition still exists after the 15 seconds.When the AC Failure condition no longer exists, the signal returns to the RS-232 Lowstate (positive voltage).

9 DC Supply Voltage(Default)

Nominal 12 Vdc/5W; 8V minimum, 24V maximum.

Page 51: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

45Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

C H A P T E R 8

MAINTENANCENOTE Technicians must observe important safety precautions while performing thesechecks.

NOTE Avaya recommends that you schedule preventive maintenance checks at leastevery six months.

The Avaya RS9 system is designed to provide years of trouble-freeoperation. Its internal control system checks the batteries and inverterperiodically to ensure reliable operation. In fact, you’ll probably findthat your Avaya RS9 system requires less maintenance than any of yourother computer peripherals.

Nevertheless, the Avaya RS9 UPS and optional battery cabinets dorequire some attention to assure continued reliable service. The servicetechnician should follow the recommended maintenance schedule,which includes the following items:

S Check operating environment for clean, cool, dry conditions.

S Inspect and clean the unit.

S Check operation of fans (power modules).

S Check and tighten all connections.

S View and record the alarm and inverter logs.

S Check the batteries.

S Check the displayed UPS readings against actual measurements andrecalibrate if necessary.

S Perform a system test.

S Check and record the values of the parameters in the System StatusMenu (menu 1) online and on battery.

S Check the MOV surge suppression pack.

For more information on preventive maintenance checks, contact yourAvaya service representative.

Page 52: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Maintenance

46 Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

Storage TemperatureStore the Avaya RS9 battery modules (in the UPS or External BatteryModule Cabinet) at –20 to +40°C (–4 to +104°F). Batteries will have alonger shelf life if they are kept below +25°C (+77°F). The remainingcomponents may be stored at –40 to +60°C (–40 to +140°F).

Battery ReplacementThe Avaya RS9 hot-swappable feature allows you to replace the batterymodules easily without disconnecting the load or damaging thebatteries.

NOTE The Avaya RS9 UPS will operate with uncharged (or no) batteries, but will havelimited (or no) battery backup capability. Backup protection requires at least threeinternal battery strings (two battery modules installed side-by-side equals one string)unless an Extended Battery Cabinet is used. If an EBC is used, only one internal batterystring is required. The UPS may indicate an alarm with no batteries present.

Use the following procedure to replace battery modules in pairs.

1. Remove the front cover panel(s) from the battery modules youneed to replace.

The panels have spring latches on the left and right sides thathold them in place.

2. Grasp the battery module handle and press down on the latchrelease.

3. Pull the module out approximately 7I (17 cm) to the secondarystop on top of the module.

4. Press down on the secondary stop release, pull the module outfurther, and support the module weight with your second handas you remove the module from the cabinet. Remove thebattery module beside the first in a similar manner. Label theoriginal modules with masking tape or some other identifier.

5. After removing a pair (one string) of battery modules, install areplacement pair. Replacements may be installed in emptycabinet slots before removing original battery modules.

Page 53: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Maintenance

47Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

6. When the battery modules have been replaced, reinstall thefront cover panel(s).

7. If the batteries are not properly installed, the Open Cell alarmactivates. Check the batteries in the slot indicated on the alarmscreen.

8. Using the shipping cartons of the new batteries, return the oldbatteries according to the normal return policy.

Power Module or Battery Charger Module ReplacementThe Avaya RS9 hot-swap feature allows you to replace a power moduleor battery charger module easily without disconnecting the load ordamaging the UPS.

NOTE The UPS may switch to internal bypass if the remaining power modules areinsufficient to supply the required power. If empty slots exist, install replacementmodules before removing original ones.

Use care in removing and installing power modules or battery chargermodules. To remove a power module:

1. Remove the front cover panel.

The panels have spring latches on the left and right sides thathold them in place.

2. Loosen the thumbscrew on the module handle. Press down onthe latch release at the center of the module handle and pull thehandle down.

As the module handle fully extends, the module disconnects.Slide the module slowly out of the cabinet.

3. Use two hands to support the module. When fully extended,lower the front down slightly and lift the rear edge over thesafety stop on the center support rail.

4. Treat the original and replacement modules with care to avoiddamaging connectors or internal circuitry. Label the originalmodule with masking tape or some other identifier. Update thecustomer record to reflect the replacement parts.

Page 54: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Maintenance

48 Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

5. Insert the replacement module by sliding it carefully into thecabinet. Lower the front down slightly and lift the rear edgeover the safety stop on the center support rail. Keep the modulehandle extended until the module is fully inserted.

