AUTOMATIC SPRINKLERS UPRIGHT, PENDENT, HORIZONTAL SIDEWALL & CONCEALED PENDENT

Page 2: AUTOMATI SPRINKLERS - Maceden

BRISTOL Sprinkler System Datasheets Rev. 0 2

CO

NT

EN

TS

Upright Sprinkler ………….………….………….………….………….………….………….………….…………………... 3

Pendent Sprinkler ………….………….………….………….………….………….………….………….…………………. 3

Horizontal Sidewall Sprinkler ………….………….………….………….………….………….………….………….…….. 4

Concealed Pendent Sprinkler ………….………….………….………….………….………….………….………….…. 5

Alarm Check Valve ………….………….………….………….………….………….………….………….………………. 7

Deluge Valve ………….………….………….………….………….………….………….………….………………………. 8

Other Valve ………….………….………….………….………….………….………….………….……………………….. 9

CONTENTS

Page 3: AUTOMATI SPRINKLERS - Maceden

BRISTOL Sprinkler System Datasheets Rev. 0 3

AU

TO

MA

TIC

SP

RIN

KLE

R S

YS

TE

M

MODEL: BF001 / BF005 / BF002 / BF004

STANDARD SPRAY, STANDARD / QUICK RESPONSE,

5/3mm BULB TYPE, K5.6, ½” CONNECTING THREAD

UPRIGHT SPRINKLERS AND

PENDENT SPRINKLERS

The BF001/BF005 Standard/Quick Response

Upright and BF002/BF004 Standard/Quick

Response Pendent.

Sprinklers (Ref. Figure A) are automatic sprin-

klers of the frangible bulb type. They are

“standard/quick response – standard orifice

spray sprinkler” intended for use in fire sprinkler

systems designed in accordance with the

standard installation rules recognized by the

applicable Listing or Approval agency (e.g.,

UL Listing is based on NFPA 13 requirements).

The Upright, Pendent Sprinklers all produce a

hemispherical water distribution pattern be-

low the deflector.

Sprinkler Operation

During a fire conditions, the thermal‐sensitive

liquid in the glass bulb expands, causing the

bulb to shatter, releasing the button and

spring seal assembly. Water flowing through

the sprinkler orifice strikes the sprinkler deflec-

tor, forming a uniform spray pattern to extin-

guish or control the fire.

Coverage

For coverage area and sprinkler placement,

refer to NFPA13 standards.

Description

Model & Sprinkler I.D. No. BF001 BF005 BF002 BF004

Style Upright Pendant

Bulb Nominal Dia. & Response

Ø5mm,

Standard

Response

Ø3mm,

Quick Re-

sponse

Ø5mm,

Standard

Response

Ø3mm, Quick

Response

Thread Size (Optional) NPT ½ or R ½

Nominal Orifice Size ½ Inch

Nominal K‐factor 5.6 (U.S.) / 80 (metric)

Max. Working Pressure 175 psig / 1.2 MPa (12 bar)

Factory Hydrostatic Test 100% @ 500 psig (3.4 MPa)

Min. Operating Pressure 7 psig / 0.048 MPa (0.48 bar)

Sprinkler Finish (Optional) Natural Brass / Chrome Plated / White Color Coated

Escutcheon Finish Chrome Plated or Color Coated in any color

Listings and Approvals UL (United States) / ULC (Canada)

Technical Specifications:

FIGURE A: MODEL BF001/BF005 UPRIGHT & MODEL BF002/BF004 PENDENT SPRINKLERS

Sprinkler Materials

Frame …………… Brass Casting DZR

Deflector……...… Brass UNS-2800

Glass Bulb……….. Glass with Glycerin Solution

JOB® G5 for BF001/BF002

JOB® F3 for BF005/BF004

Set Screw………... Brass UNS-28000

Button…………….. Brass UNS-28000

Spring……………… Stainless Steel

Seal………………… Teflon Tape

Standard Eskutcheon…… Cold Rolled Steel

Page 4: AUTOMATI SPRINKLERS - Maceden

AU

TO

MA

TIC

SP

RIN

KLE

R S

YS

TE

M

BRISTOL Sprinkler System Datasheets Rev. 0 4

MODEL: BF007 / BF008 STANDARD SPRAY, STAND-

ARD / QUICK RESPONSE, 5/3mm BULB TYPE, K5.6, ½”

