FM APPROVAL ANNOUNCEMENT Telephone: 13000 ASKIN Email: [email protected] www.askin.net.au ASKIN’s world beating XFLAM cored steel laminated insulated panel recently achieved a best in class by complying with the requirements of a Class One material under the test regime dictated by standard FM4880 and FM4881. FM4880: Parallel Panel Test The 16 foot test establishes the expected reaction of a specific product specimen to a standardized fire directed through a sand box at the base of two opposing walls, mounted to a steel frame with the following dimensions: Width: 1.1m Height: 4.9m Gap: 0.5m A gas fired burner at 360kW is applied for fifteen minutes at the base of the two walls. ASKIN’S XFLAM cored panels achieved a best in class performance without the use of joint stitching rivets. FM4880 unlimited height Class 1 Group A approval. Max heat output of 355 kW much less than the 850 kW threshold and significantly less than 550 kW generally achieved for other fire resistant insulated panels. Smoke generated 195 grams/15 minute test much less than 300 grams allowed for smoke sensitive construction, required for all food and drug manufacture. In principle, the parallel panel test determines the following: The potential for fire spread up the wall, determined by height of char inside the panel. The potential for spread of fire through the wall, determined by measuring the depth of char and the remaining untouched material after the test. The potential for fire spread through a building is evaluated by the measurement of the total rate of heat release of the fire, determining the material contribution to the fire. The hazard of reduced visibility is estimated by weighing of light-obscuring smoke. APRIL 2015 ASKIN XFLAM PANEL ACHIEVED A CLASS ONE FIRE PERFORMANCE TO STANDARDS FM4880 AND FM4881 WITHOUT SLIP JOINT STITCHING RIVETS

ASKIN FM Approval Announcement - xflam.com · FM APPROVAL ANNOUNCEMENT Telephone: 13000 ASKIN Email: [email protected] ASKIN’s world beating XFLAM cored steel laminated insulated

  • Upload
    lehanh

  • View
    219

  • Download
    0

Embed Size (px)

Citation preview

FM APPROVAL ANNOUNCEMENT

Telephone: 13000 ASKINEmail: [email protected]

www.askin.net.au

ASKIN’s world beating XFLAM cored steel laminated insulated panel recently achieved a best in class by complying with the requirements of a Class One material under the test regime dictated by standard FM4880 and FM4881.

FM4880: Parallel Panel Test

The 16 foot test establishes the expected reaction of a specific product specimen to a standardized fire directed through a sand box at the base of two opposing walls, mounted to a steel frame with the following dimensions:

• Width: 1.1m

• Height: 4.9m

• Gap: 0.5m

A gas fired burner at 360kW is applied for fifteen minutes at the base of the two walls.

ASKIN’S XFLAM cored panels achieved a best in class performance without the use of joint stitching rivets.

• FM4880 unlimited height Class 1 Group A approval.

• Max heat output of 355 kW much less than the 850 kW threshold and significantly less than 550 kW generally achieved for other fire resistant insulated panels.

• Smoke generated 195 grams/15 minute test much less than 300 grams allowed for smoke sensitive construction, required for all food and drug manufacture.

In principle, the parallel panel test determines the following:

• The potential for fire spread up the wall, determined by height of char inside the panel.

• The potential for spread of fire through the wall, determined by measuring the depth of char and the remaining untouched material after the test.

• The potential for fire spread through a building is evaluated by the measurement of

the total rate of heat release of the fire, determining the material contribution to the fire.

• The hazard of reduced visibility is estimated by weighing of light-obscuring smoke.

APRIL 2015

ASKIN XFLAM PANEL ACHIEVED A CLASS ONE FIRE PERFORMANCE TO STANDARDS FM4880 AND FM4881 WITHOUT SLIP JOINT STITCHING RIVETS