AS 3000-2007

  • Upload
    yxp2237

  • View
    274

  • Download
    3

Embed Size (px)

Citation preview

  • 8/3/2019 AS 3000-2007

    1/76

    economic growth and social wellbeing through

    fair, safe and decent work

    Wiring Rules Information

    Seminar

    AS/NZS 3000:2007

  • 8/3/2019 AS 3000-2007

    2/76

    WHATS NEW

    A survey found industry wanted a document that:

    Is more suited to the present regulatory structure;

    Is more logical and easier to understand;

    Reinstates much of the guidance information that wasremoved from the 2000 edition;

    Has more examples.

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    3/76

    WHATS NEW

    Standard is in 2 parts bound as 1 document:

    Part 1

    provides uniform essential elements that constituteminimum regulatory requirements;

    Part 2

    provides installation practices that achieve certainty of

    compliance with Part 1.

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    4/76

    WHATS NEW

    Preface contains details of 56 additions and alterations

    included in the new Standard.

    These include:

    extended application of safety switches;

    protection against arcing faults;

    requirements for discrimination between circuits;

    installation couplers recognised as a suitable means of

    connection;

    (continued)

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    5/76

    WHATS NEW

    strengthening requirements for the prevention of the spread

    of fire;

    enhanced requirements for recessed luminaires;

    requirements for sanitisation areas in the food processingindustry;

    mandatory testing of safety switches for correct operation;

    additional appendices, improved index, more logical

    layout, further illustrations and background information.

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    6/76

    PART 1

    DEFINITIONS

    Revised definition:

    Clause 1.4.82 Safety service

    A system or component that operates to identify anemergency, or is intended to operate during an emergency,

    and is primarily associated with (a) the safety of persons evacuating a building; or

    (b) fire-fighting operations; or

    (c) fire suppression.

    Called emergency systems or essential equipment inprevious editions.

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    7/76

    PART 1

    DEFINITIONS

    New definition:

    Clause 1.4.69 Outbuilding

    A structure completely separated by an area of land from

    another structure containing the switchboard from whichsupply is obtained.

    See Clause 5.5.3.3 Earthing of outbuildings.

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    8/76

    PART 1

    SCOPE, APPLICATION AND FUNDAMENTAL

    PRINCIPLES

    Part 1 (Section 1) provides a mechanism for acceptance ofdesign practices that may not be addressed in Part 2.

    This mechanism is only intended to apply wheredepartures from the methods in Part 2 are significant.

    However, a degree of flexibility exists within Part 2.

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    9/76

    PART 1

    Clause 1.9.4 Compliance by specific design and installation.

    Certain installations or portions of installations that mayhave unusual requirements, applications or intended use,

    that cannot meet Part 2 may use a specific design and

    installation method.

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    10/76

    PART 1

    Such installations may be deemed suitable provided thatthey:

    satisfy the fundamental safety principles of Part 1;

    result in a degree of safety not less than that which would

    be achieved by compliance with the particularrequirements of this Standard; and

    satisfy the other requirements of this Standard as detailedin this Clause.

    The remaining portions of such installations shall complywith Part 2.

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    11/76

    PART 1

    If all or part of the design/construction is not based on Part2, this choice must be made by the designer prior to finalcertification of construction by the person carrying out theconstruction.

    Any departures from Part 2 must be formallyacknowledged by the installation owner or operator.

    The designer shall document the Part 1 design.

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    12/76

    PART 1

    Documentation must:

    be in English;

    state why Part 2 was not used;

    list the verification requirements that are required to ensurecompliance;

    state how compliance with Part 1 is achieved;

    contain the owner/operators acknowledgement as to the

    departures from Part 2;

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    13/76

    PART 1

    List any requirements where the design requires specific

    use;

    List the verification undertaken to ensure compliance andinclude the results of this verification.

    Be retained by the designer and also on site by the person

    with overall responsibility for the installation.

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    14/76

    PART 2

    GENERAL

    Part 2 provides installation practices that achieve

    compliance with Part 1.

    It generally retains the structure of AS/NZS 3000:2000.

    It restores information from AS 3000:1991.

    Emphasis placed on common, practicable and cost-

    effective methods.