CONNECTING THREAD

Description

Horizontal sidewall sprinklers are generally used in lieu of pendent

and upright sprinklers because of building construction or installa-

tion economy considerations. They are designed for installation

along a wall or the side of a beam and just beneath a smooth

ceiling. Installed with their centerline of waterway horizontal,

these sprinklers produce a quarter‐spherical water discharge pat-

tern that is predominately directed downward and outward from

the deflec or; however, a portion of the spray is also directed

towards the back wall.

Model BF007/BF008, Standard / Quick Response Horizontal Side-

wall Sprinklers (Ref. Figure A), are automatic sprinklers of the

frangible bulb type, and standard spray, 1/2” orifice, 5 / 3 mm

bulb. They are “standard / quick response ‐ standard orifice sidewall

sprinklers” intended for use in fire sprinkler systems designed in ac-

cordance with the standard installation rules recognized by the ap-

plicable Listing or Approval agency (e.g., UL Listing is based on NFPA

13 requirements)

Sprinkler Operation

During a fire conditions, the thermal‐sensitive liquid in the glass

bulb expands, causing the bulb to shatter, releasing the button

and spring seal assembly. Water flowing through the sprinkler ori-

fice strikes the sprinkler deflector, forming a uniform spray pattern

to extinguish or control the fire.

Coverage

For coverage area and sprinkler placement,

refer to NFPA13 standards.

Model & Sprinkler I.D. No. BF007 BF008

Style Horizontal Sidewall

Bulb Nominal Dia. & Response Ø5mm, Standard

Response

Ø3mm, Quick Re-

sponse

Thread Size (Optional) NPT ½ or R ½

Nominal Orifice Size ½ Inch

Nominal K‐factor1 5.6 (U.S.) / 80 (metric)

Max. Working Pressure 175 psig / 1.2 MPa (12 bar)

Factory Hydrostatic Test 100% @ 500 psig (3.4 MPa)

Min. Operating Pressure 7 psig / 0.048 MPa (0.48 bar)

Sprinkler Finish (Optional) Natural Brass / Chrome Plated / White Color

Coated

Listings and Approvals UL (United States) / ULC (Canada)

Technical Specifications:

Sprinkler Materials

Frame ………………………… Brass Casting DZR

Deflector……………………… Brass UNS-2800

Glass Bulb…………………….. Glass with Glycerin Solution

JOB® G5 for BF007

JOB® F3 for BF008

Set Screw……………………... Brass UNS-28000

Button………………………….. Brass UNS-28000

Spring…………………………… Stainless Steel

Seal……………………………… Teflon Tape

Standard Eskutcheon………… Colrd Rolled Steel FIGURE B: MODEL BF007 / BF008 HORIZONTAL SIDEWALL SPRINKLERS

HORIZONTAL SIDEWALL

SPRINKLER

Page 5: AUTOMATI SPRINKLERS - Maceden

AU

TO

MA

TIC

SP

RIN

KLE

R S

YS

TE

M

BRISTOL Sprinkler System Datasheets Rev. 0 5

MODEL: BF007 / BF008 STANDARD SPRAY, STAND-

ARD / QUICK RESPONSE, 5/3mm BULB TYPE, K5.6, ½”

CONNECTING THREAD

Description

The BF003/BF006 Standard/Quick Response Concealed Pendent Sprin-

klers (Ref. Figure A) are automatic sprinklers of the frangible bulb type.

They are “standard/quick response – standard orifice spray sprinkler”

intended for use in fire sprinkler systems designed in accordance with

the standard installation rules recognized by the applicable Listing or

Approval agency (e.g., UL Listing is based on NFPA 13 requirements).

The Concealed Pendent Sprinklers all produce a hemispherical water

distribution pattern below the deflector.

