Upload
aaron-m-ward
View
227
Download
1
Embed Size (px)
Citation preview
8/3/2019 ASHRAE Standards for Cooling Towers
1/51
John Lane Evapco, Inc.John Lane Evapco, Inc.
Sustainability andSustainability and
Evaporative CoolingEvaporative Cooling
8/3/2019 ASHRAE Standards for Cooling Towers
2/51
ASHRAE GreenGuide definesSustainable Engineering as:
Providing for the needs of thepresent without detracting from the
ability to fulfill the needs of thefuture.
ItIts The Right Thing To Do!!!s The Right Thing To Do!!!
ASHRAE is t he eng in eer ing eng in e th a t d r i v es su st a i n ab i l i t y .
8/3/2019 ASHRAE Standards for Cooling Towers
3/51
Green Building ChoicesGreen Building Choices
Involve compromises among: Environmental goals.
Energy conservation.
Raw material conservation.
Innovative treatment and controlmethods.
Cost.
8/3/2019 ASHRAE Standards for Cooling Towers
4/51
Condenser ChoicesCondenser Choices Air CoolingAir Cooling
Economically viable onEconomically viable onsmall systems.small systems.
Uses no water onUses no water on--site.site.
Higher condensingHigher condensing
temperaturetemperature lesslessenergy efficient.energy efficient.
Typically more fans andTypically more fans and
motorsmotors mechanicalmechanical
maintenance may bemaintenance may be
higher.higher.
Water CoolingWater Cooling
Only choice on largeOnly choice on largesystems.systems.
Lower condensingLower condensing
temperaturetemperature moremore
energy efficient.energy efficient. Water use at facilityWater use at facility
offset by less water useoffset by less water use
at power plant.at power plant.
Requires treatment ofRequires treatment of
recirculated water.recirculated water.
8/3/2019 ASHRAE Standards for Cooling Towers
5/51
Lower Condensing TemperatureLower Condensing Temperature
Yields BIG Energy SavingsYields BIG Energy Savings
8/3/2019 ASHRAE Standards for Cooling Towers
6/51
Water Use at Building Offset byWater Use at Building Offset by
Reduction at Utility PlantReduction at Utility Plant
AirAir--Cooled @ 1.49Cooled @ 1.49
kWh/tonkWh/ton
Total kWh =Total kWh = 1,072,800
Utility water usage @Utility water usage @2 gal /kWh =2 gal /kWh =
2,145,6002,145,600
WaterWater--Cooled @ 0.94Cooled @ 0.94
kWh/tonkWh/ton
Total kWh =Total kWh = 676,800
Utility water usage @Utility water usage @2 gal/kWh =2 gal/kWh =
1,353,6001,353,600
Evaporation at 80%Evaporation at 80%
latent =latent = 1,036,8001,036,800 Total water usage =Total water usage =
2,390,4002,390,400
400-ton at 1,800 hr/yr equivalent full load
8/3/2019 ASHRAE Standards for Cooling Towers
7/51
Significant COSignificant CO22 ReductionsReductions
Using waterUsing water--cooling on one 400cooling on one 400--
ton system saveston system saves396,000 kWh per year.per year.
US average generation is 1.55US average generation is 1.55
pounds COpounds CO22/kWh/kWh
Annual reductions ofAnnual reductions of
307 tons CO2.
8/3/2019 ASHRAE Standards for Cooling Towers
8/51
8/3/2019 ASHRAE Standards for Cooling Towers
9/51
Cooling TowersCooling Towers
Primary GoalPrimary Goal remove heat fromremove heat from
water under specific conditions.water under specific conditions.
Secondary GoalSecondary Goal perform in anperform in an
energy efficient, water efficient, andenergy efficient, water efficient, andenvironmentally sound manner.environmentally sound manner.