6. Raise the module handle to secure the module into the cabinet.Be sure the handle latch snaps into place. Tighten thethumbscrew on the handle.

7. Reinstall the front cover panel.

Page 55: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

49Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

C H A P T E R 9

SPECIFICATIONSThis section provides the following specifications for the Avaya RS9models:

S Electrical input and output

S Weights and dimensions

S Model specifications

S Battery

S Environmental and safety

Table 7. Electrical Input and Output

Nominal Input Voltage 200–240 Vac or 100/200, 110/220, 120/208, 120/240, 127/220 Vac

Input Voltage Range 152–239 Vac for 120/208 and 127/220.

Nominal Output Voltage 200–240 Vac or 100/200, 110/220, 120/208, 120/240, 127/220 Vac

Nominal Frequency Online: 60 Hz auto-sensing; output frequency tracks input frequency toselectable limit (±0.1 to ±5.0 Hz; ±3.0 Hz default); switches to batteryoperation outside this toleranceOn battery: 60 Hz ±0.1 Hz.

Regulation ±3% load regulation (under any line, load, or battery condition)

Voltage Waveform Sine wave; <3% THD at rated linear loads, computer-grade power

Overload Capability 150% for 10 seconds; 300% for 12 cycles

DC Input Protection DC fuse and battery charger overvoltage limit network for battery module

Output Protection Microprocessor-sensed overvoltage and overcurrent, with fuse backup

Efficiency in Double-Conversion mode >88%

Table 8. Weights and Dimensions

Cabinet Size Height Width Depth Weight*

9-slot 47.0I (119.5 cm) 24.0I (61 cm) 28.5I (72.5 cm) 158 lb (72 kg)

Each power module weighs 17 lb (8 kg)Each battery module weighs 30 lb (14 kg)Each battery charger module weighs 17 lb (8 kg)

Page 56: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Specifications

50 Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

Table 9. Split-Phase Model Specifications

9 kVA, 7500 Watts

Voltage Input Current* Output Current Input Service** Heat DissipationNormal Mode

100/200 48A 45A

110/220 45A 41A

120/208 42A 43.5A 60A 860W (2.93 kBTU/hr)

127/220 39A 41A

( / )

120/240 42A 37.5A

12 kVA, 10000 Watts

Voltage Input Current* Output Current Input Service** Heat DissipationNormal Mode

100/200 64A 60A

110/220 60A 55A

120/208 56A 58A 80A 1145W (3.90 kBTU/hr)

127/220 52A 55A

( / )

120/240 56A 50A

15 kVA, 12500 Watts

Voltage Input Current* Output Current Input Service** Heat DissipationNormal Mode

100/200 80A 75A

110/220 75A 70A

120/208 70A 72.5A 100A 1430W (4.88 kBTU/hr)

127/220 65A 70A

( / )

120/240 70A 62.5A

*In Bypass modes the input current equals the output current plus 2A for each power module in the system.For redundant power module operation (N+X), increase the input current rating by 2A for each additional redundant powermodule.**To accommodate the feature of easy system expandability, it is recommended that initial installation of the Avaya RS9UPS contain wiring to support the maximum capacity of the UPS cabinet. If you are installing a battery charger module,refer to the input circuit breaker requirements in Table 1 on page 12.

Page 57: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Specifications

51Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

Table 9. Split-Phase Model Specifications (continued)

18 kVA, 15000 Watts

Voltage Input Current* Output Current Input Service** Heat DissipationNormal Mode

100/200 96A 90A

110/220 90A 84A

120/208 84A 77A 125A 1720W (5.85 kBTU/hr)

127/220 78A 84A

( / )

120/240 84A 75A

*In Bypass modes the input current equals the output current plus 2A for each power module in the system.For redundant power module operation (N+X), increase the input current rating by 2A for each additional redundant powermodule.**To accommodate the feature of easy system expandability, it is recommended that initial installation of the Avaya RS9UPS contain wiring to support the maximum capacity of the UPS cabinet. If you are installing a battery charger module,refer to the input circuit breaker requirements in Table 1 on page 12.

Table 10. Battery

Configuration (2) 60V, 7.2 Ah batteries per string

Voltage 120 VdcBattery charger module: 133 Vdc

Type Sealed, maintenance-free, valve-regulated, lead-acid

Charging Recharge time: 4 hr after full-load resistive discharge; 8 hr after half-load resistivedischarge, using standard internal battery charger.Optional battery chargers at higher current ratings are available for the External BatteryModule Cabinet.A battery charger is required when using an Extended Battery Cabinet. See the EBC manualfor information.

