STATE POINT & PROCESS REPORT Report Date: Sunday, September 06, 2015 Project Information: Altitude: 0 (Meters) Barometric Pressure: 760.001 (mm Hg) Atmospheric Pressure: 101.325 (kPa) 1. OTC STATE POINT DATA Air Flow (Standard) (L/s) Dry Bulb (°C) Wet Bulb (°C) Relative Humidity (%) Humidity Ratio (g/kg) Specific Volume (cu.m/kg) Enthalpy (kJ/kg) Dew Point (°C) Density (kg/cu.m) Vapor Pressure (mm Hg) Absolute Humidity (g/cu.m) 472 35.600 25.537 45.0 16.57 0.898 78.313 21.8396 1.1329 19.6441 18.462 2. BTR STATE POINT DATA Air Flow (Standard) (L/s) Dry Bulb (°C) Wet Bulb (°C) Relative Humidity (%) Humidity Ratio (g/kg) Specific Volume (cu.m/kg) Enthalpy (kJ/kg) Dew Point (°C) Density (kg/cu.m) Vapor Pressure (mm Hg) Absolute Humidity (g/cu.m) 472 36.200 25.686 43.5 16.57 0.899 78.935 21.8396 1.1307 19.6441 18.427 Process: Sensible Heating Start Point Name Total Heating (kW) Total Energy (W/hr) Sensible Energy (W/hr) Latent Energy (W/hr) Moisture Difference (kg/hr) Sensible Heat Ratio Enthalpy/ Humidity Ratio (kJ/kg / g/kg) OTC 0.4 352 352 0 0.0 1.000 N/A 3. MCC STATE POINT DATA Air Flow (Standard) (L/s) Dry Bulb (°C) Wet Bulb (°C) Relative Humidity (%) Humidity Ratio (g/kg) Specific Volume (cu.m/kg) Enthalpy (kJ/kg) Dew Point (°C) Density (kg/cu.m) Vapor Pressure (mm Hg) Absolute Humidity (g/cu.m) 472 15.000 14.008 90.0 9.60 0.829 39.362 13.3748 1.2186 11.5130 11.592 Process: Cooling Coil Start Point Name Total Cooling (kW/hr) Total Energy (W/hr) Sensible Energy (W/hr) Latent Energy (W/hr) Dehumidification (kg/hr) Sensible Heat Ratio Enthalpy/ Humidity Ratio (kJ/kg / g/kg) BTR -22.435 -22,435 -12,291 -10,143 -14.2 0.548 5.662 4. IN COND STATE POINT DATA Air Flow (Standard) (L/s) Dry Bulb (°C) Wet Bulb (°C) Relative Humidity (%) Humidity Ratio (g/kg) Specific Volume (cu.m/kg) Enthalpy (kJ/kg) Dew Point (°C) Density (kg/cu.m) Vapor Pressure (mm Hg) Absolute Humidity (g/cu.m) 472 21.600 14.341 45.0 7.24 0.844 40.105 9.1732 1.1929 8.7128 8.576 5. DEH STATE POINT DATA Air Flow (Standard) (L/s) Dry Bulb (°C) Wet Bulb (°C) Relative Humidity (%) Humidity Ratio (g/kg) Specific Volume (cu.m/kg) Enthalpy (kJ/kg) Dew Point (°C) Density (kg/cu.m) Vapor Pressure (mm Hg) Absolute Humidity (g/cu.m) 472 45.000 18.874 5.0 2.97 0.905 52.902 -2.8998 1.1080 3.6010 3.284 Process: Cooling Coil Start Point Name Total Cooling (kW/hr) Total Energy (W/hr) Sensible Energy (W/hr) Latent Energy (W/hr) Dehumidification (kg/hr) Sensible Heat Ratio Enthalpy/ Humidity Ratio (kJ/kg / g/kg) MCC 7.676 7,676 17,183 -9,507 -13.5 2.239 -2.060 6. RETURN AIR STATE POINT DATA Air Flow (Standard) (L/s) Dry Bulb (°C) Wet Bulb (°C) Relative Humidity (%) Humidity Ratio (g/kg) Specific Volume (cu.m/kg) Enthalpy (kJ/kg) Dew Point (°C) Density (kg/cu.m) Vapor Pressure (mm Hg) Absolute Humidity (g/cu.m) 472 22.000 14.660 45.0 7.42 0.846 40.974 9.5362 1.1912 8.9284 8.776 Process: Connect States Start Point Name Total Energy (W/hr) Sensible Energy (W/hr) Latent Energy (W/hr) Moisture Difference (kg/hr) Sensible Heat Ratio Enthalpy/ Humidity Ratio (kJ/kg / g/kg) IN COND 492 231 261 0.4 0.469 N/A 7. MIXING STATE POINT DATA Air Flow (Standard) (L/s) Dry Bulb (°C) Wet Bulb (°C) Relative Humidity (%) Humidity Ratio (g/kg) Specific Volume (cu.m/kg) Enthalpy (kJ/kg) Dew Point (°C) Density (kg/cu.m) Vapor Pressure (mm Hg) Absolute Humidity (g/cu.m) 944 33.500 16.856 16.1 5.20 0.876 46.985 4.3982 1.1480 6.2745 5.936 Process: Air Mixing Version 3.1.50 Page 1

