Upload
yxp2237
View
274
Download
3
Embed Size (px)
Citation preview
8/3/2019 AS 3000-2007
1/76
economic growth and social wellbeing through
fair, safe and decent work
Wiring Rules Information
Seminar
AS/NZS 3000:2007
8/3/2019 AS 3000-2007
2/76
WHATS NEW
A survey found industry wanted a document that:
Is more suited to the present regulatory structure;
Is more logical and easier to understand;
Reinstates much of the guidance information that wasremoved from the 2000 edition;
Has more examples.
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
3/76
WHATS NEW
Standard is in 2 parts bound as 1 document:
Part 1
provides uniform essential elements that constituteminimum regulatory requirements;
Part 2
provides installation practices that achieve certainty of
compliance with Part 1.
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
4/76
WHATS NEW
Preface contains details of 56 additions and alterations
included in the new Standard.
These include:
extended application of safety switches;
protection against arcing faults;
requirements for discrimination between circuits;
installation couplers recognised as a suitable means of
connection;
(continued)
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
5/76
WHATS NEW
strengthening requirements for the prevention of the spread
of fire;
enhanced requirements for recessed luminaires;
requirements for sanitisation areas in the food processingindustry;
mandatory testing of safety switches for correct operation;
additional appendices, improved index, more logical
layout, further illustrations and background information.
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
6/76
PART 1
DEFINITIONS
Revised definition:
Clause 1.4.82 Safety service
A system or component that operates to identify anemergency, or is intended to operate during an emergency,
and is primarily associated with (a) the safety of persons evacuating a building; or
(b) fire-fighting operations; or
(c) fire suppression.
Called emergency systems or essential equipment inprevious editions.
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
7/76
PART 1
DEFINITIONS
New definition:
Clause 1.4.69 Outbuilding
A structure completely separated by an area of land from
another structure containing the switchboard from whichsupply is obtained.
See Clause 5.5.3.3 Earthing of outbuildings.
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
8/76
PART 1
SCOPE, APPLICATION AND FUNDAMENTAL
PRINCIPLES
Part 1 (Section 1) provides a mechanism for acceptance ofdesign practices that may not be addressed in Part 2.
This mechanism is only intended to apply wheredepartures from the methods in Part 2 are significant.
However, a degree of flexibility exists within Part 2.
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
9/76
PART 1
Clause 1.9.4 Compliance by specific design and installation.
Certain installations or portions of installations that mayhave unusual requirements, applications or intended use,
that cannot meet Part 2 may use a specific design and
installation method.
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
10/76
PART 1
Such installations may be deemed suitable provided thatthey:
satisfy the fundamental safety principles of Part 1;
result in a degree of safety not less than that which would
be achieved by compliance with the particularrequirements of this Standard; and
satisfy the other requirements of this Standard as detailedin this Clause.
The remaining portions of such installations shall complywith Part 2.
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
11/76
PART 1
If all or part of the design/construction is not based on Part2, this choice must be made by the designer prior to finalcertification of construction by the person carrying out theconstruction.
Any departures from Part 2 must be formallyacknowledged by the installation owner or operator.
The designer shall document the Part 1 design.
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
12/76
PART 1
Documentation must:
be in English;
state why Part 2 was not used;
list the verification requirements that are required to ensurecompliance;
state how compliance with Part 1 is achieved;
contain the owner/operators acknowledgement as to the
departures from Part 2;
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
13/76
PART 1
List any requirements where the design requires specific
use;
List the verification undertaken to ensure compliance andinclude the results of this verification.
Be retained by the designer and also on site by the person
with overall responsibility for the installation.
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
14/76
PART 2
GENERAL
Part 2 provides installation practices that achieve
compliance with Part 1.
It generally retains the structure of AS/NZS 3000:2000.
It restores information from AS 3000:1991.
Emphasis placed on common, practicable and cost-
effective methods.
