1 of 74 TABLE : 3C-6/10kV 3C 6/10kV RFOU Nominal Resistance Resistance Reactance 3C Cable (AC) at 90 C (DC) at 20 C at 50 Hz In air size 45°C (mm²) (Ohm/km) (Ohm/km) (Ohm/km) (Amp) 16 1.479 1.1600 0.126 63 25 0.936 0.7340 0.119 84 35 0.674 0.5290 0.114 102 50 0.499 0.3910 0.106 126 70 0.344 0.2700 0.101 158 95 0.249 0.1950 0.097 193 120 0.196 0.1540 0.093 224 150 0.161 0.1260 0.091 256 185 0.128 0.1000 0.089 290 240 0.097 0.0762 0.086 345 390 Note : 1. Based on Nexans cables

Att-1_Cable Selection Chart

Embed Size (px)

DESCRIPTION

Att-1_Cable Selection Chart

Citation preview

TFM UTILITIES

DATA 3C(6-10kV)TABLE : 3C-6/10kV3C 6/10kVRFOUNominalResistanceResistanceReactance3CCable(AC) at 90 C(DC) at 20 Cat 50 HzIn airsize45C(mm)(Ohm/km)(Ohm/km)(Ohm/km)(Amp)161.4791.16000.12663250.9360.73400.11984350.6740.52900.114102500.4990.39100.106126700.3440.27000.101158950.2490.19500.0971931200.1960.15400.0932241500.1610.12600.0912561850.1280.10000.0892902400.0970.07620.086345390Note :1. Based on Nexans cables

&C&P of &N

REF DATA_0.6-1kVTABLE : 0.6/1KV0.6/1kVL3RFOU (Normal service)BFOU (Vital service)L4=VSD cableNominalResistanceResistanceReactanceReactance1C2C3C1C2C3C3C+3ECable(AC) at 90 C(DC) at 20 Cat 50 Hzat 50 HzIn airIn airIn airIn airIn airIn airIn airsizeFor multi coreFor 1Core45C45C45C45C45C45C45C(mm)(Ohm/km)(Ohm/km)(Ohm/km)(Ohm/km)(Amp)(Amp)(Amp)(Amp)(Amp)(Amp)(Amp)L3L3L32.59.6397.5600.1030.15630262130262145.9934.7000.0960.14540342840342863.9653.1100.0900.135524436524436102.3461.8400.0850.126726150726150161.4791.1600.0800.117968267968267250.9360.7340.0790.112127108891271088989350.6740.5290.0770.107157133110157133110110500.4990.3910.0760.104196167137196167137137700.3440.2700.0760.101242206169242206169169950.2490.1950.0740.0972932492052932492052051200.1960.1540.0720.0943392882373392882372371500.1610.1260.0720.0933893312723893312722721850.1280.1000.0720.0924443773114443773113112400.0970.0760.0720.0905224443655224443653653000.0770.0610.0710.0896015114216015114214214000.0610.0480.0897196117196115000.0470.0370.0878278276300.0360.0290.087955955Note :1. Based on Nexans cables

&C&P of &NWong Yit Sin (Kuala Lumpur):(refer IEC 61892-4. table 5)Wong Yit Sin (Kuala Lumpur):(refer IEC 61892-4. table 5)Wong Yit Sin (Kuala Lumpur):(refer IEC 61892-4. table 5)Wong Yit Sin (Kuala Lumpur):(refer IEC 61892-4. table 5)Wong Yit Sin (Kuala Lumpur):(refer IEC 61892-4. table 5)Wong Yit Sin (Kuala Lumpur):(refer IEC 61892-4. table 5)Wong Yit Sin (Kuala Lumpur):(refer IEC 61892-4. table 5)Wong Yit Sin (Kuala Lumpur):(refer IEC 61892-4. table 5)

MVMFDPTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)HV MOTOR FEEDER CABLE SELECTION CHART (H1)CLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable Parameters0.9360.6740.4990.3440.2490.196Resistance (Ohms/km) at 90C0.1190.1140.1060.1010.0970.093Reactance (Ohms/km) 50Hz84.0102.0126.0158.0193.0224.0Current Rating (Amps.) at 45CKWEFFFLCSteady StateLRCStarting75.091.0112.5141.0172.3199.9Derated Rating (Amps.)(Amp)cos@sin@(Amp)cos@sin@2535507095120Conductor Size (mm2)3C3C3C3C3C3CNo. of Cable core1320.9514.30.850.5383.10.220.989295**********1600.9517.30.850.53100.50.220.987684**********1800.9519.50.850.53109.10.230.9768389272********2000.9521.60.850.53125.40.230.9761608353********2250.9524.00.860.51132.10.230.97549974639851******2500.9626.90.850.53164.00.220.98495467188859******2800.9630.10.850.53177.70.230.97442359987910******3150.9633.80.850.53199.70.230.973936533770389775****3550.9638.10.850.53224.50.230.973500474662588691****4000.9642.70.850.53252.20.210.983116422555717738****4500.9648.00.850.53278.60.210.9827723759495768859056**5000.9753.30.850.53309.30.200.982498338744666203815994545600.9759.70.850.53352.00.200.982232302739925544729383076300.9765.60.870.49380.30.180.98--271335844994659279047100.9773.80.870.49435.60.180.98--241031844436585569018000.9783.10.870.49473.70.180.98----282839415202634610000.97102.60.880.47595.00.180.98------31784202505212500.97128.00.880.47755.00.180.98--------33693981Notes:1) CABLE DATA IS BASED ON NEXANS CABLES.6)System Nominal Voltage :6600V2) MOTOR DATA IS BASED ON LOHER MOTORSSystem Frequency :50Hz3) CABLE DERATING FACTORS ARE AS FOLLOWS :-Steady State Volt Drop :3%A)Ambient temp at 40C1.05Motor Starting Volt Drop :10%B)Grouping (6 and above cables bunching)0.857)-- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 10000 METRES.Total correction factor0.898)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10004) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER AND FULLY LOADED.1.732 x I x (RCos@+XSin@)5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.

&L&"Arial,Regular"&8&F-&A

24VFDR-L1PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)24V DC FEEDER SELECTION CHART (L1)CLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable ParametersFeeder Rating9.6395.9933.9652.3461.4790.9360.6740.4990.3440.2490.1960.1610.1280.1250.0980.0810.0640.0770.0610.0390.031Resistance (Ohms/km) at 90C26.034.044.061.082.0108.0133.0167.0206.0249.0288.0331.0377.0498.0576.0662.0754.0601.0719.01202.01438.0Current Rating (Amps.) at 45CCBFLC23.230.339.354.473.296.4118.7149.0183.9222.2257.0295.4336.5444.5514.1590.8672.9536.4641.71072.81283.4Derated Rating (Amps.)(Amp)(Amp)2.546101625355070951201501852x952x1202x1502x1853004002x3002x400Conductor Size (mm2)2C2C2C2C2C2C2C2C2C2C2C2C2C2C2C2C2C1C1C1C1CNo. of Cable core43.2081319325180111150218301383466586602765932**974******108.003581320324560871201531862342413063734693904927799841612.802358132028385575961161461511912332932443074876153225.60----246101419273848587375961161461221542443074032.00------35811152230384759607793117971231952465040.00--------4691217243137474861759478981561976350.40--------3571014192430373849597462781241568064.00----------46811151923293038475949619712310080.00------------469121519232431374739497898125100.00--------------57101215191924303831396279160128.00------------------81012151519232924314961200160.00--------------------89121215192319253949250200.00----------------------791012151916203139Notes:1) CABLE DATA IS BASED ON NEXANS CABLES.6)System Nominal Voltage :24V2) CABLE DE-RATING FACTORS ARE AS FOLLOWS :-Steady State Allowable Volt Drop :2%A)Ambient temp at 40C1.05B)Grouping (6 and above cables bunching)0.85Total correction factor0.897)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10003) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER2 x I x RAND FULLY LOADED.8)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,4) -- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZED5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.FOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

