7
Page | 1 Australian Wiring Instructions: Generator/Switch Wiring: Remove the generator controller fascia and identify wire #44 going to the circuit breaker in the external connection box, this wire is the active (hot) wire and has a piece of brown heat shrink for identification to coincide with Australian standard structural wiring. Wire #11, also going to the generator breaker is the neutral and it has a piece of blue heat shrink on it for identification. Wire 11 (Neutral) Wire 44 (Active) Generator Circuit Breaker

Australian Wiring Instructions - My Generator...Generator/Switch Wiring: Remove the generator controller fascia and identify wire #44 going to the circuit breaker in the external connection

  • Upload
    others

  • View
    11

  • Download
    1

Embed Size (px)

Citation preview

Page | 1

Australian Wiring Instructions:

Generator/Switch Wiring: Remove the generator controller fascia and identify wire #44 going to the

circuit breaker in the external connection box, this wire is the active (hot) wire and has a piece of brown

heat shrink for identification to coincide with Australian standard structural wiring. Wire #11, also going

to the generator breaker is the neutral and it has a piece of blue heat shrink on it for identification.

Wire 11 (Neutral)

Wire 44 (Active)

Generator Circuit Breaker

Page | 2

The installer will need to provide a NEMA 3R box to house a 35, 50 or 65 amp, Australian approved

single pole breaker which can be mounted on the building or on the generator itself. The installer would

connect the brown conductor (hot wire) to the opposite side of the circuit breaker that is fed by wire

#44 identified by the brown heat shrink. This wire is then fed into the NEMA 3R box and connected on

the input side of the Australian approved breaker. Another brown conductor will be run out of the box

after being protected on the output side of the Australian breaker and fed to the transfer switch. An

example of the required box is pictured below, it can be found at any electrical distributor for less than

$30.

A blue conductor (neutral) will be connected to the breaker opposite to the wire identified as #11 and

identified by the blue heat shrink. This conductor is then run to the transfer switch. It does not need to

be routed with the brown conductor but can be for ease of wire routing/conduit connection.

Installer provided NEMA 3R box

and Australian approved breaker

Generator circuit breaker Neutral

Active

Page | 3

A green/yellow conductor (earth) will be landed on the ground block connector in the generator

connection shelf, then run to the transfer switch. It does not need to be routed with the brown (active)

conductor but can be for ease of wire routing/conduit connection.

Connect your control wires (N1, N2, 23, 194, T1 & T2) to the appropriate landings on the generator

connection shelf. NOTE: In this application, T2 will be landed on the main neutral post.

These wires can be run in the same conduit as the power wires if the proper insulation is used.

Earth/Ground

Land T2 wire here to

the Neutral post

Control wires N1, N2, 23, 194, T1

Page | 4

RTS Transfer Switch:

After mounting the switch, remove the cover to make the electrical connections. Please note that if

being used in an application to back up the entire electrical panel, this switch requires a disconnect be

installed between the electrical meter and transfer switch since this is a non-service rated switch.

Next, install a jumper wire between the provided Neutral block and Earth ground. See below.

Page | 5

Run the incoming conductors from the utility disconnect through the appropriate knock out in the

transfer switch. Connect the earth ground (green/yellow) to the ground strip provided. Connect the

Active (Hot) brown wire to the left top terminal contact of the transfer mechanism and connect the

neutral blue wire to the top right terminal contact of the transfer mechanism. NOTE: It is important

that the active and neutral wires are not installed in reverse positions. See below.

Page | 6

The next step is to connect the wires that will feed the customer’s load center or sub panel. Land an

earth (green/yellow) wire on the provided ground terminal and route to the customer’s electrical panel.

Connect an Active (brown) and Neutral (blue) wire to the customer load terminals labeled T1 & T2 on

the transfer mechanism. Be sure that the colors all match, See below.

Page | 7

The next activity will be to connect the generator fed conductors. Connect the generator fed earth

(green/yellow) to the provided neutral connection block. Connect the Active (brown) and the Neutral

(blue) to the top lugs on the bottom of the of the transfer mechanism. Be sure to match Brown for

Brown and Blue for Blue in the correspoding lugs.

Connect your control wires (N1, N2, 23, 194, T1 & T2) to the fuse block and connection strip. See below.

Proceed with the standard generator start up procedure to check operation, voltage and frequency.