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
15/76
PART 2 SECTION 2
GENERAL ARRANGEMENT, CONTROL AND
PROTECTIONClause: 2.2.1.2 Common neutral
A common neutral conductor may be used for two ormore circuits subject to the following conditions:
(a) The continuity of the common neutral shall not dependon connections at the terminals of electrical equipment,including control switches.
(b) The circuits shall be controlled and protected by linkedcircuit breakers.
(c) The neutral shall be marked at the switchboard toidentify the associated active conductors. (Cl. 2.9.9.5)
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
16/76
SECTION 2
Clause: 2.3.3.2 Number of main switches
The number of main switches should be kept to theminimum practicable to provide effective operation in an
emergency.Domestic installations:
One switch per separately metered supply;
Where there is more than one separately controlled supply
from a meter, a main switch is required for each supply.
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
17/76
SECTION 2
Clause: 2.5.1.1 requires overcurrent protection of the
consumers mains in accordance with one of the following:
short circuit and overload protection at the origin (point of
supply);
short circuit at the origin and overload protection at the
main switchboard;
short circuit protection not required where overload
protection is provided at main swb. and mains are
constructed and installed to Clause 3.9.7.1.2. (unprotectedU/G tee-off arrangement)
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
18/76
SECTION 2
Clause: 2.5.1.1 (continued)
Note:
Distributors Service fuse will provide short circuit
protection. (Requirement of the Qld Electrical SafetyAct & Regulation 2002)
Distributors circuit breaker may provide both shortcircuit and overload protection.
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
19/76
SECTION 2
Clause: 2.5.1.1 (continued)Note:
Consumers mains supplying circuits that areindividually protected against overload are deemed tohave overload protection where the sum of the circuit
breaker ratings does not exceed the current carryingcapacity of the consumers mains.
Eg. Simple domestic installation with gas range and water
heater comprising of 220A power circuits and 210A lighting circuits and 63A consumers mainswill comply with the above.
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
20/76
SECTION 2
Clause: 2.5.5.1 Protection against switchboard internalarcing fault currents
Protection against arcing faults while equipment is inservice, or is undergoing maintenance, shall be provided
for heavy current switchboards. (ie. switchboards >800Aper phase).
The supply conductors up to the line side of the protectivedevices shall be provided with means to reduce initiationof arcing faults by insulation or by separation.
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
21/76
SECTION 2
Clause: 2.5.5.2
Heavy current switchboards shall be provided with internal
separation in accordance with AS/NZS 3439.1.
Note:
Arc fault containment is not required and is considered to
be an enhancement of internal separation.
See Clause 7.2.8 for switchboards supplying Safety
Services.
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
22/76
SECTION 2
Clause: 2.5.5.3
Protective devices shall be provided to limit, as far as
practicable, the harmful effects of a switchboard internal
arcing fault by automatic disconnection.
Note:
Switchboards complying with AS/NZS 3439.1
Forms 3b 4bh should meet these requirements.
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
23/76
SECTION 2
Clause: 2.5.7.1 Reliability of supply
The electrical installation shall be designed to provide areliable supply by dividing the electrical installation intoappropriate circuits and selecting protective devices with
appropriate discrimination so that in the event of a faultoccurring, the loss of supply resulting from operation of a
protective device is minimized.
The selection and setting of the protective devices shall beverified by inspection.
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
24/76
SECTION 2
Clause: 2.5.7.2 Coordination of protective devices
Coordination of various protective devices requiresconsideration of both discrimination and backup(cascading) protection.
Clause 2.5.7.2.3 General supply circuit discriminationIn accordance with Clause 2.5.7.1, to minimize loss ofsupply, discrimination shall be arranged between
protective devices for outgoing circuits and the upstreamprotective device.
Downstream devices shall be selected to discriminate withupstream devices, using time-current curves.
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
25/76
SECTION 2
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
26/76
SECTION 2
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
27/76
SECTION 2
Clause: 2.6.1 RCD protection - General
The use of fixed setting RCDs with a rated operating
residual current not exceeding 30mA, is recognized as
providing additional protection in areas where excessive
earth leakage current in the event of failure of other
measures of protection or carelessness by users could
present a significant risk of electric shock.
