Upload
others
View
1
Download
0
Embed Size (px)
Citation preview
4th International Conference On Building Energy, Environment
An Application Study of Ground Source Direct Cooling Compound
System
J.H. Chen1, J. Song1, Z.L. Wu1
1Department of Urban Construction and Environmental Engineering,
Chongqing University, Chongqing 400013, China
SUMMARY
Based on a small mountain tourism building in Chongqing
(China), combined with experiment and numerical simulation,
the reliability and adaptability of ground-sink direct cooling
(GSDC) and ground source heat pump (GSHP) compound
system integrated with capillary radiant system is analyzed. The
experimental results show the outlet temperature of the GSDC
compound system with fresh air in summer could satisfy the
indoor comfort during 3 weeks’ intermittent operation and the
diurnal average coefficient of performance (COP) of system is
up to 7.6 on the typical hot day. In winter, with switching control
of compressor running states, the GSHP could promise the soil
temperature in good recovery. A three-dimensional heat transfer
model of GHEs is built to analyze the operation of whole cooling
season. With the simulated building load, the whole year
unbalance rate of rejection and absorption heat was 7.1%,
which demonstrates the reasonability of the compound system
operating for continuous years.
INTRODUCTION
Ground source heat pump (GSHP) has become one of the
representative forms of energy saving, efficient and low
operation costs, and been thought of the most energy saving
promising by many famous academic researchers (Xu 2010;
Sanner et al. 2003). So far many researches concentrating on
the heat transfer mechanism, aid design software of ground
heat exchanger (GHE) and operation simulation (Aristodimos
and Marita 2001) have been studied.
Ground source direct sink (GSDC) system is a technology which
directly utilizes shallow geothermal resource and well connects
with the temperature and humidity independent control (THIC)
system and capillary radiant system. On the one hand, the soil
temperature in summer in most areas of China could satisfy the
capillary’s requirement of high temperature supply water and on
the other hand partial indoor sensible load could solve the
problems of unbalanced heating and cooling load.
Li et al (2009) built a GSDC system with fan coil in severe cold
district in China. The soil temperature rose 0.0167°C per day
during 45 days’ intermittent operation. Ni et al (2012) tested the
GSDC system in Shanghai for 20 days and achieved high COP
but poor dehumidifying ability due to the high outlet temperature
of single U buried pipe. Zhao (2014) proposed the GSDC
system with water storage and proved its economic benefits. Xin
et al (2012) established the soil sensible heat handled model
including total heat recovery from hot water unit and GSDC
system.
So far the researches on GSDC system still remains in the early
stage. Most experiments are aimed at cooling season but the
effects on the soil after a whole year operation is also of vital
importance. No experiments or projects were applied to
evaluate the feasibility of GSDC system with capillary. As a
result, based on a small mountain tourism building in Chongqing
(China), this paper combines experiment and numerical
simulation to analyze the reliability and adaptability of the GSDC
and GSHP integrated with capillary compound system.
METHOD
Experiment method
Fig. 1 Schematic of the ground sink direct cooling and heat
pump system
ISBN: 978-0-646-98213-7 COBEE2018-Paper243 page 723
4th International Conference On Building Energy, Environment
The experiment was based on a small mountain tourism
building in Chongqing (China), with the above mentioned
compound system. By regulating valves, the system could
realize three kinds of operation: GSDC, GSHP cooling and
GSHP heating. Fig.1 shows the system schematic.
At design stage, the thermal response test (TRT) was made to
confirm the thermal properties of soil, the heat exchange
capacity for unit well depth, etc. On the basis of the TRT results,
4 test wells (90m in depth) with heat exchange capacity
39.46W/m2 and 1 monitor well with same depth were set.
Due to the special load of the mountain building, the intermittent
cooling tests (8:30 ~18:00) by GSDC system were made in
summer and the continuous heating test in three different kinds
of capillary supply water temperature conditions (30°C, 35°C,
40°C) of GSHP were made in winter.