400VFDR-L1 (2%)PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)400V FEEDER SELECTION CHART (L1)CLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable ParametersFeeder Rating9.6395.9933.9652.3461.4790.9360.6740.4990.3440.2490.1960.1610.1280.1250.0980.0810.0640.0650.0540.043Resistance (Ohms/km) at 90C0.1030.0960.0900.0850.0800.0790.0770.0760.0760.0740.0720.0720.0720.0370.0360.0360.0360.0240.0240.024Reactance (Ohms/km) 50Hz21.028.036.050.067.089.0110.0137.0169.0205.0237.0272.0311.0410.0474.0544.0622.0711.0816.0933.0Current Rating (Amps.) at 45CCBFLC18.725.032.144.659.879.498.2122.3150.8183.0211.5242.8277.6365.9423.0485.5555.1634.6728.3832.7Derated Rating (Amps.)(Amp)(Amp)Cos@Sin@2.546101625355070951201501852x952x1202x1502x1853x1203x1503x185Conductor Size (mm2)3C3C3C3C3C3C3C3C3C3C3C3C3C3C3C3C3C3C3C3CNo. of Cable core43.200.850.53175281422708********************************108.000.850.5370112169283444690941**************************1612.800.850.534470106177278431588777************************3225.600.850.53------88139216294389543720882******************4032.000.850.53--------111172235311434576706826984**************5040.000.850.53--------89138188249347461565661787921************6350.400.850.53----------109149197276366448524625731896**********8064.000.850.53------------118155217288353413492576706826984******10080.000.850.53--------------124174230282330393461565661787847991**125100.000.850.53----------------139184226264315369452529630678793944160128.000.850.53--------------------176206246288353413492529619738200160.000.850.53----------------------165197230282330393423496590250200.000.850.53--------------------------184226264315339396472300240.000.850.53--------------------------154188220262282330393400320.000.850.53------------------------------165197212248295500400.000.850.53----------------------------------169198236630504.000.850.53------------------------------------157187800640.000.850.53----------------------------------------1000800.000.850.53----------------------------------------12501000.000.850.53----------------------------------------16001280.000.850.53----------------------------------------20001600.000.850.53----------------------------------------25002000.000.850.53----------------------------------------30002400.000.850.53----------------------------------------35002800.000.850.53----------------------------------------Notes:1) CABLE DATA IS BASED ON NEXANS CABLES.6)System Nominal Voltage :400V2) CABLE DERATING FACTORS ARE AS FOLLOWS :-System Frequency :50HzA)Ambient temp at 40C1.05Steady State Allowable Volt Drop :2%B)Grouping (6 and above cables bunching)0.85Total correction factor0.897)-- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.C)Safety factor1.158)FORMULA USED FOR DETERMINING LENGTH :3) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHERLENGTH (L) =System Voltage (V) x Volt Drop X 1000AND FULLY LOADED.1.732 x I x (RCos@+XSin@)4) * CABLES WITHIN BRACKETS ARE SINGLE CORE CABLES PER PHASE9)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZEDFOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

400VFDR-L2 (2%)PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)400V FEEDER SELECTION CHART (L2)CLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable ParametersFeeder Rating9.6395.9933.9652.3461.4790.9360.6740.4990.3440.2490.1960.1610.1280.1250.0980.0810.0640.0650.0540.043Resistance (Ohms/km) at 90C0.1030.0960.0900.0850.0800.0790.0770.0760.0760.0740.0720.0720.0720.0370.0360.0360.0360.0240.0240.024Reactance (Ohms/km) 50Hz21.028.036.050.067.089.0110.0137.0169.0205.0237.0272.0311.0410.0474.0544.0622.0711.0816.0933.0Current Rating (Amps.) at 45CCBFLC18.725.032.144.659.879.498.2122.3150.8183.0211.5242.8277.6365.9423.0485.5555.1634.6728.3832.7Derated Rating (Amps.)(Amp)(Amp)Cos@Sin@2.546101625355070951201501852x952x1202x1502x1853x1203x1503x185Conductor Size (mm2)3C3C3C3C3C3C3C3C3C3C3C3C3C3C3C3C3C3C3C3CNo. of Cable core43.200.850.53175281422708********************************108.000.850.5370112169283444690941**************************1612.800.850.534470106177278431588777************************3225.600.850.53------88139216294389543720882******************4032.000.850.53--------111172235311434576706826984**************5040.000.850.53--------89138188249347461565661787921************6350.400.850.53----------109149197276366448524625731896**********8064.000.850.53------------118155217288353413492576706826984******10080.000.850.53--------------124174230282330393461565661787847991**125100.000.850.53----------------139184226264315369452529630678793944160128.000.850.53--------------------176206246288353413492529619738200160.000.850.53----------------------165197230282330393423496590250200.000.850.53--------------------------184226264315339396472300240.000.850.53--------------------------154188220262282330393400320.000.850.53------------------------------165197212248295500400.000.850.53----------------------------------169198236630504.000.850.53------------------------------------157187800640.000.850.53----------------------------------------1000800.000.850.53----------------------------------------12501000.000.850.53----------------------------------------16001280.000.850.53----------------------------------------20001600.000.850.53----------------------------------------25002000.000.850.53----------------------------------------30002400.000.850.53----------------------------------------35002800.000.850.53----------------------------------------Notes:1) CABLE DATA IS BASED ON NEXANS CABLES.6)System Nominal Voltage :400V2) CABLE DE-RATING FACTORS ARE AS FOLLOWS :-System Frequency :50HzA)Ambient temp at 40C1.05Steady State Allowable Volt Drop :2%B)Grouping (6 and above cables bunching)0.85Total correction factor0.897)-- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.C)Safety factor1.158)FORMULA USED FOR DETERMINING LENGTH :3) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHERLENGTH (L) =System Voltage (V) x Volt Drop X 1000AND FULLY LOADED.1.732 x I x (RCos@+XSin@)4) * CABLES WITHIN BRACKETS ARE SINGLE CORE CABLES PER PHASE9)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZEDFOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

400VFDR-L3 (2%)PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)400V FEEDER SELECTION CHART (L3)CLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable ParametersFeeder Rating0.0970.0770.0610.0490.0320.0240.0390.0260.0190.0150.0130.0110.0310.0200.0150.012Resistance (Ohms/km) at 90C0.0900.0890.0890.0450.0300.0230.0450.0300.0220.0180.0150.0130.0450.0300.0220.018Reactance (Ohms/km) 50Hz522.0601.0719.01044.01566.02088.01202.01803.02404.03005.03606.04207.01438.02157.02876.03595.0Current Rating (Amps.) at 45CCBFLC465.9536.4641.7931.81397.71863.51072.81609.22145.62682.03218.43754.71283.41925.12566.83208.5Derated Rating (Amps.)(Amp)(Amp)Cos@Sin@2403004002x(240)*3x(240)*4x(240)*2x(300)*3x(300)*4x(300)*5x(300)*6x(300)*7x(300)*2x(400)*3x(400)*4x(400)*5x(400)*Conductor Size (mm2)1C1C1C1C1C1C1C1C1C1C1C1C1C1C1C1CNo. of Cable core43.200.850.53********************************108.000.850.53********************************1612.800.850.53********************************3225.600.850.53********************************4032.000.850.53********************************5040.000.850.53889******************************6350.400.850.53706816928**************************8064.000.850.53556642731**************************10080.000.850.53445514585889************************125100.000.850.53356411468711****822**********936******160128.000.850.53278321365556834**642964********731******200160.000.850.53222257292445667889514771********585877****250200.000.850.53178206234356534711411617822******468702936**300240.000.850.53148171195296445593343514685857****390585780975400320.000.850.53111128146222333445257385514642771899292439585731500400.000.850.53----117178267356206308411514617720234351468585630504.000.850.53------141212282163245326408490571186278371464800640.000.850.53------1111672221281932573213854501462192923651000800.000.850.53--------133178--15420625730836011717523429212501000.000.850.53----------142--123164206247288--14018723416001280.000.850.53----------111----128161193225--11014618320001600.000.850.53------------------128154180----11714625002000.000.850.53--------------------123144------11730002400.000.850.53----------------------120--------35002800.000.850.53--------------------------------Notes:1) CABLE DATA IS BASED ON NEXANS CABLES.6)System Nominal Voltage :400V2) CABLE DE-RATING FACTORS ARE AS FOLLOWS :-Single coreSystem Frequency :50HzA)Ambient temp at 40C1.05Steady State Allowable Volt Drop :2%B)Grouping (6 and above cables bunching)0.85Total correction factor0.89(single core trefoil formation)7)-- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.C)Safety factor1.158)FORMULA USED FOR DETERMINING LENGTH :3) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHERLENGTH (L) =System Voltage (V) x Volt Drop X 1000AND FULLY LOADED.1.732 x I x (RCos@+XSin@)4) * CABLES WITHIN BRACKETS ARE SINGLE CORE CABLES PER PHASE5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.