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
28/76
SECTION 2
Clause: 2.6.2.3 Protection against initiation of fire
Although not a mandatory requirement of this Standard, to
provide additional protection against the initiation of firecaused by leakage current across insulation, a Type S RCDwith a rated residual current in the range of 100 mA to 300mA may be used as a main switch in a domesticinstallation.
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
29/76
SECTION 2
Clause: 2.6.2.4 Arrangement
Where RCDs are required in accordance with Clause 2.6.3the circuits shall be arranged as follows:
(a) Not more than 3 final subcircuits shall be protected byany one RCD; and
(b) Where (i) the number of RCDs exceeds 1; and
(ii) more than 1 lighting circuit is installed;
lighting circuits shall be distributed betweenRCDs.
(c) In domestic installations having more than 1 finalsubcircuit, a minimum of 2 RCDs shall be installed.
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
30/76
SECTION 2
Clause: 2.6.3.1 Residential electrical installations
RCDs are required for socket outlets and lighting circuits
in residential electrical installations. And also for:
(c) directly connected hand-held(Cl.1.4.8) electrical
equipment, eg directly connected hair dryers or tools;forming part of
(i) individual domestic installations; or
(ii) residential areas of other electrical installations(motels, hospitals etc); or
(iii) multiple residential electrical installations that areprovided for common use;
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
31/76
SECTION 2
Clause: 2.6.3.1 (continued)
Exceptions:
Sockets outlets located in a home dialysis installation shallbe protected in accordance with Clause 2.6.3.3.
Clause: 2.6.3.3Home dialysis installationsIn accordance with AS/NZS 3003 medical equipment usedin home dialysis installations shall be:
(a) supplied by a dedicated circuit; and
(b) protected by a 10mA RCD positioned so that it maybe reset by the patient while under treatment.
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
32/76
SECTION 2
Clause: 2.6.3.2 Other electrical installations
Additional protection by 30mA RCDs shall be provided
for final subcircuits supplying
(a) socket outlets having a rated current not exceeding20A; and
(b) one or more lighting points and having a rated current
not exceeding 20A; and
(c) directly connected hand-held electrical equipment.
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
33/76
SECTION 2
Clause: 2.6.3.2 (continued)
Note: The final subcircuits referred to in Item (b) include,without limitation, those supplying the following:
(a) External lighting installations, such as bollard-type
luminaires; and(b) Illuminated signs; and
(c) Ground mounted lighting for the illumination ofpublic features.
Exception: Where disconnection could cause a dangerous
situation. E.g. Traffic lights.
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
34/76
SECTION 2
Clause: 2.6.3.4Alterations, additions and repairs
Socket outlets added to an existing circuit shallbe
protected by an RCD.
Exception:
(a) Where socket outlets or lighting points are not RCDprotected are replaced, including the replacement of a
single outlet with a multiple.
(b) Extensions to circuits supplying lighting points only,
provided the existing circuit is not RCD protected.
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
35/76
SECTION 2Clause 2.9.2.5 (k)
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
36/76
PART 2 SECTION 3
SELECTION AND INSTALLATION OF WIRING
SYSTEMS
Clause: 3.5.2(b)(ii)Neutral conductor Multiple phase
The current carrying capacity of the neutral conductor ofmultiphase consumers mains, submains or final subcircuitshall be not less than that of the current carrying capacityof the largest associated active conductor.
Exception 2:
Current carrying capacity of the neutral can be lower if
detection device fitted.
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
37/76
SECTION 3
Clause: 3.6.2 Voltage drop
Voltage drop remains at 5% with several exceptions. The
most common exception is shown below.
Exceptions:
3. Where the point of supply is the low voltage
terminals of a substation located on the premises
containing the electrical installation and dedicatedto
the installation, the permissible voltage drop may beincreased to 7%.