This model sprinkler includes a Cover Plate Assembly that conceals the

sprinkler operating components above the ceiling. The Cover Plate

Assembly, which installs onto the Sprinkler/ Mounting Cup Assembly,

consists of a Cover Plate that is soldered to an Enclosure at three equi-

distant locations around their peripheries. The Ejection Spring is located

between the flange of the Enclosure and the Cover Plate, to ensure

separation of the two pieces when the solder melts.

A Label located on the Cover Plate Assembly indicates the nominal

temperature of the sprinkler and the nominal diameter of the Glass

Bulb.

The small Cover Plate is flat with a low profile that blends in with

the ceiling for an aesthetically pleasing appearance. Standard

finishes for the Cover Plate are satin chrome plated and painted

white. Other factory applied painted finishes for the Cover Plate is

available on special order

The separable two‐piece design of the Cover Plate and Mounting

Cup Assemblies allows installation of the sprinklers and pressure

testing of the fire protection system prior to installation of a sus-

pended ceiling or application of the finish coating to a fixed ceiling.

The separable design also permits removal of suspended ceiling panels

for access to building service equipment, without having to first shut

down the fire protection system and remove sprinklers.

Also, the separable two piece design of the BF003 / BF006 Concealed

Sprinkler provides for 1/6 inch (4.2mm) of vertical adjustment, to re-

duce the accuracy to which the length of fixed pipe drops to the

sprinklers must be cut

Sprinkler Operation

During a fire conditions, the thermal‐sensitive liquid in the glass

bulb expands, causing the bulb to shatter, releasing the button

and spring seal assembly. Water flowing through the sprinkler ori-

fice strikes the sprinkler deflector, forming a uniform spray pattern

to extinguish or control the fire.

Coverage

For coverage area and sprinkler placement,

refer to NFPA13 standards.

Model & Sprinkler I.D. No. BF003 BF006

Style Concealed Pendent

Bulb Nominal Dia. & Response Ø5mm, Standard

Response

Ø3mm, Quick Re-

sponse

Thread Size (Optional) NPT ½ or R ½

Nominal Orifice Size ½ Inch

Nominal K‐factor1 5.6 (U.S.) / 80 (metric)

Max. Working Pressure 175 psig / 1.2 MPa (12 bar)

Factory Hydrostatic Test 100% @ 500 psig (3.4 MPa)

Min. Operating Pressure 7 psig / 0.048 MPa (0.48 bar)

Sprinkler Finish (Optional) Natural Brass / Chrome Plated / White Color

Coated

Listings and Approvals UL (United States) / ULC (Canada)

Technical Specifications:

Sprinkler Materials

Frame ………………………… Brass Forgoin UNS-C87400

Deflector……………………… Brass UNS-2800

Glass Bulb…………………….. Glass with Glycerin Solution

JOB® G5 for BF003

JOB® F3 for BF006

Set Screw……………………... Brass UNS-28000

Button………………………….. Brass UNS-28000

Mounting Cup………………… Low Carbon Sheet Steel UNS-G10080

Enclosure……………………….. Brass UNS-C2800

Ejection Spring…………………. Stainless Steel UNS-s30452

Spring…………………………… Stainless Steel

Seal……………………………… Teflon Tape

Label……………………………. Mylar (Sticky - Back)

FIGURE C: MODEL BF003 / BF006 CONCEALED PENDENT SPRINKLERS

CONCEALED PENDENT

SPRINKLER

Page 6: AUTOMATI SPRINKLERS - Maceden

BRISTOL Sprinkler System Datasheets Rev. 0 6

AU

TO

MA

TIC

SP

RIN

KLE

R S

YS

TE

M

Temp. Classification Ordinary Ordinary Intermediate Intermediate

Nominal Temp. Rating 135⁰F / 57⁰C 155⁰F / 68⁰C 175⁰F / 79⁰C 200⁰F / 93⁰C

Max. Ambient Temp. Allowed ⁵

115⁰F / 46⁰C

135⁰F / 57⁰C

155⁰F / 68⁰C

180⁰F / 82⁰C

Max. Recommended Ambient Temp. ⁶

100⁰F / 38⁰C

100⁰F / 38⁰C

150⁰F / 65⁰C

150⁰F / 65⁰C

Glass Bulb Color Orange Red Yellow Green

Available Temperature Rating

Discharge Coefficient

Sprinklers are rated for use at a maximum service pressure of 175

psig (12 bar). The nominal discharge curve plotted in Figure B

represents the flow “Q” in GPM (LPM) as determined by the fol-

lowing formula:

Q = K (P) 0.5

Q = Flow, GPM (LPM)

K = Discharge Coefficient, K = 5.6 (80)

P = Discharge Pessure, psig (bar)

MODEL: BF001 / BF005 / BF002 / BF004 /

BF003 / BF006 / BF007 / BF008

STANDARD SPRAY, STANDARD / QUICK

RESPONSE,

5/3mm BULB TYPE, K5.6, ½” CONNECTING

THREAD

Where,

Standard Escutcheon

Type E‐1

Installation Wrench

Type T‐1

Accessories

Page 7: AUTOMATI SPRINKLERS - Maceden

BRISTOL Sprinkler System Datasheets Rev. 0 7

AU

TO

MA

TIC

SP

RIN

KLE

R S

YS

TE

M

ALARM CHECK VALVE

Standard ………………………… ANSI/UL 193

Sizes :……………………………….4”/DN100 & 6” /DN150

Inlet Connection :………………. Flanged Class 150 ANSI

B16.1

Max. Working Pressure :………… 175psi / 12bar

Test Pressure :…………………….. 350psi / 24bar

Body Material :…………………… Ductile Iron

Accessories :……………………… Retard Chamber, Wa-

ter Motor Alarm, Alarm Pressure Switch

Standard Finish :………………….. RAL 3000 (Flame Red)

Model BAV-146 Alarm Check Valve is a wet pipe sprin-

kler system water supply check valve that makes

possible the installation of sprinkler systems in buildings

not subject to freezing temperatures. It is designed so

that water pressure in the piping system will hold back

water pressure at the valve until a significant flow of

water occurs. The Alarm Check Valve serves as a

check valve by trapping pressurized water above the

clapper and preventing reverse flow from sprinkler

piping.

Size 4" (DN100) 6" (DN150)

Inlet Connection Style Flange Groove Flange Groove

Outlet Connection Style Flange Groove Flange Groove

Shipping Weight 55 lbs∕25 kg 51 lbs∕23 kg 75 lbs∕34 kg 66 lbs∕30 kg

Max. Working Pressure 175 psig∕1.2 MPa (12 bar)

Factory Hydro Test 100% @ 350 psig∕2.4 MPa (24 bar)

Standard Finish Red Painted

Flange & Groove Specification Flange: Class 150 ANSI B16.1 & Groove: C606 ANSI∕AWWA

Required Accessories Standard Trim

Optional Accessories Retard Chamber, Water Motor Alarm, Alarm Pressure Switch

Installation Manner Vertically

Listings and Approvals UL (United States)

Valve Size H H1 H2 H3 H4 H5 H6 RefH7 H8 OD D1 D2 D3

4" Flange 270 2.0 23.9 40 83 193 230 77 103 Ø 228.6 Ø 190.5 Ø 157.5 Ø 19

6" Flange 346 2.0 23.9 53 111 270 244 76 132 Ø 279.4 Ø 241.3 Ø 215.9 Ø 23

DIMENSIONS

No. Part Name

1 Valve Body (Flanged Side)

2 Valve Body (Grooved Side)

3 Cover Plate

4 Seat Ring

5 Cover Plate Bolt

6 Spring Washer

7 Cover Plate Gasket

8 Clapper Seal Retainer

9 Clapper Seal

10 Clapper Screw

11 Clapper

12 Clapper Shaft

13 Clapper Bushing

Page 8: AUTOMATI SPRINKLERS - Maceden

BRISTOL Sprinkler System Datasheets Rev. 0 8

AU

TO

MA

TIC

SP

RIN

KLE

R S

YS

TE

M

DELUGE VALVE

For Solenoid Actuated

Available in sizes 4‖, 6‖, & 8‖

Quick response to air supply to pilot

No gland packing

Dry pilot trim when air is used for sprinkler system

BRISTOL DELUGE VALVE XT-4080P is used for Dry Pilot Trim-Air Operated Deluge System.