&L&"Arial,Regular"&8&F-&A

400VMTFDR-L1 (2%)PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)400V MOTOR FEEDER SELECTION CHART (L1)CLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable Parameters9.6395.9933.9652.3461.4790.9360.6740.4990.3440.2490.1960.1610.128Resistance (Ohms/km) at 90C0.1030.0960.0900.0850.0800.0790.0770.0760.0760.0740.0720.0720.072Reactance (Ohms/km) 50Hz21.028.036.050.067.089.0110.0137.0169.0205.0237.0272.0311.0Current Rating (Amps.) at 45CKWEFFFLCSteady StateLRCStarting18.725.032.144.659.879.498.2122.3150.8183.0211.5242.8277.6Derated Rating (Amps.)(Amp)cos@sin@(Amp)%cos@[email protected] Size (mm2)3C3C3C3C3C3C3C3C3C3C3C3C3CNo. of Cable core0.250.660.70.730.683.95200.091.00872************************0.370.711.00.750.665.25200.100.99629************************0.550.751.50.730.687.55200.110.99448717**********************0.750.761.90.760.6511.26000.101.00335536805********************1.10.792.60.780.6315.66000.100.99235376566946******************1.50.813.40.780.6320.76000.100.99177283425711******************2.20.834.80.800.6028.96000.110.99124198298498780****************30.856.20.820.5740.66500.110.9993149224375587909**************40.868.30.810.5953.96500.110.9971113171286448693943************5.50.8710.80.840.5470.36500.110.995284126212332515703928**********7.50.8914.30.850.5393.06500.120.99396394158248386526695971********110.9121.20.820.57163.37700.101.00--4466110173268365481669883******150.9228.40.830.56215.57600.100.99------82128198270357497657803937**18.50.9335.20.820.57257.07300.100.99------67104161220290403532650757898220.9341.80.820.57296.97100.110.99--------88136185244339448547638756300.9455.10.840.54408.07400.110.99----------101138182254336411481572370.9467.90.840.54523.07700.100.99----------82112148206273334390464450.9480.00.860.51592.17400.110.99------------93123173229281330393550.95101.10.830.56697.66900.110.99--------------100139184225263312750.95132.50.860.51914.36900.120.99------------------138170199237900.95156.80.870.491129.37200.120.99------------------1161431682011100.96190.90.870.491336.37000.120.99----------------------1381651320.96228.60.870.491623.17100.120.99------------------------138Notes:1) MOTOR DATA IS BASED ON ABB MOTORS6)System Nominal Voltage :400V2) CABLE DATA IS BASED ON NEXANS CABLES.System Frequency :50Hz3) CABLE DERATING FACTORS ARE AS FOLLOWS :-Steady State Volt Drop :2%A)Ambient temp at 40C1.05Motor Starting Volt Drop :10%B)Grouping (6 and above cables bunching)0.857)-- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.Total correction factor0.898)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10004) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER1.732X Full / Starting Current I (fl/st) x (RCos@+XSin@)AND FULLY LOADED.9)* CABLES WITHIN BRACKETS ARE SINGLE CORE CABLES PER PHASE5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.10)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZEDFOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

400VMTFDR-L2 (2%)PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)400V MOTOR FEEDER SELECTION CHART (L2)CLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable Parameters9.6395.9933.9652.3461.4790.9360.6740.4990.3440.2490.1960.1610.128Resistance (Ohms/km) at 90C0.1030.0960.0900.0850.0800.0790.0770.0760.0760.0740.0720.0720.072Reactance (Ohms/km) 50Hz21.028.036.050.067.089.0110.0137.0169.0205.0237.0272.0311.0Current Rating (Amps.) at 45CKWEFFFLCSteady StateLRCStarting18.725.032.144.659.879.498.2122.3150.8183.0211.5242.8277.6Derated Rating (Amps.)(Amp)cos@sin@(Amp)%cos@[email protected] Size (mm2)3C3C3C3C3C3C3C3C3C3C3C3C3CNo. of Cable core0.250.660.70.730.683.95200.091.00872************************0.370.711.00.750.665.25200.100.99629************************0.550.751.50.730.687.55200.110.99448717**********************0.750.761.90.760.6511.26000.101.00335536805********************1.10.792.60.780.6315.66000.100.99235376566946******************1.50.813.40.780.6320.76000.100.99177283425711******************2.20.834.80.800.6028.96000.110.99124198298498780****************30.856.20.820.5740.66500.110.9993149224375587909**************40.868.30.810.5953.96500.110.9971113171286448693943************5.50.8710.80.840.5470.36500.110.995284126212332515703928**********7.50.8914.30.850.5393.06500.120.99396394158248386526695971********110.9121.20.820.57163.37700.101.00--4466110173268365481669883******150.9228.40.830.56215.57600.100.99------82128198270357497657803937**18.50.9335.20.820.57257.07300.100.99------67104161220290403532650757898220.9341.80.820.57296.97100.110.99--------88136185244339448547638756300.9455.10.840.54408.07400.110.99----------101138182254336411481572370.9467.90.840.54523.07700.100.99----------82112148206273334390464450.9480.00.860.51592.17400.110.99------------93123173229281330393550.95101.10.830.56697.66900.110.99--------------100139184225263312750.95132.50.860.51914.36900.120.99------------------138170199237900.95156.80.870.491129.37200.120.99------------------1161431682011100.96190.90.870.491336.37000.120.99----------------------1381651320.96228.60.870.491623.17100.120.99------------------------138Notes:1) MOTOR DATA IS BASED ON ABB MOTORS6)System Nominal Voltage :400V2) CABLE DATA IS BASED ON NEXANS CABLES.System Frequency :50Hz3) CABLE DERATING FACTORS ARE AS FOLLOWS :-Steady State Volt Drop :2%A)Ambient temp at 40C1.05Motor Starting Volt Drop :10%B)Grouping (6 and above cables bunching)0.857)-- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.Total correction factor0.898)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10004) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER1.732X Full / Starting Current I (fl/st) x (RCos@+XSin@)AND FULLY LOADED.9)* CABLES WITHIN BRACKETS ARE SINGLE CORE CABLES PER PHASE5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.10)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZEDFOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