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
38/76
SECTION 3
Clause: 3.9.3.2 Suspended ceilings(a) Wiring systems may be supported by the suspended
ceiling system unless this is not permitted by thesuspended ceiling manufacturer; and
(b) Cables shall be provided with additional protection
against mechanical injury where in contact withconductive ceiling support runners (Cl. 3.3.2.6); and
(c) Wiring systems installed above suspended ceilings shallbe fixed at suitable intervals to prevent undue sagging ofcables.
Note 2: National Building Codes may restrict use ofsuspended ceilings to support services.
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
39/76
SECTION 3
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
40/76
SECTION 3
Clause: 3.11.4.4 & TABLE 3.6 U/G wiring systems
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
41/76
SECTION 3
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
42/76
SECTION 3
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
43/76
SECTION 3
Clause: 3.11.4.5 Identification ofU/G wiring systems
Underground wiring systems shall be identified by anorange marker tape complying with AS/NZS 2648.1 and
positioned at approximately 50% of the depth of coverabove the wiring system or any additional mechanical
protection.
Exception:
Underground wiring systems installed by boring,provided the location is marked and recorded in a readilyavailable permanent location. If a pipe is retained after
the boring operation, orange-coloured pipe or conduit isrecommended.
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
44/76
SECTION 3
Clause: 3.11.4.6 Marking and recording ofU/G cablelocation
The presence of U/G wiring shall be marked andrecorded as follows:
(a) Permanent cable marker signs shall be provided toindicate the point where a cable enters or leaves astructure;
Exception:
Cable entry signs need not be provided where the
position ofU/G cable entry into the ground is obvious.
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
45/76
SECTION 3
Clause: 3.11.4.6 Marking and recording ofU/G cablelocation (continued)
or
The route shall be recorded on a plan to enable future
location. This plan shall be located at the switchboardfrom which the circuit originates. The plan locating theconsumers mains shall be kept at the main switchboard.
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
46/76
PART 2 - SECTION 4
SELECTION AND INSTALLATION OF
APPLIANCES AND ACCESSORIES
Clause: 4.5.2.3 Recessed luminaires
Recessed luminaires and their auxiliary equipment shallbe installed in a manner designed to minimizetemperature rise and prevent the risk of fire.
This requirement shall be satisfied by one of thefollowing methods:
(a) The use of a luminaire specifically designed andcertified by the manufacturer to permit
(i) contact with combustible materials; or(ii) enclosure or covering by thermal insulation, as
appropriate to the location of the luminaire.
economic growth and social wellbeing through
fair, safe and decent work
SECTION 4
8/3/2019 AS 3000-2007
47/76
SECTION 4
Clause: 4.5.2.3 Recessed luminaires (continued)
(b) Installation of the luminaire within a fire-resistantenclosure.
(c) Provision of required clearances from combustible andthermal insulating material as specified by themanufacturer of the luminaire.
(d) Provision of the default clearances from combustible andthermal insulating material as specified in Figure 4.7.
Where manufacturers installation instructions thatspecify required clearances are not available the
luminaire shall be installed in accordance with (b) or(d).
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
48/76
SECTION 4
Clause: 4.5.2.3 Recessed luminaires (continued)
Where thermal insulation is of a type that is not fixed in
position, e.g. loose fill, a barrier or guard constructed of
fire-resistant material shall be provided and secured in
position to maintain the necessary clearance (see Figure
4.7).Where thermal insulation may reasonably be expected to
be installed in the space containing a recessed luminare,
the luminaire shall be installed in such a manner as to
provide for the subsequent installation of thermalinsulation.
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
49/76
SECTION 4
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
50/76
SECTION 5 - EARTHING
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
51/76
SECTION 5
Clause 5.5.1.3L
abelingThe main earthing conductor shall have a permanent label
attached at the connection to the earth electrode with a
legible warning against disconnection in the following
form:
WARNING: MAIN ELECTRICAL EARTHING
CONDUCTORDONOTDISCONNECT
Exception: Where the method of connection to the
electrode precludes disconnection this requirement need
not apply.
