Front Facia 4 position operating mode keyswitch:– Off/reset Lamp Test Auto Test (Manual) 7 status/fault LEDs OFF RESET SERIES 700 START FAIL LOW OIL PRESS HIGH TEMP OVERSPEED MAINS FAIL CHARGE FAIL PLANT FAIL LAMP TEST AUTO TEST Top Facia and Switch Settings NO 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 S1 1 to 9 S2 S3 S4 S5 +ve DC closed to –ve open from –ve closed to +ve open from +ve –ve DC Number of Start Attempts LOP and HET input fault state Lamp Test input/output polarity BATTERY –VE CHARGE FAIL BATTERY +VE NOT USED MAG PICKUP AUTO MODE O/P CRANK O/P BATTERY +VE FUEL O/P ALARM O/P S1 S2 S3 S4 S5 LOAD RELAY NO LOAD RELAY COM LOAD RELAY NC L N LAMP TEST 1mA METER +VE TEMP INPUT INTERLOCK OIL INPUT MAINS FAIL Generator AC 300 V rms MAX STOP START –VE AUTOSTART 700 % OVERSPEED COOL C/BACK START 100 - 120 % TIME DELAYS 5 MIN 60 MIN 60 SEC Rear Facia and Electrical Connection ON OFF 1 2 3 Battery –ve DC power supply Charge fail warning input Battery +ve DC power supply – No connection – L N Lamp test input/output Tacho/calibration meter output High Engine Temp. (HET) input Interlock (plant fail) input: –ve DC Low Oil Pressure (LOP) input Mains fail input 14 15 16 17 18 19 20 21 22 23 4 5 6 7 8 9 10 11 12 13 SW1 Switch settings: (N.B. ON = up, OFF = down) SW3a SW2 SW3b ON OFF ON OFF ON OFF 12 V DC power supply 24 V DC power supply Battery charger fail warning Charge alternator fail warning Generator AC speed sensing Magnetic pickup speed sensing Load relay enabled in Test mode Load relay disabled in Test mode Starter motor pulse/dwell time: 0.5 - 30 seconds Low Oil Pressure and High Engine Temperature fault override timer: 0.5 - 30 seconds Speed calibration:– Connect 0 – 1mA meter (meter +VE to pin 17, meter –VE to pin 1), run the engine at normal speed, then adjust potentiometer until meter reads 0.75mA. ve test/manual stop test/manual start Generator AC 50/60Hz. 300 VAC max. Magnetic pickup input Auto mode output: +ve, 250mA Crank relay output: +ve, 16A max. + ve DC (feed for relays) Fuel relay output: + ve, 16A max. Alarm relay output: + ve, 5A max. NO CO NC Load relay output: volt free contacts Typical Connection (Automatic Mains Fail Application) Fuel LOP manual start manual stop HET plant fail (interlock) Autostart 700 RFL RST RAL 1A Auto Calibration/ RPM meter 0 - 1mA 75 Ohm Magnetic Pickup ve DC +ve DC MCR UVR MCR1 LOAD mains contactor gen contactor GCR1 GCR G E N E R A T O R L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N 1 2 3 4 5 6 M A I N S fuse 5A WL + Starter Alarm 20 22 21 9 7 10 11 12 13 18 19 14 15 1 3 8 23 2 5 17 6 Panel Installation 1 B A 92 92 (mm) 2 C D E Autostart 700 (model numbers AS3/E…) Engine/Generator Controller Installation Reference Sheet mi5316 revision B, 8 th October 2001 catalogue section 75

Autostart_700

Embed Size (px)

DESCRIPTION

Autostart_700

Citation preview

  • Front Facia 4 position operating mode keyswitch: Off/reset Lamp Test Auto Test (Manual)