400VMTVSD-L4 (2%)PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)400V MOTOR FEEDER SELECTION CHART (L4)CLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable Parameters0.9360.6740.4990.3440.2490.1960.1610.128Resistance (Ohms/km) at 90C0.0790.0770.0760.0760.0740.0720.0720.072Reactance (Ohms/km) 50Hz89.0110.0137.0169.0205.0237.0272.0311.0Current Rating (Amps.) at 45CKWEFFFLCSteady StateLRCStarting79.498.2122.3150.8183.0211.5242.8277.6Derated Rating (Amps.)(Amp)cos@sin@(Amp)%cos@sin@2535507095120150185Conductor Size (mm2)3C+3E3C+3E3C+3E3C+3E3C+3E3C+3E3C+3E3C+3ENo. of Cable core0.250.660.70.730.683.95200.091.00****************0.370.711.00.750.665.25200.100.99****************0.550.751.50.730.687.55200.110.99****************0.750.761.90.760.6511.26000.101.00****************1.10.792.60.780.6315.66000.100.99****************1.50.813.40.780.6320.76000.100.99****************2.20.834.80.800.6028.96000.110.99****************30.856.20.820.5740.66500.110.99909**************40.868.30.810.5953.96500.110.99693943************5.50.8710.80.840.5470.36500.110.99515703928**********7.50.8914.30.850.5393.06500.120.99386526695971********110.9121.20.820.57163.37700.101.00268365481669883******150.9228.40.830.56215.57600.100.99198270357497657803937**18.50.9335.20.820.57257.07300.100.99161220290403532650757898220.9341.80.820.57296.97100.110.99136185244339448547638756300.9455.10.840.54408.07400.110.99101138182254336411481572370.9467.90.840.54523.07700.100.9982112148206273334390464450.9480.00.860.51592.17400.110.99--93123173229281330393550.95101.10.830.56697.66900.110.99----100139184225263312750.95132.50.860.51914.36900.120.99--------138170199237900.95156.80.870.491129.37200.120.99--------1161431682011100.96190.90.870.491336.37000.120.99------------1381651320.96228.60.870.491623.17100.120.99--------------138Notes:1) MOTOR DATA IS BASED ON ABB MOTORS6)System Nominal Voltage :400V2) CABLE DATA IS BASED ON NEXANS CABLES.System Frequency :50Hz3) CABLE DERATING FACTORS ARE AS FOLLOWS :-Steady State Volt Drop :2%A)Ambient temp at 40C1.05Motor Starting Volt Drop :10%B)Grouping (6 and above cables bunching)0.857)-- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.Total correction factor0.898)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10004) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER1.732X Full / Starting Current I (fl/st) x (RCos@+XSin@)AND FULLY LOADED.9)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZEDFOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

400VMTFDR-L1 (2.5%)PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)400V MOTOR FEEDER SELECTION CHART (L1)CLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable Parameters9.6395.9933.9652.3461.4790.9360.6740.4990.3440.2490.1960.1610.128Resistance (Ohms/km) at 90C0.1030.0960.0900.0850.0800.0790.0770.0760.0760.0740.0720.0720.072Reactance (Ohms/km) 50Hz21.028.036.050.067.089.0110.0137.0169.0205.0237.0272.0311.0Current Rating (Amps.) at 45CKWEFFFLCSteady StateLRCStarting18.725.032.144.659.879.498.2122.3150.8183.0211.5242.8277.6Derated Rating (Amps.)(Amp)cos@sin@(Amp)%cos@[email protected] Size (mm2)3C3C3C3C3C3C3C3C3C3C3C3C3CNo. of Cable core0.250.660.70.730.683.95200.091.00**************************0.370.711.00.750.665.25200.100.99787************************0.550.751.50.730.687.55200.110.99560897**********************0.750.761.90.760.6511.26000.101.00418670**********************1.10.792.60.780.6315.66000.100.99294470707********************1.50.813.40.780.6320.76000.100.99221354532889******************2.20.834.80.800.6028.96000.110.99154247372622975****************30.856.20.820.5740.66500.110.99116186280468734****************40.868.30.810.5953.96500.110.9989142213357560866**************5.50.8710.80.840.5470.36500.110.9965105158265415644878************7.50.8914.30.850.5393.06500.120.994978118198311482658869**********110.9121.20.820.57163.37700.101.00--5582138216335456601836********150.9228.40.830.56215.57600.100.99------102160248338446621821******18.50.9335.20.820.57257.07300.100.99------83130202275362504665812947**220.9341.80.820.57296.97100.110.99--------110170231305424560684797912300.9455.10.840.54408.07400.110.99----------126172227317420514601665370.9467.90.840.54523.07700.100.99----------103140185257341417488521450.9480.00.860.51592.17400.110.99------------117154216286352412456550.95101.10.830.56697.66900.110.99--------------125174230282329384750.95132.50.860.51914.36900.120.99------------------173212249292900.95156.80.870.491129.37200.120.99------------------1451792102371100.96190.90.870.491336.37000.120.99----------------------1721991320.96228.60.870.491623.17100.120.99------------------------164Notes:1) MOTOR DATA IS BASED ON ABB MOTORS6)System Nominal Voltage :400V2) CABLE DATA IS BASED ON NEXANS CABLES.System Frequency :50Hz3) CABLE DERATING FACTORS ARE AS FOLLOWS :-Steady State Volt Drop :2.5%A)Ambient temp at 40C1.05Motor Starting Volt Drop :10%B)Grouping (6 and above cables bunching)0.857)-- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.Total correction factor0.898)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10004) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER1.732X Full / Starting Current I (fl/st) x (RCos@+XSin@)AND FULLY LOADED.9)* CABLES WITHIN BRACKETS ARE SINGLE CORE CABLES PER PHASE5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.10)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZEDFOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

400VMTFDR-L2 (2.5%)PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)400V MOTOR FEEDER SELECTION CHART (L2)CLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable Parameters9.6395.9933.9652.3461.4790.9360.6740.4990.3440.2490.1960.1610.128Resistance (Ohms/km) at 90C0.1030.0960.0900.0850.0800.0790.0770.0760.0760.0740.0720.0720.072Reactance (Ohms/km) 50Hz21.028.036.050.067.089.0110.0137.0169.0205.0237.0272.0311.0Current Rating (Amps.) at 45CKWEFFFLCSteady StateLRCStarting18.725.032.144.659.879.498.2122.3150.8183.0211.5242.8277.6Derated Rating (Amps.)(Amp)cos@sin@(Amp)%cos@[email protected] Size (mm2)3C3C3C3C3C3C3C3C3C3C3C3C3CNo. of Cable core0.250.660.70.730.683.95200.091.00**************************0.370.711.00.750.665.25200.100.99787************************0.550.751.50.730.687.55200.110.99560897**********************0.750.761.90.760.6511.26000.101.00418670**********************1.10.792.60.780.6315.66000.100.99294470707********************1.50.813.40.780.6320.76000.100.99221354532889******************2.20.834.80.800.6028.96000.110.99154247372622975****************30.856.20.820.5740.66500.110.99116186280468734****************40.868.30.810.5953.96500.110.9989142213357560866**************5.50.8710.80.840.5470.36500.110.9965105158265415644878************7.50.8914.30.850.5393.06500.120.994978118198311482658869**********110.9121.20.820.57163.37700.101.00--5582138216335456601836********150.9228.40.830.56215.57600.100.99------102160248338446621821******18.50.9335.20.820.57257.07300.100.99------83130202275362504665812947**220.9341.80.820.57296.97100.110.99--------110170231305424560684797912300.9455.10.840.54408.07400.110.99----------126172227317420514601665370.9467.90.840.54523.07700.100.99----------103140185257341417488521450.9480.00.860.51592.17400.110.99------------117154216286352412456550.95101.10.830.56697.66900.110.99--------------125174230282329384750.95132.50.860.51914.36900.120.99------------------173212249292900.95156.80.870.491129.37200.120.99------------------1451792102371100.96190.90.870.491336.37000.120.99----------------------1721991320.96228.60.870.491623.17100.120.99------------------------164Notes:1) MOTOR DATA IS BASED ON ABB MOTORS6)System Nominal Voltage :400V2) CABLE DATA IS BASED ON NEXANS CABLES.System Frequency :50Hz3) CABLE DERATING FACTORS ARE AS FOLLOWS :-Steady State Volt Drop :2.5%A)Ambient temp at 40C1.05Motor Starting Volt Drop :10%B)Grouping (6 and above cables bunching)0.857)-- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.Total correction factor0.898)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10004) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER1.732X Full / Starting Current I (fl/st) x (RCos@+XSin@)AND FULLY LOADED.9)* CABLES WITHIN BRACKETS ARE SINGLE CORE CABLES PER PHASE5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.10)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZEDFOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