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
52/76
SECTION 5
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
53/76
SECTION 5
Clause 5.6.2.5 Showers and bathrooms
Any conductive reinforcing within a concrete floor or
wall forming part of a shower or bathroom shall be
bonded to the earthing system of the electrical installationto avoid any potential differences that may occur between
conductive piping (including taps, drain, etc) connected
to, or in contact with, the electrical installation earthing
system and the concrete floor or wall.
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
54/76
SECTION 5
Clause 5.6.2.5 Showers and bathrooms (continued)
An equipotential bonding conductor, in accordance with
Clause 5.6.3, shall be connected between the reinforcing
material and any part of the earthing system within the
room.
Note: Clause 5.6.3.2(b) requires 4mm2 conductor.
economic growth and social wellbeing through
fair, safe and decent work
PART 2 SECTION 6
8/3/2019 AS 3000-2007
55/76
PART 2 - SECTION 6
DAMP SITUATIONS
Clause 6.7 Sanitization and general hosing-down operations
Electrical installations where the requirements of this
clause may apply include, without limitation, food
production or processing areas and agricultural or
horticultural premises, such as rooms, locations orareas where
(a) livestock are kept; or
(b) feed, fertilizers, vegetable or animal are produced,
stored, prepared or processed; or
economic growth and social wellbeing through
fair, safe and decent work
SECTION 6
8/3/2019 AS 3000-2007
56/76
SECTION 6
Clause 6.7 Sanitization and general hosing-down operations
(continued)
(c) Plants are grown, such as greenhouses or hydroponic
installations; or
(d) Agricultural or horticultural products are produced,prepared or processed, e.g. dairies, drying, stewing,
pressing out, fermenting, butchering, meat processing,
etc.
Clause 6.7.4.4. Switchboards shall have IPX6 enclosures.
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
57/76
PART 2 - SECTION 7
SPECIAL ELECTRICAL INSTALLATIONS
Clause 7.3Electrical Generation Systems
New Clause covering:
(i) Engine-driven generator sets;
(ii) Stand-alone power systems, e.g. photovoltaic, wind
turbine etc;
(iii)Grid-connected inverter systems.
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
58/76
SECTION 7
Clause 7.3.5.2.2 - RCDs
Where an electricity generation system includes an inverter,
the RCD shall be of a type suitable for the waveform of the
particular inverter, and in accordance with the invertermanufacturers instructions.
Note: Requirements for types of RCDs are set out in Clause
2.6.2.2.
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
59/76
SECTION 2
Clause 2.6.2.2 Types of RCDs
States in part:
In Australia, an RCD shall be of the type that tripping is
ensured when the waveform is sinusoidal.Note:
1. The possible waveform of a fault current to earth can
affect the operation of an RCD and shall be taken into
account for the selection of the type of RCD.
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
60/76
SECTION 7
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
61/76
SECTION 7
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
62/76
SECTION 7
economic growth and social wellbeing through
fair, safe and decent work
Clause 7.8 Specific ElectricalInstallation Standards
This Clause outlines those Standards that are applicable to
specific electrical installations.
AS/NZS 3001 Relocatable installations and their sitesupply;
AS/NZS 3002 Shows and carnivals;
AS/NZS 3003 Electromedical treatment areas;
AS/NZS 3004 Marinas and recreational boats;
8/3/2019 AS 3000-2007
63/76
SECTION 7
economic growth and social wellbeing through
fair, safe and decent work
Clause 7.8 Specific ElectricalInstallation Standards(continued)
AS/NZS 3012 Construction & demolition sites;
AS/NZS 3832 Cold-cathode illumination systems (HV
neon);AS/NZS 3015 Telecommunications networks power
supplies;
Installations complying with AS/NZS 3018 (Single
domestic installations) are deemed to comply with thisStandard.
8/3/2019 AS 3000-2007
64/76
SECTION 7
economic growth and social wellbeing through
fair, safe and decent work
Guidance Standards:
AS/NZS 3010 Generating sets;
AS/NZS 3014 & 3016 Electric fences
AS/NZS 4249 Film, video & TV sites.
Appendix A contains a list of referenced documents,
compliance with which is called up as a mandatory
requirement for those Standards listed as Normative
References.