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    15/76

    PART 2 SECTION 2

    GENERAL ARRANGEMENT, CONTROL AND

    PROTECTIONClause: 2.2.1.2 Common neutral

    A common neutral conductor may be used for two ormore circuits subject to the following conditions:

    (a) The continuity of the common neutral shall not dependon connections at the terminals of electrical equipment,including control switches.

    (b) The circuits shall be controlled and protected by linkedcircuit breakers.

    (c) The neutral shall be marked at the switchboard toidentify the associated active conductors. (Cl. 2.9.9.5)

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    16/76

    SECTION 2

    Clause: 2.3.3.2 Number of main switches

    The number of main switches should be kept to theminimum practicable to provide effective operation in an

    emergency.Domestic installations:

    One switch per separately metered supply;

    Where there is more than one separately controlled supply

    from a meter, a main switch is required for each supply.

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    17/76

    SECTION 2

    Clause: 2.5.1.1 requires overcurrent protection of the

    consumers mains in accordance with one of the following:

    short circuit and overload protection at the origin (point of

    supply);

    short circuit at the origin and overload protection at the

    main switchboard;

    short circuit protection not required where overload

    protection is provided at main swb. and mains are

    constructed and installed to Clause 3.9.7.1.2. (unprotectedU/G tee-off arrangement)

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    18/76

    SECTION 2

    Clause: 2.5.1.1 (continued)

    Note:

    Distributors Service fuse will provide short circuit

    protection. (Requirement of the Qld Electrical SafetyAct & Regulation 2002)

    Distributors circuit breaker may provide both shortcircuit and overload protection.

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    19/76

    SECTION 2

    Clause: 2.5.1.1 (continued)Note:

    Consumers mains supplying circuits that areindividually protected against overload are deemed tohave overload protection where the sum of the circuit

    breaker ratings does not exceed the current carryingcapacity of the consumers mains.

    Eg. Simple domestic installation with gas range and water

    heater comprising of 220A power circuits and 210A lighting circuits and 63A consumers mainswill comply with the above.

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    20/76

    SECTION 2

    Clause: 2.5.5.1 Protection against switchboard internalarcing fault currents

    Protection against arcing faults while equipment is inservice, or is undergoing maintenance, shall be provided

    for heavy current switchboards. (ie. switchboards >800Aper phase).

    The supply conductors up to the line side of the protectivedevices shall be provided with means to reduce initiationof arcing faults by insulation or by separation.

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    21/76

    SECTION 2

    Clause: 2.5.5.2

    Heavy current switchboards shall be provided with internal

    separation in accordance with AS/NZS 3439.1.

    Note:

    Arc fault containment is not required and is considered to

    be an enhancement of internal separation.

    See Clause 7.2.8 for switchboards supplying Safety

    Services.

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    22/76

    SECTION 2

    Clause: 2.5.5.3

    Protective devices shall be provided to limit, as far as

    practicable, the harmful effects of a switchboard internal

    arcing fault by automatic disconnection.

    Note:

    Switchboards complying with AS/NZS 3439.1

    Forms 3b 4bh should meet these requirements.

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    23/76

    SECTION 2

    Clause: 2.5.7.1 Reliability of supply

    The electrical installation shall be designed to provide areliable supply by dividing the electrical installation intoappropriate circuits and selecting protective devices with

    appropriate discrimination so that in the event of a faultoccurring, the loss of supply resulting from operation of a

    protective device is minimized.

    The selection and setting of the protective devices shall beverified by inspection.

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    24/76

    SECTION 2

    Clause: 2.5.7.2 Coordination of protective devices

    Coordination of various protective devices requiresconsideration of both discrimination and backup(cascading) protection.

    Clause 2.5.7.2.3 General supply circuit discriminationIn accordance with Clause 2.5.7.1, to minimize loss ofsupply, discrimination shall be arranged between

    protective devices for outgoing circuits and the upstreamprotective device.

    Downstream devices shall be selected to discriminate withupstream devices, using time-current curves.

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    25/76

    SECTION 2

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    26/76

    SECTION 2

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    27/76

    SECTION 2

    Clause: 2.6.1 RCD protection - General

    The use of fixed setting RCDs with a rated operating

    residual current not exceeding 30mA, is recognized as

    providing additional protection in areas where excessive

    earth leakage current in the event of failure of other

    measures of protection or carelessness by users could

    present a significant risk of electric shock.