400VMTVSD-L4 (2.5%)PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)400V MOTOR FEEDER SELECTION CHART (L4)CLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable Parameters0.9360.6740.4990.3440.2490.1960.1610.128Resistance (Ohms/km) at 90C0.0790.0770.0760.0760.0740.0720.0720.072Reactance (Ohms/km) 50Hz89.0110.0137.0169.0205.0237.0272.0311.0Current Rating (Amps.) at 45CKWEFFFLCSteady StateLRCStarting79.498.2122.3150.8183.0211.5242.8277.6Derated Rating (Amps.)(Amp)cos@sin@(Amp)%cos@sin@2535507095120150185Conductor Size (mm2)3C+3E3C+3E3C+3E3C+3E3C+3E3C+3E3C+3E3C+3ENo. of Cable core0.250.660.70.730.683.95200.091.00****************0.370.711.00.750.665.25200.100.99****************0.550.751.50.730.687.55200.110.99****************0.750.761.90.760.6511.26000.101.00****************1.10.792.60.780.6315.66000.100.99****************1.50.813.40.780.6320.76000.100.99****************2.20.834.80.800.6028.96000.110.99****************30.856.20.820.5740.66500.110.99****************40.868.30.810.5953.96500.110.99866**************5.50.8710.80.840.5470.36500.110.99644878************7.50.8914.30.850.5393.06500.120.99482658869**********110.9121.20.820.57163.37700.101.00335456601836********150.9228.40.830.56215.57600.100.99248338446621821******18.50.9335.20.820.57257.07300.100.99202275362504665812947**220.9341.80.820.57296.97100.110.99170231305424560684797912300.9455.10.840.54408.07400.110.99126172227317420514601665370.9467.90.840.54523.07700.100.99103140185257341417488521450.9480.00.860.51592.17400.110.99--117154216286352412456550.95101.10.830.56697.66900.110.99----125174230282329384750.95132.50.860.51914.36900.120.99--------173212249292900.95156.80.870.491129.37200.120.99--------1451792102371100.96190.90.870.491336.37000.120.99------------1721991320.96228.60.870.491623.17100.120.99--------------164Notes:1) MOTOR DATA IS BASED ON ABB MOTORS6)System Nominal Voltage :400V2) CABLE DATA IS BASED ON NEXANS CABLES.System Frequency :50Hz3) CABLE DERATING FACTORS ARE AS FOLLOWS :-Steady State Volt Drop :2.5%A)Ambient temp at 40C1.05Motor Starting Volt Drop :10%B)Grouping (6 and above cables bunching)0.857)-- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.Total correction factor0.898)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10004) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER1.732X Full / Starting Current I (fl/st) x (RCos@+XSin@)AND FULLY LOADED.9)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZEDFOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

400VMTFDR-L1 (3%)PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)400V MOTOR FEEDER SELECTION CHART (L1)CLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable Parameters9.6395.9933.9652.3461.4790.9360.6740.4990.3440.2490.1960.1610.128Resistance (Ohms/km) at 90C0.1030.0960.0900.0850.0800.0790.0770.0760.0760.0740.0720.0720.072Reactance (Ohms/km) 50Hz21.028.036.050.067.089.0110.0137.0169.0205.0237.0272.0311.0Current Rating (Amps.) at 45CKWEFFFLCSteady StateLRCStarting18.725.032.144.659.879.498.2122.3150.8183.0211.5242.8277.6Derated Rating (Amps.)(Amp)cos@sin@(Amp)%cos@[email protected] Size (mm2)3C3C3C3C3C3C3C3C3C3C3C3C3CNo. of Cable core0.250.660.70.730.683.95200.091.00**************************0.370.711.00.750.665.25200.100.99944************************0.550.751.50.730.687.55200.110.99672************************0.750.761.90.760.6511.26000.101.00502804**********************1.10.792.60.780.6315.66000.100.99352564848********************1.50.813.40.780.6320.76000.100.99265424638********************2.20.834.80.800.6028.96000.110.99185297446747******************30.856.20.820.5740.66500.110.99139223336562881****************40.868.30.810.5953.96500.110.99106170256429671****************5.50.8710.80.840.5470.36500.110.9979126190318498773**************7.50.8914.30.850.5393.06500.120.995994142237373578789************110.9121.20.820.57163.37700.101.00--6699166260402547722**********150.9228.40.830.56215.57600.100.99------123192298406535745986******18.50.9335.20.820.57257.07300.100.99------100156242330435604798975****220.9341.80.820.57296.97100.110.99--------132204278366509672820876912300.9455.10.840.54408.07400.110.99----------152207273381504613638665370.9467.90.840.54523.07700.100.99----------123168222309409482501521450.9480.00.860.51592.17400.110.99------------140185259344419437456550.95101.10.830.56697.66900.110.99--------------150209276338368384750.95132.50.860.51914.36900.120.99------------------208255279292900.95156.80.870.491129.37200.120.99------------------1752142272371100.96190.90.870.491336.37000.120.99----------------------1911991320.96228.60.870.491623.17100.120.99------------------------164Notes:1) MOTOR DATA IS BASED ON ABB MOTORS6)System Nominal Voltage :400V2) CABLE DATA IS BASED ON NEXANS CABLES.System Frequency :50Hz3) CABLE DERATING FACTORS ARE AS FOLLOWS :-Steady State Volt Drop :3%A)Ambient temp at 40C1.05Motor Starting Volt Drop :10%B)Grouping (6 and above cables bunching)0.857)-- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.Total correction factor0.898)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10004) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER1.732X Full / Starting Current I (fl/st) x (RCos@+XSin@)AND FULLY LOADED.9)* CABLES WITHIN BRACKETS ARE SINGLE CORE CABLES PER PHASE5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.10)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZEDFOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

400VMTFDR-L2 (3%)PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)400V MOTOR FEEDER SELECTION CHART (L2)CLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable Parameters9.6395.9933.9652.3461.4790.9360.6740.4990.3440.2490.1960.1610.128Resistance (Ohms/km) at 90C0.1030.0960.0900.0850.0800.0790.0770.0760.0760.0740.0720.0720.072Reactance (Ohms/km) 50Hz21.028.036.050.067.089.0110.0137.0169.0205.0237.0272.0311.0Current Rating (Amps.) at 45CKWEFFFLCSteady StateLRCStarting18.725.032.144.659.879.498.2122.3150.8183.0211.5242.8277.6Derated Rating (Amps.)(Amp)cos@sin@(Amp)%cos@[email protected] Size (mm2)3C3C3C3C3C3C3C3C3C3C3C3C3CNo. of Cable core0.250.660.70.730.683.95200.091.00**************************0.370.711.00.750.665.25200.100.99944************************0.550.751.50.730.687.55200.110.99672************************0.750.761.90.760.6511.26000.101.00502804**********************1.10.792.60.780.6315.66000.100.99352564848********************1.50.813.40.780.6320.76000.100.99265424638********************2.20.834.80.800.6028.96000.110.99185297446747******************30.856.20.820.5740.66500.110.99139223336562881****************40.868.30.810.5953.96500.110.99106170256429671****************5.50.8710.80.840.5470.36500.110.9979126190318498773**************7.50.8914.30.850.5393.06500.120.995994142237373578789************110.9121.20.820.57163.37700.101.00--6699166260402547722**********150.9228.40.830.56215.57600.100.99------123192298406535745986******18.50.9335.20.820.57257.07300.100.99------100156242330435604798975****220.9341.80.820.57296.97100.110.99--------132204278366509672820876912300.9455.10.840.54408.07400.110.99----------152207273381504613638665370.9467.90.840.54523.07700.100.99----------123168222309409482501521450.9480.00.860.51592.17400.110.99------------140185259344419437456550.95101.10.830.56697.66900.110.99--------------150209276338368384750.95132.50.860.51914.36900.120.99------------------208255279292900.95156.80.870.491129.37200.120.99------------------1752142272371100.96190.90.870.491336.37000.120.99----------------------1911991320.96228.60.870.491623.17100.120.99------------------------164Notes:1) MOTOR DATA IS BASED ON ABB MOTORS6)System Nominal Voltage :400V2) CABLE DATA IS BASED ON NEXANS CABLES.System Frequency :50Hz3) CABLE DERATING FACTORS ARE AS FOLLOWS :-Steady State Volt Drop :3%A)Ambient temp at 40C1.05Motor Starting Volt Drop :10%B)Grouping (6 and above cables bunching)0.857)-- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.Total correction factor0.898)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10004) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER1.732X Full / Starting Current I (fl/st) x (RCos@+XSin@)AND FULLY LOADED.9)* CABLES WITHIN BRACKETS ARE SINGLE CORE CABLES PER PHASE5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.10)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZEDFOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

