Ashrae 621 2008 High Performance Bldgr Presentation

Embed Size (px)

Citation preview

  • 8/6/2019 Ashrae 621 2008 High Performance Bldgr Presentation

    1/33

    Ventilation for Acceptable

    Indoor Air Quality62.1-2007

    Dave Kahn, P.E.Dave Kahn, P.E.

  • 8/6/2019 Ashrae 621 2008 High Performance Bldgr Presentation

    2/33

    The Industries Ventilation Standard

    Consensus Standard

    Standard of CareUsed in NFPA 5000 BuildingConstruction and Safety Code

    LEED Requirement

    Not adopted by 06 IMC Somesimilarities

  • 8/6/2019 Ashrae 621 2008 High Performance Bldgr Presentation

    3/33

    1973 First Issued office 15 cfm/p

    1981 Lower Rates office 5 cfm/p

    1989 Higher Rates office 20 cfm/p1999 Little Change office 20 cfm/p

    2001 More Mandatory Language

    2004 occupancy component +

    area component

    2007 Incorporate Addendums

  • 8/6/2019 Ashrae 621 2008 High Performance Bldgr Presentation

    4/33

    Exceptions to 65% RH requirements fordehumidification systems

    Appendix B references expanded & updated

    Added Appendix H documentation requirements

    Separation of ETS areas

    Requirement for residential spaces in buildingsover 3 stories

  • 8/6/2019 Ashrae 621 2008 High Performance Bldgr Presentation

    5/33

    Means to balance the system to achieve minimumairflow.

    Design documentation to state ventilation rate andair distribution assumptions.

    Controls to enable the fan to operate wheneverthe spaces served are occupied.

    VAV systems with fixed OA dampers must complyat minimum supply airflow.

    MERV 6 filters upstream of all coils or otherdevices with wetted surfaces.

  • 8/6/2019 Ashrae 621 2008 High Performance Bldgr Presentation

    6/33

    Treatment of Outdoor air is required if in anonattainment area.

    National Ambient Air Quality StandardsNAAQS

    1. Ozone

    2. Particulate Matter

    3. Carbon Monoxide

    4. Sulfur Oxides

    5. Nitrogen Dioxide

    6. Lead

  • 8/6/2019 Ashrae 621 2008 High Performance Bldgr Presentation

    7/33

    Prescriptive

    Space must be within 25 of permanent wall or

    roof openingOpenable area 4%of net occupiable floor area

    Free area of opening must be used

    Ventilation through adjoining rooms can be used

    EngineeredMust be approved by the Authority HavingJursdiction

  • 8/6/2019 Ashrae 621 2008 High Performance Bldgr Presentation

    8/33

    Ventilation Rate ProcedureMost commonly used method

    Lookup table

    Need zone air distribution effectiveness

    LEED requires this method

    Indoor Air Quality ProcedureDesign to maintain specific contaminant levels

    Mass Balance Analysis

    Methods used in similar buildings

    Validation by contaminant monitoring

  • 8/6/2019 Ashrae 621 2008 High Performance Bldgr Presentation

    9/33

    Ventilation

    Rate

    Procedure

  • 8/6/2019 Ashrae 621 2008 High Performance Bldgr Presentation

    10/33

    Use of building code occupantdensities is not required by the

    standardUse actual number ofoccupants (maximum)

    Use ASHRAE default valves

    form Table 6-1

  • 8/6/2019 Ashrae 621 2008 High Performance Bldgr Presentation

    11/33

  • 8/6/2019 Ashrae 621 2008 High Performance Bldgr Presentation

    12/33

  • 8/6/2019 Ashrae 621 2008 High Performance Bldgr Presentation

    13/33

  • 8/6/2019 Ashrae 621 2008 High Performance Bldgr Presentation

    14/33

    Single zone 2007

    High School classroom 35x35 30 people

    Vbz = RpPz + RaAz (Breathing Zone air flow rate)10 cfm /person 10 * 30 = 300 cfm

    0.12 cfm/ft2 0.12 * 35 * 35 = 147 cfm

    300 + 147 = 447 cfm

    Zone outdoor airflow Voz =Vbz/Ez447 /1 = 447 cfm or 14.9 cfm/person

  • 8/6/2019 Ashrae 621 2008 High Performance Bldgr Presentation

    15/33

    Single zone 2001

    High school classroom 35 x 35 30 people

    15 cfm /person 15 * 30 = 450 cfm cfm

  • 8/6/2019 Ashrae 621 2008 High Performance Bldgr Presentation

    16/33

    Single zone 2007

    Hotel auditorium 40x30, 170 people

    Vbz = RpPz + RaAz5 cfm /person 5 * 170 = 850 cfm

    0.06 cfm/ft2 0.06 * 40 * 30 = 72 cfm

    850 + 72 = 922 cfm

    Zone outdoor airflow Voz =Vbz/Ez922 /1 = 922 cfm or 5.4 cfm/person

  • 8/6/2019 Ashrae 621 2008 High Performance Bldgr Presentation

    17/33

    Standard does not prescribespecific ventilation rate

    requirements for spaces thatcontain smoking or that do notmeet the requirements in thestandard for separation fromspaces that contain smokingETS free areas shall be at a

    positive pressure with respect toany adjacent or connected ETSareas

  • 8/6/2019 Ashrae 621 2008 High Performance Bldgr Presentation

    18/33

  • 8/6/2019 Ashrae 621 2008 High Performance Bldgr Presentation

    19/33

  • 8/6/2019 Ashrae 621 2008 High Performance Bldgr Presentation

    20/33

    Vou = DSall zonesRpPz + Sall zones RaAz

    Vou - uncorrected outdoor air intakeD - occupant diversity = Ps/ Sall zones PzPs -total population of area servedby the system