Arial

Embed Size (px)

DESCRIPTION

Arial

Citation preview

Page 1: Arial

STATE POINT & PROCESS REPORT

Report Date: Sunday, September 06, 2015Project Information:

Altitude: 0 (Meters)Barometric Pressure: 760.001 (mm Hg)Atmospheric Pressure: 101.325 (kPa)

1. OTC

STATE POINT DATA

Air Flow(Standard)

(L/s)

DryBulb(°C)

WetBulb(°C)

RelativeHumidity

(%)

HumidityRatio(g/kg)

SpecificVolume

(cu.m/kg)

Enthalpy

(kJ/kg)

DewPoint(°C)

Density

(kg/cu.m)

VaporPressure(mm Hg)

AbsoluteHumidity(g/cu.m)

472 35.600 25.537 45.0 16.57 0.898 78.313 21.8396 1.1329 19.6441 18.462

2. BTR

STATE POINT DATA

Air Flow(Standard)

(L/s)

DryBulb(°C)

WetBulb(°C)

RelativeHumidity

(%)

HumidityRatio(g/kg)

SpecificVolume

(cu.m/kg)

Enthalpy

(kJ/kg)

DewPoint(°C)

Density

(kg/cu.m)

VaporPressure(mm Hg)

AbsoluteHumidity(g/cu.m)

472 36.200 25.686 43.5 16.57 0.899 78.935 21.8396 1.1307 19.6441 18.427

Process: Sensible Heating

Start Point NameTotal

Heating(kW)

TotalEnergy(W/hr)

SensibleEnergy(W/hr)

LatentEnergy(W/hr)

MoistureDifference

(kg/hr)

SensibleHeat Ratio

Enthalpy/Humidity Ratio(kJ/kg / g/kg)

OTC 0.4 352 352 0 0.0 1.000 N/A

3. MCC

STATE POINT DATA

Air Flow(Standard)

(L/s)

DryBulb(°C)

WetBulb(°C)

RelativeHumidity

(%)

HumidityRatio(g/kg)

SpecificVolume

(cu.m/kg)

Enthalpy

(kJ/kg)

DewPoint(°C)

Density

(kg/cu.m)

VaporPressure(mm Hg)

AbsoluteHumidity(g/cu.m)

472 15.000 14.008 90.0 9.60 0.829 39.362 13.3748 1.2186 11.5130 11.592

Process: Cooling Coil

Start Point Name

TotalCooling(kW/hr)

TotalEnergy(W/hr)

SensibleEnergy(W/hr)

LatentEnergy(W/hr)

Dehumidification

(kg/hr)

SensibleHeat Ratio

Enthalpy/Humidity Ratio(kJ/kg / g/kg)

BTR -22.435 -22,435 -12,291 -10,143 -14.2 0.548 5.662

4. IN COND

STATE POINT DATA

Air Flow(Standard)

(L/s)

DryBulb(°C)

WetBulb(°C)

RelativeHumidity

(%)

HumidityRatio(g/kg)

SpecificVolume

(cu.m/kg)

Enthalpy

(kJ/kg)

DewPoint(°C)

Density

(kg/cu.m)

VaporPressure(mm Hg)

AbsoluteHumidity(g/cu.m)

472 21.600 14.341 45.0 7.24 0.844 40.105 9.1732 1.1929 8.7128 8.576

5. DEH

STATE POINT DATA

Air Flow(Standard)

(L/s)

DryBulb(°C)

WetBulb(°C)

RelativeHumidity

(%)

HumidityRatio(g/kg)

SpecificVolume

(cu.m/kg)

Enthalpy

(kJ/kg)

DewPoint(°C)

Density

(kg/cu.m)