400VMTVSD-L4 (3%)PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)400V MOTOR FEEDER SELECTION CHART (L4)CLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable Parameters0.9360.6740.4990.3440.2490.1960.1610.1280.1250.0980.0810.064Resistance (Ohms/km) at 90C0.0790.0770.0760.0760.0740.0720.0720.0720.0370.0360.0360.036Reactance (Ohms/km) 50Hz89.0110.0137.0169.0205.0237.0272.0311.0410.0474.0544.0622.0Current Rating (Amps.) at 45CKWEFFFLCSteady StateLRCStarting79.498.2122.3150.8183.0211.5242.8277.6365.9423.0485.5555.1Derated Rating (Amps.)(Amp)cos@sin@(Amp)%cos@sin@25355070951201501852x952x1202x1502x180Conductor Size (mm2)3C+3E3C+3E3C+3E3C+3E3C+3E3C+3E3C+3E3C+3E3C+3E3C+3E3C+3E3C+3ENo. of Cable core0.250.660.70.730.683.95200.091.00************************0.370.711.00.750.665.25200.100.99************************0.550.751.50.730.687.55200.110.99************************0.750.761.90.760.6511.26000.101.00************************1.10.792.60.780.6315.66000.100.99************************1.50.813.40.780.6320.76000.100.99************************2.20.834.80.800.6028.96000.110.99************************30.856.20.820.5740.66500.110.99************************40.868.30.810.5953.96500.110.99************************5.50.8710.80.840.5470.36500.110.99773**********************7.50.8914.30.850.5393.06500.120.99578789********************110.9121.20.820.57163.37700.101.00402547722******************150.9228.40.830.56215.57600.100.99298406535745986**************18.50.9335.20.820.57257.07300.100.99242330435604798975************220.9341.80.820.57296.97100.110.99204278366509672820876912********300.9455.10.840.54408.07400.110.99152207273381504613638665********370.9467.90.840.54523.07700.100.99123168222309409482501521818964****450.9480.00.860.51592.17400.110.99--140185259344419437456688838874911550.95101.10.830.56697.66900.110.99----150209276338368384553676737769750.95132.50.860.51914.36900.120.99--------208255279292415509558583900.95156.80.870.491129.37200.120.99--------1752142272373494294544741100.96190.90.870.491336.37000.120.99------------1911992873523813991320.96228.60.870.491623.17100.120.99--------------1642392943153291600.96277.10.870.491967.47100.120.99----------------198243260271Notes:1) MOTOR DATA IS BASED ON ABB MOTORS6)System Nominal Voltage :400V2) CABLE DATA IS BASED ON NEXANS CABLES.System Frequency :50Hz3) CABLE DERATING FACTORS ARE AS FOLLOWS :-Steady State Volt Drop :3%A)Ambient temp at 40C1.05Motor Starting Volt Drop :10%B)Grouping (6 and above cables bunching)0.857)-- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.Total correction factor0.898)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10004) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER1.732X Full / Starting Current I (fl/st) x (RCos@+XSin@)AND FULLY LOADED.9)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZEDFOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

230VFDR-L1 (3%)PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)230V FEEDER SELECTION CHART (L1) - 3% VdropCLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable ParametersFeeder Rating9.6395.9933.9652.3461.4790.9360.6740.4990.3440.2490.1960.1610.1280.1250.098Resistance (Ohms/km) at 90C0.1030.0960.0900.0850.0800.0790.0770.0760.0760.0740.0720.0720.0720.0370.036Reactance (Ohms/km) 50Hz26.034.044.061.082.0108.0133.0167.0206.0249.0288.0331.0377.0498.0576.0Current Rating (Amps.) at 45CCBFLC23.230.339.354.473.296.4118.7149.0183.9222.2257.0295.4336.5444.5514.1Derated Rating (Amps.)(Amp)(Amp)Cos@[email protected] Size (mm2)2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PENo. of Cable core43.200.850.53131210315529830********************108.000.850.535284126212332515703929**************1612.800.850.53335279132207322439581811************3225.600.850.53----3966104161220290405538659771918****4032.000.850.53------5383129176232324430527617735860**5040.000.850.53--------661031411862593444224935886888436350.400.850.53--------53821121472062733353924675466698064.000.850.53----------648811616221526430836743052710080.000.850.53------------7093130172211247294344422125100.000.850.53--------------74104138169197235275337160128.000.850.53------------------108132154184215264200160.000.850.53--------------------105123147172211250200.000.850.53----------------------99118138169300240.000.850.53--------------------------115141Notes:1) CABLE DATA IS BASED ON NEXANS CABLES.6)System Nominal Voltage :230V2) CABLE DERATING FACTORS ARE AS FOLLOWS :-System Frequency :50HzA)Ambient temp at 40C1.05Steady State Allowable Volt Drop :3%B)Grouping (6 and above cables bunching)0.85Total correction factor0.897)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10003) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER2 x I x (RCos@+XSin@)AND FULLY LOADED.8)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,4) -- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZED5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.FOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

230VFDR-L2 (3%)PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)230V FEEDER SELECTION CHART (L2) - 3% VdropCLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable ParametersFeeder Rating9.6395.9933.9652.3461.4790.9360.6740.4990.3440.2490.1960.1610.1280.1250.098Resistance (Ohms/km) at 90C0.1030.0960.0900.0850.0800.0790.0770.0760.0760.0740.0720.0720.0720.0370.036Reactance (Ohms/km) 50Hz26.034.044.061.082.0108.0133.0167.0206.0249.0288.0331.0377.0498.0576.0Current Rating (Amps.) at 45CCBFLC23.230.339.354.473.296.4118.7149.0183.9222.2257.0295.4336.5444.5514.1Derated Rating (Amps.)(Amp)(Amp)Cos@[email protected] Size (mm2)2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PENo. of Cable core43.200.850.53131210315529830********************108.000.850.535284126212332515703929**************1612.800.850.53335279132207322439581811************3225.600.850.53----3966104161220290405538659771918****4032.000.850.53------5383129176232324430527617735860**5040.000.850.53--------661031411862593444224935886888436350.400.850.53--------53821121472062733353924675466698064.000.850.53----------648811616221526430836743052710080.000.850.53------------7093130172211247294344422125100.000.850.53--------------74104138169197235275337160128.000.850.53------------------108132154184215264200160.000.850.53--------------------105123147172211250200.000.850.53----------------------99118138169300240.000.850.53--------------------------115141Notes:1) CABLE DATA IS BASED ON NEXANS CABLES.6)System Nominal Voltage :230V2) CABLE DERATING FACTORS ARE AS FOLLOWS :-System Frequency :50HzA)Ambient temp at 40C1.05Steady State Allowable Volt Drop :3%B)Grouping (6 and above cables bunching)0.85Total correction factor0.897)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10003) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER2 x I x (RCos@+XSin@)AND FULLY LOADED.8)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,4) -- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZED5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.FOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