    Pz - largest number of peoplein the zone

  • 8/6/2019 Ashrae 621 2008 High Performance Bldgr Presentation

    21/33

    Vot = Vou/EvVot - design outdoor air intake flow

    Vou - uncorrected outdoor air intake

    Ev - ventilation efficiency from Table 6-3or Appendix A

  • 8/6/2019 Ashrae 621 2008 High Performance Bldgr Presentation

    22/33

    Table 6-3 approach

    Manual calculation may result in more OA

    Appendix A approach

    Spreadsheet

  • 8/6/2019 Ashrae 621 2008 High Performance Bldgr Presentation

    23/33

    Zones served by system Zone 1 Zone 2 Zone 3 Zone 4

    Space type (select from pull-down list) Officespace

    Receptionareas

    Classrooms (age 9plus)

    Conference /meeting

    Officespace

    Az Floor area of zone, ft2 1000 1000 1000 500

    Pz Zone population, largest # of people expectedto occupy zone

    20 4 20 10

    Rp Area outdoor air rate from Table 6.1, cfm/ft2 5 5 10 5 5

    Ra People outdoor air rate from Table 6.1,cfm/person 0.06 0.06 0.12 0.06 0.06

    Pz*Rp

    100 20 200 50 0

    Az*Ra

    60 60 120 30 0

    Ez Zone air distribution effectiveness, Table 6.2 0.9 0.9 0.9 0.9

    Voz Outdoor airflow to the zone corrected for zoneair distribution effectiveness, (Pz*Rp +Az*Ra)/Ez, cfm

    178 89 356 89 #DIV/0!

    Vpz Primary airflow to zone from air handler. InVAV systems, use the design value. cfm

    1200 1200 1200 1200

    Vpzm

    The minimum value of the primary airflow tozone from air handler. In CAV systems, Vpzm= Vpz. cfm

    1200 1200 1200 1200

    Zp Primary outdoor air fraction, Voz/Vpzm 0.15 0.07 0.30 0.07

  • 8/6/2019 Ashrae 621 2008 High Performance Bldgr Presentation

    24/33

    SYSTEM LEVEL

    Ps System population, maximum simultaneious # of occupants ofspace served by system

    25

    D Occupant diversity, ratio of system peak occupancy to sum of spacepeak occupancies, = Ps/ Pz

    0.46

    Vou Uncorrected outdoor air intake, = D* Rp*Pz + Ra*Az, cfm 441

    Xs Mixing ratio at primary air handler of uncorrected outdoor air intaketo system primary flow, = Vou/Vps

    0.09 Not used in calculation

    SYSTEM EFFICIENCY

    Max Zp Max Zp 0.30

    Ev System venti lation efficiency, Table 6.3 based on maxZp 0.80

    Percent outdoor air intake

    Vot Minimum outdoor air intake, Vou/Ev, cfm 552 11% = Vot/Sum of Vpz

  • 8/6/2019 Ashrae 621 2008 High Performance Bldgr Presentation

    25/33

  • 8/6/2019 Ashrae 621 2008 High Performance Bldgr Presentation

    26/33

  • 8/6/2019 Ashrae 621 2008 High Performance Bldgr Presentation

    27/33

    Time Averaging

    Fluctuating occupancy

    Intermittent interruption of the supply airflow

    Intermittent closure of the OA damper

  • 8/6/2019 Ashrae 621 2008 High Performance Bldgr Presentation

    28/33

  • 8/6/2019 Ashrae 621 2008 High Performance Bldgr Presentation

    29/33

    Reset outdoor air intake flow.Occupancy

    Expected occupancy scheduled by time of day.

    Occupancy sensors.Estimate occupancy based on CO2.

    Air Distribution EfficiencyIf min OA determined in heating mode, OA can be reduced duringcooling due to a higher EzSolve equations in appendix A dynamically based on zone and

    system flows to reset zone minimums and outdoor airflow.Dont drop below the area outdoor air rate Ra.Economically limited to high-density occupancies.

  • 8/6/2019 Ashrae 621 2008 High Performance Bldgr Presentation

    30/33

    CO2 with VAV Systems%CO2 = (CR -400)/(CR-max 400) 400 ppm ambient assumed

    Zone Minimum Primary

    Airflow Setpoint ResetSystem OA Setpoint Reset

    CR zone concentration

    Cooling Max

  • 8/6/2019 Ashrae 621 2008 High Performance Bldgr Presentation

    31/33

    DCV for multiple zone recirculating systemshas not been adequately developed at this

    time.

  • 8/6/2019 Ashrae 621 2008 High Performance Bldgr Presentation

    32/33

    Read the standard

    Handbook is available

    ASHRAE courses

  • 8/6/2019 Ashrae 621 2008 High Performance Bldgr Presentation

    33/33