Two general types of towersTwo general types of towers CounterflowCounterflow andand CrossflowCrossflow
8/3/2019 ASHRAE Standards for Cooling Towers
10/51
CrossCross--flow Schematicflow Schematic
Hot waterdeck
Inlet airslats
8/3/2019 ASHRAE Standards for Cooling Towers
11/51
CrossCross--flow Cooling Towerflow Cooling Tower
8/3/2019 ASHRAE Standards for Cooling Towers
12/51
CrossCross--flow Cooling Towerflow Cooling Tower
8/3/2019 ASHRAE Standards for Cooling Towers
13/51
CounterCounter--flow Schematicflow Schematic
DriftEliminator
Inlet AirLouvers
Fill
Spray Header
8/3/2019 ASHRAE Standards for Cooling Towers
14/51
CounterCounter--flow Towerflow Tower
8/3/2019 ASHRAE Standards for Cooling Towers
15/51
CrossCross--flowflowCombinationCombination
Fill & Drift EliminatorFill & Drift Eliminator
8/3/2019 ASHRAE Standards for Cooling Towers
16/51
CrossCross--flowflow CombinationCombination
Air Inlet, Fill & Drift EliminatorAir Inlet, Fill & Drift Eliminator
8/3/2019 ASHRAE Standards for Cooling Towers
17/51
CounterCounter--flowflow FillFill
8/3/2019 ASHRAE Standards for Cooling Towers
18/51
CounterCounter--flowflowDrift EliminatorDrift Eliminator
8/3/2019 ASHRAE Standards for Cooling Towers
19/51
Cooling Towers Conserve WaterCooling Towers Conserve Water
Cold water 1,184 gpm
Evaporation 12 gpm
Warm water 1,200 gpm
Blowdown 4 gpm
Air 90,000 CFM
8/3/2019 ASHRAE Standards for Cooling Towers
20/51
Traditional Water TreatmentTraditional Water Treatment
BiocidesBiocides
OxidizingOxidizing chlorine or brominechlorine or bromine
NonNon--oxidizingoxidizing
Corrosion InhibitorsCorrosion Inhibitors Scale InhibitorsScale Inhibitors
8/3/2019 ASHRAE Standards for Cooling Towers
21/51
Potential Release PathwaysPotential Release Pathways DriftDrift tower water dropletstower water droplets
entrained in cooling air.entrained in cooling air. Blowout/splashoutBlowout/splashout wind carriedwind carried
tower water.tower water.
Spills and LeaksSpills and Leaks Blowdown or BleedBlowdown or Bleed intentionalintentional
discharge of tower water.discharge of tower water.
Chemical releases and emissionsChemical releases and emissions
NoiseNoise particularly fan noise.particularly fan noise.
8/3/2019 ASHRAE Standards for Cooling Towers
22/51
DriftDrift Entrainment of waterEntrainment of water
droplets in air.droplets in air. Contains all theContains all the
chemicals and bacteriachemicals and bacteria
in the tower water.in the tower water.
Described as a % ofDescribed as a % ofrecirculating waterrecirculating water
flow.flow.
Ranges from 0.02% toRanges from 0.02% to0.001%.0.001%.
1,0301,0300.001%0.001%
5,1805,1800.005%0.005%
20,72020,7200.02%0.02%
Total DriftTotal Drift
Gal/yrGal/yr
Drift RateDrift Rate
400-ton Tower
1,800 hours
8/3/2019 ASHRAE Standards for Cooling Towers
23/51
Excessive DriftExcessive Drift
8/3/2019 ASHRAE Standards for Cooling Towers
24/51
Legionella Transmission
Microbial Associations
NutrientsBiocidesSystem Cleanliness
Temp., pH,
NutrientsMicrobial Associations
Temp., Humidity,Droplet Production
Factors
Environmental
2
Amplification
1
Survival inReservoir (Nature)
3Dissemination
(Aerosolization)
Events
6
Multiply inHuman
Phagocytes
7Diagnosis ofLegionnaires
Disease
5
Susceptible HostExposure
Events
Clinical
Virulence
SymptomsLab Tests
Surveillance
Age
DiseaseImmunodeficiency
Factors
4Transmission
HumidityDroplet Size
Distance
Risk
Minimization(Prevention)
8/3/2019 ASHRAE Standards for Cooling Towers
25/51
AWTAWTLegionellaLegionellaTransmissionTransmission
8/3/2019 ASHRAE Standards for Cooling Towers
26/51
Basin Splashout and SpillsBasin Splashout and Spills
Strong cross windsStrong cross winds
Slat inlet air louvers with no fan loadSlat inlet air louvers with no fan load Clogged nozzles in hotClogged nozzles in hot--water basinwater basin
Flooding at shutdownFlooding at shutdown Improperly designed equalizersImproperly designed equalizers
Old or damaged equipmentOld or damaged equipment
Uncontrolled Discharges
8/3/2019 ASHRAE Standards for Cooling Towers
27/51
Gravity Flow WaterGravity Flow Water
Distribution SystemDistribution System
If nozzles clog, basin will overflow.If nozzles clog, basin will overflow.