    7 status/fault LEDs

    OFFRESET

    SERIES 700

    START FAIL

    LOW OIL PRESS

    HIGH TEMP

    OVERSPEED

    MAINS FAIL

    CHARGE FAIL

    PLANT FAIL

    LAMPTEST AUTO TEST

    Top Facia and Switch Settings

    NO

    0 1 2

    3

    4 5 6 7 8 9

    0 1 2 3

    4 5 6 7 8 9

    S11 to 9

    S2 S3 S4

    S5+ve DC

    closed to ve

    open from ve closed to +ve

    open from +ve

    ve DC

    Number of Start Attempts

    LOP and HET input fault state

    Lamp Test input/output polarity

    BATTERY VECHARGE FAILBATTERY +VENOT USEDMAG PICKUPAUTO MODE O/PCRANK O/PBATTERY +VEFUEL O/PALARM O/P

    S1 S2 S3 S4 S5

    LOAD RELAY NOLOAD RELAY COMLOAD RELAY NCLNLAMP TEST1mA METER +VE

    TEMP INPUTINTERLOCKOIL INPUTMAINS FAIL

    Generator AC300 V rms MAX

    STOP START

    VE

    AUTOSTART 700

    % OVERSPEED COOL C/BACK START100 - 120 %

    TIME DELAYS

    5 MIN 60 MIN 60 SEC

    Rear Facia and Electrical Connection

    ONOFF

    123

    Battery ve DC power supplyCharge fail warning inputBattery +ve DC power supply No connection

    LNLamp test input/output Tacho/calibration meter output

    High Engine Temp. (HET) inputInterlock (plant fail) input: ve DCLow Oil Pressure (LOP) inputMains fail input

    14151617181920212223

    456789

    10111213

    SW1Switch settings: (N.B. ON = up, OFF = down)

    SW3a

    SW2

    SW3b

    ONOFF

    ONOFF

    ONOFF

    12 V DC power supply24 V DC power supply

    Battery charger fail warningCharge alternator fail warning

    Generator AC speed sensingMagnetic pickup speed sensing

    Load relay enabled in Test modeLoad relay disabled in Test mode

    Starter motor pulse/dwell time:0.5 - 30 seconds

    Low Oil Pressure and HighEngine Temperature fault override timer: 0.5 - 30 seconds

    Speed calibration:Connect 0 1mA meter (meter +VE to pin 17, meter VE topin 1), run the engine at normal speed, then adjust potentiometer until meterreads 0.75mA.

    vetest/manual stoptest/manual start

    Generator AC 50/60Hz.300 VAC max.

    Magnetic pickup inputAuto mode output: +ve, 250mACrank relay output: +ve, 16A max.+ ve DC (feed for relays)Fuel relay output: + ve, 16A max.Alarm relay output: + ve, 5A max.NOCONC

    Load relay output:volt free contacts

    Typical Connection (Automatic Mains Fail Application)

    Fuel

    LOP

    man

    ual

    star

    tm

    anua

    lst

    op

    HET

    plant fail(interlock)

    Autostart700

    RFL

    RST

    RAL

    1A

    Auto

    Calibration/RPM meter

    0 - 1mA75 Ohm

    MagneticPickup

    ve DC

    +ve DC

    MCRUVR

    MCR1

    LOADmainscontactor

    gencontactor

    GCR1

    GCR

    GENERATOR

    L1L2L3N

    L1L2L3N

    L1 L2 L3 N

    L1 L2 L3 N

    1 2 3 4 5 6

    MAINS

    fuse5A

    WL+

    Starter

    Alarm

    20

    22

    21971011121318191415

    1

    38

    23

    2

    5

    17

    6

    Panel Installation 1

    B A

    92

    92(mm)

    2

    C D

    E

    Autostart 700 (model numbers AS3/E) Engine/Generator Controller Installation Reference Sheet

    mi5316revision B, 8th October 2001

    catalogue section 75

  • FWMurphy - Autostart 700 installation reference sheet mi5316 revision B 8th October 2001 p2/2

    Electrical Connection Electrical connection to the Autostart 700 is via individual 1/4 inch blade terminals. All connections should be made with Autostart switched off and the wiring isolated from the DC/AC supply:- Pin Function

    1 3

    Negative DC power supply Positive DC power supply Before connection of these terminals, switch 1 (brown) at the rear must be set for the correct supply voltage:- Switch 1 on (up) 12 VDC operation (9 - 16 V) Switch 1 off (down) 24 VDC operation (18 - 32 V) The AS700 has an internal, self-recharging Ni-Cd battery that protects against DC supply brown-outs during engine cranking. The internal battery charge is maintained as long as pins 1 and 3 are connected to the DC supply. Note: the internal battery means that Autostart cannot be reset or powered down by removing the DC power connections. Use a 5 Amp anti-surge fuse in the positive DC power line (pin 3).