Estimated Battery Life Internal battery strings and EBMC: 3–5 years dependent upon the number ofdischarge/charge cycles and the operating temperature.EBC A through F: 8-10 years dependent upon the number of discharge/charge cycles andthe operating temperature.

Page 58: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Specifications

52 Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

Table 11. Environmental and Safety

Operating Temperature 0°C to 40°C (32°F to 104°F)Optimal battery performance: 25°C (77°F)

Storage Temperature UPS with battery modules: –20°C to +40°C (–4°F to 104°F)UPS without batteries: –40°C to +60°C (–40°F to 140°F)

Relative Humidity 5–95% noncondensingDo not operate near water or excessive humidity (95% max).

Operating Altitude Up to 3,050 meters above sea level (10,000 ft)The maximum operating ambient temperature decreases 1°C per 300m above 1525m(2°F per 1000 ft above 5000 ft)

Non-Operating Altitude Up to 12,200 meters above sea level (40,000 ft)

Ventilation The air around the UPS must be clean and free of dust, corrosive chemicals, and othercontaminants. The Avaya RS9 UPS uses internal fans to circulate the air for cooling. The airmust be free to circulate around the UPS and battery cabinet(s). Do not operate the UPS ina sealed room or container.

Audible Noise Less than 53 dBA

Surge Suppression ANSI C62.41 Category B (formerly IEEE 587); IEC 61000-4-5

Safety Conformance CAN/CSA C22.2, No. 107.1; UL 1778;EN 50091-1-1 and IEC 60950

Agency Markings UL, cUL, TÜV, CE, C-Tick

EMC (Class A) EN 50091-2, FCC Part 15, ICES-003, VCCI

Page 59: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

53Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

C H A P T E R 10

TROUBLESHOOTINGThe following questions provide a few quick-to-find answers tocommonly asked questions.

Table 12. Frequently Asked Questions

Question: “How do I... ” Answer

Turn the UPS on? Verify that all power modules are securely plugged into the cabinet, and eachmodule handle is latched.If an External Battery Module Cabinet is installed, confirm that the DCdisconnect switch button on the back of the EBMC is closed (pulled out). Toclose the DC disconnect switch button, insert the switch key supplied with thecabinet into the button and turn clockwise 1/2-turn. Pull the button out to closethe switch. Turn the key back counter-clockwise, and remove the key.If Extended Battery Cabinets are installed, confirm that the battery circuitbreaker on each EBC front panel is in the ON (���) position.Refer to the front panel display and press the button labeled ON. (If On/Offcontrol is password-protected, enter the user password: 0377.) Confirm theselection by pressing the button labeled Yes. After a few seconds, the greenLED illuminates to signal the UPS is operating and producing power.

Turn the UPS off? Refer to the front panel display and press the button labeled OFF. Confirm theselection by pressing the button labeled Yes. (If On/Off control is password-protected, enter the user password: 0377.)In the event of a front panel display failure, you can turn the unit on or off usinga computer connected to the communication port.In an emergency or when the above two methods fail to turn the unit off,remove the front cover panels, and unlatch and pull the handles of all powermodules out at least one inch (2.5 cm) to turn off the power control circuitry. Ifyour UPS has an EBMC, push in the DC disconnect switch button on the back ofthe battery cabinet. If EBCs are installed, switch the battery circuit breaker oneach EBC front panel to the OFF (O) position.

Turn off the alarm beeps? Press the lower left button on the front panel display. Note the alarm messageand see “Alarms” on page 54 to correct the problem. After the problem hasbeen resolved, press the lower center button to clear the alarm.

View the alarm log? Go to menu 2-2. Press the button to view the most recent alarm. Press thebutton to scroll down through the log to view older alarms.

B

Install the LanSafe software? See the instructions accompanying the LanSafe software CD.

Page 60: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Troubleshooting

54 Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

AnswerQuestion: “How do I... ”

Check the input or output voltage? Go to menus 1-1-2 and 1-1-3 for the input voltage; go to menus 1-2-2 and 1-2-3for the output voltage.

Check the battery voltage? Go to menu 1-3-1. To view other system status parameters, see the Menu mapon page 40.

Check the condition of the batteries? The results of the most recent battery test are stored at menu 3-1-2-1. To run atest of battery condition, go to menu 3-1-1 and press the button. When thetest is complete, the results are again stored in the Battery Results parameter.

Change the battery low-voltage alarmthreshold? (or any other alarm oroperating limit?)

This is one of the parameters that require a trained person, knowing the correctpassword, to perform. Without the proper password, you are only able to viewoperating limits, not change them. Only authorized personnel should changethese limits. For information about making this or other password-protectedadjustments, contact your Avaya service representative.