Indoor horizontal temperature measuring points were evenly
arranged in diagonal shape and at each point the temperature
is measured at the height of 0.1m, 0.6m, 1.1m, 1.4m, and 1.7m
to tell the vertical temperature field. For soil temperature, two
points respectively on inlet and outlet pipes at every 10m in
depth added with 5m below the ground of 2 GHE wells and 1
monitor well were tested to analyze the heat transfer.
Simulation method
Because of the limited test time, a three-dimensional unsteady
heat transfer model based on the experiment system was built
by Gambit to analyze the system feasibility in whole year. The
main structure of GHEs was simplified into three parts: double
U buried pipes, backfill zone inside the borehole and soil outside
the borehole. The parameters of each part were set on the basis
of TRT and realistic situations.
Since the heat transfer between borehole heat exchangers and
their surrounding soil was influenced by many unstable variable,
the following available assumptions are made to simplify the
model. Thermal resistances caused by the contact between
backfill materials and soil or borehole heat exchangers are
negligible. The gravity and solar radiant are ignored and the fluid
velocity remains unchanged. Heat transfer in the bending of U-
tube, which is relatively small compared to the whole heat
transfer, is negligible. The soil in different depths is considered
as the same, with the integrated thermophysical parameters
and average soil temperature. In addition, thermal parameters
of buried pipes, soil and fluid are thought unchanged in the
transfer process.
The heat transfer model is composed of two parts: one is
transferred between soil and backfill and the other is between
the fluid and pipe wall. The soil heat transfer, as an unsteady
process, adopts the 3D unsteady heat conductivity model
without interior heat source, whose general form is
𝜕(𝜌𝑇)
𝜕𝑡=
𝜕
𝜕𝑥(
𝜆
𝐶𝑝·
𝜕𝑇
𝜕𝑥) +
𝜕
𝜕𝑦(
𝜆
𝐶𝑝·
𝜕𝑇
𝜕𝑦) +
𝜕
𝜕𝑧(
𝜆
𝐶𝑝·
𝜕𝑇
𝜕𝑧) (1)
Where 𝐶𝑝 is specific heat, J/ (kg·K); 𝜆 is thermal conductivity,
W/ (m·K); and T is temperature, °C.
The fluid in GHEs is seen as turbulent and the Re-normalized
group (RNG) k–ε model is general accepted when calculating
the fluid flow and its heat transfer. The standard k–ε equation,
along with the continuity equation, momentum equation and
energy equation composes the governing equation, which could
be simplified further for the fluid water is re-circulating,
incompressible, constant viscosity and not concerned with
gravity.
Considering the turbulence state of circulating water, the
boundary flow field of inner pipe wall adopts the refined grid.
Due to the complicated and irregular structure, the backfill zone
is uniformly meshed every 0.5 meters in the axial direction and
the grid spacing of soil is increased by the factor 1.05 to improve
the accuracy. The mesh is displayed in Fig.2.
Fig. 2 The display of mesh
RESULTS
Performance of GSDC system in summer
The GSDC with ceiling capillary and dedicated outdoor air
system (DOAS) test procedure was operated for 3 weeks (15th
Jul~4th Aug). The day with peak load (26th Jul) is chosen as the
typical hot day to illustrate the cooling effect.
ISBN: 978-0-646-98213-7 COBEE2018-Paper243 page 724
4th International Conference On Building Energy, Environment
Fig.2 shows that the ambient temperature remains stable in the
range of 26~27°C and matches the indoor design temperature
(27°C) with the fluctuation of outdoor temperature and it is
26.56°C when the outdoor temperature peaks at 36.8°C. As for
the space temperature distribution, the maximum temperature
difference as sitting position and as standing position appears
0.4°C and 0.6°C respectively, which indicates a good mixing of
room air. The ceiling capillary cooling system with DOAS could
keep the indoor temperature field uniform.