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    28/76

    SECTION 2

    Clause: 2.6.2.3 Protection against initiation of fire

    Although not a mandatory requirement of this Standard, to

    provide additional protection against the initiation of firecaused by leakage current across insulation, a Type S RCDwith a rated residual current in the range of 100 mA to 300mA may be used as a main switch in a domesticinstallation.

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    29/76

    SECTION 2

    Clause: 2.6.2.4 Arrangement

    Where RCDs are required in accordance with Clause 2.6.3the circuits shall be arranged as follows:

    (a) Not more than 3 final subcircuits shall be protected byany one RCD; and

    (b) Where (i) the number of RCDs exceeds 1; and

    (ii) more than 1 lighting circuit is installed;

    lighting circuits shall be distributed betweenRCDs.

    (c) In domestic installations having more than 1 finalsubcircuit, a minimum of 2 RCDs shall be installed.

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    30/76

    SECTION 2

    Clause: 2.6.3.1 Residential electrical installations

    RCDs are required for socket outlets and lighting circuits

    in residential electrical installations. And also for:

    (c) directly connected hand-held(Cl.1.4.8) electrical

    equipment, eg directly connected hair dryers or tools;forming part of

    (i) individual domestic installations; or

    (ii) residential areas of other electrical installations(motels, hospitals etc); or

    (iii) multiple residential electrical installations that areprovided for common use;

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    31/76

    SECTION 2

    Clause: 2.6.3.1 (continued)

    Exceptions:

    Sockets outlets located in a home dialysis installation shallbe protected in accordance with Clause 2.6.3.3.

    Clause: 2.6.3.3Home dialysis installationsIn accordance with AS/NZS 3003 medical equipment usedin home dialysis installations shall be:

    (a) supplied by a dedicated circuit; and

    (b) protected by a 10mA RCD positioned so that it maybe reset by the patient while under treatment.

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    32/76

    SECTION 2

    Clause: 2.6.3.2 Other electrical installations

    Additional protection by 30mA RCDs shall be provided

    for final subcircuits supplying

    (a) socket outlets having a rated current not exceeding20A; and

    (b) one or more lighting points and having a rated current

    not exceeding 20A; and

    (c) directly connected hand-held electrical equipment.

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    33/76

    SECTION 2

    Clause: 2.6.3.2 (continued)

    Note: The final subcircuits referred to in Item (b) include,without limitation, those supplying the following:

    (a) External lighting installations, such as bollard-type

    luminaires; and(b) Illuminated signs; and

    (c) Ground mounted lighting for the illumination ofpublic features.

    Exception: Where disconnection could cause a dangerous

    situation. E.g. Traffic lights.

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    34/76

    SECTION 2

    Clause: 2.6.3.4Alterations, additions and repairs

    Socket outlets added to an existing circuit shallbe

    protected by an RCD.

    Exception:

    (a) Where socket outlets or lighting points are not RCDprotected are replaced, including the replacement of a

    single outlet with a multiple.

    (b) Extensions to circuits supplying lighting points only,

    provided the existing circuit is not RCD protected.

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    35/76

    SECTION 2Clause 2.9.2.5 (k)

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    36/76

    PART 2 SECTION 3

    SELECTION AND INSTALLATION OF WIRING

    SYSTEMS

    Clause: 3.5.2(b)(ii)Neutral conductor Multiple phase

    The current carrying capacity of the neutral conductor ofmultiphase consumers mains, submains or final subcircuitshall be not less than that of the current carrying capacityof the largest associated active conductor.

    Exception 2:

    Current carrying capacity of the neutral can be lower if

    detection device fitted.

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    37/76

    SECTION 3

    Clause: 3.6.2 Voltage drop

    Voltage drop remains at 5% with several exceptions. The

    most common exception is shown below.

    Exceptions:

    3. Where the point of supply is the low voltage

    terminals of a substation located on the premises

    containing the electrical installation and dedicatedto

    the installation, the permissible voltage drop may beincreased to 7%.

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    38/76

    SECTION 3

    Clause: 3.9.3.2 Suspended ceilings(a) Wiring systems may be supported by the suspended

    ceiling system unless this is not permitted by thesuspended ceiling manufacturer; and

    (b) Cables shall be provided with additional protection

    against mechanical injury where in contact withconductive ceiling support runners (Cl. 3.3.2.6); and

    (c) Wiring systems installed above suspended ceilings shallbe fixed at suitable intervals to prevent undue sagging ofcables.