With slat inlet louvers water can splash outWith slat inlet louvers water can splash outunder nounder no--fan conditions.fan conditions.
8/3/2019 ASHRAE Standards for Cooling Towers
28/51
Spills and SplashoutSpills and Splashout -- CounterflowCounterflow
No Overflowwith SprayHeaders
Water inside
louvers
8/3/2019 ASHRAE Standards for Cooling Towers
29/51
Overflow at ShutdownOverflow at Shutdown
8/3/2019 ASHRAE Standards for Cooling Towers
30/51
LeaksLeaks
8/3/2019 ASHRAE Standards for Cooling Towers
31/51
BlowdownBlowdown Intentional discharge of water.Intentional discharge of water.
Contains all the residual chemicalsContains all the residual chemicals
and microbes in the tower.and microbes in the tower.
Usually discharged to the sewerUsually discharged to the sewertreatment systems (POTW).treatment systems (POTW).
POTW discharges to rivers orPOTW discharges to rivers orgeneratesgenerates sludgessludges that are recycled.that are recycled.
8/3/2019 ASHRAE Standards for Cooling Towers
32/51
Where Do the Chemicals Go?Where Do the Chemicals Go?
8/3/2019 ASHRAE Standards for Cooling Towers
33/51
Poor Condenser Water Piping & PracticePoor Condenser Water Piping & Practice
Dead LegsDead Legs
Infrequent useInfrequent use
loopsloops Plate andPlate and
Frame HeatFrame HeatExchangersExchangers
Chiller LeadChiller Lead--LagLag
ProtocolProtocol
8/3/2019 ASHRAE Standards for Cooling Towers
34/51
Poor Equalizer Piping =Poor Equalizer Piping =
Harsher BiocidesHarsher Biocides
Nocleanout
BottomConnection
Low-flow
Legs
8/3/2019 ASHRAE Standards for Cooling Towers
35/51
Algae GrowthAlgae GrowthHarsher BiocidesHarsher Biocides
Sunlight intobasin promotesalgae growth
8/3/2019 ASHRAE Standards for Cooling Towers
36/51
Sound Reduction TechnologySound Reduction TechnologySound Reduction Technology
Alternate FansAlternate Fans5 feet above the fan5 feet above the fan
99--1515 dB(AdB(A) Reduction) Reduction
8/3/2019 ASHRAE Standards for Cooling Towers
37/51
Choices in Evaporative CoolingChoices in Evaporative Cooling
GreenGreenbiocides e.g. hydrogen peroxide, ozonebiocides e.g. hydrogen peroxide, ozoneor nonor non--chemical techniques.chemical techniques.
GreenGreencorrosion inhibitors instead of zinc andcorrosion inhibitors instead of zinc andmolybdenates.molybdenates.
High efficiency drift eliminators.High efficiency drift eliminators.
Keep sunlight off of basin and minimizeKeep sunlight off of basin and minimizedeaddeadlegslegs..
Low sound fans.Low sound fans.
Good maintenance practices.Good maintenance practices.
8/3/2019 ASHRAE Standards for Cooling Towers
38/51
Water Treatment GoalsWater Treatment Goals Control Biological GrowthControl Biological Growth
Control Scale FormationControl Scale Formation
Minimize CorrosionMinimize Corrosion
Reasonable CostReasonable Cost
Minimize Environmental, Health andMinimize Environmental, Health and
Safety ImpactSafety Impact
These goals are being achievedwith some non-chemical methods.
8/3/2019 ASHRAE Standards for Cooling Towers
39/51
Physical Water TreatmentPhysical Water Treatment
Ashrae issued a research report onAshrae issued a research report onscale control in 2002.scale control in 2002.
Ashrae is developing a researchAshrae is developing a researchprogram to investigate biologicalprogram to investigate biologicalcontrol.control.
A variety of technologies areA variety of technologies arecommercially availablecommercially available somesome
eliminate all chemical additions.eliminate all chemical additions. Blowdown may be used for irrigation.Blowdown may be used for irrigation.