Fig.3 The daily variations of indoor temperature on Jul 26th
The THIC system has great difficulty in dewing which happens
easily if the radiant surface temperature or fresh air temperature
is lower than dew point temperature. With the indoor load
increasing, the outlet temperature of GHEs increases while the
dehumidification of fresh air unit goes down, so the radiant
surface temperature and the fresh air temperature increases
gradually. As is illustrated in Fig. 4, with flow rate 350 m3/h, there
is no difference between fresh air temperature and dew point
temperature with the average 20.1°C and 20°C respectively. On
the contrary, the average radiant surface temperature (23°C) is
obviously 2~3°C higher than dew point temperature. So there is
no dew formation on the ceiling but tiny dew on the fresh air inlet.
By calculation, the indoor load and sensible part of it are 1.04kW
and 0.65kW respectively.
Fig. 4 Fresh air temperature, radiant surface temperature
and dew point temperature
Before the system operation, the natural soil temperature is
recorded via the monitor well and the highest appears in the
depth of 5m below the ground, where is easily influenced by the
solar radiant, and the temperatures below 10 meters
underground fluctuate slightly within 0.5°C with average
17.68°C, which proves that the soil is perfect natural cooling
source for capillary.
Fig. 5 (a) shows the variation of soil temperature on 26th Jul. The
soil temperature increases apparently from 18.30°C in the first
hour and then rises constantly by 1.51°C when the system stops
at 18:00 after which the soil recovered slowly. It is back to
18.44°C after 5 hours and 18.32°C at next 8:00. After
continuous running for 15 days, the initial soil temperature rises
from 18.09°C to 18.40°C, corresponding to 0.021°C/d (see Fig.
5 (b)). It concluded that the intermittent operation of running for
9.5h every day could guarantee the system in high cooling
capacity and soil in good recovery.
(a)
(b)
Fig.5 Distribution of the soil temperature on 26th Jul (a) and in
15 days (b)
On the typical hot day, the whole cooling system still keeps in
normal and stable running. The water flow rate of tested room
is stable at 0.7 m3/h and that of system is 1.75m3/h. Fig. 6
reflects the water temperature and cooling capacity of capillary
and system. As is shown, the efficiency of GSDC system is so
high that capillary supply temperature is nearly equated to
GHEs outlet temperature. The radiant surface heat flux is
ISBN: 978-0-646-98213-7 COBEE2018-Paper243 page 725
4th International Conference On Building Energy, Environment
measured by the sensor with averaged 20.3 W/m2. Multiplied by
heating area (40 m2), the average effective heat release of
capillary is 0.81kW, accounting for 89.2% of the capillary
average cooling capacity (0.91kW). Considered with indoor
sensible load by fresh air (0.65kW mentioned before), it is only
55% of sensible load that is taken by capillary. Unlike the GSHP
system, all energy consumption of GSDC system comes from
water pump (0.55kW) and all the heat exchanged from soil is
directly provided for room. So connected with cooling capacity
(4.18kW), the average COP of GSDC system on Jul 26th is 7.60
and as high as 8.18 when the indoor load peaks.
Fig.6 Water temperature and cooling capacity of capillary and
system on 26th Jul
Performance of GSHP system in winter
The continuous tests in winter are made to compare the effects
of three different supply water temperature of floor capillary. The
results of three conditions in stabilization are listed in Tab.1. It is
shown that ambient temperature of 35°C condition is lower than
the designed value (18°C) while the indoor comfort of both 40°C
and 45°C condition could satisfy the requirements in ASHRAE
(2004) and ISO (2005).
Tab. 1 The tested results of three conditions in winter
Conditions 35°C 40°C 45°C
Outdoor temperature /°C 7.55 7.45 6.93
Ambient temperature /°C 16.08 18.08 19.12
Maximum vertical difference /°C 0.22 0.31 0.82
Capillary supply temperature /°C 35.13 40.25 45.73
Capillary return temperature /°C 33.25 35.97 41.67
Capillary temperature difference /°C 1.88 4.29 4.06
Flow rate /m3/h 0.62
Seen in Tab. 2, the increase of floor surface temperature is only
1.1°C when the supply temperature changing from 40°C to 45°C
and the effective heat ratio of 45°C condition is no more than
70%. As a conclusion, the 40°C condition is the perfect for to
achieve the comfort with low energy consumption and high
efficiency operation.
