Upload
mdalt9180
View
212
Download
0
Embed Size (px)
DESCRIPTION
Arial
Citation preview
STATE POINT & PROCESS REPORT
Report Date: Sunday, September 06, 2015Project Information:
Altitude: 0 (Meters)Barometric Pressure: 760.001 (mm Hg)Atmospheric Pressure: 101.325 (kPa)
1. OTC
STATE POINT DATA
Air Flow(Standard)
(L/s)
DryBulb(°C)
WetBulb(°C)
RelativeHumidity
(%)
HumidityRatio(g/kg)
SpecificVolume
(cu.m/kg)
Enthalpy
(kJ/kg)
DewPoint(°C)
Density
(kg/cu.m)
VaporPressure(mm Hg)
AbsoluteHumidity(g/cu.m)
472 35.600 25.537 45.0 16.57 0.898 78.313 21.8396 1.1329 19.6441 18.462
2. BTR
STATE POINT DATA
Air Flow(Standard)
(L/s)
DryBulb(°C)
WetBulb(°C)
RelativeHumidity
(%)
HumidityRatio(g/kg)
SpecificVolume
(cu.m/kg)
Enthalpy
(kJ/kg)
DewPoint(°C)
Density
(kg/cu.m)
VaporPressure(mm Hg)
AbsoluteHumidity(g/cu.m)
472 36.200 25.686 43.5 16.57 0.899 78.935 21.8396 1.1307 19.6441 18.427
Process: Sensible Heating
Start Point NameTotal
Heating(kW)
TotalEnergy(W/hr)
SensibleEnergy(W/hr)
LatentEnergy(W/hr)
MoistureDifference
(kg/hr)
SensibleHeat Ratio
Enthalpy/Humidity Ratio(kJ/kg / g/kg)
OTC 0.4 352 352 0 0.0 1.000 N/A
3. MCC
STATE POINT DATA
Air Flow(Standard)
(L/s)
DryBulb(°C)
WetBulb(°C)
RelativeHumidity
(%)
HumidityRatio(g/kg)
SpecificVolume
(cu.m/kg)
Enthalpy
(kJ/kg)
DewPoint(°C)
Density
(kg/cu.m)
VaporPressure(mm Hg)
AbsoluteHumidity(g/cu.m)
472 15.000 14.008 90.0 9.60 0.829 39.362 13.3748 1.2186 11.5130 11.592
Process: Cooling Coil
Start Point Name
TotalCooling(kW/hr)
TotalEnergy(W/hr)
SensibleEnergy(W/hr)
LatentEnergy(W/hr)
Dehumidification
(kg/hr)
SensibleHeat Ratio
Enthalpy/Humidity Ratio(kJ/kg / g/kg)
BTR -22.435 -22,435 -12,291 -10,143 -14.2 0.548 5.662
4. IN COND
STATE POINT DATA
Air Flow(Standard)
(L/s)
DryBulb(°C)
WetBulb(°C)
RelativeHumidity
(%)
HumidityRatio(g/kg)
SpecificVolume
(cu.m/kg)
Enthalpy
(kJ/kg)
DewPoint(°C)
Density
(kg/cu.m)
VaporPressure(mm Hg)
AbsoluteHumidity(g/cu.m)
472 21.600 14.341 45.0 7.24 0.844 40.105 9.1732 1.1929 8.7128 8.576
5. DEH
STATE POINT DATA
Air Flow(Standard)
(L/s)
DryBulb(°C)
WetBulb(°C)
RelativeHumidity
(%)
HumidityRatio(g/kg)
SpecificVolume
(cu.m/kg)
Enthalpy
(kJ/kg)
DewPoint(°C)
Density
(kg/cu.m)
VaporPressure(mm Hg)
AbsoluteHumidity(g/cu.m)
472 45.000 18.874 5.0 2.97 0.905 52.902 -2.8998 1.1080 3.6010 3.284
Process: Cooling Coil
Start Point Name
TotalCooling(kW/hr)
TotalEnergy(W/hr)
SensibleEnergy(W/hr)