    Note 2: National Building Codes may restrict use ofsuspended ceilings to support services.

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    39/76

    SECTION 3

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    40/76

    SECTION 3

    Clause: 3.11.4.4 & TABLE 3.6 U/G wiring systems

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    41/76

    SECTION 3

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    42/76

    SECTION 3

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    43/76

    SECTION 3

    Clause: 3.11.4.5 Identification ofU/G wiring systems

    Underground wiring systems shall be identified by anorange marker tape complying with AS/NZS 2648.1 and

    positioned at approximately 50% of the depth of coverabove the wiring system or any additional mechanical

    protection.

    Exception:

    Underground wiring systems installed by boring,provided the location is marked and recorded in a readilyavailable permanent location. If a pipe is retained after

    the boring operation, orange-coloured pipe or conduit isrecommended.

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    44/76

    SECTION 3

    Clause: 3.11.4.6 Marking and recording ofU/G cablelocation

    The presence of U/G wiring shall be marked andrecorded as follows:

    (a) Permanent cable marker signs shall be provided toindicate the point where a cable enters or leaves astructure;

    Exception:

    Cable entry signs need not be provided where the

    position ofU/G cable entry into the ground is obvious.

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    45/76

    SECTION 3

    Clause: 3.11.4.6 Marking and recording ofU/G cablelocation (continued)

    or

    The route shall be recorded on a plan to enable future

    location. This plan shall be located at the switchboardfrom which the circuit originates. The plan locating theconsumers mains shall be kept at the main switchboard.

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    46/76

    PART 2 - SECTION 4

    SELECTION AND INSTALLATION OF

    APPLIANCES AND ACCESSORIES

    Clause: 4.5.2.3 Recessed luminaires

    Recessed luminaires and their auxiliary equipment shallbe installed in a manner designed to minimizetemperature rise and prevent the risk of fire.

    This requirement shall be satisfied by one of thefollowing methods:

    (a) The use of a luminaire specifically designed andcertified by the manufacturer to permit

    (i) contact with combustible materials; or(ii) enclosure or covering by thermal insulation, as

    appropriate to the location of the luminaire.

    economic growth and social wellbeing through

    fair, safe and decent work

    SECTION 4

  • 8/3/2019 AS 3000-2007

    47/76

    SECTION 4

    Clause: 4.5.2.3 Recessed luminaires (continued)

    (b) Installation of the luminaire within a fire-resistantenclosure.

    (c) Provision of required clearances from combustible andthermal insulating material as specified by themanufacturer of the luminaire.

    (d) Provision of the default clearances from combustible andthermal insulating material as specified in Figure 4.7.

    Where manufacturers installation instructions thatspecify required clearances are not available the

    luminaire shall be installed in accordance with (b) or(d).

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    48/76

    SECTION 4

    Clause: 4.5.2.3 Recessed luminaires (continued)

    Where thermal insulation is of a type that is not fixed in

    position, e.g. loose fill, a barrier or guard constructed of

    fire-resistant material shall be provided and secured in

    position to maintain the necessary clearance (see Figure

    4.7).Where thermal insulation may reasonably be expected to

    be installed in the space containing a recessed luminare,

    the luminaire shall be installed in such a manner as to

    provide for the subsequent installation of thermalinsulation.

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    49/76

    SECTION 4

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    50/76

    SECTION 5 - EARTHING

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    51/76

    SECTION 5

    Clause 5.5.1.3L

    abelingThe main earthing conductor shall have a permanent label

    attached at the connection to the earth electrode with a

    legible warning against disconnection in the following

    form:

    WARNING: MAIN ELECTRICAL EARTHING

    CONDUCTORDONOTDISCONNECT

    Exception: Where the method of connection to the

    electrode precludes disconnection this requirement need

    not apply.

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    52/76

    SECTION 5

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    53/76

    SECTION 5

    Clause 5.6.2.5 Showers and bathrooms

    Any conductive reinforcing within a concrete floor or

    wall forming part of a shower or bathroom shall be

    bonded to the earthing system of the electrical installationto avoid any potential differences that may occur between

    conductive piping (including taps, drain, etc) connected

    to, or in contact with, the electrical installation earthing

    system and the concrete floor or wall.