Tab. 2 The heating capacity analysis of 40°C,45°C conditions
As is seen in Fig. 6, in the beginning of system operation, the
unit works in the double compressor mode and the soil
temperature changes dramatically. When ambient temperature
stable, the unit switches to the single compressor or stop mode,
where the soil could provide less heat and get short recovery.
Seen from the curves, the duration of every two switch is nearly
30min, when the soil temperature recovers by around 1°C.
Fig.7 Variations of soil temperature at different depth in 40°C
condition
Although the unit consumption of single mode is less than that
of double mode, lower cooling load decreases its unit COP (3.65
and 3.49 for single and double mode respectively). Added to the
application of fixed frequency pump, the COP of GSHP system
is as low as 2.61 and 2.85 respectively for the two modes.
Model validation
The test data from 17th Jul to 27th Jul is chosen to validate the
effectiveness of model. The initial inlet temperature is set as the
initial soil temperature (18.12°C). Influenced by the numeric
diffusion of unsteady state phase, there is a difference between
simulated and tested data at the beginning. Gradually, the
simulated outlet temperature basically matches the
Conditions 40°C 45°C
Radiant surface temperature /°C 24.00 25.10
Heat capacity /kW 3.34 3.96
Heat capacity unit area W/m² 83.17 100.65
Heat flux W/m² 60.74 69.66
Effective heat ratio /% 73.03 69.21
Lost heat ratio /% 26.97 30.79
ISBN: 978-0-646-98213-7 COBEE2018-Paper243 page 726
4th International Conference On Building Energy, Environment
experimental one and the relative error of two stabilizes within
1% (see Fig.8 (a)). Because the effect of solar radiant on fluid is
ignored in simulation, the tested soil temperature is always
higher than the simulated. But the difference decreases with the
simulation time passing and concentrates on the recovery stage
(Fig.8(b)). The average is 0.28°C in difference and 1.7% in
relative error. So the numerical model is enough accurate to
analyze the GSCD system performance during the whole
cooling season.
(a)
(b)
Fig. 8 Comparison of simulated and tested outlet water
temperature (a) and soil temperature (b)
Simulation results
To simulate a worse situation, the cooling hours in summer is
set as 13h and the rest to recover for all rooms when the annual
dynamic load calculated. Based on the proportions (55% and
89.2%) that concluded before and the simulated building hourly
sensible cooling load by software Dest, the heat released to the
ground by GSDC system could be calculated and used as the
fundamental data to simulate the outlet and soil temperature of
the whole cooling season.
Fig.9 describes the variation of simulated outlet temperature of
the whole cooling season. The outlet temperature fluctuates
within the range of 18°C~20°C and peaks at 21°C in the middle
of cooling season. Since the fact that the building load
decreases by the late cooling season, the soil could remove the
day’s heat at night, leading to the similar fluctuation of outlet
temperature every day. To verify the indoor comfort at the
condition of 21°C outlet temperature, the air source heat pump
is used to replace the GSDC system, for whose outlet
temperature is influenced by building load and difficult to change.
As is seen in Fig.10, with the help of the fresh air, when the
outdoor temperature peaks (35.8°C), the ambient temperature
(27°C) and ceiling surface temperature (24°C) could remain
stable and satisfy the thermal comfort requirements.
Fig. 9 Hourly variations of the outlet temperatures of the GHE
Fig. 10 The hourly variations of environment parameter in the
condition of 21°C supply temperature
It is only partial indoor load that the GSDC system deals with,
the maximal inlet temperature of GHEs is only 23.8°C and the
heat released to the soil is far less than that of ordinary GSHP
system. Compared with initial soil temperature before operation,
the soil temperature rises from 17.69°C to 18.56°C (0.87°C in
total). Additionally, no short circuit and heat accumulation
happens around the GHEs (see Fig. 11).