VaporPressure(mm Hg)

AbsoluteHumidity(g/cu.m)

472 45.000 18.874 5.0 2.97 0.905 52.902 -2.8998 1.1080 3.6010 3.284

Process: Cooling Coil

Start Point Name

TotalCooling(kW/hr)

TotalEnergy(W/hr)

SensibleEnergy(W/hr)

LatentEnergy(W/hr)

Dehumidification

(kg/hr)

SensibleHeat Ratio

Enthalpy/Humidity Ratio(kJ/kg / g/kg)

MCC 7.676 7,676 17,183 -9,507 -13.5 2.239 -2.060

6. RETURN AIR

STATE POINT DATA

Air Flow(Standard)

(L/s)

DryBulb(°C)

WetBulb(°C)

RelativeHumidity

(%)

HumidityRatio(g/kg)

SpecificVolume

(cu.m/kg)

Enthalpy

(kJ/kg)

DewPoint(°C)

Density

(kg/cu.m)

VaporPressure(mm Hg)

AbsoluteHumidity(g/cu.m)

472 22.000 14.660 45.0 7.42 0.846 40.974 9.5362 1.1912 8.9284 8.776

Process: Connect States

Start Point NameTotal

Energy(W/hr)

SensibleEnergy(W/hr)

LatentEnergy(W/hr)

MoistureDifference

(kg/hr)

SensibleHeat Ratio

Enthalpy/Humidity Ratio(kJ/kg / g/kg)

IN COND 492 231 261 0.4 0.469 N/A

7. MIXING

STATE POINT DATA

Air Flow(Standard)

(L/s)

DryBulb(°C)

WetBulb(°C)

RelativeHumidity

(%)

HumidityRatio(g/kg)

SpecificVolume

(cu.m/kg)

Enthalpy

(kJ/kg)

DewPoint(°C)

Density

(kg/cu.m)

VaporPressure(mm Hg)

AbsoluteHumidity(g/cu.m)

944 33.500 16.856 16.1 5.20 0.876 46.985 4.3982 1.1480 6.2745 5.936

Process: Air Mixing

Version 3.1.50 Page 1

Page 2: Arial

STATE POINT & PROCESS REPORT

State Point No. 1 NameAir FlowStandard

(L/s)

DryBulb(°C)

HumidityRatio(g/kg)

State Point No. 2 NameAir FlowStandard

(L/s)

DryBulb(°C)

HumidityRatio(g/kg)

DEH 472.0 45.0 3 RETURN AIR 472.0 22.0 7.4

8. BLOWER HEAT

STATE POINT DATA

Air Flow(Standard)

(L/s)

DryBulb(°C)

WetBulb(°C)

RelativeHumidity

(%)

HumidityRatio(g/kg)

SpecificVolume

(cu.m/kg)

Enthalpy

(kJ/kg)

DewPoint(°C)

Density

(kg/cu.m)

VaporPressure(mm Hg)

AbsoluteHumidity(g/cu.m)

0 35.000 17.373 14.9 5.20 0.880 48.507 4.3982 1.1424 6.2745 5.907

Process: Sensible Heating

Start Point NameTotal

Heating(kW)

TotalEnergy(W/hr)

SensibleEnergy(W/hr)

LatentEnergy(W/hr)

MoistureDifference

(kg/hr)

SensibleHeat Ratio

Enthalpy/Humidity Ratio(kJ/kg / g/kg)

MIXING 1.7 1,725 1,725 0 0.0 1.000 N/A

9. SEN. COOLING

STATE POINT DATA

Air Flow(Standard)

(L/s)

DryBulb(°C)

WetBulb(°C)

RelativeHumidity

(%)

HumidityRatio(g/kg)

SpecificVolume

(cu.m/kg)

Enthalpy

(kJ/kg)

DewPoint(°C)

Density

(kg/cu.m)

VaporPressure(mm Hg)

AbsoluteHumidity(g/cu.m)

0 15.000 9.548 49.0 5.20 0.823 28.217 4.3982 1.2217 6.2745 6.317

Process: Sensible Cooling

Start Point NameTotal

Cooling(kW)

TotalEnergy(W/hr)

SensibleEnergy(W/hr)

LatentEnergy(W/hr)

MoistureDifference

(kg/hr)

SensibleHeat Ratio

Enthalpy/Humidity Ratio(kJ/kg / g/kg)

BLOWER HEAT 0.0 0 0 0 0.0 1.000 N/A

Version 3.1.50 Page 2