230VFDR-L1 (2%)PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)230V FEEDER SELECTION CHART (L1) - 2% VdropCLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable ParametersFeeder Rating9.6395.9933.9652.3461.4790.9360.6740.4990.3440.2490.1960.1610.1280.1250.098Resistance (Ohms/km) at 90C0.1030.0960.0900.0850.0800.0790.0770.0760.0760.0740.0720.0720.0720.0370.036Reactance (Ohms/km) 50Hz26.034.044.061.082.0108.0133.0167.0206.0249.0288.0331.0377.0498.0576.0Current Rating (Amps.) at 45CCBFLC23.230.339.354.473.296.4118.7149.0183.9222.2257.0295.4336.5444.5514.1Derated Rating (Amps.)(Amp)(Amp)Cos@[email protected] Size (mm2)2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PENo. of Cable core43.200.850.5387140210353553859******************108.000.850.53355684141221343469619865************1612.800.850.5322355388138215293387541717879********3225.600.850.53----2644691071461942703584395146127178794032.000.850.53------3555861171552162873514114905747035040.000.850.53--------4469941241732292813293924595626350.400.850.53--------355574981371822232613113644468064.000.850.53----------43597710814317620624528735110080.000.850.53------------476286115141164196229281125100.000.850.53--------------506992112132157184225160128.000.850.53------------------7288103122143176200160.000.850.53--------------------708298115141250200.000.850.53----------------------667892112300240.000.850.53--------------------------7694Notes:1) CABLE DATA IS BASED ON NEXANS CABLES.6)System Nominal Voltage :230V2) CABLE DERATING FACTORS ARE AS FOLLOWS :-System Frequency :50HzA)Ambient temp at 40C1.05Steady State Allowable Volt Drop :2%B)Grouping (6 and above cables bunching)0.85Total correction factor0.897)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10003) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER2 x I x (RCos@+XSin@)AND FULLY LOADED.8)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,4) -- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZED5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.FOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

230VFDR-L2 (2%)PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)230V FEEDER SELECTION CHART (L2) - 2% VdropCLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable ParametersFeeder Rating9.6395.9933.9652.3461.4790.9360.6740.4990.3440.2490.1960.1610.1280.1250.098Resistance (Ohms/km) at 90C0.1030.0960.0900.0850.0800.0790.0770.0760.0760.0740.0720.0720.0720.0370.036Reactance (Ohms/km) 50Hz26.034.044.061.082.0108.0133.0167.0206.0249.0288.0331.0377.0498.0576.0Current Rating (Amps.) at 45CCBFLC23.230.339.354.473.296.4118.7149.0183.9222.2257.0295.4336.5444.5514.1Derated Rating (Amps.)(Amp)(Amp)Cos@[email protected] Size (mm2)2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PENo. of Cable core43.200.850.5387140210353553859******************108.000.850.53355684141221343469619865************1612.800.850.5322355388138215293387541717879********3225.600.850.53----2644691071461942703584395146127178794032.000.850.53------3555861171552162873514114905747035040.000.850.53--------4469941241732292813293924595626350.400.850.53--------355574981371822232613113644468064.000.850.53----------43597710814317620624528735110080.000.850.53------------476286115141164196229281125100.000.850.53--------------506992112132157184225160128.000.850.53------------------7288103122143176200160.000.850.53--------------------708298115141250200.000.850.53----------------------667892112300240.000.850.53--------------------------7694Notes:1) CABLE DATA IS BASED ON NEXANS CABLES.6)System Nominal Voltage :230V2) CABLE DERATING FACTORS ARE AS FOLLOWS :-System Frequency :50HzA)Ambient temp at 40C1.05Steady State Allowable Volt Drop :2%B)Grouping (6 and above cables bunching)0.85Total correction factor0.897)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10003) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER2 x I x (RCos@+XSin@)AND FULLY LOADED.8)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,4) -- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZED5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.FOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

230VFDR-L2 (1%)PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)230V FEEDER SELECTION CHART (L2) - 1% VdropCLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable ParametersFeeder Rating9.6395.9933.9652.3461.4790.9360.6740.4990.3440.2490.1960.1610.1280.1250.0980.0810.0640.0830.0650.0540.043Resistance (Ohms/km) at 90C0.1030.0960.0900.0850.0800.0790.0770.0760.0760.0740.0720.0720.0720.0370.0360.0360.0360.0250.0240.0240.024Reactance (Ohms/km) 50Hz26.034.044.061.082.0108.0133.0167.0206.0249.0288.0331.0377.0498.0576.0662.0754.0747.0864.0993.01131.0Current Rating (Amps.) at 45CCBFLC23.230.339.354.473.296.4118.7149.0183.9222.2257.0295.4336.5444.5514.1590.8672.9666.7771.1886.31009.4Derated Rating (Amps.)(Amp)(Amp)Cos@Sin@2.546101625355070951201501852x952x1202x1502x1853x953x1203x1503x185Conductor Size (mm2)2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PENo. of Cable core43.200.850.534470105176277429586774**************************108.000.850.5317284271111172234310432574703822980****************1612.800.850.531117264469107146194270358439514612717879************3225.600.850.53----1322355473971351792202573063584395146125386597719184032.000.850.53------18284359771081431762062452873514114904305276177355040.000.850.53--------22344762861151411641962292813293923444224935886350.400.850.53--------1827374969911121311561822232613112733353924678064.000.850.53----------21293954728810312214317620624521526430836710080.000.850.53------------23314357708298115141164196172211247294125100.000.850.53--------------25354656667892112132157138169197235160128.000.850.53------------------364451617288103122108132154184200160.000.850.53--------------------3541495770829886105123147250200.000.850.53----------------------333946566678698499118312.5250.000.850.53--------------------------3745536355677994500400.000.850.53------------------------------333934424959625500.000.850.53------------------------------------343947787.5630.000.850.53----------------------------------------37Notes:1) CABLE DATA IS BASED ON NEXANS CABLES.6)System Nominal Voltage :230V2) CABLE DERATING FACTORS ARE AS FOLLOWS :-System Frequency :50HzA)Ambient temp at 40C1.05Steady State Allowable Volt Drop :1%B)Grouping (6 and above cables bunching)0.85Total correction factor0.897)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10003) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER2 x I x (RCos@+XSin@)AND FULLY LOADED.8)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,4) -- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZED5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.FOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

120VFDR-L1 (2%)PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)120V DC FEEDER SELECTION CHART (L1)CLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable ParametersFeeder Rating9.6395.9933.9652.3461.4790.9360.6740.4990.3440.2490.1960.1610.1280.1250.0980.0810.064Resistance (Ohms/km) at 90C26.034.044.061.082.0108.0133.0167.0206.0249.0288.0331.0377.0498.0576.0662.0754.0Current Rating (Amps.) at 45CCBFLC23.230.339.354.473.296.4118.7149.0183.9222.2257.0295.4336.5444.5514.1590.8672.9Derated Rating (Amps.)(Amp)(Amp)2.546101625355070951201501852x952x1202x1502x185Conductor Size (mm2)2C2C2C2C2C2C2C2C2C2C2C2C2C2C2C2C2CNo. of Cable core2016.0081319325180111150218301383466586602765932**108.0016253864101160223301436602765932**********1612.801016244063100139188273377478582732753957****3225.60----1220325070941361882392913663774785827324032.00------16254056751091511912332933013834665865040.00--------20324560871201531862342413063734696350.40--------1625354869961211481861912432963728064.00----------20283855759611614615119123329310080.00------------223044607793117120153186234125100.00--------------24354861759496122149188160128.00------------------384858737596116146200160.00--------------------384759607793117250200.00----------------------374748617594Notes:1) CABLE DATA IS BASED ON NEXANS CABLES.6)System Nominal Voltage :120V2) CABLE DE-RATING FACTORS ARE AS FOLLOWS :-Steady State Allowable Volt Drop :2%A)Ambient temp at 40C1.05B)Grouping (6 and above cables bunching)0.85Total correction factor0.897)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10003) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER2 x I x RAND FULLY LOADED.8)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,4) -- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZED5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.FOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