8/3/2019 ASHRAE Standards for Cooling Towers
40/51
PulsedPulsed--Power Water TreatmentPower Water Treatment The most successful physical waterThe most successful physical water
treatment technologytreatment technology Low power requirementLow power requirement
Continuous water treatment of 100%Continuous water treatment of 100%of the circulating waterof the circulating water
8/3/2019 ASHRAE Standards for Cooling Towers
41/51
Pulsed PowerPulsed Power
FDA Approved for Pasteurization.FDA Approved for Pasteurization.
Independent StudiesIndependent Studies
Sacramento Municipal UtilitySacramento Municipal Utility
District AlcoaDistrict Alcoa on performanceon performancein thein the field.field.
Several thousand successfulSeveral thousand successfulinstallations in the U.S.installations in the U.S.
8/3/2019 ASHRAE Standards for Cooling Towers
42/51
PulsedPulsed--Power Water TreatmentPower Water Treatment
Corrosion
Solve all Three Critical Challenges
of Treating Water Cooled Systems-Without Chemicals:
Scale Biological
8/3/2019 ASHRAE Standards for Cooling Towers
43/51
Result:Result:
Without Pulsed-Power With Pulsed-Power
Controls ScalingControls Scaling
Precipitation occurs on the seedsPrecipitation occurs on the seeds
not on heat transfer surfaces suchnot on heat transfer surfaces suchas chillers or condenser tubes.as chillers or condenser tubes.
8/3/2019 ASHRAE Standards for Cooling Towers
44/51
Powder Formation Instead of Scale
Biological ControlBiological Control - ElectroporationElectroporation
8/3/2019 ASHRAE Standards for Cooling Towers
45/51
Pulsed Electric Fields CreateHoles in Cell Walls
Biological ControlBiological Control -- ElectroporationElectroporation
FDA Approved Method ofCold Pasteurization
B C S
8/3/2019 ASHRAE Standards for Cooling Towers
46/51
Growing particlesagglomeratebacteria and
other smallparticles.
Biological ControlBiological ControlSedimentationSedimentation
C i C lC i C t l
8/3/2019 ASHRAE Standards for Cooling Towers
47/51
Eliminates acids for scalecontrol.
Eliminates oxidizing biocides
(chlorine, bromine).
Corrosion ControlCorrosion Control
Elimination of ChemicalsElimination of Chemicals
8/3/2019 ASHRAE Standards for Cooling Towers
48/51
Operation CharacteristicsOperation Characteristics
Operates at benign pH of 8.0to 9.0.
Operates at saturation ofcalcium carbonate.
Eliminates microbial influencedcorrosion (MIC).
P i W t T t tP i W t T t t
8/3/2019 ASHRAE Standards for Cooling Towers
49/51
Fluid cooler maintainsR&D cold room.
Cooler operated withchemical treatment @ 2cycles.
Heavy scale formed on
tubes, basin, and louvers.
Biological activitymeasured between
10,000 and 100,000CFU/ml.
Previous Water TreatmentPrevious Water Treatment
P l d P T t t
8/3/2019 ASHRAE Standards for Cooling Towers
50/51
Pulsed- PowerStarted
Biological Results
0
10,000
20,000
30,000
40,000
50,000
8/18/0
5
8/25/0
5
9/1/0
5
9/8/0
5
9/15/0
5
9/22/0
5
9/29/0
5
10/6/0
5
10/13/0
10/20/0
5
10/27/0 11
/3/0
5
11/10/0
Date
HPC
CFU/m
l
.
Reduced blowdown by
over 50%. Biological growth 1%
of previous levels.
Basin scalecompletely removedafter 2 months.
After 1 year tubes are
starting to de-scaleand biological controlcontinues.
Pulsed-Power Treatment
8/3/2019 ASHRAE Standards for Cooling Towers
51/51
SummarySummary Evaporation is the most energyEvaporation is the most energy
efficient form of cooling.efficient form of cooling.
Systems with reduced noise, driftSystems with reduced noise, driftand spill potential are available.and spill potential are available.
Good maintenance and operationalGood maintenance and operationalpractices are essential.practices are essential.
The environmental impact of waterThe environmental impact of watertreatment should be considered.treatment should be considered.