SECTION 8
8/3/2019 AS 3000-2007
65/76
SECTION 8
VERIFICATION
economic growth and social wellbeing through
fair, safe and decent work
Clause 8.3.6.2 Results
The insulation resistance between
(a) the conductors of consumers mains and submains; and
(b) live and earthed parts of an electrical installation, orparts thereof, including consumers mains and submains
shall be not less than 1 M.
8/3/2019 AS 3000-2007
66/76
SECTION 8
economic growth and social wellbeing through
fair, safe and decent work
Clause 8.3.9.1 Socket outlets not RCD protectedThe impedance required for automatic disconnection of
supply to socket outlet circuits not RCD protected shall
be verified by
(a) verification of the total resistance (Rphe) of the activeand protective earthing conductors; or
(b) where supply is available, verification of the earth fault
loop impedance,
in accordance with Clause 8.3.9.3. (eg. measurement or
by using a fault loop impedance test device).
S. 12 ElectricalSafety Regulation 2002.
8/3/2019 AS 3000-2007
67/76
SECTION 8
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
68/76
SECTION 8
economic growth and social wellbeing through
fair, safe and decent work
Clause 8.3.10 Operation of RCDsWhere supply is available, the function of the RCD shall beverified by the operation of the integral test device, or bythe use of special test equipment.
Tests shall be performed on each final subcircuit protectedby an RCD to verify that the RCD functions correctly todisconnect the designated circuit
Clause 8.3.10.3 The RCD shall disconnect
supply.
8/3/2019 AS 3000-2007
69/76
SECTION 8
economic growth and social wellbeing through
fair, safe and decent work
Clause 8.4Date of initial energisation of an installation
The date of initial energisation of an installation should be
available on-site, either by marking or in an accessible
record.
Either month and year or year only will be acceptable.
8/3/2019 AS 3000-2007
70/76
APPENDIX C
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
71/76
APPENDIX C
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
72/76
APPENDIX C
economic growth and social wellbeing through
fair, safe and decent work
Examples of other Tables in Appendix C:
TABLE C1 Maximum demand single & multiple
domestic;
TABLE C2 Maximum demand non-domestic;
TABLE C3 Maximum demand Energy demand method
for non-domestic installations;
TABLE C8 Guidance on the loading of points per final
subcircuit.
8/3/2019 AS 3000-2007
73/76
APPENDIX D
economic growth and social wellbeing through
fair, safe and decent work
8/3/2019 AS 3000-2007
74/76
APPENDIX D
economic growth and social wellbeing through
fair, safe and decent work
Examples of Tables in Appendix D:
TABLE D1 Sinking of posts/poles in ground;
TABLE D2 Force exerted by aerial line conductors;
TABLE D6 Round hardwood pole - strength ratings;
TABLE D10 Grade 250 steel pipe strength ratings;
TABLE D12(a) Grade 350 steel square section strength
ratings.
8/3/2019 AS 3000-2007
75/76
OTHER NEW APPENDICES
economic growth and social wellbeing through
fair, safe and decent work
APPENDIX E Electrical installation requirements in
National Building Codes (e.g. BCA);
APPENDIX F Installation of surge protective devices;
APPENDIX G Degrees of protection of enclosed equipment
(i.e. IP ratings);
APPENDIX H WS Classification of wiring systems (i.e.
fire ratings);
APPENDIX I Protective device ratings and sizes of
imperial cables;
APPENDIX J1 Symbols used in this Standard.
8/3/2019 AS 3000-2007
76/76
WHAT HAPPENS NEXT?
economic growth and social wellbeing through
fair safe and decent work
Electrical work commenced under AS/NZS 3000:2000
prior to 01/06/2008 may continue;
Electrical work which has been quoted and a contract has
been awarded may be performed under AS/NZS
3000:2000;
Large projects designed under AS/NZS 3000:2000 (e.g.
shopping centres) may be performed under that Standard.
Can be applied immediately, but comes into force in Qld on
01/06/2008.