    2 Charge fail input This may be activated by external connection to negative DC. Pin 2 may therefore be connected to a charge alternator WL terminal (Autostart provides the necessary excitation current), or to the 'charge fail' output of a Murphy BC700 series charger, or direct to negative DC via relay contacts which close on fault. Rear facia switch 3a (orange) allows further control of the front facia charge fail LED indicator:- Sw 3a on (up) Mains charger mode (LED always active) Sw 3a off (down) Charge alternator mode (LED overridden before engine startup)

    5 Magnetic pickup Allows optional use of a magnetic pickup engine speed sensing. Rear facia switch S2 (red) must be set DOWN. Connect one terminal of the pickup to pin 5, the other terminal to pin 1 or battery negative. The interconnection must use a two core and screen cable, with the screen earthed at one end only. If a magnetic pickup is not used, leave pin 5 open circuit.

    6 Auto mode output Pin 6 gives a positive DC output (250mA max.) while the unit is switched to Auto mode.

    8 Positive DC (feed for relays) Pin 8 is the common positive DC feed for the Crank, Fuel and Alarm outputs (pins 7, 9 and 10).

    7 9

    Crank output Fuel output Pins 7 and 9 give positive DC outputs (max. rating 16 Amps) for the control of engine fuel and starter motor circuits. Murphy recommend the connection of slave relays with suppressed coils between each output and the fuel/starter motor solenoid coils.

    10 Alarm output Pin 10 gives a positive DC output (maximum rating 5 Amps) when Autostart has detected a fault and has shutdown the engine.

    11 12 13

    Load relay: normally open contact Load relay: change-over contact Load relay: normally closed contact The load relay is a volt-free set of SPCO relay contacts, used for the control of the generator contactor. The relay activates immediately after a generator start, provided that the generator is running within

    normal frequency, voltage and oil pressure limits. Once the mains fail input de-activates, the load relay will remain energised (keeping the generator on load) until the changeback timer has expired.

    14 15

    Generator AC Live Generator AC Neutral

    DANGER ! HIGH VOLTAGE

    Autostart uses these terminals to sense generator voltage. Pins 14 and 15 are also optionally used to sense frequency (depending on the setting of rear switch S2). Frequency and voltage information are needed for the correct operation of the crank release, load relay and overspeed trip.

    A 1 Amp anti-surge fuse should be connected in series with the generator live terminal (pin 14).

    16 Lamp Test input/output Switch S5 on the top facia sets the DC polarity of this input/output. Used as an input, all LEDs light when this pin is connected to the correct polarity DC rail. As an output, this pin gives the selected polarity signal when the Autostart is switched to LAMP TEST. WARNING: incorrect polarity switch setting and connection will result in internal shorting and damage to Autostart and panel wiring.

    17 RPM Meter/calibration output This output, with the rear facia multi-turn potentiometer, is used to calibrate the Autostart's speed sensing circuit this is necessary for the correct operation of the crank release, load switching and overspeed trip. After correct calibration, the output may also be used to drive a suitably scaled engine tachometer. With the engine running normally and Autostart correctly calibrated, this terminal should give a 0.75mA output into a 75 Ohm meter.

    18 19

    Manual StartManual Stopve DC

    These terminals may be wired as above, providing operator controlled starting and stopping of the engine when the Autostart is in test/manual mode. Alternatively, hard-wire pins 18 and 19 to battery negative to give an immediate engine start on switching to test mode.

    20 22

    High Engine Temperature (HET) switch input Low Oil Pressure (LOP) switch input These inputs are dedicated for use with low oil pressure (LOP) and high engine temperature (HET) fault switches. Top facia switches S2, S3 and S4 allow the inputs to be configured for fault switches which open or close on fault, with wiring to either positive or negative DC.

    Each fault switch is wired between the input and the appropriate DC rail. An 'active' input results in the automatic, immediate shutdown of the engine, and the lighting of the appropriate front facia LED.

    23

    Mains fail input Use this input to initiate an automatic engine start. Pin 23 must be switched to battery positive when the generator is required to be on standby, and made open circuit to initiate an automatic start.

    Further information: - Document Ref. Description ms5893 AS700 sales bulletin and specification

    FRANK W MURPHY LTD. Church Road, Laverstock, Salisbury, SP1 1QZ, United Kingdom tel: +44 (0)1722 410055 fax: +44 (0)1722 410088 email: [email protected] web: www.fwmurphy.co.uk

    In order to consistently bring you the highest quality, full featured products, we reserve the right to change our specifications and designs at any time.