LatentEnergy(W/hr)
Dehumidification
(kg/hr)
SensibleHeat Ratio
Enthalpy/Humidity Ratio(kJ/kg / g/kg)
MCC 7.676 7,676 17,183 -9,507 -13.5 2.239 -2.060
6. RETURN AIR
STATE POINT DATA
Air Flow(Standard)
(L/s)
DryBulb(°C)
WetBulb(°C)
RelativeHumidity
(%)
HumidityRatio(g/kg)
SpecificVolume
(cu.m/kg)
Enthalpy
(kJ/kg)
DewPoint(°C)
Density
(kg/cu.m)
VaporPressure(mm Hg)
AbsoluteHumidity(g/cu.m)
472 22.000 14.660 45.0 7.42 0.846 40.974 9.5362 1.1912 8.9284 8.776
Process: Connect States
Start Point NameTotal
Energy(W/hr)
SensibleEnergy(W/hr)
LatentEnergy(W/hr)
MoistureDifference
(kg/hr)
SensibleHeat Ratio
Enthalpy/Humidity Ratio(kJ/kg / g/kg)
IN COND 492 231 261 0.4 0.469 N/A
7. MIXING
STATE POINT DATA
Air Flow(Standard)
(L/s)
DryBulb(°C)
WetBulb(°C)
RelativeHumidity
(%)
HumidityRatio(g/kg)
SpecificVolume
(cu.m/kg)
Enthalpy
(kJ/kg)
DewPoint(°C)
Density
(kg/cu.m)
VaporPressure(mm Hg)
AbsoluteHumidity(g/cu.m)
944 33.500 16.856 16.1 5.20 0.876 46.985 4.3982 1.1480 6.2745 5.936
Process: Air Mixing
Version 3.1.50 Page 1
STATE POINT & PROCESS REPORT
State Point No. 1 NameAir FlowStandard
(L/s)
DryBulb(°C)
HumidityRatio(g/kg)
State Point No. 2 NameAir FlowStandard
(L/s)
DryBulb(°C)
HumidityRatio(g/kg)
DEH 472.0 45.0 3 RETURN AIR 472.0 22.0 7.4
8. BLOWER HEAT
STATE POINT DATA
Air Flow(Standard)
(L/s)
DryBulb(°C)
WetBulb(°C)
RelativeHumidity
(%)
HumidityRatio(g/kg)
SpecificVolume
(cu.m/kg)
Enthalpy
(kJ/kg)
DewPoint(°C)
Density
(kg/cu.m)
VaporPressure(mm Hg)
AbsoluteHumidity(g/cu.m)
0 35.000 17.373 14.9 5.20 0.880 48.507 4.3982 1.1424 6.2745 5.907
Process: Sensible Heating
Start Point NameTotal
Heating(kW)
TotalEnergy(W/hr)
SensibleEnergy(W/hr)
LatentEnergy(W/hr)
MoistureDifference
(kg/hr)
SensibleHeat Ratio
Enthalpy/Humidity Ratio(kJ/kg / g/kg)
MIXING 1.7 1,725 1,725 0 0.0 1.000 N/A
9. SEN. COOLING
STATE POINT DATA
Air Flow(Standard)
(L/s)
DryBulb(°C)
WetBulb(°C)
RelativeHumidity
(%)
HumidityRatio(g/kg)
SpecificVolume
(cu.m/kg)
Enthalpy
(kJ/kg)
DewPoint(°C)
Density
(kg/cu.m)
VaporPressure(mm Hg)
AbsoluteHumidity(g/cu.m)
0 15.000 9.548 49.0 5.20 0.823 28.217 4.3982 1.2217 6.2745 6.317
Process: Sensible Cooling
Start Point NameTotal
Cooling(kW)
TotalEnergy(W/hr)
SensibleEnergy(W/hr)
LatentEnergy(W/hr)
MoistureDifference
(kg/hr)
SensibleHeat Ratio
Enthalpy/Humidity Ratio(kJ/kg / g/kg)
BLOWER HEAT 0.0 0 0 0 0.0 1.000 N/A
Version 3.1.50 Page 2