120VFDR-L2 (2%)PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)120V DC FEEDER SELECTION CHART (L2)CLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable ParametersFeeder Rating9.6395.9933.9652.3461.4790.9360.6740.4990.3440.2490.1960.1610.1280.1250.0980.0810.064Resistance (Ohms/km) at 90C26.034.044.061.082.0108.0133.0167.0206.0249.0288.0331.0377.0498.0576.0662.0754.0Current Rating (Amps.) at 45CCBFLC23.230.339.354.473.296.4118.7149.0183.9222.2257.0295.4336.5444.5514.1590.8672.9Derated Rating (Amps.)(Amp)(Amp)2.546101625355070951201501852x952x1202x1502x185Conductor Size (mm2)2C2C2C2C2C2C2C2C2C2C2C2C2C2C2C2C2CNo. of Cable core43.20396395160254401556752******************108.0016253864101160223301436602765932**********1612.801016244063100139188273377478582732753957****3225.60----1220325070941361882392913663774785827324032.00------16254056751091511912332933013834665865040.00--------20324560871201531862342413063734696350.40--------1625354869961211481861912432963728064.00----------20283855759611614615119123329310080.00------------223044607793117120153186234125100.00--------------24354861759496122149188160128.00------------------384858737596116146200160.00--------------------384759607793117250200.00----------------------374748617594Notes:1) CABLE DATA IS BASED ON NEXANS CABLES.6)System Nominal Voltage :120V2) CABLE DE-RATING FACTORS ARE AS FOLLOWS :-Steady State Allowable Volt Drop :2%A)Ambient temp at 40C1.05B)Grouping (6 and above cables bunching)0.85Total correction factor0.897)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10003) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER2 x I x RAND FULLY LOADED.8)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,4) -- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZED5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.FOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

120VFDR-L2 (1%)PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)120V DC FEEDER SELECTION CHART (L2)CLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable ParametersFeeder Rating9.6395.9933.9652.3461.4790.9360.6740.4990.3440.2490.1960.1610.1280.1250.0980.0810.064Resistance (Ohms/km) at 90C26.034.044.061.082.0108.0133.0167.0206.0249.0288.0331.0377.0498.0576.0662.0754.0Current Rating (Amps.) at 45CCBFLC23.230.339.354.473.296.4118.7149.0183.9222.2257.0295.4336.5444.5514.1590.8672.9Derated Rating (Amps.)(Amp)(Amp)2.546101625355070951201501852x952x1202x1502x185Conductor Size (mm2)2C2C2C2C2C2C2C2C2C2C2C2C2C2C2C2C2CNo. of Cable core43.2019314780127200278376545753957************108.0081319325180111150218301383466586602765932**1612.80581220325070941361882392913663774785827323225.60----6101625354768941201461831882392913664032.00------8132028385575961161461511912332935040.00--------10162230446077931171201531862346350.40--------81318243548617493961211481868064.00----------1014192738485873759611614610080.00------------11152230384759607793117125100.00--------------12172431374748617594160128.00------------------1924293738485873200160.00--------------------19232930384759250200.00----------------------192324313747Notes:1) CABLE DATA IS BASED ON NEXANS CABLES.6)System Nominal Voltage :120V2) CABLE DE-RATING FACTORS ARE AS FOLLOWS :-Steady State Allowable Volt Drop :1%A)Ambient temp at 40C1.05B)Grouping (6 and above cables bunching)0.85Total correction factor0.897)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10003) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER2 x I x RAND FULLY LOADED.8)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,4) -- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZED5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.FOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

110VFDR-L1PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)110V DC FEEDER SELECTION CHART (L1)CLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable ParametersFeeder Rating9.6395.9933.9652.3461.4790.9360.6740.4990.3440.2490.1960.1610.1280.1250.0980.0810.064Resistance (Ohms/km) at 90C26.034.044.061.082.0108.0133.0167.0206.0249.0288.0331.0377.0498.0576.0662.0754.0Current Rating (Amps.) at 45CCBFLC23.230.339.354.473.296.4118.7149.0183.9222.2257.0295.4336.5444.5514.1590.8672.9Derated Rating (Amps.)(Amp)(Amp)2.546101625355070951201501852x952x1202x1502x185Conductor Size (mm2)2C2C2C2C2C2C2C2C2C2C2C2C2C2C2C2C2CNo. of Cable core43.20365787147232367510689999****************108.001423355993147204276400552702854**********1612.8091422375892128172250345438534671690877****3225.60----1118294664861251732192673363454385346714032.00------15233751691001381752142692763514275375040.00--------19294155801101401712152212813424306350.40--------1523324463881111361711752232713418064.00----------18263450698810713413817521426910080.00------------202840557085107110140171215125100.00--------------22324456688688112137172160128.00------------------354453676988107134200160.00--------------------354354557085107250200.00----------------------344344566886Notes:1) CABLE DATA IS BASED ON NEXANS CABLES.6)System Nominal Voltage :110V2) CABLE DE-RATING FACTORS ARE AS FOLLOWS :-Steady State Allowable Volt Drop :2%A)Ambient temp at 40C1.05B)Grouping (6 and above cables bunching)0.85Total correction factor0.897)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10003) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER2 x I x RAND FULLY LOADED.8)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,4) -- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZED5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.FOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

110VFDR-L2PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)110V DC FEEDER SELECTION CHART (L2)CLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable ParametersFeeder Rating9.6395.9933.9652.3461.4790.9360.6740.4990.3440.2490.1960.1610.1280.1250.0980.0810.064Resistance (Ohms/km) at 90C26.034.044.061.082.0108.0133.0167.0206.0249.0288.0331.0377.0498.0576.0662.0754.0Current Rating (Amps.) at 45CCBFLC23.230.339.354.473.296.4118.7149.0183.9222.2257.0295.4336.5444.5514.1590.8672.9Derated Rating (Amps.)(Amp)(Amp)2.546101625355070951201501852x952x1202x1502x185Conductor Size (mm2)2C2C2C2C2C2C2C2C2C2C2C2C2C2C2C2C2CNo. of Cable core43.20365787147232367510689999****************108.001423355993147204276400552702854**********1612.8091422375892128172250345438534671690877****3225.60----1118294664861251732192673363454385346714032.00------15233751691001381752142692763514275375040.00--------19294155801101401712152212813424306350.40--------1523324463881111361711752232713418064.00----------18263450698810713413817521426910080.00------------202840557085107110140171215125100.00--------------22324456688688112137172160128.00------------------354453676988107134200160.00--------------------354354557085107250200.00----------------------344344566886Notes:1) CABLE DATA IS BASED ON NEXANS CABLES.6)System Nominal Voltage :110V2) CABLE DE-RATING FACTORS ARE AS FOLLOWS :-Steady State Allowable Volt Drop :2%A)Ambient temp at 40C1.05B)Grouping (6 and above cables bunching)0.85Total correction factor0.897)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10003) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER2 x I x RAND FULLY LOADED.8)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,4) -- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZED5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.FOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

24VFDR-L2PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)24V DC FEEDER SELECTION CHART (L2)CLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable ParametersFeeder Rating9.6395.9933.9652.3461.4790.9360.6740.4990.3440.2490.1960.1610.1280.1250.0980.0810.064Resistance (Ohms/km) at 90C26.034.044.061.082.0108.0133.0167.0206.0249.0288.0331.0377.0498.0576.0662.0754.0Current Rating (Amps.) at 45CCBFLC23.230.339.354.473.296.4118.7149.0183.9222.2257.0295.4336.5444.5514.1590.8672.9Derated Rating (Amps.)(Amp)(Amp)2.546101625355070951201501852x952x1202x1502x185Conductor Size (mm2)2C2C2C2C2C2C2C2C2C2C2C2C2C2C2C2C2CNo. of Cable core43.2081319325180111150218301383466586602765932**108.003581320324560871201531862342413063734691612.802358132028385575961161461511912332933225.60----246101419273848587375961161464032.00------358111522303847596077931175040.00--------469121724313747486175946350.40--------357101419243037384959748064.00----------46811151923293038475910080.00------------4691215192324313747125100.00--------------571012151919243038160128.00------------------810121515192329200160.00--------------------891212151923250200.00----------------------7910121519Notes:1) CABLE DATA IS BASED ON NEXANS CABLES.6)System Nominal Voltage :24V2) CABLE DE-RATING FACTORS ARE AS FOLLOWS :-Steady State Allowable Volt Drop :2%A)Ambient temp at 40C1.05B)Grouping (6 and above cables bunching)0.85Total correction factor0.897)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10003) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER2 x I x RAND FULLY LOADED.8)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,4) -- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZED5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.FOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A