Change the level of systemredundancy?

To view or change the redundancy level, go to menu 4-2-5.

Change the batteries? Each side-by-side pair of battery modules forms one series string on the batterybus. See “Battery Replacement” on page 46 for the battery replacementprocedure.

Add/delete one or more strings ofbatteries?

Physically install or remove battery modules as described on page 24. Recordcapacity of external battery strings by going to menu 4-2-6.

Add/delete one or more powermodules?

Physically install or remove power modules as described on page 24. Thesystem operating software senses the number and location of all powermodules in the cabinet. If you want to change the number of redundant powermodules, go to menu 4-2-5 and change the level of system redundancy.

AlarmsFigure 28 shows a typical alarm display. Alarms are annunciated by aconstant Alarm LED and a constant beep. During alarm display, button(A) silences the audible alarm, button (B) clears the alarm display, andbutton (C) performs the normal Escape function to exit from the alarmdisplay. The button enables you to scroll through all alarms.

Page 61: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Troubleshooting

55Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

S High AC Input

System

(A) (B) (C)

(Silence) (Clear) (ESC)

Figure 28. Typical System Active Alarm Display

Figure 29 shows a detailed alarm entry. Some alarms provide additionalinformation on the second line of the display to help identify the causeof the alarm. The third line may also display a specific slot numberwhere the fault occurred. If the alarm is not specific to a slot number,“System” appears on the display.

M Batt Test Failed 1Open CellSlot 4

(A) (B) (C)

(Silence) (Clear) (ESC)

Figure 29. Detailed Alarm Entry

When the Avaya RS9 UPS detects an alarm condition, the UPS displaysthe alarm with the following indications:

S the red LED next to the front panel display illuminates

S sounds an audible alarm

S displays an alarm message

Page 62: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Troubleshooting

56 Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

When this happens, follow these steps:

1. Observe the display to see which alarm is active.

NOTE To find out if more than one alarm is active, press . This switches the displaybetween alarm messages. To silence the audible alarm, press button (A) below thedisplay.

2. Find the alarm message in Table 13 or Table 14 and follow theinstructions to resolve the problem. To clear an alarm afterresolving the problem, press button (B) below the display. Ifthe problem is still present, the alarm will sound again after ashort delay.

Table 13 contains descriptions of critical alarm messages. Critical alarmsrequire immediate operator attention and corrective action.

Table 13. Critical Alarm Messages

Alarm Message What It Means What to Do

A Low Battery The UPS has shut down after runningon battery and discharging thebatteries.

Wait for AC input power to be restored. When AC inputpower returns, the UPS begins recharging batteries andapplies power to the load.

C High Battery The battery voltage is too highbecause of a charger problem,battery problem, or incorrectparameter setting.

Contact your Avaya service representative.

E Low AC Output The UPS has shut down because theAC output voltage is too low toprovide power to the load.

Contact your Avaya service representative.

F High AC Output The UPS has shut down because theAC output voltage is too high.

Contact your Avaya service representative.

S High AC Input The AC input voltage is too high; anyfurther increase to the voltage maydamage the UPS.

This alarm automatically clears when input voltagereturns to normal limits. The UPS will continue to supportthe load until the batteries are depleted.

G Output Overload The load is requiring more powerthan the UPS power modules arecapable of supplying, and the UPShas switched to Bypass mode.

Switch off your equipment one piece at a time until thealarm stops.

I Overload Shutdown The UPS has shut down due toexcessive load.

Remove excess load(s) from the UPS output and restartthe UPS by pressing the ON button through the frontpanel display.

Page 63: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Troubleshooting

57Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

What to DoWhat It MeansAlarm Message

H High HeatsinkTemperature

The inverter temperature is too high.If the temperature reaches a presetlimit, the unit will shut down.

Shut down your equipment and turn the UPS off. Contactyour Avaya service representative.

P EPO The Emergency Power-Off functionhas been activated.

Deactivate the external EPO switch and restart the UPSby pressing the ON button through the front paneldisplay.

T Call Service The UPS has detected a problem thatrequires service.

Contact your Avaya service representative.

T Call ServicePhase Error

The UPS has detected the inputphase rotation to be incompatiblewith its output wiring and will notstart up.

Correct the input wiring problem and restart the UPS.

T Call ServiceModule Failure

A power module has detected aninternal fault and has shut down.

Look for the slot number (third line on display) of thepower module and replace the defective module.

T Call ServiceExcessive Transfers

The UPS has detected an excessivelyhigh number of automatic transfersand has switched to DoubleConversion (Auto) mode.