Fig. 11 Hourly variations of the soil temperatures
ISBN: 978-0-646-98213-7 COBEE2018-Paper243 page 727
4th International Conference On Building Energy, Environment
So far, it has proved the cooling ability of GHEs in the first
cooling season. According to the Dest results, accumulative
indoor sensible cooling load is 7754kW and accumulative indoor
heating load without fresh air in winter, all solved by GSHP
system is 7149kW. Thus, via the proportion and equation (2),
the heat to the soil in summer is 4781kW and absorbed from the
soil in winter is 5146kW. The unbalance rate of soil heat is 7.1%.
𝑄1 = 𝑄ZR × (1 − 1/𝐶𝑂𝑃𝑅) (2)
where 𝑄1 is the heat absorbed from the soil in winter, 𝑄ZR is
the accumulated heating load by GSHP system and 𝐶𝑂𝑃𝑅 is
the coefficient of unit performance.
DISCUSSION
The fact that the GSDC system only solves partial sensible heat
makes the transferred heat between building and soil far less
than the normal GSHP system in summer. The experiment and
simulation results prove that GSDC system with capillary could
provide a stable long-term heating and cooling process and the
change of soil temperature could promise good indoor comfort.
When it comes to the energy saving, the energy consumption of
fresh air will be of crucial importance.
CONCLUSION
Connected with the simulation and experimental results, the
GSDC with heat pump and capillary compound system is
reasonable and feasible for cooling mountain building in
Chongqing (China). Three main conclusions are followed:
In the first cooling season, with the help of DOAS the outlet
temperature of GHEs could stasfy the capillarys’ requirements
and make comfortable indoor environment. Meantime, the
system keeps high COP.
In winter, 40°C is determined to be the perfect supply
temperature for capillary in terms of indoor environment and
heat capacity. The switch of GSHP unit running modes are good
for soil in recovery.
By simulation, the compound system could keep in good
operations in the whole cooling season. There is no soil heat
accumulation and the outlet temperature could suit the indoor
comfort. The soil unbalanced rate of absorption and rejection
heat is very low, which determined the feasibility of the GSDC
with heat pump and capillary compound system.
ACKNOWLEDGEMENTS
Great thanks to people for financing and building the
experimental system. Also thanks to those always helpful and
co-operative operational personnel in our group.
REFERENCES
Aristodimos J P, Marita L B. Influence of debonding in ground
heat exchangers used with geothermal heat pumps.
Geothermic. 2001, (3): 527-542.
Li Z J, Zheng R Y, Lei B W, Zhao L Q. Experimental study on
ground temperature variation characteristics of a ground-sink
direct cooling system [J]. Journal of Harbin institute of
technology, 2009, 06: 72-77.
Liu J Y, Xie X N, Qin F H, Song S J, Lv D L. A case study of
ground source direct cooling system integrated with water
storage tank system [J]. Building simulation, 2016, 9: 659-668.
Ni X, Tan H W, Lei Y. Experimental study of a free cooling
system using soil as heat sink in Shanghai [J]. Building energy
consumption, 2012, 10: 19-23.
Sanner B, Karytsas C, Mendrinos D, et al. Current status of
source heat pumps and underground thermal energy storage
in Europe[J]. Geothermics. 2003, 32: 579-588.
Xin Y G. Research and application of ground-source system of
sensible treatment in temperature and humidity independent
control system [D]. Hefei institute of technology, 2012.
Xu W. The development report for ground source heat pump in
China [J]. Construction Science and Technology, 2010, 18: 14-
18.
Zhao F Q. The application research on the compound air
conditioning system of ground source direct cooling system
and water storage system [D]. Shandong Jianzhu University,
2014.
ISBN: 978-0-646-98213-7 COBEE2018-Paper243 page 728