The valve can be used with direct air supply to the pilot in which case, the Deluge Valve

will open in case of Air Pressure Loss. The valve can also be used with Solenoid Valve,

where air is supplied to Pilot Valve through 3/2 way Solenoid Valve which keeps Deluge

Valve in closed condition.

In case of FIRE or TEST, the 3/2 way Solenoid Valve is energized, which removes air from

the Pilot Valve. This open the Pilot Valve and releases water from the cover chamber of

main valve which opens Main Valve - Deluge Valve.

PNEUMATIC/HYDRAULIC , XT-4080P

SOLENOID ACTUATED, XT-4080S

BRISTOL DELUGE VALVE XT-4080S (Solenoid Controlled) is

an ON/OFF control valve which either opens or closes

upon receiving an Electrical Signal to the Solenoid Pilot

Control. This valve consists of XT-4080 UL-listed Main

Valve, a 3/2 way Solenoid Valve, an Auxiliary Pilot and a

Manual Release Station.

The Pilot Control System applies line water pressure to or

relieves water pressure from the diaphragm chamber of

the main valve to close or open the Deluge Valve. It is

supplied either Normally Closed (Energize Solenoid to

open) or Normally Open (De-energize Solenoid Valve to

open)

For Pneumatic/Hydraulic

Available in sizes 4‖, 6‖, & 8‖

Fast-acting solenoid Control

Drip-Tight Shutoff

Simple Design-Pressure Reliability

Easy installation and maintenance without remov-

ing valve from the line

All Deluge Valve trims are pre-piped at factory

FEATURES

The valve opens on demand to provide water flow to

the fire protection sprinkler system. Pilot system can be

hydraulically, pneumatically or manually operated.

Opening of the Valve is by electrical signal to solenoid

valve/loss of control pressure.

BRISTOL DELUGE VALVE XT-4080S /XT-4080SP

Connection Type 4‖ / 6‖ / 8‖ Flanged to ANSI B16.5 Class 150 & 300

Pressure Rating 150 Class, Max 285psig (20barg)

300 Class, Max 375psig (26barg)

Temperature Range 70°C / 160°F Max. (Water)

Main Valve Body & Cover

Cast Steel ASTM A216 Gr. WCB

Naval Bronze: ASTM B61

Nickel Al-Bronze: ASTM B148/BS1400 Gr. AB2

Stainless Steel: ASTM A351 Gr. CF8/CF8M

Valve Seat Stainless Steel Gr. 316

All other internal parts Stainless Steel Gr. 304

Stem Stainless Steel Gr. 316

Pilot Stainless Steel

Tubing & Fitting Stainless Steel

Elastomers NBR / Buna-N Nylon Reinforced

Specifications & Materials

BRISTOL DELUGE VALVE XT-4080S /XT-4080SP

Valve DN (inches) 4” 6” 8”

Valve DN (mm) 100 150 200

Valve Cover Chamber Capacity (L) 0.616 1.96 4.73

Flow Rate (gpm @ 1psi Δ P) 220 460 840

Max. Continuous Flow Rate (gpm, Water) 800 1800 3100

Max. Intermittent Flow Rate (gpm, Water) 1000 2300 3900

Approx. Weight (kgs) 55 115 182

Page 9: AUTOMATI SPRINKLERS - Maceden

BRISTOL Sprinkler System Datasheets Rev. 0 9

AU

TO

MA

TIC

SP

RIN

KLE

R S

YS

TE

M

Test & Drain Valve, BF-VT001

Standard ………………………… UL Subject 258

Connection Type……………….. 1” M x F NPT

Body Material :…………………… Brass

Working Pressure :………………. 175psig / 12bar

K Factor :…………………………. 5.6

Air Release Valve, BFE090203

Standard ………………………… BS5041-3

Test Pressure : ……………………. 24bar

Inlet Coupling Type :...…………. DN25 Male BSPT

Max. Working Pressure :………… 175psi / 12bar

Body Material :…………………… Brass

Body Color :……………………….. Cast Brass