Contact your Avaya service representative.

T Call ServicePrecharge Failure

A power module has detected aninitialization sequence problem andwill not start up.

Look for the slot number (third line on display) of theaffected module. Contact your Avaya servicerepresentative.

T Call ServiceIncompatible Module

A power module with incompatiblefirmware has been installed in thesystem.

Look for the slot number (third line on display) of theaffected module. Contact your Avaya servicerepresentative.

5 Fan Failure The UPS has detected a module fanproblem that requires service.

Contact your Avaya service representative.

Page 64: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Troubleshooting

58 Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

Table 14 contains descriptions of non-critical alarm messages.Non-critical alarms are not as urgent as critical alarms, but should beattended to as soon as convenient to avoid the problem becomingcritical.

Table 14. Non-Critical Alarm Messages

Alarm Message What It Means What to Do

B Near Low Battery The battery voltage has reached theNear Low Battery set point.

If the voltage increases, the alarm clears automatically. Ifit drops further, it will cause a Low Battery alarm.

D Low Runtime Batteries in the unit are nearlydischarged.

Perform an orderly shutdown of all equipment and waitfor AC input power to return. When AC input powerreturns, the UPS begins recharging batteries andautomatically restarts.

O Check Memory The configuration as stored in thesystem memory may have beencorrupted.

Look for the slot number (third line on display) of thefailed module. Contact your Avaya service representative.

M Check Battery The batteries have failed anautomatic system test.

Contact your Avaya service representative.

M Check BatteryOpen Cell

A battery (pair of modules) has failedan open cell test.

Look for the slot number (third line on display) of thefailed modules. Verify that both battery modules areproperly installed. If properly installed, replace bothbattery modules.

M Check BatteryWeak Battery

The system batteries have degradedto the point where system runtime isless than the designed rating.

Replace all battery modules.

U Low Redundancy The number of active power modulesis too low to provide the programmedredundancy level to protect thecurrent load.

The unit is able to protect the equipment, but will not befault tolerant. To regain the desired redundancy, eitheradd power modules or reduce the load.

U Low RedundancyInsufficient Batteries

The UPS load exceeds 2800 watts perbattery string. The system will protectthe load during short power outages,but battery degradation or damagemay result.

Reduce the load or install additional battery modules (twomodules per string).

U Low RedundancyInsufficient Modules

The number of active power modulesis too few to provide the programmedredundancy level while protecting theload. The UPS will protect the load,but will not be fault tolerant.

Reduce the load or install additional power modules.

Page 65: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Troubleshooting

59Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

Obtaining ServiceThe troubleshooting chart covers most of the difficulties you mayencounter during normal operations. If you have any questions orproblems with your UPS, call your Avaya service representative or theappropriate telephone number on the service label of your UPS.

Please have the following information ready when you call:

S Model number

S Serial number

S Version number (if available)

S Date of failure or problem

S Symptoms of failure or problem

S Customer return address and contact information

Parts ListItem Material Code Description

9-Slot UPS Enclosure 700326689 RS9 UPS Chassis 9-Slot Enclosure Hardwired In/Out

9-Slot EBMC 700326705 RS9 UPS Battery Chassis 9-Slot Enclosure

SNMP Web Adapter 700249048 RS9 ConnectUPStWeb/SNMP Card

3 kVA Power Module 700248974 RS9 3 kVA UPS Power Module

Battery Module 700248982 RS9 Internal Battery Module

20A Charger Module 700249030 RS9 Internal 20A Battery Charger Module

EBC A 700326721 RS9 1CR1-10TC150C-120-H225-CA Extended Battery Cabinet (A)

EBC B 700326739 RS9 1CR3-20TC100S-120-H225-CA Extended Battery Cabinet (B)

EBC C 700326747 RS9 1CR3-20TC150C-120-H225-CA Extended Battery Cabinet (C)

EBC D 700326754 RS9 1CR6-30TC120S-120-H225-CA Extended Battery Cabinet (D)

EBC E 700326762 RS9 1CR6-30TC150C-120-H225-CA Extended Battery Cabinet (E)

EBC F 700326770 RS9 1CR4-40TC150C-120-H225-CA Extended Battery Cabinet (F)

Page 66: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

Troubleshooting

60 Avayat RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual S 164201543 Rev A

Page 67: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot
Page 68: Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot ...lit.powerware.com/ll_download.asp?file=9_18RS9UPS9slot.pdf · Avaya RS9 Uninterruptible Power Systems (9–18 kVA, 9-Slot

164201543 A*164201543A*