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    54/76

    SECTION 5

    Clause 5.6.2.5 Showers and bathrooms (continued)

    An equipotential bonding conductor, in accordance with

    Clause 5.6.3, shall be connected between the reinforcing

    material and any part of the earthing system within the

    room.

    Note: Clause 5.6.3.2(b) requires 4mm2 conductor.

    economic growth and social wellbeing through

    fair, safe and decent work

    PART 2 SECTION 6

  • 8/3/2019 AS 3000-2007

    55/76

    PART 2 - SECTION 6

    DAMP SITUATIONS

    Clause 6.7 Sanitization and general hosing-down operations

    Electrical installations where the requirements of this

    clause may apply include, without limitation, food

    production or processing areas and agricultural or

    horticultural premises, such as rooms, locations orareas where

    (a) livestock are kept; or

    (b) feed, fertilizers, vegetable or animal are produced,

    stored, prepared or processed; or

    economic growth and social wellbeing through

    fair, safe and decent work

    SECTION 6

  • 8/3/2019 AS 3000-2007

    56/76

    SECTION 6

    Clause 6.7 Sanitization and general hosing-down operations

    (continued)

    (c) Plants are grown, such as greenhouses or hydroponic

    installations; or

    (d) Agricultural or horticultural products are produced,prepared or processed, e.g. dairies, drying, stewing,

    pressing out, fermenting, butchering, meat processing,

    etc.

    Clause 6.7.4.4. Switchboards shall have IPX6 enclosures.

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    57/76

    PART 2 - SECTION 7

    SPECIAL ELECTRICAL INSTALLATIONS

    Clause 7.3Electrical Generation Systems

    New Clause covering:

    (i) Engine-driven generator sets;

    (ii) Stand-alone power systems, e.g. photovoltaic, wind

    turbine etc;

    (iii)Grid-connected inverter systems.

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    58/76

    SECTION 7

    Clause 7.3.5.2.2 - RCDs

    Where an electricity generation system includes an inverter,

    the RCD shall be of a type suitable for the waveform of the

    particular inverter, and in accordance with the invertermanufacturers instructions.

    Note: Requirements for types of RCDs are set out in Clause

    2.6.2.2.

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    59/76

    SECTION 2

    Clause 2.6.2.2 Types of RCDs

    States in part:

    In Australia, an RCD shall be of the type that tripping is

    ensured when the waveform is sinusoidal.Note:

    1. The possible waveform of a fault current to earth can

    affect the operation of an RCD and shall be taken into

    account for the selection of the type of RCD.

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    60/76

    SECTION 7

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    61/76

    SECTION 7

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    62/76

    SECTION 7

    economic growth and social wellbeing through

    fair, safe and decent work

    Clause 7.8 Specific ElectricalInstallation Standards

    This Clause outlines those Standards that are applicable to

    specific electrical installations.

    AS/NZS 3001 Relocatable installations and their sitesupply;

    AS/NZS 3002 Shows and carnivals;

    AS/NZS 3003 Electromedical treatment areas;

    AS/NZS 3004 Marinas and recreational boats;

  • 8/3/2019 AS 3000-2007

    63/76

    SECTION 7

    economic growth and social wellbeing through

    fair, safe and decent work

    Clause 7.8 Specific ElectricalInstallation Standards(continued)

    AS/NZS 3012 Construction & demolition sites;

    AS/NZS 3832 Cold-cathode illumination systems (HV

    neon);AS/NZS 3015 Telecommunications networks power

    supplies;

    Installations complying with AS/NZS 3018 (Single

    domestic installations) are deemed to comply with thisStandard.

  • 8/3/2019 AS 3000-2007

    64/76

    SECTION 7

    economic growth and social wellbeing through

    fair, safe and decent work

    Guidance Standards:

    AS/NZS 3010 Generating sets;

    AS/NZS 3014 & 3016 Electric fences

    AS/NZS 4249 Film, video & TV sites.

    Appendix A contains a list of referenced documents,

    compliance with which is called up as a mandatory

    requirement for those Standards listed as Normative

    References.

    SECTION 8

  • 8/3/2019 AS 3000-2007

    65/76

    SECTION 8

    VERIFICATION

    economic growth and social wellbeing through

    fair, safe and decent work

    Clause 8.3.6.2 Results

    The insulation resistance between

    (a) the conductors of consumers mains and submains; and

    (b) live and earthed parts of an electrical installation, orparts thereof, including consumers mains and submains

    shall be not less than 1 M.

  • 8/3/2019 AS 3000-2007

    66/76

    SECTION 8

    economic growth and social wellbeing through

    fair, safe and decent work

    Clause 8.3.9.1 Socket outlets not RCD protectedThe impedance required for automatic disconnection of

    supply to socket outlet circuits not RCD protected shall

    be verified by

    (a) verification of the total resistance (Rphe) of the activeand protective earthing conductors; or

    (b) where supply is available, verification of the earth fault

    loop impedance,

    in accordance with Clause 8.3.9.3. (eg. measurement or

    by using a fault loop impedance test device).

    S. 12 ElectricalSafety Regulation 2002.

  • 8/3/2019 AS 3000-2007

    67/76

    SECTION 8

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    68/76

    SECTION 8

    economic growth and social wellbeing through

    fair, safe and decent work

    Clause 8.3.10 Operation of RCDsWhere supply is available, the function of the RCD shall beverified by the operation of the integral test device, or bythe use of special test equipment.

    Tests shall be performed on each final subcircuit protectedby an RCD to verify that the RCD functions correctly todisconnect the designated circuit

    Clause 8.3.10.3 The RCD shall disconnect

    supply.

  • 8/3/2019 AS 3000-2007

    69/76

    SECTION 8

    economic growth and social wellbeing through

    fair, safe and decent work

    Clause 8.4Date of initial energisation of an installation

    The date of initial energisation of an installation should be

    available on-site, either by marking or in an accessible

    record.

    Either month and year or year only will be acceptable.

  • 8/3/2019 AS 3000-2007

    70/76

    APPENDIX C

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    71/76

    APPENDIX C

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    72/76

    APPENDIX C

    economic growth and social wellbeing through

    fair, safe and decent work

    Examples of other Tables in Appendix C:

    TABLE C1 Maximum demand single & multiple

    domestic;

    TABLE C2 Maximum demand non-domestic;

    TABLE C3 Maximum demand Energy demand method

    for non-domestic installations;

    TABLE C8 Guidance on the loading of points per final

    subcircuit.

  • 8/3/2019 AS 3000-2007

    73/76

    APPENDIX D

    economic growth and social wellbeing through

    fair, safe and decent work

  • 8/3/2019 AS 3000-2007

    74/76

    APPENDIX D

    economic growth and social wellbeing through

    fair, safe and decent work

    Examples of Tables in Appendix D:

    TABLE D1 Sinking of posts/poles in ground;

    TABLE D2 Force exerted by aerial line conductors;

    TABLE D6 Round hardwood pole - strength ratings;

    TABLE D10 Grade 250 steel pipe strength ratings;

    TABLE D12(a) Grade 350 steel square section strength

    ratings.

  • 8/3/2019 AS 3000-2007

    75/76

    OTHER NEW APPENDICES

    economic growth and social wellbeing through

    fair, safe and decent work

    APPENDIX E Electrical installation requirements in

    National Building Codes (e.g. BCA);

    APPENDIX F Installation of surge protective devices;

    APPENDIX G Degrees of protection of enclosed equipment

    (i.e. IP ratings);

    APPENDIX H WS Classification of wiring systems (i.e.

    fire ratings);

    APPENDIX I Protective device ratings and sizes of

    imperial cables;

    APPENDIX J1 Symbols used in this Standard.

  • 8/3/2019 AS 3000-2007

    76/76

    WHAT HAPPENS NEXT?

    economic growth and social wellbeing through

    fair safe and decent work

    Electrical work commenced under AS/NZS 3000:2000

    prior to 01/06/2008 may continue;

    Electrical work which has been quoted and a contract has

    been awarded may be performed under AS/NZS

    3000:2000;

    Large projects designed under AS/NZS 3000:2000 (e.g.

    shopping centres) may be performed under that Standard.

    Can be applied immediately, but comes into force in Qld on

    01/06/2008.